DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/20/2025        Last Data Refresh: 04/19/2025        Report Generated from DOPPLER
 
District Southwest   Type    Fuel user/Non-retail
 
County Pinellas   Status    OPEN
 
ID 9818557   Latitude    27° 48' 48.6286
 
Name SHORE ACRES CARE CTR AND REHAB
4500 INDIANAPOLIS ST NE
Longitude    82° 36' 7.2459
  ST PETERSBURG, FL 33703 LL Method    DPHO
 
Contact CARLOS MORENO   LL Status    REVIEWED
 
Phone (727) 209-4600   Status Date    06/02/2021
 
Account Owner Information
 
Name SHORE ACRES NURSING AND REHAB LLC
4500 INDIANAPOLIS ST NE
ST PETERSBURG, FL 33703-4317
Effective Date    08/01/2023
 
Contact CARLOS MORENO
 
Phone (727) 209-4600
 
Email CARLOS.MORENO@SHOREACRESCC.COM
  Placard # / Date    696652 - 06/27/2024
Property Owner Information
 
Name SHORE ACRES NURSING HOLDCO LLC
4500 INDIANAPOLIS ST NE
SAINT PETERSBURG, FL 33703
Effective Date    04/10/2023
 
Contact CARLOS MORENO
 
Phone (727) 527-5801
 
Email CARLOS.MORENO@SHOREACRESCC.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 1750 Emerg Generator Diesel (G) 05/01/2021 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(I) Suction piping system
(Z) DEP approved piping
(6) External piping monitoring
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   06/10/2022 06/10/2023 MT. HAWLEY INSURANCE COMPANY
INSURANCE   06/10/2021 06/10/2022 MT. HAWLEY INSURANCE COMPANY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 02/26/2025 Major Out of Compliance PUHR_NM_1 1/0 Routine Compliance
 
Electronic Communication 02/24/2025 Satisfied PUHR_NM_1 Routine Compliance
 
Letter 04/06/2023 Satisfied COLSON_NJ_1 Compliance Assistance
 
Record Document 04/06/2023 Satisfied COLSON_NJ_1 Compliance Assistance
 
Site Inspection 10/04/2022 Major Out of Compliance COLSON_NJ_1 1/0 Installation
 
Letter 10/04/2022 Satisfied COLSON_NJ_1 Compliance Assistance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
02/24/2025 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. *Submit any monthly tank system visual inspections or alarm history logs if found; otherwise, submit the next two consecutive months of inspections/alarm logs. Be sure to include an explanation/resolution for any alarms.
 
02/24/2025 7072 Minor 1.8 Annual operability testing of release detection systems not completed. *Submit the 2024 record if found; otherwise, have testing performed and submit results to this office for review.
 
02/24/2025 7010 SNC-A 1.8 No financial responsibility instrument or expired instrument for > 180 days. *Submit missing FR from 06/10/2023. Be sure to include the Part D from the policy as well as a Part P (completed by facility).
 
02/24/2025 7004 Minor 1.4 Placard not displayed (or available upon request). *Display the placard at the facility. Provide a copy of the placard to document this.
 
02/24/2025 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Violation resolved with testing during inspection on 2/13/2025, of the Krueger Level Gauge.
 
 
 
No Discharges Found