DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 05/09/2025        Last Data Refresh: 05/08/2025        Report Generated from DOPPLER
 
District Central   Type    Fuel user/Non-retail
 
County Volusia   Status    OPEN
 
ID 9818595   Latitude    29° 2' 7.6675
 
Name STETSON UNIVERSITY - SAGE HALL
136 E MINNESOTA AVE
Longitude    81° 18' 2.5874
  DELAND, FL 32723 LL Method    DPHO
 
Contact FACILITIES MGMNT   LL Status    REVIEWED
 
Phone (386) 822-8808   Status Date    07/26/2021
 
Account Owner Information
 
Name STETSON UNIVERSITY
421 N WOODLAND BLVD, UN#8420
DELAND, FL 32720-3702
Effective Date    06/28/2021
 
Contact BONITA DUKES / MICHELE CLIFTON (AP)
 
Phone (386) 822-8800
 
Email BDUKES@STETSON.EDU
  Placard # / Date    694194 - 06/25/2024
Property Owner Information
 
Name STETSON UNIVERSITY
421 N WOODLAND BLVD, UN#8420
DELAND, FL 32720-3702
Effective Date    06/28/2021
 
Contact BONITA DUKES / MICHELE CLIFTON (AP)
 
Phone (386) 822-8800
 
Email BDUKES@STETSON.EDU
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
49138 1761 Emerg Generator Diesel (G) 07/01/2021 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(M) Spill containment bucket
(P) Level gauges/alarms
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(D) External protective coating
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
(R) Monitor tank bottom space
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   06/01/2023 06/01/2024 CRUM & FORSTER SPECIALTY INSURANCE COMPANY
INSURANCE   06/01/2022 06/01/2023 CRUM & FORSTER SPECIALTY INSURANCE COMPANY
INSURANCE   08/09/2021 06/01/2022 CRUM & FORSTER INDEMNITY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 07/30/2024 Accepted BECKER_GT_1 Enforcement
 
Electronic Communication 04/10/2024 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 03/20/2024 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 02/23/2024 Satisfied GREGORY_JW_1 Compliance Assistance
 
Phone Conversation 02/23/2024 Satisfied PIERCE_BN_1 Compliance Assistance
 
Issue Document 02/15/2024 Satisfied BECKER_GT_1 Compliance Assistance
 
Electronic Communication 01/16/2024 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 10/19/2023 Satisfied PIERCE_BN_1 Compliance Assistance
 
Site Inspection 10/18/2023 Major Out of Compliance BECKER_GT_1 1/0 Installation
 
Letter 10/18/2023 Satisfied PIERCE_BN_1 Compliance Assistance
 
Electronic Communication 08/11/2022 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 08/12/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 08/12/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 08/12/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 08/11/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 08/05/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 08/05/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 08/03/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 07/29/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 06/30/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 06/28/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 06/28/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 06/28/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 06/28/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 06/28/2021 Satisfied BECKER_GT_1 Installation
 
Electronic Communication 06/28/2021 Satisfied BECKER_GT_1 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
10/18/2023 7031 SNC-B 3.1 Any component(s) of storage tank system not installed according to manufacturer's instructions. An onsite breach of integrity test is required after the tank is set in place. Please have the breach of integrity testing completed, or supply testing records from the time of installation. All integrity tests should be conducted in accordance with manufacturer's specifications. This can be provided by: 1) The tank holding vacuum for at least one hour following being set in place 2) An onsite pressure testing showing the tank secondary holds for at least one hour
 
 
 
No Discharges Found