Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 04/19/2025 Last Data Refresh: 04/18/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | Fuel user/Non-retail | ||||||||
County | Miami-Dade | Status | OPEN | ||||||||
ID | 9818659 | Latitude | 25° 52' 46.8013 | ||||||||
Name |
ANIXTER 11420 NW 122ND ST |
Longitude | 80° 23' 3.4525 | ||||||||
MIAMI, FL 33178 | LL Method | DPHO | |||||||||
Contact | TIM MUIR | LL Status | REVIEWED | ||||||||
Phone | (954) 242-3071 | Status Date | 01/04/2022 | ||||||||
Account Owner Information | |||||||||||
Name | ANIXTER INC 2301 PATRIOT BLVD GLENVIEW, IL 60026 |
Effective Date | 07/28/2021 | ||||||||
Contact | KEN HAGAMAN | ||||||||||
Phone | (224) 521-8385 | ||||||||||
KEN.HAGAMAN@ANIXTER.COM | |||||||||||
Placard # / Date | 704730 - 12/19/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | LIBERTY PROPERTY LTD PARTNERSHIP 1800 WAZEE ST, SU#500 DENVER, CO 80202 |
Effective Date | 07/28/2021 | ||||||||
Contact | CATHERYN CELAYA | ||||||||||
Phone | (305) 392-4271 | ||||||||||
CCELAYA@PROLOGIS.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 1128 | Emerg Generator Diesel (G) | 05/01/2021 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket |
(A) Abv, no soil contact (B) Steel/galvanized metal (I) Suction piping system |
(Q) Visual inspection of ASTs (R) Monitor tank bottom space |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 09/14/2024 | 09/14/2025 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 09/14/2023 | 09/14/2024 | NAUTILUS INSURANCE COMPANY | ||||||||
INSURANCE | 09/14/2021 | 09/14/2022 | NAUTILUS INSURANCE COMPANY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 03/24/2025 | Satisfied | MATUTERODRIGUEZ_MA_1 | Compliance Assistance | |||||||
Site Inspection | 03/19/2025 | Major Out of Compliance | MATUTERODRIGUEZ_MA_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 03/19/2025 | Satisfied | MATUTERODRIGUEZ_MA_1 | Routine Compliance | |||||||
Site Inspection | 12/31/2024 | In Compliance | JACQUET_F_1 | 1/0 | Compliance Assistance | ||||||
Enforcement Tracking | 12/31/2024 | Closed Without Enforcement | JACQUET_F_1 | Enforcement | |||||||
Electronic Communication | 12/31/2024 | Satisfied | JACQUET_F_1 | Compliance Assistance | |||||||
Letter | 12/31/2024 | Satisfied | JACQUET_F_1 | Compliance Assistance | |||||||
Enforcement Referral | 11/25/2024 | Accepted | JACQUET_F_1 | Enforcement | |||||||
Site Inspection | 11/19/2024 | Major Out of Compliance | JACQUET_F_1 | 1/0 | Compliance Assistance | ||||||
Site Inspection | 09/25/2024 | Major Out of Compliance | JACQUET_F_1 | 1/0 | Compliance Assistance | ||||||
Electronic Communication | 09/25/2024 | Satisfied | JACQUET_F_1 | Compliance Assistance | |||||||
Letter | 09/25/2024 | Satisfied | JACQUET_F_1 | Compliance Assistance | |||||||
Electronic Communication | 02/08/2024 | Satisfied | JACQUET_F_1 | Compliance Assistance | |||||||
Electronic Communication | 06/29/2022 | Satisfied | JACQUET_F_1 | Compliance Assistance | |||||||
Letter | 06/28/2022 | Satisfied | JACQUET_F_1 | Compliance Assistance | |||||||
Site Inspection | 06/28/2022 | Major Out of Compliance | JACQUET_F_1 | 1/0 | Installation | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
03/19/2025 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Begin monthly visual logs of the AST. A template will be provided, fill it out for the most current month, and provide a copy of the completed log. | |||||||
03/19/2025 | 7004 | Minor | 1.4 Placard not displayed (or available upon request). | Provide the current FDEP registration placard that is mailed to the facility every year after paying registration fees. The placard must be posted on-site. | |||||||
03/19/2025 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide a current and passing annual operability test of the overfill protection device (Fuel level gauge and/or high level sensor with alarm) | |||||||
No Discharges Found |