District Southeast   Type    Fuel user/Non-retail
 
County Monroe   Status    CLOSED
 
ID 9818710   Latitude    25° 0' 53.8976
 
Name NATIONWIDE PLUMBING SRVCS
92425 OVERSEAS HWY UNIT #2
Longitude    80° 30' 43.0698
  TAVERNIER, FL 33070 LL Method    DPHO
 
Contact CHRIS REY   LL Status    REVIEWED
 
Phone (305) 853-1848   Status Date    09/07/2021
 
Account Owner Information
 
Name NATIONWIDE PLUMBING SERVICES
97671 OVERSEAS HWY
KEY LARGO, FL 33037
Effective Date    09/01/2021
 
Contact CHRIS REY / CHRIS SANTE
 
Phone (305) 216-6365
 
Email INFO@NWPFLKEYS.COM
  Placard # / Date    656051 - 06/08/2023
Property Owner Information
 
Name NATIONWIDE PLUMBING SERVICES
97671 OVERSEAS HWY
KEY LARGO, FL 33037
Effective Date    09/01/2021
 
Contact CHRIS REY / CHRIS SANTE
 
Phone (305) 216-6365
 
Email INFO@NWPFLKEYS.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 1000 Vehicular Diesel (D) 08/01/2021 ABOVEGROUND Removed from Site (B)
 
Constructions   Pipings Monitorings
(C) Steel
(I) Double wall
(L) Compartmented
(P) Level gauges/alarms
(W) Built on supports
  (A) Abv, no soil contact
(B) Steel/galvanized metal
(D) External protective coating
(F) Double wall
(4) Visual inspect dispenser liners
(6) External piping monitoring
(F) Monitor dbl wall tank space
(Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   12/21/2023 12/21/2024 ACE AMERICAN INSURANCE COMPANY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Enforcement Referral 09/17/2024 Accepted PORTANYI_E Enforcement
 
Site Inspection 08/20/2024 Major Out of Compliance PORTANYI_E 1/0 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
07/31/2024 7042 SNC-B 3.9 Storage tank system not installed with a spill containment system at each tank fill connection. Does not meet performance requirements. Install Department-approved spill bucket to the fill port of the regulated storage tank and provide evidence to the Department. Reference the Department's equipment (EQ) list if unsure.
 
11/21/2023 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Provide monthly monitoring records for 2021, 2022, and 2023.
 
11/21/2023 7010 SNC-A 1.8 No financial responsibility instrument or expired instrument for > 180 days. Provide financial responsibility records for 2021, 2022, and 2023.
 
11/21/2023 7007 Minor 3.1 Incident Notification Form (INF) not received in a timely manner. Investigate why the vegetation around the dispenser is dead and report findings to the Department via Incident Notification Form (INF). The form has been provided via email and can also be found at the FDEP Tanks compliance website.
 
11/21/2023 7090 Minor 3.15 Spill containment, dispenser liners and piping sumps not accessible; water and regulated substances not removed. Properly dispose of liquid in dispenser holder and provide photo documentation to the Department.
 
11/21/2023 7068 SNC-B 3.7 Release detection not properly installed. Install and test release detection mechanism and provide photo evidence to the Department.
 
11/21/2023 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Provide Annual Operability Test (AOT) for 2021, 2022, and 2023.
 
 
 