Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Southeast | Type | Fuel user/Non-retail | ||||||||
County | Monroe | Status | CLOSED | ||||||||
ID | 9818710 | Latitude | 25° 0' 53.8976 | ||||||||
Name |
NATIONWIDE PLUMBING SRVCS 92425 OVERSEAS HWY UNIT #2 |
Longitude | 80° 30' 43.0698 | ||||||||
TAVERNIER, FL 33070 | LL Method | DPHO | |||||||||
Contact | CHRIS REY | LL Status | REVIEWED | ||||||||
Phone | (305) 853-1848 | Status Date | 09/07/2021 | ||||||||
Account Owner Information | |||||||||||
Name | NATIONWIDE PLUMBING SERVICES 97671 OVERSEAS HWY KEY LARGO, FL 33037 |
Effective Date | 09/01/2021 | ||||||||
Contact | CHRIS REY / CHRIS SANTE | ||||||||||
Phone | (305) 216-6365 | ||||||||||
INFO@NWPFLKEYS.COM | |||||||||||
Placard # / Date | 656051 - 06/08/2023 | ||||||||||
Property Owner Information | |||||||||||
Name | NATIONWIDE PLUMBING SERVICES 97671 OVERSEAS HWY KEY LARGO, FL 33037 |
Effective Date | 09/01/2021 | ||||||||
Contact | CHRIS REY / CHRIS SANTE | ||||||||||
Phone | (305) 216-6365 | ||||||||||
INFO@NWPFLKEYS.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 1000 | Vehicular Diesel (D) | 08/01/2021 | ABOVEGROUND | Removed from Site (B) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (L) Compartmented (P) Level gauges/alarms (W) Built on supports |
(A) Abv, no soil contact (B) Steel/galvanized metal (D) External protective coating (F) Double wall |
(4) Visual inspect dispenser liners (6) External piping monitoring (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 12/21/2023 | 12/21/2024 | ACE AMERICAN INSURANCE COMPANY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Enforcement Referral | 09/17/2024 | Accepted | PORTANYI_E | Enforcement | |||||||
Site Inspection | 08/20/2024 | Major Out of Compliance | PORTANYI_E | 1/0 | Routine Compliance | ||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
07/31/2024 | 7042 | SNC-B | 3.9 Storage tank system not installed with a spill containment system at each tank fill connection. Does not meet performance requirements. | Install Department-approved spill bucket to the fill port of the regulated storage tank and provide evidence to the Department. Reference the Department's equipment (EQ) list if unsure. | |||||||
11/21/2023 | 7065 | SNC-B | 1.6 Storage tank system not visually inspected once a month. | Provide monthly monitoring records for 2021, 2022, and 2023. | |||||||
11/21/2023 | 7010 | SNC-A | 1.8 No financial responsibility instrument or expired instrument for > 180 days. | Provide financial responsibility records for 2021, 2022, and 2023. | |||||||
11/21/2023 | 7007 | Minor | 3.1 Incident Notification Form (INF) not received in a timely manner. | Investigate why the vegetation around the dispenser is dead and report findings to the Department via Incident Notification Form (INF). The form has been provided via email and can also be found at the FDEP Tanks compliance website. | |||||||
11/21/2023 | 7090 | Minor | 3.15 Spill containment, dispenser liners and piping sumps not accessible; water and regulated substances not removed. | Properly dispose of liquid in dispenser holder and provide photo documentation to the Department. | |||||||
11/21/2023 | 7068 | SNC-B | 3.7 Release detection not properly installed. | Install and test release detection mechanism and provide photo evidence to the Department. | |||||||
11/21/2023 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Provide Annual Operability Test (AOT) for 2021, 2022, and 2023. | |||||||
No Discharges Found |