DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 01/22/2025        Last Data Refresh: 01/21/2025        Report Generated from DOPPLER
 
District Northwest   Type    State Government
 
County Leon   Status    OPEN
 
ID 9818753   Latitude    30° 28' 26.9385
 
Name DEPARTMENT OF CHILDREN AND FAMILIES
2415 N MONROE ST , SU#1176
Longitude    84° 17' 23.7875
  TALLAHASSEE, FL 32303 LL Method    DPHO
 
Contact PETE SHIRAH   LL Status    REVIEWED
 
Phone (850) 717-4031   Status Date    10/12/2021
 
Account Owner Information
 
Name FL DEPT OF CHILDREN & FAMILIES
2415 N MONROE ST, SU#400 RM J104
TALLAHASSEE, FL 32303
Effective Date    10/07/2021
 
Contact PETE SHIRAH | RENITA BARKLEY (DCF PROCUREMENT)
 
Phone (850) 717-4031
 
Email PETE.SHIRAH@MYFLFAMILIES.COM
  Placard # / Date    702644 - 10/25/2024
Property Owner Information
 
Name TALLAHASSEE RETAIL VENTURE
2415 N MONROE ST
TALLAHASSEE, FL 32303
Effective Date    10/07/2021
 
Contact TRACY PYKE
 
Phone (850) 688-2870
 
Email TPYKE@TALCOR.COM
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 1000 Emerg Generator Diesel (G) 12/01/2020 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
EXEMPT-STATE OR FEDERAL GOVERNMENT ENTITY  
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Electronic Communication 12/04/2024 Satisfied PROFFITT_B Enforcement
 
Letter 11/26/2024 Satisfied PROFFITT_B Enforcement
 
Electronic Communication 11/04/2024 Satisfied PROFFITT_B Enforcement
 
Electronic Communication 10/29/2024 Satisfied PROFFITT_B Enforcement
 
Enforcement Referral 09/26/2024 Accepted HATCHER_JD_1 Enforcement
 
Phone Conversation 09/19/2024 Satisfied HATCHER_JD_1 Compliance Assistance
 
Electronic Communication 09/09/2024 Satisfied HATCHER_JD_1 Routine Compliance
 
Electronic Communication 09/09/2024 Satisfied HATCHER_JD_1 Routine Compliance
 
Phone Conversation 09/09/2024 Satisfied HATCHER_JD_1 Routine Compliance
 
Site Inspection 08/30/2024 Major Out of Compliance HATCHER_JD_1 1/0 Routine Compliance
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
08/30/2024 7020 Minor 1.2 Integrity Testing of secondary containment systems and interstitial spaces not performed before being placed into service. Provide a interstice secondary containment integrity test.
 
08/30/2024 7063 SNC-A 1.5 Storage tank systems does not have appropriate testing, including breach of integrity, tightness or electronic leak detection. Release detection and overfill devices must be tested each year within the same month of previous year.
 
08/30/2024 7098 Minor 1.16 Testing shall be up-to-date and indicate proper operation before adding regulated substances to the storage tank system or returning system to service. Provide required annual testing for each year tank system has been in service.
 
08/30/2024 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Provide required annual testing for overfill device.
 
 
 