Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Northeast | Type | Retail Station | ||||||||
County | Duval | Status | OPEN | ||||||||
ID | 9819381 | Latitude | 30° 12' 17.4805 | ||||||||
Name |
DAYBREAK MARKET 6655 COLLINS ROAD |
Longitude | 81° 45' 3.2921 | ||||||||
JACKSONVILLE, FL 32244 | LL Method | DPHO | |||||||||
Contact | HANI BASKARON | LL Status | REVIEWED | ||||||||
Phone | (714) 794-7630 | Status Date | 12/22/2022 | ||||||||
Account Owner Information | |||||||||||
Name | DAYBREAK MARKET & FUEL LLC 20101 PEACHLAND BLVD PORT CHARLOTTE, FL 33954 |
Effective Date | 12/21/2022 | ||||||||
Contact | HANI BASKARON | ||||||||||
Phone | (714) 794-7630 | ||||||||||
HSBPETRO@YAHOO.COM | |||||||||||
Placard # / Date | 694291 - 06/25/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | PLAZA STREET PARTNERS (FUND 115 LLC) 2400 W 75TH ST ,SU#220 PRAIRIE VILLAGE, KS 66208 |
Effective Date | 12/21/2022 | ||||||||
Contact | BRET ELLIOT | ||||||||||
Phone | (913) 683-9459 | ||||||||||
BELLIOTT@PLAZASTREETPARTNERS.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
1 | 20000 | Ethanol E10 (8) | 01/01/2023 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (H) Mechanical line leak detector |
|||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 20000 | Unleaded Gas (B) | 01/01/2023 | UNDERGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(E) Fiberglass (I) Double wall (L) Compartmented (M) Spill containment bucket (N) Flow shut-Off (O) Tight fill (P) Level gauges/alarms |
(F) Double wall (J) Pressurized piping system (K) Dispenser liners (N) Approved synthetic material |
(3) Electronic monitor pipe sumps (4) Visual inspect dispenser liners (F) Monitor dbl wall tank space (N) Groundwater monitoring |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 09/01/2023 | 09/01/2024 | ACE AMERICAN INSURANCE COMPANY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 05/06/2025 | Satisfied | MCNEIL_A | Enforcement | |||||||
Enforcement Referral | 03/24/2025 | Accepted | AMES_J | Enforcement | |||||||
Letter | 03/14/2025 | Satisfied | VILLEGASAVILA_OE_1 | Compliance Assistance | |||||||
Site Inspection | 03/13/2025 | Major Out of Compliance | VILLEGASAVILA_OE_1 | 0/2 | Routine Compliance | ||||||
Electronic Communication | 03/12/2025 | Satisfied | VILLEGASAVILA_OE_1 | Compliance Assistance | |||||||
Record Document | 11/08/2023 | Satisfied | BRANCH_BL_1 | Installation | |||||||
Letter | 11/08/2023 | Satisfied | BRANCH_BL_1 | Installation | |||||||
Site Inspection | 11/08/2023 | In Compliance | BRANCH_BL_1 | 0/2 | Installation | ||||||
Electronic Communication | 05/08/2023 | Satisfied | BRANCH_BL_1 | Installation | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
03/25/2025 | 6003 | Minor | 2.2 Registration Form not submitted for a new system, change in service, closure, owner change, or discovery of unregistered facility. | Please complete and submit the Storage Tank Registration Form on paper or in electronic format to tankregistration@floridadep.gov, to reflect change in the owner or operator of a facility or of a storage tank system. | |||||||
03/12/2025 | 6014 | SNC-B | 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. | The facility must submit an Incident Notification Form (INF). The responsible party must determine if a discharge to the environment occurred or not. Incident investigation and resolution documentation must be provided. | |||||||
03/12/2025 | 6053 | Minor | 4.7 Primary overfill protection not provided, registered, or tested as required. | The facility must provide records for the Overfill Protection device annual operability testing from 2023 to the present. | |||||||
03/12/2025 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | The facility must remove liquid from the premium STP Sump and dispose of it properly. Furthermore, the facility must ensure that the sump sensor status is returned to normal. The responsible party must determine the source of the liquid. Post-liquid removal integrity testing may be required. Sampling may be required. Provide resolution documentation. | |||||||
03/12/2025 | 6012 | SNC-A | 2.9 No financial responsibility instrument or expired instrument for > 180 days. | The facility must provide the Financial Responsibility documentation from 2024 to the present. Documentation includes Part P State form (Certification of Financial Responsibility) and other assurance form depending on the mechanism used, e.g. Part D, Part C, etc. | |||||||
03/12/2025 | 6073 | Minor | 4.9 Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. | The facility must remove liquid from all spill buckets (E-85, Regular, E-free, Diesel, and Premium), along with the vapor recovery buckets, and dispose of it properly. The responsible party must determine the source of the liquid and if a discharge could have occurred. Provide resolution documentation and photos of interstitial gauges. Post-liquid removal integrity testing may be required. Sampling may be required. | |||||||
03/12/2025 | 6014 | SNC-B | 4.2 Incident investigation not initiated within 24-hours (or by next business day) to determine if discharge occurred. | The facility must submit an Incident Notification Form (INF). The responsible party must determine if a discharge to the environment occurred or not. Incident investigation and resolution documentation must be provided. | |||||||
03/12/2025 | 6056 | SNC-B | 2.4 Release detection not tested or visually inspected once a month or problems found during the visual inspections not recorded. | The facility must provide to the EQD inspector the records for monthly visual inspections from 2023 to the present. | |||||||
03/12/2025 | 6062 | Minor | 2.5 Release detection devices not tested annually. | The facility must provide records for the Release Detection systems' annual operability testing from 2023 to the present. | |||||||
No Discharges Found |