Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Cover Page Report | |||||||||||
Report Run Date: 05/09/2025 Last Data Refresh: 05/08/2025 Report Generated from DOPPLER | |||||||||||
District | Northwest | Type | Fuel user/Non-retail | ||||||||
County | Santa Rosa | Status | OPEN | ||||||||
ID | 9819488 | Latitude | 30° 38' 49.1328 | ||||||||
Name |
FAIRPOINT REGIONAL UTILITIES SYSTEM- WELLH7 PINEWOOD LN |
Longitude | 86° 53' 27.6814 | ||||||||
MILTON, FL 32583 | LL Method | DPHO | |||||||||
Contact | JEFF CRIGLER | LL Status | REVIEWED | ||||||||
Phone | (850) 939-2427 | Status Date | 03/29/2023 | ||||||||
Account Owner Information | |||||||||||
Name | FAIRPOINT REGIONAL UTILITIES SYSTEM PO BOX 6539 Navarre, FL 32566 |
Effective Date | 03/14/2023 | ||||||||
Contact | Jeff Crigler | ||||||||||
Phone | (850) 939-2427 | ||||||||||
DLUPOLA@HNWS-FL.COM | |||||||||||
Placard # / Date | 694064 - 06/25/2024 | ||||||||||
Property Owner Information | |||||||||||
Name | FAIRPOINT REGIONAL UTILITIES SYSTEM PO BOX 6539 Navarre, FL 32566 |
Effective Date | 03/14/2023 | ||||||||
Contact | Jeff Crigler | ||||||||||
Phone | (850) 939-2427 | ||||||||||
DLUPOLA@HNWS-FL.COM | |||||||||||
Tank | Tank Size | Content | Installed | Placement | Status | ||||||
2 | 917 | Emerg Generator Diesel (G) | 03/02/2023 | ABOVEGROUND | In Service (U) | ||||||
Constructions | Pipings | Monitorings | |||||||||
(C) Steel (I) Double wall (M) Spill containment bucket |
(A) Abv, no soil contact (B) Steel/galvanized metal (F) Double wall |
(6) External piping monitoring (F) Monitor dbl wall tank space (Q) Visual inspection of ASTs |
|||||||||
Insurance Documents | |||||||||||
FR Type | Effective Date | Expiration Date | Company Name | ||||||||
INSURANCE | 05/22/2024 | 05/22/2025 | COMMERCE AND INDUSTRY INSURANCE COMPANY | ||||||||
No Legacy Data Found | |||||||||||
Compliance Activity Information | |||||||||||
Activity Code |
Date Completed |
Results | Inspector | AST/UST Count |
Description | ||||||
Letter | 03/27/2025 | Satisfied | MILLS_KJ | Enforcement | |||||||
Enforcement Referral | 02/20/2025 | Accepted | GARTIN_D | Enforcement | |||||||
Letter | 09/16/2024 | Satisfied | PAYNE_CL_1 | Compliance Assistance | |||||||
Site Inspection | 09/16/2024 | Minor Out of Compliance | PAYNE_CL_1 | 1/0 | Installation | ||||||
Letter | 09/11/2024 | Satisfied | PAYNE_CL_1 | Compliance Assistance | |||||||
Site Inspection | 09/11/2024 | Minor Out of Compliance | PAYNE_CL_1 | 1/0 | Routine Compliance | ||||||
Electronic Communication | 09/09/2024 | Satisfied | PAYNE_CL_1 | Routine Compliance | |||||||
No Open AOCs Found | |||||||||||
Open Violations | |||||||||||
Insp Date | Vio # | Significance | Violation Text | Corrective Action | |||||||
09/16/2024 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Have the high fuel alarm, rochester fuel level gauge and overfill prevention valve tested for proper operation. Email a copy of the test results to the inspector for review. Email: Charles.Payne@flhealth.gov | |||||||
09/16/2024 | 7020 | Minor | 1.2 Integrity Testing of secondary containment systems and interstitial spaces not performed before being placed into service. | Have a technician test the spill/fill containment bucket to ensure it is liquid tight. Email a copy of the test results to the inspector for review. Email: Charles.Payne@flhealth.gov | |||||||
09/16/2024 | 7020 | Minor | 1.2 Integrity Testing of secondary containment systems and interstitial spaces not performed before being placed into service. | Have a technician test the integrity of the interstice and email a copy of the test results to the inspector for review. Email: Charles.Payne@flhealth.gov | |||||||
09/11/2024 | 7041 | Minor | 1.10 Failure to designate, register, or annually test primary overfill protection device, | Testing of the designated overfill device is overdue. The facility will need to designate a primary overfill device (either the fuel level gauge or the high fuel alarm) and that device will need to be tested annually. Email a copy of the test results to the inspector. Email: Charles.Payne@flhealth.gov | |||||||
09/11/2024 | 7072 | Minor | 1.8 Annual operability testing of release detection systems not completed. | Have a technician test the rupture basin sensor and alarm. Email a copy of the test results to the inspector for review. Email: Charles.Payne@flhealth.gov | |||||||
No Discharges Found |