DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Cover Page Report
Report Run Date: 04/19/2025        Last Data Refresh: 04/18/2025        Report Generated from DOPPLER
 
District Southeast   Type    County Government
 
County Monroe   Status    OPEN
 
ID 9819753   Latitude    24° 43' 14.5028
 
Name EOC MARATHON
7280 OVERSEAS HWY
Longitude    81° 3' 44.7127
  MARATHON, FL 33050 LL Method    DPHO
 
Contact JOHN NULL   LL Status    REVIEWED
 
Phone (305) 289-6036   Status Date    09/26/2023
 
Account Owner Information
 
Name MONROE CNTY PUBLIC WORKS DIV
3583 S Roosevelt Blvd
Key West, FL 33040-5209
Effective Date    09/22/2023
 
Contact TANIA STOUGHTON/ DAN BENSLEY
 
Phone (305) 295-3572
 
Email STOUGHTON-TANIA@MONROECOUNTY-FL.GOV
  Placard # / Date    693055 - 06/21/2024
Property Owner Information
 
Name MONROE CNTY PUBLIC WORKS DIV
3583 S Roosevelt Blvd
Key West, FL 33040-5209
Effective Date    09/22/2023
 
Contact TANIA STOUGHTON/ DAN BENSLEY
 
Phone (305) 295-3572
 
Email STOUGHTON-TANIA@MONROECOUNTY-FL.GOV
 
 
 
 
 
 
 
 
 
Tank Tank Size Content Installed Placement Status
1 2500 Emerg Generator Diesel (G) 10/01/2023 ABOVEGROUND In Service (U)
 
Constructions   Pipings Monitorings
(C) Steel   (B) Steel/galvanized metal (Q) Visual inspection of ASTs
 
 
Insurance Documents
 
FR Type   Effective Date Expiration Date Company Name
INSURANCE   05/01/2024 05/01/2025 IRONSHORE SPECIALTY INSURANCE COMPANY
 
 
No Legacy Data Found
 
 
Compliance Activity Information
 
Activity
Code
Date
Completed
Results Inspector AST/UST
Count
Description
Site Inspection 03/26/2025 Minor Out of Compliance GRON_L 1/0 Routine Compliance
 
Site Inspection 03/26/2025 Major Out of Compliance GRON_L 1/0 Installation
 
 
 
No Open AOCs Found
 
 
Open Violations
 
Insp Date Vio # Significance Violation Text Corrective Action
03/12/2025 7009 SNC-B 1.7 No financial responsibility instrument or expired instrument for < 180 days. Provide financial responsibility for 12/7/2023 to 5/1/2024.
 
03/12/2025 7043 Minor 1.11 Fillbox covers not marked according to requirements. Mark the fill port with the appropriate label and provide photo evidence to the department.
 
03/12/2025 7063 SNC-A 1.5 Storage tank systems does not have appropriate testing, including breach of integrity, tightness or electronic leak detection. Provide test results for overfill protection, release detection, spill bucket integrity, and piping integrity testing from installation.
 
03/12/2025 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Provide MVIs from December 2023 to April 2024.
 
 
 
No Discharges Found