DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/27/2025        Last Data Refresh: 04/26/2025        Report Generated from DOPPLER
 
Facility ID: 8500063
Facility Name: 253 TEXACO
 
03/28/2024 Enforcement Tracking Activity Paul, Jennifer
Activity Status: Open
03/27/2024 Enforcement Referral Activity Keim, Michael J
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/28/2024
Events:
Event Type: Activity has been submitted for approval Date: 03/27/2024
Comment: Submitted for approval by: Michael J Keim: Please accept this referral for enforcement. Attempts were made for follow up regarding the open violation discussed in the memo attached. Thank you,
Events:
Event Type: Activity has been assigned Date: 03/28/2024
Comment: Assigned to Jennifer Paul
Events:
Event Type: Activity/Document was accepted on this date Date: 03/28/2024
Comment: Accepted by Jennifer Paul: Accepted
Events:
Event Type: Activity has been finished Date: 03/28/2024
Comment: Finished
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/28/2024
Comment: Acknowledged and Assigned by Jennifer Paul
Comments:
Comment Date: 03/27/2024 User: KEIM_MJ_1
Description: Please accept this referral for enforcement. Attempts were made for follow up regarding the open violation discussed in the memo attached. Thank you, Attached documents: Last inspection report Referral Memo Sunbiz information Property appraisers card
Comments:
Comment Date: 03/27/2024 User: KEIM_MJ_1
Description: Please accept this referral for enforcement. Attempts were made for follow up regarding the open violation discussed in the memo attached. Thank you,
03/27/2024 Enforcement Referral Activity Keim, Michael J
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/28/2024
Events:
Event Type: Activity has been submitted for approval Date: 03/27/2024
Comment: Submitted for approval by: Michael J Keim: Please accept this referral for enforcement. Attempts were made for follow up regarding the open violation discussed in the memo attached. Thank you,
Events:
Event Type: Activity has been assigned Date: 03/28/2024
Comment: Assigned to Jennifer Paul
Events:
Event Type: Activity/Document was accepted on this date Date: 03/28/2024
Comment: Accepted by Jennifer Paul: Accepted
Events:
Event Type: Activity has been finished Date: 03/28/2024
Comment: Finished
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/28/2024
Comment: Acknowledged and Assigned by Jennifer Paul
Comments:
Comment Date: 03/27/2024 User: KEIM_MJ_1
Description: Please accept this referral for enforcement. Attempts were made for follow up regarding the open violation discussed in the memo attached. Thank you, Attached documents: Last inspection report Referral Memo Sunbiz information Property appraisers card
Comments:
Comment Date: 03/27/2024 User: KEIM_MJ_1
Description: Please accept this referral for enforcement. Attempts were made for follow up regarding the open violation discussed in the memo attached. Thank you,
12/27/2023 Violation Open Keim, Michael J
Significance: Minor Status: Open
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
12/27/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 12/27/2023 Activity Status: Closed
Date: 12/27/2023
Recipient: Wenda Lewis
Sender: M Keim
Subject: TCI
Message: E-mail correspondence with Wenda Lewis regarding TCI scheduling and records needed.
Events:
Event Type: Activity has been finished Date: 12/27/2023
Comment: Finished
12/27/2023 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Description: Issued Warning Letter
Events:
Event Type: Activity has been finished Date: 12/27/2023
Comment: Finished
Events:
Event Type: Document has been sent Date: 12/27/2023
Comment: Sent
Attachments:
Attachment Date: 12/27/2023 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
12/27/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 12/27/2023 Activity Status: Closed
Date: 12/27/2023
Recipient: Wenda Lewis
Sender: M Keim
Subject: TCI report
Message: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com
Events:
Event Type: Activity has been finished Date: 12/27/2023
Comment: Finished
12/27/2023 Site Inspection Activity Closed Keim, Michael J
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 12/05/2023
Activity Closed Date: 12/27/2023 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 12/27/2023
Comment: Finished
Comments:
Comment Date: 12/27/2023 User: KEIM_MJ_1
Description: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com Compliance assist with Aron of ARC Dynamics
12/27/2023 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
12/27/2023 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 6024
Rule: 62-761.500(1)(b)4, 62-761.500(1)(b)5, 62-761.500(1)(b)6, 62-761.500(1)(b)7
08/19/2022 Record Document Activity Harrington, Richard D.
Activity Status: Closed
Contact Name: wenda lewis Activity Closed Date: 08/19/2022
Events:
Event Type: Activity has been finished Date: 08/19/2022
Comment: Finished
06/02/2022 Comment Zimmerman, Robert A
Description: Wenda Lewis cell (352) 339.4048
09/27/2021 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Wenda Lewis Activity Closed Date: 09/27/2021
Events:
Event Type: Activity has been finished Date: 09/27/2021
Comment: Finished
08/29/2021 Violation Closed Keim, Michael J
Significance: SNC-B Status: Closed
Criteria ID: 6011
Rule: 62-761.420(2)
08/29/2021 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 08/29/2021 Activity Status: Closed
Date: 08/29/2021
Recipient: Wenda Lewis
Sender: M Keim
Subject: TCI report
Message: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com
Events:
Event Type: Activity has been finished Date: 08/29/2021
Comment: Finished
08/29/2021 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 08/29/2021 Activity Status: Closed
Date: 08/29/2021
Recipient: Joe Long
Sender: M Keim
Subject: TCI
Message: E-mail correspondence regarding TCI scheduling and records needed.
Events:
Event Type: Activity has been finished Date: 08/29/2021
Comment: Finished
08/29/2021 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 08/29/2021
Comment: Sent
Events:
Event Type: Activity has been finished Date: 08/29/2021
Comment: Finished
Attachments:
Attachment Date: 08/29/2021 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
08/13/2021 Site Inspection Activity Closed Keim, Michael J
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 08/13/2021
Activity Closed Date: 08/29/2021 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 08/29/2021
Comment: Finished
Comments:
Comment Date: 08/29/2021 User: KEIM_MJ_1
Description: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com Compliance assist with Jesse Wilkinson
11/17/2019 Electronic Communication Activity Harrington, Richard D.
Activity Closed Date: 11/17/2019 Activity Status: Closed
Date: 11/17/2019
Recipient: wenda lewis, joe long
Sender: rh
Subject: sent 2019 tci and cao
Message: -
Events:
Event Type: Activity has been finished Date: 11/17/2019
Comment: Finished
11/10/2019 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 4079
Rule: 62-761.710(2), 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d)
11/10/2019 Editable Letter Activity Harrington, Richard D.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 11/17/2019
Comment: Finished
Events:
Event Type: Document has been sent Date: 11/17/2019
Comment: Sent
Attachments:
Attachment Date: 11/17/2019 User: HARRINGTON_RD_1
Description: CAO 2019
View Attachment
11/10/2019 Site Inspection Activity Closed Harrington, Richard D.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 11/04/2019
Activity Closed Date: 11/10/2019 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 11/10/2019
Comment: Finished
Comments:
Comment Date: 11/10/2019 User: HARRINGTON_RD_1
Description: Report and CAO Letter to be emailed to Wenda Lewis and Joe Long.
11/10/2019 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
11/10/2019 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 4068
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1., 62-761.700(1)(a)2.
11/10/2019 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 4057
Rule: 62-761.500(7)(e)
05/17/2017 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 05/17/2017 Activity Status: Closed
Date: 05/17/2017
Recipient: Wenda Lewis
Sender: Robert Zimmerman
Subject: TCI Report.
Message: Sent TCI report email attachment to facility representative.
Events:
Event Type: Activity has been finished Date: 05/17/2017
Comment: Finished
05/11/2017 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/11/2017
Activity Closed Date: 05/17/2017 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 05/17/2017
Comment: Finished
Comments:
Comment Date: 05/11/2017 User: ZIMMERMAN_RA_2
Description: Sent TCI report email attachment to facility representative.
Comments:
Comment Date: 05/11/2017 User: ZIMMERMAN_RA_2
Description: Have discussed modification to the UST and AST rule and presented the UST and AST outreach tool with facility representative.
05/11/2017 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/11/2017
Activity Closed Date: 05/17/2017 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 05/17/2017
Comment: Finished
Comments:
Comment Date: 05/11/2017 User: ZIMMERMAN_RA_2
Description: Sent TCI report email attachment to facility representative.
Comments:
Comment Date: 05/11/2017 User: ZIMMERMAN_RA_2
Description: Have discussed modification to the UST and AST rule and presented the UST and AST outreach tool with facility representative.
05/01/2017 Phone Conversation Activity Zimmerman, Robert A
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 339-4839 Activity Closed Date: 05/01/2017
Subject: Contact facility representative for notification and schedule upcoming TCI.
Events:
Event Type: Activity has been finished Date: 05/01/2017
Comment: Finished
08/25/2015 Phone Conversation Activity Harrington, Richard D.
Call Type: Incoming Activity Status: Closed
Phone Number: (352) 339-4839 Activity Closed Date: 08/25/2015
Subject: Recd call from Agustin Andres (LOC). The diesel sump lid has now been replaced and the leak detector test valves in dispenser 4 have been removed.
Events:
Event Type: Activity has been finished Date: 08/25/2015
Comment: Finished
03/31/2015 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
03/31/2015 Editable Letter Activity Harrington, Richard D.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: In Compliance Letter
Events:
Event Type: Activity has been finished Date: 04/02/2015
Comment: Finished
Attachments:
Attachment Date: 04/02/2015 User: HARRINGTON_RD_1
Description: ncl
View Attachment
03/31/2015 Site Inspection Activity Closed Harrington, Richard D.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/30/2015
Activity Closed Date: 03/31/2015 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 03/31/2015
Comment: Finished
Comments:
Comment Date: 03/31/2015 User: HARRINGTON_RD_1
Description: E-mailed report and ncl to Wenda Lewis 3/31/2015.
03/31/2015 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 1059
Rule: 62-761.600(1)(a)2.
Comments: Mark this as out of compliance if release detection systems are not functioning or not maintained properly. The inspector will have to know what release detection components have been installed at the facility. Furthermore, develop a library of installation and system operation specifications. These documents will assist you in determining calibration/maintenance as required by the manufacturer. Additional guidance can be found in the Appendix sections of the USEPA "List of Leak Detection Evaluations for Underground Storage Tank Systems" and the DEP Master Equipment List. Installations - have the release detection components been function tested? Just because a piece of equipment is new out of the box does not mean it is fully functional. Have it demonstrated! Calibration/Maintenance - the facility must provide documentation attesting to these operability tests. Operation - The RDRL must be developed, and the facility personnel must be knowledgeable of all the components of the release detection system. Theoretically, they should be able to demonstrate to you how they monitor the release detection system. See rule 62-761.700(1)(c)3
04/08/2013 Record Document Activity Harrington, Richard D.
Activity Status: Closed
Contact Name: wenda lewis Activity Closed Date: 04/08/2013
Events:
Event Type: Activity has been finished Date: 04/08/2013
Comment: Finished
03/20/2013 Record Document Activity Harrington, Richard D.
Activity Status: Closed
Contact Name: wenda lewis Activity Closed Date: 03/20/2013
Events:
Event Type: Activity has been finished Date: 03/20/2013
Comment: Finished
02/11/2013 Editable Letter Activity Harrington, Richard D.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: Compliance Assistance Offer Letter
Events:
Event Type: Document has been sent Date: 02/11/2013
Comment: Sent on Mon Feb 11 00:00:00 EST 2013
Events:
Event Type: Activity has been finished Date: 02/11/2013
Comment: Finished
Attachments:
Attachment Date: 02/11/2013 User: HARRINGTON_RD_1
Description: ncl
View Attachment
02/11/2013 Electronic Communication Activity Harrington, Richard D.
Activity Closed Date: 02/11/2013 Activity Status: Closed
Date: 02/11/2013
Recipient: wenda lewis, agustin andreas
Sender: rh
Subject: sent report and ncl
Message: -
Events:
Event Type: Activity has been finished Date: 02/11/2013
Comment: Finished
02/08/2013 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
02/08/2013 Site Inspection Activity Closed Harrington, Richard D.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/05/2013
Activity Closed Date: 02/11/2013 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 02/11/2013
Comment: Finished
02/08/2013 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 1020
Rule: 62-761.500(1)(d)5.
Comments: The breach of integrity test is intended for closed interstices only. A closed interstice has no unsecured or unsealed opening to the outside. Double-walled piping without a boot connector, or if the boot has a bleed valve (for tightness testing), is considered an open interstice. The breach of integrity test may be performed by using at least one of the following methods: a. A continuous hydrostatic system b. A continuous vacuum system c. Testing of the interstice for liquid tightness in accordance with manufacturer's installation instructions; or d. Another method in accordance with subsection 62-761.850(2). How the breach of integrity test is performed or to what degree can depend on the depth to groundwater at each facility. When the tank and or piping are fully submerged, the lack of water intrusion into the secondary containment may be considered a verification of its integrity. However, when total submersion is not the case, one of the rule stipulated options must be used. The breach of integrity test should not be confused with a precision tightness test, which tests the primary tank or piping only. The breach of integrity test will test the secondary and primary shells, but is not a precision test.
06/01/2011 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/01/2011
Activity Closed Date: 06/07/2011 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 06/07/2011
Comment: Finished
06/01/2011 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/01/2011
Events:
Event Type: Activity has been finished Date: 06/01/2011
Comment: Finished
05/20/2010 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 05/20/2010
Events:
Event Type: Activity has been finished Date: 05/20/2010
Comment: Finished
05/19/2010 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/19/2010
Activity Closed Date: 05/19/2010 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 05/19/2010
Comment: Finished
Comments:
Comment Date: 05/19/2010 User: OWENS_JS_1
Description: MLLD's due next month
07/02/2009 TCAR Activity Ramsey, Timothy H
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 07/02/2009
07/02/2009 Editable Letter Activity Ramsey, Timothy H
Activity Title: Closure Review Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 07/02/2009
Comment: Sent on Thu Jul 02 10:22:26 EST 2009
Comments:
Comment Date: 07/02/2009 User: RAMSEY_TH_1
Description: Alternate Closure Review Letter issued on July 2, 2009
06/15/2009 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/15/2009
05/12/2009 Attachment Owens, Joe S.
05/11/2009 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/11/2009
Activity Closed Date: 08/19/2009 Activity Closed By: OWENS_JS_1
03/03/2009 Record Document Activity Dohaney, Tim
Activity Status: Closed
Contact Name: rp Activity Closed Date: 03/03/2009
12/10/2008 Enforcement Referral Activity Dohaney, Tim
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 12/10/2008
Events:
Event Type: Activity/Document was accepted on this date Date: 12/10/2008
Comment: self referred
Events:
Event Type: Activity/Document was acknowledged on this date Date: 12/10/2008
Comment: self referred
Events:
Event Type: Activity has been submitted for approval Date: 12/10/2008
Comment: self referred due to fr issue and dep policy
Comments:
Comment Date: 12/10/2008 User: DOHANEY_T
Description: self referred
Comments:
Comment Date: 12/10/2008 User: DOHANEY_T
Description: self referred
Comments:
Comment Date: 12/10/2008 User: DOHANEY_T
Description: self referred due to fr issue and dep policy
12/10/2008 Issue Document Activity Dohaney, Tim
Activity Status: Closed
Contact Name: dohaney_t Activity Closed Date: 12/10/2008
12/10/2008 Enforcement Tracking Activity Dohaney, Tim
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 03/03/2009
12/10/2008 Enforcement Referral Activity Dohaney, Tim
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 12/10/2008
Events:
Event Type: Activity/Document was accepted on this date Date: 12/10/2008
Comment: self referred
Events:
Event Type: Activity/Document was acknowledged on this date Date: 12/10/2008
Comment: self referred
Events:
Event Type: Activity has been submitted for approval Date: 12/10/2008
Comment: self referred due to fr issue and dep policy
Comments:
Comment Date: 12/10/2008 User: DOHANEY_T
Description: self referred
Comments:
Comment Date: 12/10/2008 User: DOHANEY_T
Description: self referred
Comments:
Comment Date: 12/10/2008 User: DOHANEY_T
Description: self referred due to fr issue and dep policy
12/10/2008 Enforcement Referral Activity Dohaney, Tim
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 12/10/2008
Events:
Event Type: Activity/Document was accepted on this date Date: 12/10/2008
Comment: self referred
Events:
Event Type: Activity/Document was acknowledged on this date Date: 12/10/2008
Comment: self referred
Events:
Event Type: Activity has been submitted for approval Date: 12/10/2008
Comment: self referred due to fr issue and dep policy
Comments:
Comment Date: 12/10/2008 User: DOHANEY_T
Description: self referred
Comments:
Comment Date: 12/10/2008 User: DOHANEY_T
Description: self referred
Comments:
Comment Date: 12/10/2008 User: DOHANEY_T
Description: self referred due to fr issue and dep policy
11/24/2008 Attachment Owens, Joe S.
10/30/2008 Editable Letter Activity Owens, Joe S.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
09/04/2008 Violation Closed Owens, Joe S.
Significance: SNC-B Status: Closed
Criteria ID: 1004
Rule: 62-761.400(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2).
09/04/2008 Editable Letter Activity Owens, Joe S.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
09/04/2008 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/04/2008
09/02/2008 Site Inspection Activity Closed Owens, Joe S.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 09/02/2008
Activity Closed Date: 09/04/2008 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 09/04/2008 User: OWENS_JS_1
Description: Visual inspection conducted w/ Brad Wentworth - AET Inc. compliance contractor. Inspection form completed offsite w/ NCL - both E-mailed to Alan Fogg owner & Dana Spence - AET Inc.
08/31/2007 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/31/2007
Activity Closed Date: 08/31/2007 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 08/31/2007 User: OWENS_JS_1
Description: CONTACT PRESENTED DOCUMENTS FOR REVIEW FOR FAC: 8500063 Placard current & displayed: OK CFR form complete - FR records are updated - OK RDRL - present and applicable for facility: TANKS; Elect. monitoring of tank by ATG w/ 3yr. tank tite test. / PIPING; Visual monitoring of piping interstice within STP sumps. MLLD. All disp. liners, spill buckets visual inspection. Site Diagram for accuracy, attached to ATTACHMENT Facility information. No changes frm. last TCI. Facility registration information including tank system attributes appear to be accurate. Monthly release detection records - Accepted - daily status printouts reviewed - periodic tank test is not possible during first 7 days of month, therefore inspect the facility after the 8th of the month so that a passing test for the month is acheived - it is advised to have the inspection date the same as the printout date. Date range for Inspection records: 9/2006 to present No Monthly ATG alarm status documented on insp. form - all systems normal w/ printout to verify - OK FUTURE DUE DATES OF FOLLOWING: Tank Insurance Renewal Due: 7/2008 MLLD annual testing due - 10/2007 Placard Registration renewal due: 6/2008 Tank Tite test due - 12/2007 Visual inspection revealed: STP sumps (3) are dry and clean, Spill buckets contain a trace of fuel but appear maintained - with positive shut-off overfill devices. Dispenser liners (2) are dry with no trace of any release, no issues addressed during monthly visual inspections. Monthly inspections should document any maint. which is performed or recommended as needed to prevent any release. The entry boots on the piping within the sumps and disp. liners appear sound and flexible ¿ no cracks observed. Facility has a documented release and is currently scored a 11 - below current clean-up work status. The compliance inspection folder is complete and concise from present operator- RDRL is posted and is applicable for facility - Facility inspection records well maintained. Brad Wentworth - compliance inspector onsite for inspection - AET Inc. is compliance contractor - form completed offsite following inspection - copy of report to Beth Fleming; AET Inc.
08/31/2007 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 08/31/2007
02/08/2007 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/08/2007
12/21/2006 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/21/2006
Activity Closed Date: 12/21/2006 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 12/21/2006 User: OWENS_JS_1
Description: DOCUMENTS REVIEWED: Placard displayed and current CFR form complete -OK - FR record updated. RDRL - present and applicable for facility - TANKS: ATG w/CSLD for tanks,Tank tite test every 3 years; PIPING: visual inspection of sumps, dispenser liners, spill buckets. Site Diagram for accuracy, attached to facility level ATTACHMENTS. Facility registration information including tank system attributes appear to be accurate. Monthly release detection records printouts are retained for documentation - Accepted. FILL ports have positive shut-off overfill devices installed for overfill prevention. Spill buckets clean and dry - OK Previous TCI date: 12/2005 Date range for Inspection records: 12/2005 to present Tank tite test performed- 12/08/2004 - due again 12/2007 ADVISED CONTACT OF FOLLOWING: MLLD required testing due:11/2007 Tank Tite test due:12/2007 Tank Insurance Renewal Due: 07/2007 Placard Registration renewal due: 6/2007 REMINDER FOR SINGLE-WALL TANK OWNERS - UPGRADE DEADLINE 12/2009. Visual inspection revealed clean sumps & spill buckets - well maintained. Fill covers recently painted although this facility has a large amount of traffic. Placard posted in stock room next to RDRL. Flapper devices in Fill appear to be operational w/ no visible defects. Records complete.
Comments:
Comment Date: 12/21/2006 User: OWENS_JS_1
Description: Walter Gammon - compliance contact for AET Inc. onsite for inspection.
12/21/2006 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/21/2006
Activity Closed Date: 12/21/2006 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 12/21/2006 User: OWENS_JS_1
Description: DOCUMENTS REVIEWED: Placard displayed and current CFR form complete -OK - FR record updated. RDRL - present and applicable for facility - TANKS: ATG w/CSLD for tanks,Tank tite test every 3 years; PIPING: visual inspection of sumps, dispenser liners, spill buckets. Site Diagram for accuracy, attached to facility level ATTACHMENTS. Facility registration information including tank system attributes appear to be accurate. Monthly release detection records printouts are retained for documentation - Accepted. FILL ports have positive shut-off overfill devices installed for overfill prevention. Spill buckets clean and dry - OK Previous TCI date: 12/2005 Date range for Inspection records: 12/2005 to present Tank tite test performed- 12/08/2004 - due again 12/2007 ADVISED CONTACT OF FOLLOWING: MLLD required testing due:11/2007 Tank Tite test due:12/2007 Tank Insurance Renewal Due: 07/2007 Placard Registration renewal due: 6/2007 REMINDER FOR SINGLE-WALL TANK OWNERS - UPGRADE DEADLINE 12/2009. Visual inspection revealed clean sumps & spill buckets - well maintained. Fill covers recently painted although this facility has a large amount of traffic. Placard posted in stock room next to RDRL. Flapper devices in Fill appear to be operational w/ no visible defects. Records complete.
Comments:
Comment Date: 12/21/2006 User: OWENS_JS_1
Description: Walter Gammon - compliance contact for AET Inc. onsite for inspection.
09/22/2006 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/22/2006
09/14/2006 Attachment Owens, Joe S.
09/14/2006 Attachment Owens, Joe S.
02/10/2006 Legacy Activity Ramsey, Timothy H
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: PREMIUM SUMP LID REPLACED
12/07/2005 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 761.700(1)(a)1
12/07/2005 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: MLLD TEST 11/29/05, TANK TIGHTNESS TEST DUE 12/07
02/23/2005 Legacy Activity Ramsey, Timothy H
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: PROPER OVERFILL INSTALLED IN DIESEL TANK, RECORDS REVIEWED
12/14/2004 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 761.710(2)
12/14/2004 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: LLD TEST 12/8/04
12/14/2004 Violation Closed Ramsey, Timothy H
Significance: SNC-B Status: Closed
Rule: 761.500(5)(b)
09/30/2003 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: LLD TEST 3/5/03
11/06/2002 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: LLD TEST 12/4/01, ANNUAL OPERABILITY TEST 11/6/02
12/10/2001 Legacy Activity Ramsey, Timothy H
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: RESPONSE RECEIVED BY DEPARTMENT
11/13/2001 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 700(1)(c)3
11/13/2001 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE INSPECTION
11/01/2000 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE INSPECTION
09/11/2000 Legacy Activity Ramsey, Timothy H
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE REINSPECTION
06/05/2000 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 600(1)(k)
06/05/2000 Legacy Activity Ramsey, Timothy H
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE REINSPECTION
06/05/2000 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 600(1)(k)
03/22/2000 Legacy Activity Dohaney, Tim
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
09/21/1999 Violation Closed Buono, Mike
Significance: SNC-B Status: Closed
Rule: 600(1)(g)
Comments:
Comment Date: 03/15/2012 User: TOWLE_M
Description: CFR and CFO letter dated 1-11-12.
09/21/1999 Legacy Activity Buono, Mike
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/17/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 600(1)(e)
06/17/1999 Legacy Activity Buono, Mike
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
06/17/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 700(1)(c)1
Comments:
Comment Date: 03/10/2006 User: UNKNOWN
Description: COMMUNICATION: TO: LASHBROOK_S, SITE MANAGER Email: scott_lashbrook2@doh.state.fl.us Email Date: 03/10/2006 ACTIVITY ID: 11702970 - TANK ANNUAL COMPLIANCE INSPECTION WAS PERFORMED AT FACILITY ID: 9100063 ON 02/17/2006 BY ROGGELIN. EVALUATION RESULT = IN-COMPLIANCE. ACTIVITY RECORDED ON 03/10/2006 USER: ERNEST ROGGELIN OF PINELLAS COUNTY HEALTH DEPARTMENT
04/22/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 800(4)(c)
04/22/1999 Legacy Activity Buono, Mike
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/22/1999 Violation Closed Buono, Mike
Significance: SNC-B Status: Closed
Rule: 450(3)(a)
Attachments:
Attachment Date: 08/07/2007 User: TRETHEWEY_MB_1
Description: 8-7-2007 SITE PHOTO (3080)
View Attachment
Attachments:
Attachment Date: 08/07/2007 User: TRETHEWEY_MB_1
Description: 8-7-07 SITE PHOTO (58805-58806-58807)
View Attachment
Attachments:
Attachment Date: 04/22/2019 User: TRETHEWEY_MB_1
Description: Site Diagram & equipment Locations
View Attachment
Attachments:
Attachment Date: 03/23/2022 User: TRETHEWEY_MB_1
Description: TCI 3-23-22 photo update 2
View Attachment
Attachments:
Attachment Date: 03/23/2022 User: TRETHEWEY_MB_1
Description: TCI 3-23-22 photo update 1
View Attachment
04/22/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 700(1)(c)6
04/22/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 700(1)(c)1
Comments:
Comment Date: 06/25/2008 User: CONDOLEON_GJ_1
Description: Major Parts List and EQ numbers: Tank(s) - (EQ-191) Two Containment Solutions 10,000 gal. double wall fiberglass STP Sump- (EQ-578) Fiberlite Composites Dispenser Sumps (EQ-439) Environ Spill Bucket- (EQ- 224) OPW Overfill Protection- (EQ-414) Emco Wheaton A1100 Piping- (EQ-511) OPW (Environ) PGF-2150/C15 Tank Monitor (EQ- 596, 614) Veeder Root TLS 350 Line Leak Detector (EQ-329) Vaporless
Comments:
Comment Date: 02/08/2007 User: CONDOLEON_GJ_1
Description: This facility consists of 2-10,000 gallon single wall cathodically protected steel underground storage tanks containing gasoline. The piping for the regular tank is Environ Geoflex-D (EQ-511). The piping for the premium tank is Total Containment blue flex pipe in a tight chase pipe.
04/22/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 700(1)(c)1
Comments:
Comment Date: 06/25/2008 User: CONDOLEON_GJ_1
Description: Major Parts List and EQ numbers: Tank(s) - (EQ-191) Two Containment Solutions 10,000 gal. double wall fiberglass STP Sump- (EQ-578) Fiberlite Composites Dispenser Sumps (EQ-439) Environ Spill Bucket- (EQ- 224) OPW Overfill Protection- (EQ-414) Emco Wheaton A1100 Piping- (EQ-511) OPW (Environ) PGF-2150/C15 Tank Monitor (EQ- 596, 614) Veeder Root TLS 350 Line Leak Detector (EQ-329) Vaporless
Comments:
Comment Date: 02/08/2007 User: CONDOLEON_GJ_1
Description: This facility consists of 2-10,000 gallon single wall cathodically protected steel underground storage tanks containing gasoline. The piping for the regular tank is Environ Geoflex-D (EQ-511). The piping for the premium tank is Total Containment blue flex pipe in a tight chase pipe.
04/22/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 600(1)(a)1
Comments:
Comment Date: 11/14/2005 User: UNKNOWN
Description: GENERAL: PIPING: ABOVEGROUND SINGLE WALL STEEL PIPING. TANKS: 6-24000 GALLON ASTS ARE PE CERTIFIED THAT THE MEET THE CONSTRUCTION REQUIREMENTS OF UL-142 TANKS.
Attachments:
Attachment Date: 05/11/2020 User: JARRETT_SE_1
Description: 2020-04-30 Tank Field (Looking SE).
View Attachment
Attachments:
Attachment Date: 05/11/2020 User: JARRETT_SE_1
Description: 2020-04-30 Tank Field (WSW)
View Attachment
Attachments:
Attachment Date: 05/11/2020 User: JARRETT_SE_1
Description: 2020-04-30 Updated Facility Site Map.
View Attachment
Attachments:
Attachment Date: 05/11/2020 User: JARRETT_SE_1
Description: 2020-04-30 Truck & Railroad Loading Racks.
View Attachment
Attachments:
Attachment Date: 05/11/2020 User: JARRETT_SE_1
Description: 2020-04-30 Truck & Railroad Loading Racks.
View Attachment
04/22/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 820(2)(a)
Comments:
Comment Date: 06/26/2015 User: MERRYMAN_DT_1
Description: Contact Travis Fowler at 863-965-7733 x84089 or 863-559-8450 to schedule routine compliance inspections.
Comments:
Comment Date: 09/18/2003 User: UNKNOWN
Description: GENERAL: PIPING: ABOVEGROUND SINGLE-WALL PAINTED STEEL
04/22/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 820(2)(a)
Comments:
Comment Date: 06/26/2015 User: MERRYMAN_DT_1
Description: Contact Travis Fowler at 863-965-7733 x84089 or 863-559-8450 to schedule routine compliance inspections.
Comments:
Comment Date: 09/18/2003 User: UNKNOWN
Description: GENERAL: PIPING: ABOVEGROUND SINGLE-WALL PAINTED STEEL
02/26/1999 Legacy Activity Buono, Mike
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
02/15/1999 Legacy Activity Buono, Mike
Activity Name: TANK CLOSURE INSPECTION Activity Status: Closed
11/05/1997 Violation Closed Unknown, User
Significance: SNC-A Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
11/05/1997 Legacy Activity Carawan, Lorraine S.
Activity Name: UST ROUTINE COMPLIANCE INSPECTION Activity Status: Closed