DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/20/2025        Last Data Refresh: 04/19/2025        Report Generated from DOPPLER
 
Facility ID: 8500142
Facility Name: LOC CARDLOCK 23RD AVE
 
02/27/2025 Violation Open Keim, Michael J
Significance: Minor Status: Open
Criteria ID: 6024
Rule: 62-761.500(1)(b)4, 62-761.500(1)(b)5, 62-761.500(1)(b)6, 62-761.500(1)(b)7
02/27/2025 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 02/27/2025 Activity Status: Closed
Date: 02/27/2025
Recipient: Wenda Lewis, Chris Leonard
Sender: M Keim
Subject: TCI
Message: E-mail correspondence with Wenda Lewis of Lewis Oil and Chris Leonard of ARC Dynamics regarding TCI scheduling and records needed.
Events:
Event Type: Activity has been finished Date: 02/27/2025
Comment: Finished
02/27/2025 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 02/27/2025
Comment: Sent
Events:
Event Type: Activity has been finished Date: 02/27/2025
Comment: Finished
Attachments:
Attachment Date: 02/27/2025 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
02/27/2025 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 02/27/2025 Activity Status: Closed
Date: 02/27/2025
Recipient: Wenda Lewis, Chris Leonard
Sender: M Keim
Subject: TCI report
Message: Storage tank compliance report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com
Events:
Event Type: Activity has been finished Date: 02/27/2025
Comment: Finished
02/27/2025 Site Inspection Activity Closed Keim, Michael J
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/13/2025
Activity Closed Date: 02/27/2025 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 02/27/2025
Comment: Finished
Comments:
Comment Date: 02/27/2025 User: KEIM_MJ_1
Description: Storage tank compliance report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com Compliance assist with Chris Leonard of ARC Dynamics
02/27/2025 Violation Open Keim, Michael J
Significance: Minor Status: Open
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
02/27/2025 Violation Open Keim, Michael J
Significance: Minor Status: Open
Criteria ID: 6066
Rule: 62-761.700(1)(c), 62-761.700(1)(c)1, 62-761.700(1)(c)2
03/11/2024 Enforcement Tracking Activity Dallas, Richard D
Activity Status: Open
05/15/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 05/15/2023 Activity Status: Closed
Date: 05/15/2023
Recipient: M Keim
Sender: Wenda Lewis
Subject: Violation status
Message: Received e-mail correspondence regarding violation status. see comments
Events:
Event Type: Activity has been finished Date: 05/15/2023
Comment: Finished
05/15/2023 Enforcement Referral Activity Keim, Michael J
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/11/2024
Events:
Event Type: Activity/Document was accepted on this date Date: 03/11/2024
Comment: Accepted by Richard D Dallas: Accepted
Events:
Event Type: Activity has been finished Date: 03/11/2024
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 05/15/2023
Comment: Submitted for approval by: Michael J Keim: Please accept this referral as several attempts have been made to have the violations resolved. Some progress has been made though no records or testing documents have been received yet. I have attached the referral memorandum for your review.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 02/29/2024
Comment: Acknowledged and Assigned by Brierra Mack
Events:
Event Type: Activity has been assigned Date: 02/29/2024
Comment: Assigned to Richard D Dallas
Comments:
Comment Date: 05/15/2023 User: KEIM_MJ_1
Description: Please accept this referral as several attempts have been made to have the violations resolved. Some progress has been made though no records or testing documents have been received yet. I have attached the referral memorandum for your review.
Comments:
Comment Date: 05/15/2023 User: KEIM_MJ_1
Description: Please accept this referral as several attempts have been made to have the violations resolved. Some progress has been made though no records or testing documents have been received yet. I have attached the referral memorandum for your review.
05/15/2023 Enforcement Referral Activity Keim, Michael J
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/11/2024
Events:
Event Type: Activity/Document was accepted on this date Date: 03/11/2024
Comment: Accepted by Richard D Dallas: Accepted
Events:
Event Type: Activity has been finished Date: 03/11/2024
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 05/15/2023
Comment: Submitted for approval by: Michael J Keim: Please accept this referral as several attempts have been made to have the violations resolved. Some progress has been made though no records or testing documents have been received yet. I have attached the referral memorandum for your review.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 02/29/2024
Comment: Acknowledged and Assigned by Brierra Mack
Events:
Event Type: Activity has been assigned Date: 02/29/2024
Comment: Assigned to Richard D Dallas
Comments:
Comment Date: 05/15/2023 User: KEIM_MJ_1
Description: Please accept this referral as several attempts have been made to have the violations resolved. Some progress has been made though no records or testing documents have been received yet. I have attached the referral memorandum for your review.
Comments:
Comment Date: 05/15/2023 User: KEIM_MJ_1
Description: Please accept this referral as several attempts have been made to have the violations resolved. Some progress has been made though no records or testing documents have been received yet. I have attached the referral memorandum for your review.
05/15/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 05/15/2023 Activity Status: Closed
Date: 05/15/2023
Recipient: M Keim
Sender: Shawn Crain
Subject: Violations status
Message: Received e-mail regarding some progress regarding violations (see comments)
Events:
Event Type: Activity has been finished Date: 05/15/2023
Comment: Finished
Comments:
Comment Date: 05/15/2023 User: KEIM_MJ_1
Description: Shawn Crain Wenda Lewis Michael Keim CAUTION: This email originated from outside your organization. Exercise caution when opening attachments or clicking links, especially from unknown senders. Mr. Michael on 1942 NE 23 Ave I am trying to round up the Paper work and Pics for this site . My Guys Went out and Test all Sensors for Operability , They removed the Ball Valve that was improperly install above the Shear Valve . NO we do Have a Conduit in the Dispenser Sump that we are getting the Electricians out to it has Snapped Off but the Cabling is all Intact We also are changing Out one of the Probes . Tech went out and tested for Operability and move the Probe to other position and problem followed this should be getting Completed today and I should have the Operability paper work for this probe today . West gate Food Mart . Dispenser Sumps/Stp Sump Are metal and I need to have these changed out , I am finishing up this quote , I have reached out to the DEP to Confirm if we can do a Spray In Liner to the Dispenser Sumps in Order to provide them some Integrity while we are getting in the Sumps to Change them Out . I should have a Response as of today . this will be a Minimum of about 4 Weeks before I can get any replacement sumps in for this site to get these issues corrected . Please advise if you have any questions . Shawn Crain Guardian Fueling technologies Cell Phone # 904-237-5165
05/15/2023 Phone Conversation Activity Keim, Michael J
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 339-4048 Activity Closed Date: 05/15/2023
Subject: Spoke with Wenda regarding violation status. Informed that Guardian Fueling has been working on the violations and will receive update from Shawn Crain regarding work completed.
Events:
Event Type: Activity has been finished Date: 05/15/2023
Comment: Finished
05/15/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 05/15/2023 Activity Status: Closed
Date: 05/15/2023
Recipient: M Keim
Sender: Wenda Lewis
Subject: Violation status
Message: Received e-mail from Wenda Lewis regarding violations being resolved. see comments
Events:
Event Type: Activity has been finished Date: 05/15/2023
Comment: Finished
Comments:
Comment Date: 05/15/2023 User: KEIM_MJ_1
Description: Wenda Lewis Michael Keim Shawn Crain CAUTION: This email originated from outside your organization. Exercise caution when opening attachments or clicking links, especially from unknown senders. OK, Guardian has the parts and are on it now…
04/29/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 04/29/2023 Activity Status: Closed
Date: 04/29/2023
Recipient: Wenda Lewis
Sender: M Keim
Subject: Outreach regarding violations
Message: Wenda, I just wanted to reach out and remind you that the (3) facilities listed have violations reaching the 90 day limit before referral to enforcement. Please forward any information regarding the correction of the violations to me as soon as possible. I have attached the last inspection reports for your review. Thank you, 8500142 23rd Ave. Cardlock 8500220 Westgate 8500282 Chevron High Springs
Events:
Event Type: Activity has been finished Date: 04/29/2023
Comment: Finished
01/31/2023 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 7030
Rule: 62-762.501(1)(f), 62-762.502(1)(f)
01/31/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 01/31/2023 Activity Status: Closed
Date: 01/31/2023
Recipient: Wenda Lewis
Sender: M Keim
Subject: TCI report
Message: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com
Events:
Event Type: Activity has been finished Date: 01/31/2023
Comment: Finished
01/31/2023 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/31/2023
Comment: Finished
Events:
Event Type: Document has been sent Date: 01/31/2023
Comment: Sent
Attachments:
Attachment Date: 01/31/2023 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
01/31/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 01/31/2023 Activity Status: Closed
Date: 01/31/2023
Recipient: Wenda Lewis
Sender: M Keim
Subject: TCI
Message: E-mail correspondence with Wenda Lewis regarding TCI scheduling and records needed.
Events:
Event Type: Activity has been finished Date: 01/31/2023
Comment: Finished
01/31/2023 Site Inspection Activity Closed Keim, Michael J
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/23/2023
Activity Closed Date: 01/31/2023 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 01/31/2023
Comment: Finished
Comments:
Comment Date: 01/31/2023 User: KEIM_MJ_1
Description: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com Note: Unable to access building to view or test ATG.
01/31/2023 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
01/31/2023 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 6029
Rule: 62-761.500(1)(e)
06/02/2022 Comment Zimmerman, Robert A
Description: Wenda Lewis cell (352) 339.4048
08/20/2020 Editable Letter Activity Zimmerman, Robert A
Activity Title: In Compliance Letter Activity Status: Closed
Description: In Compliance Letter
Events:
Event Type: Document has been sent Date: 08/20/2020
Comment: Sent
Events:
Event Type: Activity has been finished Date: 08/20/2020
Comment: Finished
Attachments:
Attachment Date: 08/20/2020 User: ZIMMERMAN_RA_2
Description: ICL 8500142, LOC CARDLOCK 23RD AVE.
View Attachment
08/20/2020 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 08/20/2020 Activity Status: Closed
Date: 08/20/2020
Recipient: Joe Long
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and ICL to facility representative; Joey Long jlong@petroleumaids.co cc Jesse Wilkinson jwilkinson@petroleumaids.com
Events:
Event Type: Activity has been finished Date: 08/20/2020
Comment: Finished
08/10/2020 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/10/2020
Activity Closed Date: 08/20/2020 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 08/20/2020
Comment: Finished
Comments:
Comment Date: 08/20/2020 User: ZIMMERMAN_RA_2
Description: Sent TCI report and ICL to facility representative; Joey Long jlong@petroleumaids.co cc Jesse Wilkinson jwilkinson@petroleumaids.com
08/03/2020 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 08/03/2020 Activity Status: Closed
Date: 08/03/2020
Recipient: Joe Long
Sender: Robert Zimmerman
Subject: Compliance outreach TCI notification-scheduling
Message: Contact facility representative "Joey Long" jlong@petroleumaids.com for notification and schedule upcoming TCI and to give a reminder that the three-year record review requirement is: Registration Placards, Proof of Financial Responsibility, STFM, monthly visual inspections and electronic release detection records, A/B/C level UST operator certifications, annual operability testing, line leak detector testing, containment integrity testing and overfill protection device testing certifications.
Events:
Event Type: Activity has been finished Date: 08/03/2020
Comment: Finished
10/04/2018 Record Document Activity Zimmerman, Robert A
Activity Status: Closed
Contact Name: Joe long Activity Closed Date: 10/04/2018
Events:
Event Type: Activity has been finished Date: 10/04/2018
Comment: Finished
Comments:
Comment Date: 10/04/2018 User: ZIMMERMAN_RA_2
Description: Received violation resolution documents, line leak detector and overfill protection device test certifications;entered documents into FIRST.
10/04/2018 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 10/04/2018 Activity Status: Closed
Date: 10/04/2018
Recipient: Joe Long
Sender: Robert Zimmerman
Subject: Issued RCL
Message: Issued RCL and sent email attachment to facility representative.
Events:
Event Type: Activity has been finished Date: 10/04/2018
Comment: Finished
10/04/2018 Editable Letter Activity Zimmerman, Robert A
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 10/04/2018
Comment: Finished
Attachments:
Attachment Date: 10/04/2018 User: ZIMMERMAN_RA_2
Description: RCL LLD 8500142, LOC CARDLOCK 23RD AVE.
View Attachment
09/20/2018 Editable Letter Activity Libby, Kate K
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: RCL
Events:
Event Type: Document has been sent Date: 09/20/2018
Comment: Sent
Events:
Event Type: Activity has been finished Date: 09/20/2018
Comment: Finished
Attachments:
Attachment Date: 09/20/2018 User: LIBBY_KK_1
Description: Status of Violations Request
View Attachment
06/20/2018 Phone Conversation Activity Zimmerman, Robert A
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 318-0051 Activity Closed Date: 06/20/2018
Subject: Contact facility representative Joe Long with Petroleum Aids regarding violation resolution status.
Events:
Event Type: Activity has been finished Date: 06/20/2018
Comment: Finished
03/19/2018 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 03/19/2018 Activity Status: Closed
Date: 03/19/2018
Recipient: Wenda Lewis
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and CAO email attachments to facility representative.
Events:
Event Type: Activity has been finished Date: 03/19/2018
Comment: Finished
03/19/2018 Editable Letter Activity Zimmerman, Robert A
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 03/19/2018
Comment: Sent
Events:
Event Type: Activity has been finished Date: 03/19/2018
Comment: Finished
Attachments:
Attachment Date: 03/19/2018 User: ZIMMERMAN_RA_2
Description: CAO 8500142, LOC CARDLOCK 23RD AVE.
View Attachment
03/13/2018 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4067
Rule: 62-761.600(4)
03/13/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/13/2018
Activity Closed Date: 03/19/2018 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 03/19/2018
Comment: Finished
Comments:
Comment Date: 03/19/2018 User: ZIMMERMAN_RA_2
Description: Sent TCI report and CAO email attachments to facility representative.
Comments:
Comment Date: 03/19/2018 User: ZIMMERMAN_RA_2
Description: Due Dates Per New Rule 07/11/17 – Field erected ASTs fueled by tanker truck must have spill containment unless fill is in secondary containment for dike field or in tank truck containment area. 01/18/18 – USTs & ASTs must conduct initial overfill protection device testing by 01/18/18, and every 12 months thereafter. 01/18/18 – UST single wall spill containment devices must have initial containment integrity test performed and then every 12 months thereafter. 01/18/18 – AST below grade spill containment systems and hydrant sumps must have initial containment integrity test performed and then every 3 years thereafter. 01/18/18 – ASTs with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 01/18/18 – Existing ASTs with pressurized small diameter piping in contact with the soil must have line leak detectors installed, and must be tested every 12 months thereafter. ASTs installed after 01/11/17, must be equipped with line leak detectors at AST installation. 10/13/18 – UST systems with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 10/13/18 – Existing UST generator tanks must have/conduct release detection. UST generator tanks installed after 01/11/17 must have/conduct release detection from time of installation. 10/13/18 – UST & AST piping dispenser sumps and double wall containment devices below grade must have initial containment integrity test performed and then every 3 years thereafter. 10/13/18 – All UST facilities must have Class A, B and C operator’s certifications.
Comments:
Comment Date: 03/19/2018 User: ZIMMERMAN_RA_2
Description: Discussed facilities compliance history and modification to the UST rule and presented the UST outreach tool to the facility representative. Upcoming 2018 deadlines for obtaining UST operator certifications, overfill protection operability testing and containment integrity testing as per the new tank rule. Periodic test for storage tank system components shall occur according to the following schedule; A. Single wall spill buckets – by January 11, 2018 and, every 12 months thereafter; B. Piping and dispenser sumps - by October 13, 2018 and, every 3 years thereafter; C. Double wall spill buckets - by October 13, 2018 and, every 3 years thereafter; UST operator’s certification; Each UST facility must have a Class A, Class B and Class C operator that is trained and certified in accordance with the rule by October 13, 2018. A Class A, B or C operator must be present at all times of operation unless the facility is unmanned.
03/13/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/13/2018
Activity Closed Date: 03/19/2018 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 03/19/2018
Comment: Finished
Comments:
Comment Date: 03/19/2018 User: ZIMMERMAN_RA_2
Description: Sent TCI report and CAO email attachments to facility representative.
Comments:
Comment Date: 03/19/2018 User: ZIMMERMAN_RA_2
Description: Due Dates Per New Rule 07/11/17 – Field erected ASTs fueled by tanker truck must have spill containment unless fill is in secondary containment for dike field or in tank truck containment area. 01/18/18 – USTs & ASTs must conduct initial overfill protection device testing by 01/18/18, and every 12 months thereafter. 01/18/18 – UST single wall spill containment devices must have initial containment integrity test performed and then every 12 months thereafter. 01/18/18 – AST below grade spill containment systems and hydrant sumps must have initial containment integrity test performed and then every 3 years thereafter. 01/18/18 – ASTs with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 01/18/18 – Existing ASTs with pressurized small diameter piping in contact with the soil must have line leak detectors installed, and must be tested every 12 months thereafter. ASTs installed after 01/11/17, must be equipped with line leak detectors at AST installation. 10/13/18 – UST systems with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 10/13/18 – Existing UST generator tanks must have/conduct release detection. UST generator tanks installed after 01/11/17 must have/conduct release detection from time of installation. 10/13/18 – UST & AST piping dispenser sumps and double wall containment devices below grade must have initial containment integrity test performed and then every 3 years thereafter. 10/13/18 – All UST facilities must have Class A, B and C operator’s certifications.
Comments:
Comment Date: 03/19/2018 User: ZIMMERMAN_RA_2
Description: Discussed facilities compliance history and modification to the UST rule and presented the UST outreach tool to the facility representative. Upcoming 2018 deadlines for obtaining UST operator certifications, overfill protection operability testing and containment integrity testing as per the new tank rule. Periodic test for storage tank system components shall occur according to the following schedule; A. Single wall spill buckets – by January 11, 2018 and, every 12 months thereafter; B. Piping and dispenser sumps - by October 13, 2018 and, every 3 years thereafter; C. Double wall spill buckets - by October 13, 2018 and, every 3 years thereafter; UST operator’s certification; Each UST facility must have a Class A, Class B and Class C operator that is trained and certified in accordance with the rule by October 13, 2018. A Class A, B or C operator must be present at all times of operation unless the facility is unmanned.
03/13/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/13/2018
Activity Closed Date: 03/19/2018 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 03/19/2018
Comment: Finished
Comments:
Comment Date: 03/19/2018 User: ZIMMERMAN_RA_2
Description: Sent TCI report and CAO email attachments to facility representative.
Comments:
Comment Date: 03/19/2018 User: ZIMMERMAN_RA_2
Description: Due Dates Per New Rule 07/11/17 – Field erected ASTs fueled by tanker truck must have spill containment unless fill is in secondary containment for dike field or in tank truck containment area. 01/18/18 – USTs & ASTs must conduct initial overfill protection device testing by 01/18/18, and every 12 months thereafter. 01/18/18 – UST single wall spill containment devices must have initial containment integrity test performed and then every 12 months thereafter. 01/18/18 – AST below grade spill containment systems and hydrant sumps must have initial containment integrity test performed and then every 3 years thereafter. 01/18/18 – ASTs with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 01/18/18 – Existing ASTs with pressurized small diameter piping in contact with the soil must have line leak detectors installed, and must be tested every 12 months thereafter. ASTs installed after 01/11/17, must be equipped with line leak detectors at AST installation. 10/13/18 – UST systems with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 10/13/18 – Existing UST generator tanks must have/conduct release detection. UST generator tanks installed after 01/11/17 must have/conduct release detection from time of installation. 10/13/18 – UST & AST piping dispenser sumps and double wall containment devices below grade must have initial containment integrity test performed and then every 3 years thereafter. 10/13/18 – All UST facilities must have Class A, B and C operator’s certifications.
Comments:
Comment Date: 03/19/2018 User: ZIMMERMAN_RA_2
Description: Discussed facilities compliance history and modification to the UST rule and presented the UST outreach tool to the facility representative. Upcoming 2018 deadlines for obtaining UST operator certifications, overfill protection operability testing and containment integrity testing as per the new tank rule. Periodic test for storage tank system components shall occur according to the following schedule; A. Single wall spill buckets – by January 11, 2018 and, every 12 months thereafter; B. Piping and dispenser sumps - by October 13, 2018 and, every 3 years thereafter; C. Double wall spill buckets - by October 13, 2018 and, every 3 years thereafter; UST operator’s certification; Each UST facility must have a Class A, Class B and Class C operator that is trained and certified in accordance with the rule by October 13, 2018. A Class A, B or C operator must be present at all times of operation unless the facility is unmanned.
03/13/2018 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4057
Rule: 62-761.500(7)(e)
03/02/2018 Phone Conversation Activity Zimmerman, Robert A
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 339-4839 Activity Closed Date: 03/02/2018
Subject: Contact facility representative for notification and schedule upcoming TCI and to give a reminder that the two year record review requirement is: Registration Placard, Proof of Financial Responsibility, CFR, Monthly visual inspections and Electronic release detection records, containment integrity (if required), annual overfill protection, Line leak detector, Operability test and A/B/C UST operator certifications.
Events:
Event Type: Activity has been finished Date: 03/02/2018
Comment: Finished
12/15/2015 Record Document Activity Harrington, Richard D.
Activity Status: Closed
Contact Name: wenda lewis Activity Closed Date: 12/15/2015
Events:
Event Type: Activity has been finished Date: 12/15/2015
Comment: Finished
10/30/2015 Comment Harrington, Richard D.
Description: GPS reading taken in area of tanks 1R1, 2R1 and 3R1 (in center of tank pit): Lat N 29 40.442 / Lon W 82 17.971.
10/30/2015 Phone Conversation Activity Harrington, Richard D.
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 376-3293 Activity Closed Date: 10/30/2015
Subject: Called Wenda to confirm/discuss inspection. Not in office at time of call. Sent email with link to DEP tank video. Recd confirmation email later.
Events:
Event Type: Activity has been finished Date: 10/30/2015
Comment: Finished
10/30/2015 Editable Letter Activity Harrington, Richard D.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 10/30/2015
Comment: Finished
Attachments:
Attachment Date: 10/30/2015 User: HARRINGTON_RD_1
Description: ncl
View Attachment
10/30/2015 Site Inspection Activity Closed Harrington, Richard D.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 10/29/2015
Activity Closed Date: 10/30/2015 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 10/30/2015
Comment: Finished
Comments:
Comment Date: 10/30/2015 User: HARRINGTON_RD_1
Description: E-mailed report and ncl to Wenda Lewis 10/30/2015.
10/30/2015 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
10/28/2015 Comment Harrington, Richard D.
Description: aandres@lewisoilco.com
04/22/2014 Meeting Activity Harrington, Richard D.
Activity Closed Date: 04/22/2014 Activity Status: Closed
Location: My Fuel- Palatka
Subject: Met w/ owner rep George Ashby and Richard Enniss (KC Petro). The interstices were checked and were dry. Monthly inspections will be done unless the tank is taken out of service (most likely will be registered OOS). Clear violations.
Events:
Event Type: Activity has been finished Date: 04/22/2014
Comment: Finished
02/28/2014 Emergency Preparedness Information Activity Harrington, Richard D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/28/2014
Events:
Event Type: Activity has been finished Date: 02/28/2014
Comment: Finished
02/28/2014 Editable Letter Activity Harrington, Richard D.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/28/2014
Comment: Finished
Attachments:
Attachment Date: 02/28/2014 User: HARRINGTON_RD_1
Description: ncl
View Attachment
02/28/2014 Electronic Communication Activity Harrington, Richard D.
Activity Closed Date: 02/28/2014 Activity Status: Closed
Date: 02/28/2014
Recipient: justin dixon / george ashby/ richard enniss
Sender: rh
Subject: sent report and ncl
Message: -
Events:
Event Type: Activity has been finished Date: 02/28/2014
Comment: Finished
02/21/2014 Attachment Harrington, Richard D.
02/21/2014 Attachment Harrington, Richard D.
02/20/2014 Comment Harrington, Richard D.
Description: NO LONGER A CONTACT--- george@eagleswalk.org
02/19/2014 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
02/19/2014 Site Inspection Activity Closed Harrington, Richard D.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/20/2014
Activity Closed Date: 02/28/2014 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 02/28/2014
Comment: Finished
Comments:
Comment Date: 02/28/2014 User: HARRINGTON_RD_1
Description: E-mailed report and ncl to George Ashby, Justin Dixon and Richard Enniss 2/28/2014.
02/19/2014 Violation Closed Harrington, Richard D.
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
08/21/2013 Attachment Owens, Joe S.
07/10/2013 Electronic Communication Activity Harrington, Richard D.
Activity Closed Date: 07/10/2013 Activity Status: Closed
Date: 07/10/2013
Recipient: justin dixon, richard ennis
Sender: rh
Subject: sent install report
Message: -
Events:
Event Type: Activity has been finished Date: 07/10/2013
Comment: Finished
07/03/2013 Comment Harrington, Richard D.
Description: NO LONGER A CONTACT-- JDixon@ClayGroup.com
04/23/2012 TCAR Activity Ramsey, Timothy H
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 04/23/2012
Events:
Event Type: Activity has been finished Date: 04/23/2012
Comment: Finished
04/23/2012 Editable Letter Activity Ramsey, Timothy H
Activity Title: Limited Closure Summary Report (Complete) Activity Status: Closed
Events:
Event Type: Document has been sent Date: 04/23/2012
Comment: Sent on Mon Apr 23 00:00:00 EDT 2012
Events:
Event Type: Activity has been finished Date: 04/23/2012
Comment: Finished
Attachments:
Attachment Date: 04/23/2012 User: RAMSEY_TH_1
Description: Closure Review Letter
View Attachment
02/24/2012 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/24/2012
Activity Closed Date: 07/10/2013 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 07/10/2013
Comment: Finished
Comments:
Comment Date: 12/03/2012 User: HARRINGTON_RD_1
Description: Called facility registered contact person (Keith Patterson) and left message inquiring about facility status. They will be placing the system back into service soon per response phone message.
Comments:
Comment Date: 01/09/2013 User: HARRINGTON_RD_1
Description: Contacted facility rep Keith Patterson and left message listing the required system tests prior to system start-up (leak detectors, annual operability, and Breach of Integrity).
Comments:
Comment Date: 07/10/2013 User: HARRINGTON_RD_1
Description: Recd Breach of Integrity tests (all passed) and verification that all spill bucket, dispenser liner, and sump hydro tests passed. The BOI testing was completed due to out of service tanks being brought back into service, but the BOI test is not required every 5 years since the tanks were installed in 1991. The facility has submitted a registration form changing the facility name to My Fuel-Gainesville, and the 3 tanks have been registered as "in service". RH
Comments:
Comment Date: 07/10/2013 User: HARRINGTON_RD_1
Description: E-mailed report to Justin Dixon and Richard Ennis 7/10/2013. RH
02/24/2012 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/24/2012
Activity Closed Date: 07/10/2013 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 07/10/2013
Comment: Finished
Comments:
Comment Date: 12/03/2012 User: HARRINGTON_RD_1
Description: Called facility registered contact person (Keith Patterson) and left message inquiring about facility status. They will be placing the system back into service soon per response phone message.
Comments:
Comment Date: 01/09/2013 User: HARRINGTON_RD_1
Description: Contacted facility rep Keith Patterson and left message listing the required system tests prior to system start-up (leak detectors, annual operability, and Breach of Integrity).
Comments:
Comment Date: 07/10/2013 User: HARRINGTON_RD_1
Description: Recd Breach of Integrity tests (all passed) and verification that all spill bucket, dispenser liner, and sump hydro tests passed. The BOI testing was completed due to out of service tanks being brought back into service, but the BOI test is not required every 5 years since the tanks were installed in 1991. The facility has submitted a registration form changing the facility name to My Fuel-Gainesville, and the 3 tanks have been registered as "in service". RH
Comments:
Comment Date: 07/10/2013 User: HARRINGTON_RD_1
Description: E-mailed report to Justin Dixon and Richard Ennis 7/10/2013. RH
02/24/2012 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/24/2012
Activity Closed Date: 07/10/2013 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 07/10/2013
Comment: Finished
Comments:
Comment Date: 12/03/2012 User: HARRINGTON_RD_1
Description: Called facility registered contact person (Keith Patterson) and left message inquiring about facility status. They will be placing the system back into service soon per response phone message.
Comments:
Comment Date: 01/09/2013 User: HARRINGTON_RD_1
Description: Contacted facility rep Keith Patterson and left message listing the required system tests prior to system start-up (leak detectors, annual operability, and Breach of Integrity).
Comments:
Comment Date: 07/10/2013 User: HARRINGTON_RD_1
Description: Recd Breach of Integrity tests (all passed) and verification that all spill bucket, dispenser liner, and sump hydro tests passed. The BOI testing was completed due to out of service tanks being brought back into service, but the BOI test is not required every 5 years since the tanks were installed in 1991. The facility has submitted a registration form changing the facility name to My Fuel-Gainesville, and the 3 tanks have been registered as "in service". RH
Comments:
Comment Date: 07/10/2013 User: HARRINGTON_RD_1
Description: E-mailed report to Justin Dixon and Richard Ennis 7/10/2013. RH
02/24/2012 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/24/2012
Activity Closed Date: 07/10/2013 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 07/10/2013
Comment: Finished
Comments:
Comment Date: 12/03/2012 User: HARRINGTON_RD_1
Description: Called facility registered contact person (Keith Patterson) and left message inquiring about facility status. They will be placing the system back into service soon per response phone message.
Comments:
Comment Date: 01/09/2013 User: HARRINGTON_RD_1
Description: Contacted facility rep Keith Patterson and left message listing the required system tests prior to system start-up (leak detectors, annual operability, and Breach of Integrity).
Comments:
Comment Date: 07/10/2013 User: HARRINGTON_RD_1
Description: Recd Breach of Integrity tests (all passed) and verification that all spill bucket, dispenser liner, and sump hydro tests passed. The BOI testing was completed due to out of service tanks being brought back into service, but the BOI test is not required every 5 years since the tanks were installed in 1991. The facility has submitted a registration form changing the facility name to My Fuel-Gainesville, and the 3 tanks have been registered as "in service". RH
Comments:
Comment Date: 07/10/2013 User: HARRINGTON_RD_1
Description: E-mailed report to Justin Dixon and Richard Ennis 7/10/2013. RH
02/13/2012 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/13/2012
Activity Closed Date: 03/05/2012 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 03/05/2012
Comment: Finished
Comments:
Comment Date: 03/05/2012 User: OWENS_JS_1
Description: No facility representative onsite for report finalization. No facility representative signing for report. Inspector completed the report offsite and sent to Kieth Patterson by USPS and Richard Ennis, KCP rep. by email.
Comments:
Comment Date: 03/05/2012 User: OWENS_JS_1
Description: Tanks are listed as "T" currently and contact ( Justin Dixon) indicated that this would remain until they have a secured tenant for the business.
02/13/2012 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/13/2012
Activity Closed Date: 03/05/2012 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 03/05/2012
Comment: Finished
Comments:
Comment Date: 03/05/2012 User: OWENS_JS_1
Description: No facility representative onsite for report finalization. No facility representative signing for report. Inspector completed the report offsite and sent to Kieth Patterson by USPS and Richard Ennis, KCP rep. by email.
Comments:
Comment Date: 03/05/2012 User: OWENS_JS_1
Description: Tanks are listed as "T" currently and contact ( Justin Dixon) indicated that this would remain until they have a secured tenant for the business.
01/23/2012 Record Document Activity Owens, Joe S.
Activity Status: Closed
Contact Name: FDEP-STCM Activity Closed Date: 01/23/2012
Events:
Event Type: Activity has been finished Date: 01/23/2012
Comment: Finished
12/16/2011 Editable Letter Activity Ramsey, Timothy H
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 12/16/2011
Comment: Sent on Fri Dec 16 00:00:00 EST 2011
Events:
Event Type: Activity has been finished Date: 12/16/2011
Comment: Finished
Attachments:
Attachment Date: 12/16/2011 User: RAMSEY_TH_1
Description: 2nd Non-Compliance Letter
View Attachment
08/29/2011 Violation Closed Owens, Joe S.
Significance: Minor Status: Closed
Criteria ID: 1002
Rule: 62-761.400(2)(a)
Comments: Does STCM accurately reflect the tanks at the facility? This question concerns the registration process and payment of fees only - it is not about accurate registration. Check the number of tanks listed on the registration placard. Can the facility owner/operator produce a registration form to document submittal to DEP? Does STCM show that all DEP fees are paid? At the time of tank closure, a registration form should be submitted showing the change in tank codes.
08/29/2011 Editable Letter Activity Owens, Joe S.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/30/2011
Comment: Finished
Events:
Event Type: Document has been sent Date: 08/30/2011
Comment: Sent on Tue Aug 30 00:00:00 EDT 2011
Attachments:
Attachment Date: 08/30/2011 User: RAMSEY_TH_1
Description: 1st Non-Compliance Letter
View Attachment
08/29/2011 Site Inspection Activity Closed Owens, Joe S.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 08/29/2011
Activity Closed Date: 08/29/2011 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 08/29/2011
Comment: Finished
12/03/2010 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/03/2010
Activity Closed Date: 12/03/2010 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 12/03/2010
Comment: Finished
10/19/2010 Editable Letter Activity Ramsey, Timothy H
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 10/19/2010
Comment: Sent on Tue Oct 19 00:00:00 EDT 2010
Events:
Event Type: Activity has been finished Date: 10/19/2010
Comment: Finished
Attachments:
Attachment Date: 10/19/2010 User: RAMSEY_TH_1
Description: 2nd Non-Compliance Letter
View Attachment
10/01/2010 Site Inspection Activity Closed Owens, Joe S.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 10/01/2010
Activity Closed Date: 10/01/2010 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 10/01/2010
Comment: Finished
09/29/2010 Comment Owens, Joe S.
Description: STRF received from owner - facility out-of-service date was 9/17/2010 - owner contacted inspector indicating that Andrew Bell & Co.(PSSC) would be performing removal of fuels in tank on 9/26 or27th. No contact has been received from the PSSC contractor to request an inspection while onsite.
09/27/2010 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/27/2010
Events:
Event Type: Activity has been finished Date: 09/27/2010
Comment: Finished
09/01/2010 Violation Closed Owens, Joe S.
Significance: Minor Status: Closed
Criteria ID: 1009
Rule: 62-761.450(1)(b)1., 62-761.450(1)(b)2., 62-761.450(1)(b)3., 62-761.450(1)(b)4.
Comments: Confirm ownership changes with the facility representative. If needed, research the new owner information with the facility's other licenses, especially alcoholic beverage and occupational. Note that new personnel or a change in name may just reflect the sale of the business rather than sale of the property. If a change of ownership has occurred, allow a reasonable time (a recommended time frame can be approximately 1-3 months) for the DEP database to be updated. Ask the facility to produce a dated registration form. Mark it as a discrepancy if a longer time frame has elapsed. Note: DEP Registration Section may change the ownership without receiving any additional proof, other than a registration form. Has the Certification of Financial Responsibility been revised?
09/01/2010 Editable Letter Activity Owens, Joe S.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 09/01/2010
Comment: Finished
Events:
Event Type: Document has been sent Date: 09/01/2010
Comment: Sent on Wed Sep 01 00:00:00 EDT 2010
Attachments:
Attachment Date: 09/01/2010 User: RAMSEY_TH_1
Description: 1st Non-Compliance Letter
View Attachment
09/01/2010 Violation Closed Owens, Joe S.
Significance: Minor Status: Closed
Criteria ID: 1122
Rule: 62-761.710(1)
Comments: Was reasonable access to the facility granted? If not, document the circumstances. Were the records available within the specified time frame? If five day pre-inspection notice was not given by the inspector, this item can not be marked as a discrepancy. Make note of the missing documents, and arrange a review period.
09/01/2010 Violation Closed Owens, Joe S.
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
09/01/2010 Violation Closed Owens, Joe S.
Significance: Minor Status: Closed
Criteria ID: 1058
Rule: 62-761.600(1)(a)1.
Comments: Mark this as out of compliance if the release detection method is not able to register or detect a new release. If you feel that the release detection system has lost its ability to detect a new release, document why in the inspection report. Examples include: a. An automatic tank gauge system already in alarm mode will not be able to detect a new release; b. sumps with water/product may impair detection abilities; c. monitoring wells at contaminated sites may also have impaired ability to detect new releases. See .640(2)(c)2. for further guidance on using contaminated monitoring wells for release detection.
08/11/2010 Site Inspection Activity Closed Owens, Joe S.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 08/11/2010
Activity Closed Date: 09/01/2010 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 09/01/2010
Comment: Finished
Comments:
Comment Date: 09/01/2010 User: OWENS_JS_1
Description: Placard appears current - cert# 353829
08/26/2009 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/26/2009
Activity Closed Date: 08/26/2009 Activity Closed By: OWENS_JS_1
08/25/2008 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/25/2008
Activity Closed Date: 10/31/2008 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 10/31/2008 User: OWENS_JS_1
Description: Inspector accompanied by Lea Mason of Clay Oil Co. for inspection. Form completed offsite following inspection and E-mailed to contact.
09/26/2007 Record Document Activity Owens, Joe S.
Activity Status: Closed
Contact Name: Dawn Mattox Activity Closed Date: 09/26/2007
Comments:
Comment Date: 09/26/2007 User: OWENS_JS_1
Description: Dawn Mattox of Clay Oil notified ACEPD that new Vapor Recovery adapter had been installed instead of repairing the old unit.
07/27/2007 Violation Closed Owens, Joe S.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
07/27/2007 Editable Letter Activity Owens, Joe S.
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 07/27/2007
Comment: Sent on Fri Jul 27 15:38:55 EST 2007
Comments:
Comment Date: 07/27/2007 User: OWENS_JS_1
Description: NCL issued for TCI results indicating damaged or missing components discovered during inspection.
Attachments:
Attachment Date: 07/27/2007 User: OWENS_JS_1
Description: NCL Report
View Attachment
07/27/2007 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 07/27/2007
07/27/2007 Site Inspection Activity Closed Owens, Joe S.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 07/27/2007
Activity Closed Date: 07/27/2007 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 07/27/2007 User: OWENS_JS_1
Description: Inspection performed w/ Dawn Mattox of Clay Oil Co. and copy of inspection sent to her, following completion of report offsite, by E-mail. E-mail also included NCL.
Comments:
Comment Date: 07/27/2007 User: OWENS_JS_1
Description: REVIEWED DOCUMENTS FOR FAC #: 8500142 Placard current & displayed: OK CFR form complete - FR records are updated - OK RDRL - present and applicable for facility: TANKS; Count. elect. monitoring of tank interstice / PIPING; Count. electric monitoring of piping interstice within STP sumps. MLLD. All disp. liners, spill buckets visual inspection. Site Diagram for accuracy, attached to ATTACHMENT Facility information. No changes frm. last inspection. Facility registration information including tank system attributes appear to be accurate. Monthly release detection records - Accepted. Date range for Inspection records: 09/2006 to present No Monthly ATG alarm status documented on insp. form - all systems normal w/ printout to verify - OK. A review of the Alarm Report for the ATG confirms the Operability test for the facility was performed. FUTURE DUE DATES OF FOLLOWING: Tank Insurance Renewal Due: 4/2008 MLLD - 7/2008 Leak Sensor operability test due - 7/2008 Placard Registration renewal due: 6/2008 Visual inspection revealed: STP sumps are dry and clean, Spill buckets contain a slight trace of fuel which was evident of recent delivery and removed by contact during inspection, but otherwise appear maintained. VR poppet valve is missing on the Unl. Plus tank and the ball check vent valve is damaged and needs replaced. Dispenser liners (2) are dry with no trace of any release, no issues addressed during monthly visual inspections. Monthly inspections should document any maint. which is performed or recommended as needed to prevent any release. The entry boots within the sumps appear sound and sealed ¿ no cracks observed and no leakage from any groundwater. Facility had a documented release and was previously scored a 82 and a comment of "completed" listed for clean-up. The compliance inspection folder is complete and concise - RDRL is posted above ATG and is applicable for facility - Facility inspection records well maintained. Operability Test performed and (6) leak sensors functioned properly when inverted to simulate a leak - all reset (3 sumps & 3 interstice)- as indicated by documentation from contractor and in the Alarm report function of the ATG. Request that contractor notify ACEPD during replacement of ball check vent valve prior to installation of new VR poppet adapter for verification of replacement.
07/27/2007 Site Inspection Activity Closed Owens, Joe S.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 07/27/2007
Activity Closed Date: 07/27/2007 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 07/27/2007 User: OWENS_JS_1
Description: Inspection performed w/ Dawn Mattox of Clay Oil Co. and copy of inspection sent to her, following completion of report offsite, by E-mail. E-mail also included NCL.
Comments:
Comment Date: 07/27/2007 User: OWENS_JS_1
Description: REVIEWED DOCUMENTS FOR FAC #: 8500142 Placard current & displayed: OK CFR form complete - FR records are updated - OK RDRL - present and applicable for facility: TANKS; Count. elect. monitoring of tank interstice / PIPING; Count. electric monitoring of piping interstice within STP sumps. MLLD. All disp. liners, spill buckets visual inspection. Site Diagram for accuracy, attached to ATTACHMENT Facility information. No changes frm. last inspection. Facility registration information including tank system attributes appear to be accurate. Monthly release detection records - Accepted. Date range for Inspection records: 09/2006 to present No Monthly ATG alarm status documented on insp. form - all systems normal w/ printout to verify - OK. A review of the Alarm Report for the ATG confirms the Operability test for the facility was performed. FUTURE DUE DATES OF FOLLOWING: Tank Insurance Renewal Due: 4/2008 MLLD - 7/2008 Leak Sensor operability test due - 7/2008 Placard Registration renewal due: 6/2008 Visual inspection revealed: STP sumps are dry and clean, Spill buckets contain a slight trace of fuel which was evident of recent delivery and removed by contact during inspection, but otherwise appear maintained. VR poppet valve is missing on the Unl. Plus tank and the ball check vent valve is damaged and needs replaced. Dispenser liners (2) are dry with no trace of any release, no issues addressed during monthly visual inspections. Monthly inspections should document any maint. which is performed or recommended as needed to prevent any release. The entry boots within the sumps appear sound and sealed ¿ no cracks observed and no leakage from any groundwater. Facility had a documented release and was previously scored a 82 and a comment of "completed" listed for clean-up. The compliance inspection folder is complete and concise - RDRL is posted above ATG and is applicable for facility - Facility inspection records well maintained. Operability Test performed and (6) leak sensors functioned properly when inverted to simulate a leak - all reset (3 sumps & 3 interstice)- as indicated by documentation from contractor and in the Alarm report function of the ATG. Request that contractor notify ACEPD during replacement of ball check vent valve prior to installation of new VR poppet adapter for verification of replacement.
02/07/2007 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/07/2007
10/30/2006 Attachment Ramsey, Timothy H
10/27/2006 Attachment Ramsey, Timothy H
10/10/2006 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/10/2006
Activity Closed Date: 10/10/2006 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 10/10/2006 User: OWENS_JS_1
Description: Performed operability test on leak sensors (6) all correctly reacted.
09/21/2006 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/21/2006
08/02/2006 Violation Closed Owens, Joe S.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
08/02/2006 Editable Letter Activity Owens, Joe S.
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 08/02/2006
Comment: Sent on Wed Aug 02 00:00:00 EST 2006
Comments:
Comment Date: 08/02/2006 User: OWENS_JS_1
Description: Contractor contacted inspector during testing and indicated that (2) sensors needed replacement and complete test was not possible. Inspector requested contractor to send a copy of the ATG printout to him following completion of repairs.
Attachments:
Attachment Date: 08/02/2006 User: OWENS_JS_1
Description: NCL Report
View Attachment
08/02/2006 Site Inspection Activity Closed Owens, Joe S.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 08/02/2006
Activity Closed Date: 08/02/2006 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 08/02/2006 User: OWENS_JS_1
Description: DOCUMENTS REVIEWED: CFR form completed and updated w/ contact ¿ OK - FR record updated. RDRL for applicability ¿ Accepted. Site Diagram for accuracy, attached to facility records Compliance Inspection Cover Page; conveyed copy to contact. Monthly release detection records ¿ ATG printouts complete¿ Accepted. FILL ports have straight drop for overfill prevention. Spill buckets clean and dry ¿ OK Previous TCI date: 9/2005 Date range for Inspection records:9/2005 to present Alarm history reviewed /w noted incidents ¿ OK ADVISED CONTACT OF FOLLOWING: MLLD required testing due: 7/2007 Annual ATG leak sensor Operability test due: NOW Tank Insurance Renewal Due: 4/2007 Placard Registration renewal due: 6/2007 Visually the tanks components appear to be maintained. The dispenser hoses as pointed out to contact, need replaceing due to vehicular traffic which is allowed to drive over the hoses and have cracked the hose covering. Broken hose spill is probable if left unrepaired. REQUESTED A HYDRO-STATIC BE PERFORMED ON THE PLUS SPILL BUCKET DUE TO CONDITION OF BUCKET - CONTRACTOR TO CONTACT INSPECTOR FOR CONFIRMATORY VISUAL INSPECTION OF TEST.
09/27/2005 Legacy Activity Ramsey, Timothy H
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: REINSPECTION OF REPAIRED DISPENSER #3/4 FOR INTEGRITY-PASSED, ANNUAL OPERABILITY TEST PERFORMED TODAY 9/27/05
09/07/2005 Legacy Activity Ramsey, Timothy H
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: RECEIVED ATG PRINTOUTS AND MONTHLY VISUAL INSPECTION RECORDS FOR PAST YEAR. RECORDS REVIEWED, BUT NOT KEPT FOR FILE.
08/31/2005 Legacy Activity Ramsey, Timothy H
Activity Name: SITE VISIT Activity Status: Closed
Completion Notes: SITE VISIT TO OBSERVE HYDO TEST OF DISPENSER LINERS. #1/2 OK, 3/4 HAD SLOW LEAK AND NEEDS REPAIRED.
08/05/2005 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 761.700(1)(a)1
Comments:
Comment Date: 12/08/2010 User: MCDANIEL_ML_1
Description: Veeder Root-TLS 350 (E Q#197) panel Containment Solution (EQ# 191) Double-Walled UST¿s Ameron Fiberglass D/W piping (EQ# 378) FE Petro STPs, Vaporless In-Line Leak Detectors ¿ EQ# 329 Emco Wheaton Double Walled Spill Containment Buckets EQ- #594 OPW Overfill Protection Flow Shut-Off Drop Tubes (EQ# 223)
08/05/2005 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: MLLD TEST 10/25/04, OPERABILITY TEST DUE NOW
08/05/2005 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 761.700(1)(c)3
Comments:
Comment Date: 12/08/2010 User: MCDANIEL_ML_1
Description: Veeder Root-TLS 350 (E Q#197) panel Containment Solution (EQ# 191) Double-Walled UST¿s Ameron Fiberglass D/W piping (EQ# 378) FE Petro STPs, Vaporless In-Line Leak Detectors ¿ EQ# 329 Emco Wheaton Double Walled Spill Containment Buckets EQ- #594 OPW Overfill Protection Flow Shut-Off Drop Tubes (EQ# 223)
08/05/2005 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 761.710(2)
11/09/2004 Legacy Activity Ramsey, Timothy H
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: RECEIVED DOCUMENTATION THAT ALL NON-COMPLIANCE ITEMS HAVE BEEN CORRECTED. VISUAL INSPECTION REVIEWED ON SITE BY JOE OWENS.
08/12/2004 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 400(1)-(2)
08/12/2004 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
08/12/2004 Violation Closed Ramsey, Timothy H
Significance: SNC-B Status: Closed
Rule: 400(3)
Comments:
Comment Date: 05/30/2013 User: MORRISON_CY_1
Description: EQ information not availble.
08/12/2004 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 640(3)(d)
Comments:
Comment Date: 12/02/2019 User: HERNANDEZ_N
Description: Equipment List: Tank - double-walled, steel, sub-base tank (Com-Fab) to supply diesel to an emergency power generator. Spill Containment Overfill protection - Krueger Gauge (EQ-730) Release Detection - Electronic monitoring of tank interstice via Caterpillar panel with visual and audible alarm. The system is also monitored via SCADA system, which is connected to the main office computer.
08/12/2004 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 700(1)(c)3
08/12/2004 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 710(2)
Comments:
Comment Date: 12/06/2016 User: HERNANDEZ_N
Description: Equipment List: Tank - double-walled, steel AST Spill containment box Overfill protection - Krueger Therma Gauge (EQ-730) Release Detection - Electronic monitoring of tank interstice via Digital Genset Controller with visual and audible alarm. The system is also monitored via SCADA system, which is connected to the main office computer.
08/20/2003 Legacy Activity Ramsey, Timothy H
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: RECEIVED COPY OF INSURANCE
08/11/2003 Violation Closed Ramsey, Timothy H
Significance: SNC-B Status: Closed
Rule: 400(3)
08/11/2003 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: LLD AND ANNUAL OPERABILITY TEST 8/4/03
10/21/2002 Legacy Activity Ramsey, Timothy H
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: RESPONSE LETTER RECEIVED, ALL TESTS PERFORMED AND PLACARD ISSUED
09/18/2002 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 700(1)(c)3
09/18/2002 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE INSPECTION
09/18/2002 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 400(2)(a)6
09/18/2002 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 600(1)(a)2
07/13/2001 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE INSPECTION
07/18/2000 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE INSPECTION
07/13/1999 Legacy Activity Buono, Mike
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed