DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/27/2025        Last Data Refresh: 04/26/2025        Report Generated from DOPPLER
 
Facility ID: 8500284
Facility Name: TEXACO-KIRKWOOD
 
04/04/2025 Editable Letter Activity McNeil, Anthony P
Activity Title: Warning Letter Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 04/04/2025
Comment: Submitted for approval by: Anthony P McNeil
Events:
Event Type: Activity/Document has been approved Date: 04/07/2025
Comment: Approved by Jennifer Paul: WL24-240 11/14/2024
Events:
Event Type: Activity has been finished Date: 04/07/2025
Comment: Finished
Attachments:
Attachment Date: 04/04/2025 User: MCNEIL_A
Description: Warning Letter No. WL24-240
View Attachment
01/31/2025 Violation Open Keim, Michael J
Significance: Minor Status: Open
Criteria ID: 7084
Rule: 62-762.701(2), 62-762.701(2)(a), 62-762.702(2), 62-762.702(2)(a)
01/31/2025 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 01/31/2025 Activity Status: Closed
Date: 01/31/2025
Recipient: Wenda Lewis, Chris Leonard
Sender: M Keim
Subject: TCI
Message: E-mail correspondence with Chris Leonard and Wenda Lewis regarding TCI scheduling and records needed.
Events:
Event Type: Activity has been finished Date: 01/31/2025
Comment: Finished
01/31/2025 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/31/2025
Comment: Finished
Events:
Event Type: Document has been sent Date: 01/31/2025
Comment: Sent
Attachments:
Attachment Date: 01/31/2025 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
01/31/2025 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 01/31/2025 Activity Status: Closed
Date: 01/31/2025
Recipient: Wenda Lewis
Sender: M Keim
Subject: TCI report
Message: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com
Events:
Event Type: Activity has been finished Date: 01/31/2025
Comment: Finished
01/29/2025 Site Inspection Activity Closed Keim, Michael J
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 01/15/2025
Activity Closed Date: 01/31/2025 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 01/31/2025
Comment: Finished
Comments:
Comment Date: 01/31/2025 User: KEIM_MJ_1
Description: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com Compliance assist with Chris Leonard of ARC Dynamics
10/02/2024 Enforcement Tracking Activity McNeil, Anthony P
Activity Status: Open
11/06/2023 Attachment Harrington, Richard D.
01/30/2023 Violation Open Keim, Michael J
Significance: SNC-B Status: Open
Criteria ID: 6051
Rule: 62-761.500(7)(a)
01/30/2023 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Wenda Lewis Activity Closed Date: 01/30/2023
Events:
Event Type: Activity has been finished Date: 01/30/2023
Comment: Finished
01/30/2023 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Wenda Lewis Activity Closed Date: 01/30/2023
Events:
Event Type: Activity has been finished Date: 01/30/2023
Comment: Finished
01/30/2023 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Wenda Lewis Activity Closed Date: 01/30/2023
Events:
Event Type: Activity has been finished Date: 01/30/2023
Comment: Finished
01/30/2023 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Wenda Lewis Activity Closed Date: 01/30/2023
Events:
Event Type: Activity has been finished Date: 01/30/2023
Comment: Finished
01/30/2023 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/30/2023
Comment: Finished
Events:
Event Type: Document has been sent Date: 01/30/2023
Comment: Sent
Attachments:
Attachment Date: 01/30/2023 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
01/30/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 01/30/2023 Activity Status: Closed
Date: 01/30/2023
Recipient: Wenda Lewis
Sender: M Keim
Subject: TCI report
Message: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com
Events:
Event Type: Activity has been finished Date: 01/30/2023
Comment: Finished
01/30/2023 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
01/26/2023 Enforcement Referral Activity Harrington, Richard D.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 10/02/2024
Events:
Event Type: Activity has been submitted for approval Date: 01/26/2023
Comment: Submitted for approval by: Richard D. Harrington: Routine Inspection Activity is in progress for 2023. We will attempt to resolve issues as the report is input. Referral rejection will be requested if possible.
Events:
Event Type: Activity has been finished Date: 10/02/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 10/02/2024
Comment: Accepted by Anthony P McNeil: Accepted
Events:
Event Type: Activity/Document was acknowledged on this date Date: 10/01/2024
Comment: Acknowledged and Assigned by Jennifer Paul
Events:
Event Type: Activity has been assigned Date: 10/01/2024
Comment: Assigned to Anthony P McNeil
Events:
Event Type: Activity has been submitted for approval Date: 10/01/2024
Comment: Submitted for approval by: Richard D. Harrington: This referral was withdrawn per DEP request and is now being re-submitted by ACEPD for DEP re-assignment. * Please note that this facility is due for Routine Inspection this contract year.
Events:
Event Type: Activity has been withdrawn from submission by the requestor Date: 10/01/2024
Comment: Withdrawn by Richard D. Harrington: Withdraw referral per request of Jennifer Paul- DEP. Referral to be re-submitted by ACEPD and re-assigned by DEP.
Comments:
Comment Date: 01/26/2023 User: HARRINGTON_RD_1
Description: Routine Inspection Activity is in progress for 2023. We will attempt to resolve issues as the report is input. Referral rejection will be requested if possible.
01/18/2023 Site Inspection Activity Closed Keim, Michael J
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 01/18/2023
Activity Closed Date: 01/30/2023 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 01/30/2023
Comment: Finished
Comments:
Comment Date: 01/30/2023 User: KEIM_MJ_1
Description: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com Compliance assist with Aron of ARC Dynamics
06/10/2022 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 06/10/2022 Activity Status: Closed
Date: 06/10/2022
Recipient: Wenda Lewis
Sender: Robert Zimmerman
Subject: Violation resolution status compliance assistance outreach inquiry.
Message: Compliance assistance outreach contact with facility representative wlewis@lewisoilco.com regarding violation resolution status.
Events:
Event Type: Activity has been finished Date: 06/10/2022
Comment: Finished
06/09/2022 Record Document Activity Zimmerman, Robert A
Activity Status: Closed
Contact Name: Wenda Lewis Activity Closed Date: 06/09/2022
Events:
Event Type: Activity has been finished Date: 06/09/2022
Comment: Finished
Comments:
Comment Date: 06/09/2022 User: ZIMMERMAN_RA_2
Description: Compliance assistance outreach contact with facility representative wlewis@lewisoilco.com regarding violation resolution status.
01/21/2021 Editable Letter Activity Harris, Matthew J
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/21/2021
Comment: Finished
Attachments:
Attachment Date: 01/21/2021 User: HARRIS_MJ
Description: Return To COmpliance
View Attachment
08/24/2020 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4067
Rule: 62-761.600(4)
08/24/2020 Editable Letter Activity Zimmerman, Robert A
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/24/2020
Comment: Finished
Events:
Event Type: Document has been sent Date: 08/24/2020
Comment: Sent
Attachments:
Attachment Date: 08/24/2020 User: ZIMMERMAN_RA_2
Description: CAO 8500284, TEXACO-KIRKWOOD.
View Attachment
08/24/2020 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 08/24/2020 Activity Status: Closed
Date: 08/24/2020
Recipient: Joe Long
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and CAO to facility representative; Joey Long jlong@petroleumaids.co cc Jesse Wilkinson jwilkinson@petroleumaids.com
Events:
Event Type: Activity has been finished Date: 08/24/2020
Comment: Finished
08/24/2020 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
08/24/2020 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4068
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1., 62-761.700(1)(a)2.
08/24/2020 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4001
Rule: 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2., 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7)
08/10/2020 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 08/10/2020
Activity Closed Date: 08/24/2020 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 08/24/2020
Comment: Finished
Comments:
Comment Date: 08/24/2020 User: ZIMMERMAN_RA_2
Description: Sent TCI report and CAO to facility representative; Joey Long jlong@petroleumaids.co cc Jesse Wilkinson jwilkinson@petroleumaids.com
08/03/2020 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 08/03/2020 Activity Status: Closed
Date: 08/03/2020
Recipient: Joe Long
Sender: Robert Zimmerman
Subject: Compliance outreach TCI notification-scheduling
Message: Contact facility representative "Joey Long" jlong@petroleumaids.com for notification and schedule upcoming TCI and to give a reminder that the three-year record review requirement is: Registration Placard, Proof of Financial Responsibility, STFM, monthly visual inspections, monthly alarm history reports and electronic release detection records, A/B/C level UST operators certifications, PARABEAM Two Year Breach of integrity test, overfill protection device test, annual Cathodic Protection test, spill bucket and sump containment integrity testing, line leak detector and operability test certifications.
Events:
Event Type: Activity has been finished Date: 08/03/2020
Comment: Finished
06/02/2020 Enforcement Tracking Activity Jules, Frisberdine
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 07/28/2020
Events:
Event Type: Activity has been finished Date: 07/28/2020
Comment: Finished
Comments:
Comment Date: 06/11/2020 User: JULES_F
Description: The last time I spoke with Ms. Lewis, she had said that she had already taken care of everything since 2018 and that she's going to email me the documents. I reached out to her today to see when I should be expecting them, and she said that she is working with her local inspectors and have found almost all the documents. I'm assuming that I should be receiving the documents once they are all found. I will be in touch with her again next week.
05/29/2020 Enforcement Referral Activity Zimmerman, Robert A
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 06/02/2020
Events:
Event Type: Activity has been submitted for approval Date: 05/29/2020
Comment: Submitted for approval by: Robert A Zimmerman: Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response.
Events:
Event Type: Activity has been assigned Date: 05/29/2020
Comment: Assigned to Frisberdine Jules
Events:
Event Type: Activity/Document was acknowledged on this date Date: 05/29/2020
Comment: Acknowledged and Assigned by Matthew J Harris
Events:
Event Type: Activity has been finished Date: 06/02/2020
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 06/02/2020
Comment: Accepted by Frisberdine Jules: Accepted by Frisberdine Jules
Comments:
Comment Date: 05/29/2020 User: ZIMMERMAN_RA_2
Description: Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response.
Comments:
Comment Date: 05/29/2020 User: ZIMMERMAN_RA_2
Description: Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response.
05/29/2020 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 05/29/2020 Activity Status: Closed
Date: 05/29/2020
Recipient: Joe Long
Sender: Robert Zimmerman
Subject: Compliance assistance outreach violation resolution status inquiry.
Message: Compliance assistance outreach contact with facility representative regarding violation resolution status; no response.
Events:
Event Type: Activity has been finished Date: 05/29/2020
Comment: Finished
05/29/2020 Enforcement Referral Activity Zimmerman, Robert A
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 06/02/2020
Events:
Event Type: Activity has been submitted for approval Date: 05/29/2020
Comment: Submitted for approval by: Robert A Zimmerman: Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response.
Events:
Event Type: Activity has been assigned Date: 05/29/2020
Comment: Assigned to Frisberdine Jules
Events:
Event Type: Activity/Document was acknowledged on this date Date: 05/29/2020
Comment: Acknowledged and Assigned by Matthew J Harris
Events:
Event Type: Activity has been finished Date: 06/02/2020
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 06/02/2020
Comment: Accepted by Frisberdine Jules: Accepted by Frisberdine Jules
Comments:
Comment Date: 05/29/2020 User: ZIMMERMAN_RA_2
Description: Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response.
Comments:
Comment Date: 05/29/2020 User: ZIMMERMAN_RA_2
Description: Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response.
10/05/2018 Record Document Activity Zimmerman, Robert A
Activity Status: Closed
Contact Name: Joe Long Activity Closed Date: 10/09/2018
Events:
Event Type: Activity has been finished Date: 10/09/2018
Comment: Finished
Comments:
Comment Date: 10/05/2018 User: ZIMMERMAN_RA_2
Description: Received violation resolution documents; line leak detector test, single wall spill bucket CIE and overfill protection device test certifications; entered documents into FIRST.
09/27/2018 Editable Letter Activity Libby, Kate K
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: Compliance Assistance Offer Letter
Events:
Event Type: Document has been sent Date: 09/27/2018
Comment: Sent
Events:
Event Type: Activity has been finished Date: 09/27/2018
Comment: Finished
Attachments:
Attachment Date: 09/27/2018 User: LIBBY_KK_1
Description: Status of Violations Request
View Attachment
06/20/2018 Phone Conversation Activity Zimmerman, Robert A
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 318-0051 Activity Closed Date: 06/20/2018
Subject: Contact facility representative Joe Long with Petroleum Aids regarding violation resolution status.
Events:
Event Type: Activity has been finished Date: 06/20/2018
Comment: Finished
03/20/2018 Editable Letter Activity Zimmerman, Robert A
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Description: 8501396 Sunshine Food Mart #81 Compliance Assistance Le
Events:
Event Type: Document has been sent Date: 03/20/2018
Comment: Sent
Events:
Event Type: Activity has been finished Date: 03/20/2018
Comment: Finished
Attachments:
Attachment Date: 03/20/2018 User: ZIMMERMAN_RA_2
Description: CAO 8500284, TEXACO-KIRKWOOD.
View Attachment
03/20/2018 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 03/20/2018 Activity Status: Closed
Date: 03/20/2018
Recipient: Wenda Lewis
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and CAO email attachments to facility representative.
Events:
Event Type: Activity has been finished Date: 03/20/2018
Comment: Finished
03/15/2018 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4057
Rule: 62-761.500(7)(e)
03/15/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/15/2018
Activity Closed Date: 03/20/2018 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 03/20/2018
Comment: Finished
Comments:
Comment Date: 03/20/2018 User: ZIMMERMAN_RA_2
Description: Discussed facilities compliance history and modification to the AST rule and presented the AST outreach tool to the facility representative. Upcoming 2018 deadlines for obtaining UST operator certifications, overfill protection operability testing and containment integrity testing as per the new tank rule. Release detection and overfill protection device testing and certification – by January 11, 2018 and, every 12 months thereafter. Periodic test for storage tank system components shall occur according to the following schedule; A. Single wall spill buckets – by January 11, 2018 and, every 12 months thereafter; B. Piping and dispenser sumps - by October 13, 2018 and, every 3 years thereafter; C. Double wall spill buckets - by October 13, 2018 and, every 3 years thereafter; UST operator’s certification; Each UST facility must have a Class A, Class B and Class C operator that is trained and certified in accordance with the rule by October 13, 2018. A Class A, B or C operator must be present at all times of operation unless the facility is unmanned.
Comments:
Comment Date: 03/20/2018 User: ZIMMERMAN_RA_2
Description: Due Dates Per New Rule 07/11/17 – Field erected ASTs fueled by tanker truck must have spill containment unless fill is in secondary containment for dike field or in tank truck containment area. 01/18/18 – USTs & ASTs must conduct initial overfill protection device testing by 01/18/18, and every 12 months thereafter. 01/18/18 – UST single wall spill containment devices must have initial containment integrity test performed and then every 12 months thereafter. 01/18/18 – AST below grade spill containment systems and hydrant sumps must have initial containment integrity test performed and then every 3 years thereafter. 01/18/18 – ASTs with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 01/18/18 – Existing ASTs with pressurized small diameter piping in contact with the soil must have line leak detectors installed, and must be tested every 12 months thereafter. ASTs installed after 01/11/17, must be equipped with line leak detectors at AST installation. 10/13/18 – UST systems with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 10/13/18 – Existing UST generator tanks must have/conduct release detection. UST generator tanks installed after 01/11/17 must have/conduct release detection from time of installation. 10/13/18 – UST & AST piping dispenser sumps and double wall containment devices below grade must have initial containment integrity test performed and then every 3 years thereafter. 10/13/18 – All UST facilities must have Class A, B and C operator’s certifications.
Comments:
Comment Date: 03/20/2018 User: ZIMMERMAN_RA_2
Description: Sent TCI report and CAO email attachments to facility representative.
03/15/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/15/2018
Activity Closed Date: 03/20/2018 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 03/20/2018
Comment: Finished
Comments:
Comment Date: 03/20/2018 User: ZIMMERMAN_RA_2
Description: Discussed facilities compliance history and modification to the AST rule and presented the AST outreach tool to the facility representative. Upcoming 2018 deadlines for obtaining UST operator certifications, overfill protection operability testing and containment integrity testing as per the new tank rule. Release detection and overfill protection device testing and certification – by January 11, 2018 and, every 12 months thereafter. Periodic test for storage tank system components shall occur according to the following schedule; A. Single wall spill buckets – by January 11, 2018 and, every 12 months thereafter; B. Piping and dispenser sumps - by October 13, 2018 and, every 3 years thereafter; C. Double wall spill buckets - by October 13, 2018 and, every 3 years thereafter; UST operator’s certification; Each UST facility must have a Class A, Class B and Class C operator that is trained and certified in accordance with the rule by October 13, 2018. A Class A, B or C operator must be present at all times of operation unless the facility is unmanned.
Comments:
Comment Date: 03/20/2018 User: ZIMMERMAN_RA_2
Description: Due Dates Per New Rule 07/11/17 – Field erected ASTs fueled by tanker truck must have spill containment unless fill is in secondary containment for dike field or in tank truck containment area. 01/18/18 – USTs & ASTs must conduct initial overfill protection device testing by 01/18/18, and every 12 months thereafter. 01/18/18 – UST single wall spill containment devices must have initial containment integrity test performed and then every 12 months thereafter. 01/18/18 – AST below grade spill containment systems and hydrant sumps must have initial containment integrity test performed and then every 3 years thereafter. 01/18/18 – ASTs with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 01/18/18 – Existing ASTs with pressurized small diameter piping in contact with the soil must have line leak detectors installed, and must be tested every 12 months thereafter. ASTs installed after 01/11/17, must be equipped with line leak detectors at AST installation. 10/13/18 – UST systems with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 10/13/18 – Existing UST generator tanks must have/conduct release detection. UST generator tanks installed after 01/11/17 must have/conduct release detection from time of installation. 10/13/18 – UST & AST piping dispenser sumps and double wall containment devices below grade must have initial containment integrity test performed and then every 3 years thereafter. 10/13/18 – All UST facilities must have Class A, B and C operator’s certifications.
Comments:
Comment Date: 03/20/2018 User: ZIMMERMAN_RA_2
Description: Sent TCI report and CAO email attachments to facility representative.
03/15/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/15/2018
Activity Closed Date: 03/20/2018 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 03/20/2018
Comment: Finished
Comments:
Comment Date: 03/20/2018 User: ZIMMERMAN_RA_2
Description: Discussed facilities compliance history and modification to the AST rule and presented the AST outreach tool to the facility representative. Upcoming 2018 deadlines for obtaining UST operator certifications, overfill protection operability testing and containment integrity testing as per the new tank rule. Release detection and overfill protection device testing and certification – by January 11, 2018 and, every 12 months thereafter. Periodic test for storage tank system components shall occur according to the following schedule; A. Single wall spill buckets – by January 11, 2018 and, every 12 months thereafter; B. Piping and dispenser sumps - by October 13, 2018 and, every 3 years thereafter; C. Double wall spill buckets - by October 13, 2018 and, every 3 years thereafter; UST operator’s certification; Each UST facility must have a Class A, Class B and Class C operator that is trained and certified in accordance with the rule by October 13, 2018. A Class A, B or C operator must be present at all times of operation unless the facility is unmanned.
Comments:
Comment Date: 03/20/2018 User: ZIMMERMAN_RA_2
Description: Due Dates Per New Rule 07/11/17 – Field erected ASTs fueled by tanker truck must have spill containment unless fill is in secondary containment for dike field or in tank truck containment area. 01/18/18 – USTs & ASTs must conduct initial overfill protection device testing by 01/18/18, and every 12 months thereafter. 01/18/18 – UST single wall spill containment devices must have initial containment integrity test performed and then every 12 months thereafter. 01/18/18 – AST below grade spill containment systems and hydrant sumps must have initial containment integrity test performed and then every 3 years thereafter. 01/18/18 – ASTs with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 01/18/18 – Existing ASTs with pressurized small diameter piping in contact with the soil must have line leak detectors installed, and must be tested every 12 months thereafter. ASTs installed after 01/11/17, must be equipped with line leak detectors at AST installation. 10/13/18 – UST systems with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 10/13/18 – Existing UST generator tanks must have/conduct release detection. UST generator tanks installed after 01/11/17 must have/conduct release detection from time of installation. 10/13/18 – UST & AST piping dispenser sumps and double wall containment devices below grade must have initial containment integrity test performed and then every 3 years thereafter. 10/13/18 – All UST facilities must have Class A, B and C operator’s certifications.
Comments:
Comment Date: 03/20/2018 User: ZIMMERMAN_RA_2
Description: Sent TCI report and CAO email attachments to facility representative.
03/15/2018 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
03/15/2018 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4074
Rule: 62-761.700(2)(c)
03/15/2018 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4067
Rule: 62-761.600(4)
03/02/2018 Phone Conversation Activity Zimmerman, Robert A
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 339-4839 Activity Closed Date: 03/02/2018
Subject: Contact facility representative for notification and schedule upcoming TCI and to give a reminder that the two year record review requirement is: Registration Placard, Proof of Financial Responsibility, CFR, Monthly visual inspections and Electronic release detection records, containment integrity (if required), annual overfill protection, Line leak detector, Operability test and A/B/C UST operator certifications.
Events:
Event Type: Activity has been finished Date: 03/02/2018
Comment: Finished
02/12/2016 Record Document Activity Harrington, Richard D.
Activity Status: Closed
Contact Name: wenda lewis Activity Closed Date: 02/12/2016
Events:
Event Type: Activity has been finished Date: 02/12/2016
Comment: Finished
12/31/2015 Comment Harrington, Richard D.
Description: GPS reading in tank 1,2,3 area: Lat N 29 37.969 / Lon W 82 20.342
12/31/2015 Phone Conversation Activity Harrington, Richard D.
Call Type: Outgoing Activity Status: Closed
Activity Closed Date: 12/31/2015
Subject: Called Agustin to confirm/discuss inspection. DEP Tank video has already been emailed to LOC.
Events:
Event Type: Activity has been finished Date: 12/31/2015
Comment: Finished
12/31/2015 Editable Letter Activity Harrington, Richard D.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 12/31/2015
Comment: Finished
Attachments:
Attachment Date: 12/31/2015 User: HARRINGTON_RD_1
Description: ncl
View Attachment
12/31/2015 Site Inspection Activity Closed Harrington, Richard D.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 12/29/2015
Activity Closed Date: 12/31/2015 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 12/31/2015
Comment: Finished
Comments:
Comment Date: 12/31/2015 User: HARRINGTON_RD_1
Description: Report and ncl to be emailed to Wenda Lewis 1/4/2016.
12/31/2015 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
04/15/2014 Electronic Communication Activity Owens, Joe S.
Activity Closed Date: 04/15/2014 Activity Status: Closed
Date: 04/15/2014
Recipient: Joe Owens - ACEPD
Sender: Wenda Lewis - Lewis Oil co.
Subject: 2 year tank testing results - BOI
Message: Received testing for the Tank Tech - Parabeam 2 yr. testing requirement for the installed interstice
Events:
Event Type: Activity has been finished Date: 04/15/2014
Comment: Finished
02/17/2014 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/17/2014
Events:
Event Type: Activity has been finished Date: 02/17/2014
Comment: Finished
02/17/2014 Editable Letter Activity Owens, Joe S.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 02/17/2014
Comment: Sent on Mon Feb 17 00:00:00 EST 2014
Events:
Event Type: Activity has been finished Date: 02/17/2014
Comment: Finished
Attachments:
Attachment Date: 02/17/2014 User: OWENS_JS_1
Description: 1. 2014-02-17 - Tank NCL from inspection
View Attachment
02/12/2014 Violation Closed Owens, Joe S.
Significance: Minor Status: Closed
Criteria ID: 1020
Rule: 62-761.500(1)(d)5.
Comments: The breach of integrity test is intended for closed interstices only. A closed interstice has no unsecured or unsealed opening to the outside. Double-walled piping without a boot connector, or if the boot has a bleed valve (for tightness testing), is considered an open interstice. The breach of integrity test may be performed by using at least one of the following methods: a. A continuous hydrostatic system b. A continuous vacuum system c. Testing of the interstice for liquid tightness in accordance with manufacturer's installation instructions; or d. Another method in accordance with subsection 62-761.850(2). How the breach of integrity test is performed or to what degree can depend on the depth to groundwater at each facility. When the tank and or piping are fully submerged, the lack of water intrusion into the secondary containment may be considered a verification of its integrity. However, when total submersion is not the case, one of the rule stipulated options must be used. The breach of integrity test should not be confused with a precision tightness test, which tests the primary tank or piping only. The breach of integrity test will test the secondary and primary shells, but is not a precision test.
02/12/2014 Site Inspection Activity Closed Owens, Joe S.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/12/2014
Activity Closed Date: 02/17/2014 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 02/17/2014
Comment: Finished
Comments:
Comment Date: 02/17/2014 User: OWENS_JS_1
Description: As required by the approval process for Parabeam lined tanks - a tank tight test of the interstice was to be performed 6/2013 - this record was not available for review. Extended time was allowed to the owner to investigate and locate the testing record for this test. The test had been overlooked and is due now - VIOLATION CITED.
02/17/2012 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/17/2012
Events:
Event Type: Activity has been finished Date: 02/17/2012
Comment: Finished
02/08/2012 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/08/2012
Activity Closed Date: 02/17/2012 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 02/17/2012
Comment: Finished
06/07/2010 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/07/2010
Activity Closed Date: 06/09/2010 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 06/09/2010
Comment: Finished
06/07/2010 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/07/2010
Events:
Event Type: Activity has been finished Date: 06/07/2010
Comment: Finished
06/07/2010 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/09/2010
Events:
Event Type: Activity has been finished Date: 06/09/2010
Comment: Finished
04/23/2009 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/23/2009
Activity Closed Date: 04/24/2009 Activity Closed By: OWENS_JS_1
04/23/2009 Editable Letter Activity Ramsey, Timothy H
Activity Title: Closure Review Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 04/23/2009
Comment: Sent on Thu Apr 23 09:57:40 EST 2009
Comments:
Comment Date: 04/23/2009 User: RAMSEY_TH_1
Description: Alternate closure review letter issued on 4/23/09
04/23/2009 TCAR Activity Ramsey, Timothy H
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 04/23/2009
03/27/2009 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/27/2009
Activity Closed Date: 04/23/2009 Activity Closed By: OWENS_JS_1
09/08/2008 Attachment Owens, Joe S.
09/08/2008 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 09/08/2008
Activity Closed Date: 09/19/2008 Activity Closed By: OWENS_JS_1
09/25/2007 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/25/2007
09/24/2007 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 09/24/2007
Activity Closed Date: 09/24/2007 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 09/24/2007 User: OWENS_JS_1
Description: CONTACT PRESENTED DOCUMENTS FOR REVIEW FOR FAC: 8500284 Placard current & displayed: OK CFR form complete - FR records are updated - OK RDRL - present and applicable for facility: TANKS; Daily elect. monitoring of tank by CSLD / PIPING; Visual monitoring of piping interstice within STP sumps. MLLD. All disp. liners, spill buckets visual inspection. Site Diagram for accuracy, attached to ATTACHMENT Facility information. No changes from last inspecxtion. Facility registration information including tank system attributes appear to be accurate. Monthly release detection (CSLD) records - Accepted - daily status printouts reviewed. Date range for Inspection records: 12/2006 to present No Monthly ATG alarm status documented on insp. form - all systems normal w/ printout to verify - facility has CSLD/daily tank testing active for tanks as required for S/W system. ALso, facility conducts an annual tank tite test per approved AP requirements. FUTURE DUE DATES OF FOLLOWING: Tank Insurance Renewal Due: 1/2008 MLLD annual testing due - 8/2008 Placard Registration renewal due: 6/2008 Annual operability test due - 9/2008 Visual inspection revealed: STP sumps (3) are dry and clean, Spill buckets contain a trace of fuel but appear maintained - with positive shut-off overfill devices. Dispenser liners (2) are dry with no trace of any release, no issues addressed during monthly visual inspections. Monthly inspections should document any maint. which is performed or recommended as needed to prevent any release. Diesel dispenser area maintained and cleaner than most - good housekeeping. The entry boots on the piping within the sumps and disp. liners appear sound and flexible ¿ no cracks observed. Facility has a documented release and is currently scored a 10 - below current clean-up work status. The compliance inspection folder is complete and concise - RDRL is posted and is applicable for facility - Facility inspection records well maintained. ALL FACILITIES WITH SINGLE-WALLED TANKS OR PIPING ARE TO BE UPGRADED TO DOUBLE-WALLED STANDARDS BEFORE 12/31/2009 DEADLINE.
09/07/2007 Attachment Owens, Joe S.
02/08/2007 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/08/2007
10/31/2006 Attachment Owens, Joe S.
10/31/2006 Site Inspection Activity Closed Ramsey, Timothy H
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/31/2006
Activity Closed Date: 10/31/2006 Activity Closed By: RAMSEY_TH_1
Comments:
Comment Date: 10/31/2006 User: RAMSEY_TH_1
Description: DOCUMENTS REVIEWED: Placard current & displayed in Store - OK CFR form complete and updated - OK - FR record updated. RDRL Accepted - TANKS: Annual Tank Tite Test w/ DAILY csld atg test / PIPING: Visual inspection of sumps, spill buckets w/ Flappers positive shut-off, and disp. liner visual, MLLD annual testing. Site Diagram attached to Facility Attachemnts - OK Compliance Inspection Cover Page to contact. Monthly release detection records - ATG w/CSLD printouts complete and all indicate PASS on all products. FILL ports have FLapper positive shut off drop for overfill prevention. Spill buckets clean and dry - All (3) appear sound w/ trace of new fuel indicative of recent fuel drop - contact removed trace fuel -OK Previous TCI date: 8/2005 Date range for Inspection records:8/2005 - present Reviewed monthly C/W bailing results- for release detection of S/W tanks - no product indicated. Facility has a documented clean-up score of 10 - presently not in funding range for clean-up. ADVISED CONTACT OF FOLLOWING: MLLD required testing due: 4/2007 Tank Insurance Renewal: 1/2007 Placard Registration renewal due: 6/2007 Annual Tank Tghtness test- 10/2007 Operability test of leak sensors - 10/2007 REMINDER FOR SINGLE-WALL TANK OWNERS - UPGRADE DEADLINE 12/2009. Visual inspection of (3) sumps, spill buckets, (2) disp. liners all dry and clean. Performed operability test of sump elect. leak sensors for piping - PASSED
Comments:
Comment Date: 10/31/2006 User: RAMSEY_TH_1
Description: Inspection performed by J. OWens - Documented on T. Ramsey laptop.
10/31/2006 Site Inspection Activity Closed Ramsey, Timothy H
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/31/2006
Activity Closed Date: 10/31/2006 Activity Closed By: RAMSEY_TH_1
Comments:
Comment Date: 10/31/2006 User: RAMSEY_TH_1
Description: DOCUMENTS REVIEWED: Placard current & displayed in Store - OK CFR form complete and updated - OK - FR record updated. RDRL Accepted - TANKS: Annual Tank Tite Test w/ DAILY csld atg test / PIPING: Visual inspection of sumps, spill buckets w/ Flappers positive shut-off, and disp. liner visual, MLLD annual testing. Site Diagram attached to Facility Attachemnts - OK Compliance Inspection Cover Page to contact. Monthly release detection records - ATG w/CSLD printouts complete and all indicate PASS on all products. FILL ports have FLapper positive shut off drop for overfill prevention. Spill buckets clean and dry - All (3) appear sound w/ trace of new fuel indicative of recent fuel drop - contact removed trace fuel -OK Previous TCI date: 8/2005 Date range for Inspection records:8/2005 - present Reviewed monthly C/W bailing results- for release detection of S/W tanks - no product indicated. Facility has a documented clean-up score of 10 - presently not in funding range for clean-up. ADVISED CONTACT OF FOLLOWING: MLLD required testing due: 4/2007 Tank Insurance Renewal: 1/2007 Placard Registration renewal due: 6/2007 Annual Tank Tghtness test- 10/2007 Operability test of leak sensors - 10/2007 REMINDER FOR SINGLE-WALL TANK OWNERS - UPGRADE DEADLINE 12/2009. Visual inspection of (3) sumps, spill buckets, (2) disp. liners all dry and clean. Performed operability test of sump elect. leak sensors for piping - PASSED
Comments:
Comment Date: 10/31/2006 User: RAMSEY_TH_1
Description: Inspection performed by J. OWens - Documented on T. Ramsey laptop.
10/31/2006 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/31/2006
Activity Closed Date: 10/31/2006 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 10/31/2006 User: OWENS_JS_1
Description: Tank # 4 - Closed in Place - filled with Foam by Petroleum Aids Inc. & Southern Foam Insulation Inc. This tank has been out of service and Lewis Oil Co. was not prepared to remove the tank at present. Tank was empty and has been for a while. Limited Closure Summary Report received. Tank filled with foam and visible portion of fill pipe (to brim) filled and capped. State EQ-505 - foam used per foam company rep. Photos taken of fill port following foam installation. Requested Tank Registration Form be completed and forwarded to ACEPD & FDEP.
10/31/2006 Attachment Owens, Joe S.
10/31/2006 Attachment Owens, Joe S.
09/22/2006 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/22/2006
08/18/2005 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: MLLD TEST 4/28/05, ANNUAL OPERABILITY TEST 8/18/05
10/12/2004 Legacy Activity Ramsey, Timothy H
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: RECEIVED TANK TIGHTNESS TEST RESULTS DATED 10/1/04
08/12/2004 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 640(3)(c)4
08/12/2004 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: LLD TEST 4/27/04, ANNUAL OPERABILITY TEST 8/12/04
10/23/2003 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: LLD TEST 4/22/03, OPERABILITY TEST 10/23/03, ANNUAL TANK TIGHT TEST 11/13/03
11/21/2002 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: LLD TEST 4/22/02, OPERABILITY TEST 11/21/02
10/16/2001 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE INSPECTION
10/31/2000 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE INSPECTION
12/02/1999 Legacy Activity Buono, Mike
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: CHANDLER_D
10/06/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 710(1)
Comments:
Comment Date: 01/23/2007 User: SNIPES_SR_1
Description: TANK: 6,000 GALLON SINGLE WALL STEEL UST THAT IS CATHODICALLY PROTECTED BY IMPRESSED CURRENT. BALL CHECK VALVES FOR OVERFILL PROTECTION. STREET BOXES FOR SUMPS. SPILL CONTAINMENT BUCKETS WITH TIGHT FILL CONNECTORS. FIBERGLASS POURED UNIT DISPENSER LINERS (EQ#115) WITH SHEAR VALVES ANCHORED IN PLACE. MECHANICAL IN-LINE LEAK DETECTORS. SINGLE WALL STEEL PIPING THAT IS CATHODICALLY PROTECTED BY IMPRESSED CURRENT. RELEASE DETECTION: MONTHLY VISUAL INSPECTIONS INCLUDING SUMPS, DISPENSER LINERS, AND SPILL CONTAINMENT BUCKETS. ATG MECHANICAL IN-LINE LEAK DETECTORS/ ANNUAL LINE TIGHTNESS TESTING
10/06/1999 Legacy Activity Buono, Mike
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/14/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 800(4)(d)
Comments:
Comment Date: 06/03/2004 User: UNKNOWN
Description: GENERAL: PIPING: SINGLE WALL STEEL ABOVE GROUND INSIDE SECONDARY CONTAINMENT CORROSION PROTECTED.
Comments:
Comment Date: 05/04/2006 User: UNKNOWN
Description: GENERAL: PIPING: ABOVEGROUND SINGLE WALL STEEL.
06/14/1999 Legacy Activity Buono, Mike
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/14/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 800(4)(d)
Comments:
Comment Date: 06/03/2004 User: UNKNOWN
Description: GENERAL: PIPING: SINGLE WALL STEEL ABOVE GROUND INSIDE SECONDARY CONTAINMENT CORROSION PROTECTED.
Comments:
Comment Date: 05/04/2006 User: UNKNOWN
Description: GENERAL: PIPING: ABOVEGROUND SINGLE WALL STEEL.
05/26/1999 Legacy Activity Buono, Mike
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/27/1999 Legacy Activity Buono, Mike
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
04/07/1999 Legacy Activity Buono, Mike
Activity Name: TANK CLOSURE INSPECTION Activity Status: Closed
09/23/1998 Violation Closed Unknown, User
Significance: SNC-A Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 05/14/2007 User: BRAZILE_DO_1
Description: 2000 Gl. Single walled, steel, AST-located inside of a concrete secondary containment (no EQ). Piping- Steel, Aboveground Release Detection - Monthly Visual Inspection Overfill Protection - Concrete Secondary Containment/pop-up sight tube 1000 Gl. Single walled, steel, AST-located inside of a concrete secondary containment (no EQ). Piping- Steel, Aboveground Release Detection - Monthly Visual Inspection Overfill Protection - Concrete Secondary Containment/pop-up sight tube. #3. - 1000 Gl. Convault DW AST - (EQ 201). Dispenser pump located next to the AST. Release Detection - I/S space DW tank/pop-up site tube/Monthly visuals. Overfill Protection -Manual Tank gauging/pop-up site tube.
09/23/1998 Violation Closed Unknown, User
Significance: SNC-A Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Since the tank had been closed in place prior to the closure assessment requirements, and because results of groundwater samples from an NPDES permit indicated no contaminants present, a closure assessment was not required.
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: The storage tanks had been closed in place in June of 1990. While running a sewer line for a new Walmart store, the contractors (White-Spunner) encountered the old waste oil tank. Gallet & Associates who are the consultant of record contacted the ECHD.
09/23/1998 Violation Closed Unknown, User
Significance: SNC-A Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Since the tank had been closed in place prior to the closure assessment requirements, and because results of groundwater samples from an NPDES permit indicated no contaminants present, a closure assessment was not required.
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: The storage tanks had been closed in place in June of 1990. While running a sewer line for a new Walmart store, the contractors (White-Spunner) encountered the old waste oil tank. Gallet & Associates who are the consultant of record contacted the ECHD.
09/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/20/2018 User: FRENCH_EC_1
Description: Phone(850)856-9095
Comments:
Comment Date: 10/31/2000 User: UNKNOWN
Description: COMPLIANCE: SNC ENFORCEMENT
Comments:
Comment Date: 04/11/2005 User: UNKNOWN
Description: REGISTRATION: FORMER GREENSBORO HWY. /AWM
09/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/20/2018 User: FRENCH_EC_1
Description: Phone(850)856-9095
Comments:
Comment Date: 10/31/2000 User: UNKNOWN
Description: COMPLIANCE: SNC ENFORCEMENT
Comments:
Comment Date: 04/11/2005 User: UNKNOWN
Description: REGISTRATION: FORMER GREENSBORO HWY. /AWM
09/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/20/2018 User: FRENCH_EC_1
Description: Phone(850)856-9095
Comments:
Comment Date: 10/31/2000 User: UNKNOWN
Description: COMPLIANCE: SNC ENFORCEMENT
Comments:
Comment Date: 04/11/2005 User: UNKNOWN
Description: REGISTRATION: FORMER GREENSBORO HWY. /AWM
09/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Oz Baruch (504) 232-8111.
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Facility under new ownership. Facility now called OZ Holdings #2. New owners Garges Purtee & Oz Baruch.
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Mark Purtee (813) 514-3804.
Comments:
Comment Date: 06/29/2015 User: FOXWORTH_S_1
Description: POC is Abu T. Mridha, Property Owner and Operator, almridha@sbcglobal.net Store Manager is Rizwan Bakhshi, rizwan.bakhshi@cellularamerica.com or store Phone is 850-862-4241. The Southeastern Energy Corp POC is Jeff McConnell - jeff@secqv.net
09/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Oz Baruch (504) 232-8111.
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Facility under new ownership. Facility now called OZ Holdings #2. New owners Garges Purtee & Oz Baruch.
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Mark Purtee (813) 514-3804.
Comments:
Comment Date: 06/29/2015 User: FOXWORTH_S_1
Description: POC is Abu T. Mridha, Property Owner and Operator, almridha@sbcglobal.net Store Manager is Rizwan Bakhshi, rizwan.bakhshi@cellularamerica.com or store Phone is 850-862-4241. The Southeastern Energy Corp POC is Jeff McConnell - jeff@secqv.net
09/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Oz Baruch (504) 232-8111.
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Facility under new ownership. Facility now called OZ Holdings #2. New owners Garges Purtee & Oz Baruch.
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Mark Purtee (813) 514-3804.
Comments:
Comment Date: 06/29/2015 User: FOXWORTH_S_1
Description: POC is Abu T. Mridha, Property Owner and Operator, almridha@sbcglobal.net Store Manager is Rizwan Bakhshi, rizwan.bakhshi@cellularamerica.com or store Phone is 850-862-4241. The Southeastern Energy Corp POC is Jeff McConnell - jeff@secqv.net
09/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Oz Baruch (504) 232-8111.
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Facility under new ownership. Facility now called OZ Holdings #2. New owners Garges Purtee & Oz Baruch.
Comments:
Comment Date: 06/19/2006 User: THAYER_JD_1
Description: Mark Purtee (813) 514-3804.
Comments:
Comment Date: 06/29/2015 User: FOXWORTH_S_1
Description: POC is Abu T. Mridha, Property Owner and Operator, almridha@sbcglobal.net Store Manager is Rizwan Bakhshi, rizwan.bakhshi@cellularamerica.com or store Phone is 850-862-4241. The Southeastern Energy Corp POC is Jeff McConnell - jeff@secqv.net
09/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 10/31/2000 User: UNKNOWN
Description: COMPLIANCE: SNC ENFORCEMENT
09/23/1998 Violation Closed Unknown, User
Significance: SNC-B Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
09/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 08/05/2021 User: MATHERLY_H
Description: Facility Contacts Jimmy White - Vice President Deep South Crane Rentals, Inc. (850) 982-1679 Erik Jaspers erik@deepsouthcranes.com (850) 876-9509
09/23/1998 Legacy Activity Buono, Mike
Activity Name: UST ROUTINE COMPLIANCE INSPECTION Activity Status: Closed