Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 04/27/2025 Last Data Refresh: 04/26/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 8500284 | ||||||||||
Facility Name: | TEXACO-KIRKWOOD | ||||||||||
04/04/2025 | Editable Letter Activity | McNeil, Anthony P | |||||||||
Activity Title: | Warning Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 04/04/2025 | ||||||||
Comment: | Submitted for approval by: Anthony P McNeil | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document has been approved | Date: | 04/07/2025 | ||||||||
Comment: | Approved by Jennifer Paul: WL24-240 11/14/2024 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/07/2025 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 04/04/2025 | User: | MCNEIL_A | ||||||||
Description: | Warning Letter No. WL24-240 | ||||||||||
View Attachment | |||||||||||
01/31/2025 | Violation Open | Keim, Michael J | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7084 | ||||||||||
Rule: | 62-762.701(2), 62-762.701(2)(a), 62-762.702(2), 62-762.702(2)(a) | ||||||||||
01/31/2025 | Electronic Communication Activity | Keim, Michael J | |||||||||
Activity Closed Date: | 01/31/2025 | Activity Status: | Closed | ||||||||
Date: | 01/31/2025 | ||||||||||
Recipient: | Wenda Lewis, Chris Leonard | ||||||||||
Sender: | M Keim | ||||||||||
Subject: | TCI | ||||||||||
Message: | E-mail correspondence with Chris Leonard and Wenda Lewis regarding TCI scheduling and records needed. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/31/2025 | ||||||||
Comment: | Finished | ||||||||||
01/31/2025 | Editable Letter Activity | Keim, Michael J | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/31/2025 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 01/31/2025 | ||||||||
Comment: | Sent | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 01/31/2025 | User: | KEIM_MJ_1 | ||||||||
Description: | CAO Letter | ||||||||||
View Attachment | |||||||||||
01/31/2025 | Electronic Communication Activity | Keim, Michael J | |||||||||
Activity Closed Date: | 01/31/2025 | Activity Status: | Closed | ||||||||
Date: | 01/31/2025 | ||||||||||
Recipient: | Wenda Lewis | ||||||||||
Sender: | M Keim | ||||||||||
Subject: | TCI report | ||||||||||
Message: | Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/31/2025 | ||||||||
Comment: | Finished | ||||||||||
01/29/2025 | Site Inspection Activity Closed | Keim, Michael J | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 01/15/2025 | ||||||||||
Activity Closed Date: | 01/31/2025 | Activity Closed By: | KEIM_MJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/31/2025 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 01/31/2025 | User: | KEIM_MJ_1 | ||||||||
Description: | Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com Compliance assist with Chris Leonard of ARC Dynamics | ||||||||||
10/02/2024 | Enforcement Tracking Activity | McNeil, Anthony P | |||||||||
Activity Status: | Open | ||||||||||
11/06/2023 | Attachment | Harrington, Richard D. | |||||||||
01/30/2023 | Violation Open | Keim, Michael J | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 6051 | ||||||||||
Rule: | 62-761.500(7)(a) | ||||||||||
01/30/2023 | Record Document Activity | Keim, Michael J | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Wenda Lewis | Activity Closed Date: | 01/30/2023 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/30/2023 | ||||||||
Comment: | Finished | ||||||||||
01/30/2023 | Record Document Activity | Keim, Michael J | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Wenda Lewis | Activity Closed Date: | 01/30/2023 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/30/2023 | ||||||||
Comment: | Finished | ||||||||||
01/30/2023 | Record Document Activity | Keim, Michael J | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Wenda Lewis | Activity Closed Date: | 01/30/2023 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/30/2023 | ||||||||
Comment: | Finished | ||||||||||
01/30/2023 | Record Document Activity | Keim, Michael J | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Wenda Lewis | Activity Closed Date: | 01/30/2023 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/30/2023 | ||||||||
Comment: | Finished | ||||||||||
01/30/2023 | Editable Letter Activity | Keim, Michael J | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/30/2023 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 01/30/2023 | ||||||||
Comment: | Sent | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 01/30/2023 | User: | KEIM_MJ_1 | ||||||||
Description: | CAO Letter | ||||||||||
View Attachment | |||||||||||
01/30/2023 | Electronic Communication Activity | Keim, Michael J | |||||||||
Activity Closed Date: | 01/30/2023 | Activity Status: | Closed | ||||||||
Date: | 01/30/2023 | ||||||||||
Recipient: | Wenda Lewis | ||||||||||
Sender: | M Keim | ||||||||||
Subject: | TCI report | ||||||||||
Message: | Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/30/2023 | ||||||||
Comment: | Finished | ||||||||||
01/30/2023 | Violation Closed | Keim, Michael J | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 6062 | ||||||||||
Rule: | 62-761.600(4) | ||||||||||
01/26/2023 | Enforcement Referral Activity | Harrington, Richard D. | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 10/02/2024 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 01/26/2023 | ||||||||
Comment: | Submitted for approval by: Richard D. Harrington: Routine Inspection Activity is in progress for 2023. We will attempt to resolve issues as the report is input. Referral rejection will be requested if possible. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/02/2024 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 10/02/2024 | ||||||||
Comment: | Accepted by Anthony P McNeil: Accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 10/01/2024 | ||||||||
Comment: | Acknowledged and Assigned by Jennifer Paul | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 10/01/2024 | ||||||||
Comment: | Assigned to Anthony P McNeil | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 10/01/2024 | ||||||||
Comment: | Submitted for approval by: Richard D. Harrington: This referral was withdrawn per DEP request and is now being re-submitted by ACEPD for DEP re-assignment. * Please note that this facility is due for Routine Inspection this contract year. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been withdrawn from submission by the requestor | Date: | 10/01/2024 | ||||||||
Comment: | Withdrawn by Richard D. Harrington: Withdraw referral per request of Jennifer Paul- DEP. Referral to be re-submitted by ACEPD and re-assigned by DEP. | ||||||||||
Comments: | |||||||||||
Comment Date: | 01/26/2023 | User: | HARRINGTON_RD_1 | ||||||||
Description: | Routine Inspection Activity is in progress for 2023. We will attempt to resolve issues as the report is input. Referral rejection will be requested if possible. | ||||||||||
01/18/2023 | Site Inspection Activity Closed | Keim, Michael J | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 01/18/2023 | ||||||||||
Activity Closed Date: | 01/30/2023 | Activity Closed By: | KEIM_MJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/30/2023 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 01/30/2023 | User: | KEIM_MJ_1 | ||||||||
Description: | Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com Compliance assist with Aron of ARC Dynamics | ||||||||||
06/10/2022 | Electronic Communication Activity | Zimmerman, Robert A | |||||||||
Activity Closed Date: | 06/10/2022 | Activity Status: | Closed | ||||||||
Date: | 06/10/2022 | ||||||||||
Recipient: | Wenda Lewis | ||||||||||
Sender: | Robert Zimmerman | ||||||||||
Subject: | Violation resolution status compliance assistance outreach inquiry. | ||||||||||
Message: | Compliance assistance outreach contact with facility representative wlewis@lewisoilco.com regarding violation resolution status. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/10/2022 | ||||||||
Comment: | Finished | ||||||||||
06/09/2022 | Record Document Activity | Zimmerman, Robert A | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Wenda Lewis | Activity Closed Date: | 06/09/2022 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/09/2022 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/09/2022 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Compliance assistance outreach contact with facility representative wlewis@lewisoilco.com regarding violation resolution status. | ||||||||||
01/21/2021 | Editable Letter Activity | Harris, Matthew J | |||||||||
Activity Title: | Return to Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/21/2021 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 01/21/2021 | User: | HARRIS_MJ | ||||||||
Description: | Return To COmpliance | ||||||||||
View Attachment | |||||||||||
08/24/2020 | Violation Closed | Zimmerman, Robert A | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 4067 | ||||||||||
Rule: | 62-761.600(4) | ||||||||||
08/24/2020 | Editable Letter Activity | Zimmerman, Robert A | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/24/2020 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 08/24/2020 | ||||||||
Comment: | Sent | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 08/24/2020 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | CAO 8500284, TEXACO-KIRKWOOD. | ||||||||||
View Attachment | |||||||||||
08/24/2020 | Electronic Communication Activity | Zimmerman, Robert A | |||||||||
Activity Closed Date: | 08/24/2020 | Activity Status: | Closed | ||||||||
Date: | 08/24/2020 | ||||||||||
Recipient: | Joe Long | ||||||||||
Sender: | Robert Zimmerman | ||||||||||
Subject: | TCI report | ||||||||||
Message: | Sent TCI report and CAO to facility representative; Joey Long jlong@petroleumaids.co cc Jesse Wilkinson jwilkinson@petroleumaids.com | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/24/2020 | ||||||||
Comment: | Finished | ||||||||||
08/24/2020 | Violation Closed | Zimmerman, Robert A | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 4076 | ||||||||||
Rule: | 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2. | ||||||||||
08/24/2020 | Violation Closed | Zimmerman, Robert A | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 4068 | ||||||||||
Rule: | 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1., 62-761.700(1)(a)2. | ||||||||||
08/24/2020 | Violation Closed | Zimmerman, Robert A | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 4001 | ||||||||||
Rule: | 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2., 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7) | ||||||||||
08/10/2020 | Site Inspection Activity Closed | Zimmerman, Robert A | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/10/2020 | ||||||||||
Activity Closed Date: | 08/24/2020 | Activity Closed By: | ZIMMERMAN_RA_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/24/2020 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/24/2020 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Sent TCI report and CAO to facility representative; Joey Long jlong@petroleumaids.co cc Jesse Wilkinson jwilkinson@petroleumaids.com | ||||||||||
08/03/2020 | Electronic Communication Activity | Zimmerman, Robert A | |||||||||
Activity Closed Date: | 08/03/2020 | Activity Status: | Closed | ||||||||
Date: | 08/03/2020 | ||||||||||
Recipient: | Joe Long | ||||||||||
Sender: | Robert Zimmerman | ||||||||||
Subject: | Compliance outreach TCI notification-scheduling | ||||||||||
Message: | Contact facility representative "Joey Long" jlong@petroleumaids.com for notification and schedule upcoming TCI and to give a reminder that the three-year record review requirement is: Registration Placard, Proof of Financial Responsibility, STFM, monthly visual inspections, monthly alarm history reports and electronic release detection records, A/B/C level UST operators certifications, PARABEAM Two Year Breach of integrity test, overfill protection device test, annual Cathodic Protection test, spill bucket and sump containment integrity testing, line leak detector and operability test certifications. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/03/2020 | ||||||||
Comment: | Finished | ||||||||||
06/02/2020 | Enforcement Tracking Activity | Jules, Frisberdine | |||||||||
Activity Status: | Closed | ||||||||||
Activity Result: | Closed Without Enforcement | Activity Closed Date: | 07/28/2020 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/28/2020 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/11/2020 | User: | JULES_F | ||||||||
Description: | The last time I spoke with Ms. Lewis, she had said that she had already taken care of everything since 2018 and that she's going to email me the documents. I reached out to her today to see when I should be expecting them, and she said that she is working with her local inspectors and have found almost all the documents. I'm assuming that I should be receiving the documents once they are all found. I will be in touch with her again next week. | ||||||||||
05/29/2020 | Enforcement Referral Activity | Zimmerman, Robert A | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 06/02/2020 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 05/29/2020 | ||||||||
Comment: | Submitted for approval by: Robert A Zimmerman: Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 05/29/2020 | ||||||||
Comment: | Assigned to Frisberdine Jules | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 05/29/2020 | ||||||||
Comment: | Acknowledged and Assigned by Matthew J Harris | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/02/2020 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 06/02/2020 | ||||||||
Comment: | Accepted by Frisberdine Jules: Accepted by Frisberdine Jules | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/29/2020 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response. | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/29/2020 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response. | ||||||||||
05/29/2020 | Electronic Communication Activity | Zimmerman, Robert A | |||||||||
Activity Closed Date: | 05/29/2020 | Activity Status: | Closed | ||||||||
Date: | 05/29/2020 | ||||||||||
Recipient: | Joe Long | ||||||||||
Sender: | Robert Zimmerman | ||||||||||
Subject: | Compliance assistance outreach violation resolution status inquiry. | ||||||||||
Message: | Compliance assistance outreach contact with facility representative regarding violation resolution status; no response. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/29/2020 | ||||||||
Comment: | Finished | ||||||||||
05/29/2020 | Enforcement Referral Activity | Zimmerman, Robert A | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 06/02/2020 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 05/29/2020 | ||||||||
Comment: | Submitted for approval by: Robert A Zimmerman: Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 05/29/2020 | ||||||||
Comment: | Assigned to Frisberdine Jules | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 05/29/2020 | ||||||||
Comment: | Acknowledged and Assigned by Matthew J Harris | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/02/2020 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 06/02/2020 | ||||||||
Comment: | Accepted by Frisberdine Jules: Accepted by Frisberdine Jules | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/29/2020 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response. | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/29/2020 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Compliance assistance outreach electronic communication with facility representative regarding violation resolution status; no response. | ||||||||||
10/05/2018 | Record Document Activity | Zimmerman, Robert A | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Joe Long | Activity Closed Date: | 10/09/2018 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/09/2018 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/05/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Received violation resolution documents; line leak detector test, single wall spill bucket CIE and overfill protection device test certifications; entered documents into FIRST. | ||||||||||
09/27/2018 | Editable Letter Activity | Libby, Kate K | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
Description: | Compliance Assistance Offer Letter | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 09/27/2018 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/27/2018 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 09/27/2018 | User: | LIBBY_KK_1 | ||||||||
Description: | Status of Violations Request | ||||||||||
View Attachment | |||||||||||
06/20/2018 | Phone Conversation Activity | Zimmerman, Robert A | |||||||||
Call Type: | Outgoing | Activity Status: | Closed | ||||||||
Phone Number: | (352) 318-0051 | Activity Closed Date: | 06/20/2018 | ||||||||
Subject: | Contact facility representative Joe Long with Petroleum Aids regarding violation resolution status. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/20/2018 | ||||||||
Comment: | Finished | ||||||||||
03/20/2018 | Editable Letter Activity | Zimmerman, Robert A | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Description: | 8501396 Sunshine Food Mart #81 Compliance Assistance Le | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 03/20/2018 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/20/2018 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 03/20/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | CAO 8500284, TEXACO-KIRKWOOD. | ||||||||||
View Attachment | |||||||||||
03/20/2018 | Electronic Communication Activity | Zimmerman, Robert A | |||||||||
Activity Closed Date: | 03/20/2018 | Activity Status: | Closed | ||||||||
Date: | 03/20/2018 | ||||||||||
Recipient: | Wenda Lewis | ||||||||||
Sender: | Robert Zimmerman | ||||||||||
Subject: | TCI report | ||||||||||
Message: | Sent TCI report and CAO email attachments to facility representative. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/20/2018 | ||||||||
Comment: | Finished | ||||||||||
03/15/2018 | Violation Closed | Zimmerman, Robert A | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 4057 | ||||||||||
Rule: | 62-761.500(7)(e) | ||||||||||
03/15/2018 | Site Inspection Activity Closed | Zimmerman, Robert A | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 03/15/2018 | ||||||||||
Activity Closed Date: | 03/20/2018 | Activity Closed By: | ZIMMERMAN_RA_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/20/2018 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/20/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Discussed facilities compliance history and modification to the AST rule and presented the AST outreach tool to the facility representative. Upcoming 2018 deadlines for obtaining UST operator certifications, overfill protection operability testing and containment integrity testing as per the new tank rule. Release detection and overfill protection device testing and certification – by January 11, 2018 and, every 12 months thereafter. Periodic test for storage tank system components shall occur according to the following schedule; A. Single wall spill buckets – by January 11, 2018 and, every 12 months thereafter; B. Piping and dispenser sumps - by October 13, 2018 and, every 3 years thereafter; C. Double wall spill buckets - by October 13, 2018 and, every 3 years thereafter; UST operator’s certification; Each UST facility must have a Class A, Class B and Class C operator that is trained and certified in accordance with the rule by October 13, 2018. A Class A, B or C operator must be present at all times of operation unless the facility is unmanned. | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/20/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Due Dates Per New Rule 07/11/17 – Field erected ASTs fueled by tanker truck must have spill containment unless fill is in secondary containment for dike field or in tank truck containment area. 01/18/18 – USTs & ASTs must conduct initial overfill protection device testing by 01/18/18, and every 12 months thereafter. 01/18/18 – UST single wall spill containment devices must have initial containment integrity test performed and then every 12 months thereafter. 01/18/18 – AST below grade spill containment systems and hydrant sumps must have initial containment integrity test performed and then every 3 years thereafter. 01/18/18 – ASTs with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 01/18/18 – Existing ASTs with pressurized small diameter piping in contact with the soil must have line leak detectors installed, and must be tested every 12 months thereafter. ASTs installed after 01/11/17, must be equipped with line leak detectors at AST installation. 10/13/18 – UST systems with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 10/13/18 – Existing UST generator tanks must have/conduct release detection. UST generator tanks installed after 01/11/17 must have/conduct release detection from time of installation. 10/13/18 – UST & AST piping dispenser sumps and double wall containment devices below grade must have initial containment integrity test performed and then every 3 years thereafter. 10/13/18 – All UST facilities must have Class A, B and C operator’s certifications. | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/20/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Sent TCI report and CAO email attachments to facility representative. | ||||||||||
03/15/2018 | Site Inspection Activity Closed | Zimmerman, Robert A | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 03/15/2018 | ||||||||||
Activity Closed Date: | 03/20/2018 | Activity Closed By: | ZIMMERMAN_RA_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/20/2018 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/20/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Discussed facilities compliance history and modification to the AST rule and presented the AST outreach tool to the facility representative. Upcoming 2018 deadlines for obtaining UST operator certifications, overfill protection operability testing and containment integrity testing as per the new tank rule. Release detection and overfill protection device testing and certification – by January 11, 2018 and, every 12 months thereafter. Periodic test for storage tank system components shall occur according to the following schedule; A. Single wall spill buckets – by January 11, 2018 and, every 12 months thereafter; B. Piping and dispenser sumps - by October 13, 2018 and, every 3 years thereafter; C. Double wall spill buckets - by October 13, 2018 and, every 3 years thereafter; UST operator’s certification; Each UST facility must have a Class A, Class B and Class C operator that is trained and certified in accordance with the rule by October 13, 2018. A Class A, B or C operator must be present at all times of operation unless the facility is unmanned. | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/20/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Due Dates Per New Rule 07/11/17 – Field erected ASTs fueled by tanker truck must have spill containment unless fill is in secondary containment for dike field or in tank truck containment area. 01/18/18 – USTs & ASTs must conduct initial overfill protection device testing by 01/18/18, and every 12 months thereafter. 01/18/18 – UST single wall spill containment devices must have initial containment integrity test performed and then every 12 months thereafter. 01/18/18 – AST below grade spill containment systems and hydrant sumps must have initial containment integrity test performed and then every 3 years thereafter. 01/18/18 – ASTs with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 01/18/18 – Existing ASTs with pressurized small diameter piping in contact with the soil must have line leak detectors installed, and must be tested every 12 months thereafter. ASTs installed after 01/11/17, must be equipped with line leak detectors at AST installation. 10/13/18 – UST systems with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 10/13/18 – Existing UST generator tanks must have/conduct release detection. UST generator tanks installed after 01/11/17 must have/conduct release detection from time of installation. 10/13/18 – UST & AST piping dispenser sumps and double wall containment devices below grade must have initial containment integrity test performed and then every 3 years thereafter. 10/13/18 – All UST facilities must have Class A, B and C operator’s certifications. | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/20/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Sent TCI report and CAO email attachments to facility representative. | ||||||||||
03/15/2018 | Site Inspection Activity Closed | Zimmerman, Robert A | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 03/15/2018 | ||||||||||
Activity Closed Date: | 03/20/2018 | Activity Closed By: | ZIMMERMAN_RA_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/20/2018 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/20/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Discussed facilities compliance history and modification to the AST rule and presented the AST outreach tool to the facility representative. Upcoming 2018 deadlines for obtaining UST operator certifications, overfill protection operability testing and containment integrity testing as per the new tank rule. Release detection and overfill protection device testing and certification – by January 11, 2018 and, every 12 months thereafter. Periodic test for storage tank system components shall occur according to the following schedule; A. Single wall spill buckets – by January 11, 2018 and, every 12 months thereafter; B. Piping and dispenser sumps - by October 13, 2018 and, every 3 years thereafter; C. Double wall spill buckets - by October 13, 2018 and, every 3 years thereafter; UST operator’s certification; Each UST facility must have a Class A, Class B and Class C operator that is trained and certified in accordance with the rule by October 13, 2018. A Class A, B or C operator must be present at all times of operation unless the facility is unmanned. | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/20/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Due Dates Per New Rule 07/11/17 – Field erected ASTs fueled by tanker truck must have spill containment unless fill is in secondary containment for dike field or in tank truck containment area. 01/18/18 – USTs & ASTs must conduct initial overfill protection device testing by 01/18/18, and every 12 months thereafter. 01/18/18 – UST single wall spill containment devices must have initial containment integrity test performed and then every 12 months thereafter. 01/18/18 – AST below grade spill containment systems and hydrant sumps must have initial containment integrity test performed and then every 3 years thereafter. 01/18/18 – ASTs with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 01/18/18 – Existing ASTs with pressurized small diameter piping in contact with the soil must have line leak detectors installed, and must be tested every 12 months thereafter. ASTs installed after 01/11/17, must be equipped with line leak detectors at AST installation. 10/13/18 – UST systems with gravity head on small diameter piping must have anti-siphon valves installed in-place as well as isolation block valves on tank systems (no date listed). 10/13/18 – Existing UST generator tanks must have/conduct release detection. UST generator tanks installed after 01/11/17 must have/conduct release detection from time of installation. 10/13/18 – UST & AST piping dispenser sumps and double wall containment devices below grade must have initial containment integrity test performed and then every 3 years thereafter. 10/13/18 – All UST facilities must have Class A, B and C operator’s certifications. | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/20/2018 | User: | ZIMMERMAN_RA_2 | ||||||||
Description: | Sent TCI report and CAO email attachments to facility representative. | ||||||||||
03/15/2018 | Violation Closed | Zimmerman, Robert A | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 4076 | ||||||||||
Rule: | 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2. | ||||||||||
03/15/2018 | Violation Closed | Zimmerman, Robert A | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 4074 | ||||||||||
Rule: | 62-761.700(2)(c) | ||||||||||
03/15/2018 | Violation Closed | Zimmerman, Robert A | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 4067 | ||||||||||
Rule: | 62-761.600(4) | ||||||||||
03/02/2018 | Phone Conversation Activity | Zimmerman, Robert A | |||||||||
Call Type: | Outgoing | Activity Status: | Closed | ||||||||
Phone Number: | (352) 339-4839 | Activity Closed Date: | 03/02/2018 | ||||||||
Subject: | Contact facility representative for notification and schedule upcoming TCI and to give a reminder that the two year record review requirement is: Registration Placard, Proof of Financial Responsibility, CFR, Monthly visual inspections and Electronic release detection records, containment integrity (if required), annual overfill protection, Line leak detector, Operability test and A/B/C UST operator certifications. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/02/2018 | ||||||||
Comment: | Finished | ||||||||||
02/12/2016 | Record Document Activity | Harrington, Richard D. | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | wenda lewis | Activity Closed Date: | 02/12/2016 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/12/2016 | ||||||||
Comment: | Finished | ||||||||||
12/31/2015 | Comment | Harrington, Richard D. | |||||||||
Description: | GPS reading in tank 1,2,3 area: Lat N 29 37.969 / Lon W 82 20.342 | ||||||||||
12/31/2015 | Phone Conversation Activity | Harrington, Richard D. | |||||||||
Call Type: | Outgoing | Activity Status: | Closed | ||||||||
Activity Closed Date: | 12/31/2015 | ||||||||||
Subject: | Called Agustin to confirm/discuss inspection. DEP Tank video has already been emailed to LOC. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/31/2015 | ||||||||
Comment: | Finished | ||||||||||
12/31/2015 | Editable Letter Activity | Harrington, Richard D. | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/31/2015 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 12/31/2015 | User: | HARRINGTON_RD_1 | ||||||||
Description: | ncl | ||||||||||
View Attachment | |||||||||||
12/31/2015 | Site Inspection Activity Closed | Harrington, Richard D. | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 12/29/2015 | ||||||||||
Activity Closed Date: | 12/31/2015 | Activity Closed By: | HARRINGTON_RD_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/31/2015 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 12/31/2015 | User: | HARRINGTON_RD_1 | ||||||||
Description: | Report and ncl to be emailed to Wenda Lewis 1/4/2016. | ||||||||||
12/31/2015 | Violation Closed | Harrington, Richard D. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 1105 | ||||||||||
Rule: | 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d. | ||||||||||
Comments: | Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs? | ||||||||||
04/15/2014 | Electronic Communication Activity | Owens, Joe S. | |||||||||
Activity Closed Date: | 04/15/2014 | Activity Status: | Closed | ||||||||
Date: | 04/15/2014 | ||||||||||
Recipient: | Joe Owens - ACEPD | ||||||||||
Sender: | Wenda Lewis - Lewis Oil co. | ||||||||||
Subject: | 2 year tank testing results - BOI | ||||||||||
Message: | Received testing for the Tank Tech - Parabeam 2 yr. testing requirement for the installed interstice | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/15/2014 | ||||||||
Comment: | Finished | ||||||||||
02/17/2014 | Emergency Preparedness Information Activity | Owens, Joe S. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 02/17/2014 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/17/2014 | ||||||||
Comment: | Finished | ||||||||||
02/17/2014 | Editable Letter Activity | Owens, Joe S. | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 02/17/2014 | ||||||||
Comment: | Sent on Mon Feb 17 00:00:00 EST 2014 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/17/2014 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/17/2014 | User: | OWENS_JS_1 | ||||||||
Description: | 1. 2014-02-17 - Tank NCL from inspection | ||||||||||
View Attachment | |||||||||||
02/12/2014 | Violation Closed | Owens, Joe S. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 1020 | ||||||||||
Rule: | 62-761.500(1)(d)5. | ||||||||||
Comments: | The breach of integrity test is intended for closed interstices only. A closed interstice has no unsecured or unsealed opening to the outside. Double-walled piping without a boot connector, or if the boot has a bleed valve (for tightness testing), is considered an open interstice. The breach of integrity test may be performed by using at least one of the following methods: a. A continuous hydrostatic system b. A continuous vacuum system c. Testing of the interstice for liquid tightness in accordance with manufacturer's installation instructions; or d. Another method in accordance with subsection 62-761.850(2). How the breach of integrity test is performed or to what degree can depend on the depth to groundwater at each facility. When the tank and or piping are fully submerged, the lack of water intrusion into the secondary containment may be considered a verification of its integrity. However, when total submersion is not the case, one of the rule stipulated options must be used. The breach of integrity test should not be confused with a precision tightness test, which tests the primary tank or piping only. The breach of integrity test will test the secondary and primary shells, but is not a precision test. | ||||||||||
02/12/2014 | Site Inspection Activity Closed | Owens, Joe S. | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 02/12/2014 | ||||||||||
Activity Closed Date: | 02/17/2014 | Activity Closed By: | OWENS_JS_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/17/2014 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 02/17/2014 | User: | OWENS_JS_1 | ||||||||
Description: | As required by the approval process for Parabeam lined tanks - a tank tight test of the interstice was to be performed 6/2013 - this record was not available for review. Extended time was allowed to the owner to investigate and locate the testing record for this test. The test had been overlooked and is due now - VIOLATION CITED. | ||||||||||
02/17/2012 | Emergency Preparedness Information Activity | Owens, Joe S. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 02/17/2012 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/17/2012 | ||||||||
Comment: | Finished | ||||||||||
02/08/2012 | Site Inspection Activity Closed | Owens, Joe S. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 02/08/2012 | ||||||||||
Activity Closed Date: | 02/17/2012 | Activity Closed By: | OWENS_JS_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/17/2012 | ||||||||
Comment: | Finished | ||||||||||
06/07/2010 | Site Inspection Activity Closed | Owens, Joe S. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/07/2010 | ||||||||||
Activity Closed Date: | 06/09/2010 | Activity Closed By: | OWENS_JS_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/09/2010 | ||||||||
Comment: | Finished | ||||||||||
06/07/2010 | Emergency Preparedness Information Activity | Owens, Joe S. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 06/07/2010 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/07/2010 | ||||||||
Comment: | Finished | ||||||||||
06/07/2010 | Emergency Preparedness Information Activity | Owens, Joe S. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 06/09/2010 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/09/2010 | ||||||||
Comment: | Finished | ||||||||||
04/23/2009 | Site Inspection Activity Closed | Owens, Joe S. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 04/23/2009 | ||||||||||
Activity Closed Date: | 04/24/2009 | Activity Closed By: | OWENS_JS_1 | ||||||||
04/23/2009 | Editable Letter Activity | Ramsey, Timothy H | |||||||||
Activity Title: | Closure Review Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 04/23/2009 | ||||||||
Comment: | Sent on Thu Apr 23 09:57:40 EST 2009 | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/23/2009 | User: | RAMSEY_TH_1 | ||||||||
Description: | Alternate closure review letter issued on 4/23/09 | ||||||||||
04/23/2009 | TCAR Activity | Ramsey, Timothy H | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 04/23/2009 | ||||||||||
03/27/2009 | Site Inspection Activity Closed | Owens, Joe S. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 03/27/2009 | ||||||||||
Activity Closed Date: | 04/23/2009 | Activity Closed By: | OWENS_JS_1 | ||||||||
09/08/2008 | Attachment | Owens, Joe S. | |||||||||
09/08/2008 | Site Inspection Activity Closed | Owens, Joe S. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 09/08/2008 | ||||||||||
Activity Closed Date: | 09/19/2008 | Activity Closed By: | OWENS_JS_1 | ||||||||
09/25/2007 | Emergency Preparedness Information Activity | Owens, Joe S. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 09/25/2007 | ||||||||||
09/24/2007 | Site Inspection Activity Closed | Owens, Joe S. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 09/24/2007 | ||||||||||
Activity Closed Date: | 09/24/2007 | Activity Closed By: | OWENS_JS_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 09/24/2007 | User: | OWENS_JS_1 | ||||||||
Description: | CONTACT PRESENTED DOCUMENTS FOR REVIEW FOR FAC: 8500284 Placard current & displayed: OK CFR form complete - FR records are updated - OK RDRL - present and applicable for facility: TANKS; Daily elect. monitoring of tank by CSLD / PIPING; Visual monitoring of piping interstice within STP sumps. MLLD. All disp. liners, spill buckets visual inspection. Site Diagram for accuracy, attached to ATTACHMENT Facility information. No changes from last inspecxtion. Facility registration information including tank system attributes appear to be accurate. Monthly release detection (CSLD) records - Accepted - daily status printouts reviewed. Date range for Inspection records: 12/2006 to present No Monthly ATG alarm status documented on insp. form - all systems normal w/ printout to verify - facility has CSLD/daily tank testing active for tanks as required for S/W system. ALso, facility conducts an annual tank tite test per approved AP requirements. FUTURE DUE DATES OF FOLLOWING: Tank Insurance Renewal Due: 1/2008 MLLD annual testing due - 8/2008 Placard Registration renewal due: 6/2008 Annual operability test due - 9/2008 Visual inspection revealed: STP sumps (3) are dry and clean, Spill buckets contain a trace of fuel but appear maintained - with positive shut-off overfill devices. Dispenser liners (2) are dry with no trace of any release, no issues addressed during monthly visual inspections. Monthly inspections should document any maint. which is performed or recommended as needed to prevent any release. Diesel dispenser area maintained and cleaner than most - good housekeeping. The entry boots on the piping within the sumps and disp. liners appear sound and flexible ¿ no cracks observed. Facility has a documented release and is currently scored a 10 - below current clean-up work status. The compliance inspection folder is complete and concise - RDRL is posted and is applicable for facility - Facility inspection records well maintained. ALL FACILITIES WITH SINGLE-WALLED TANKS OR PIPING ARE TO BE UPGRADED TO DOUBLE-WALLED STANDARDS BEFORE 12/31/2009 DEADLINE. | ||||||||||
09/07/2007 | Attachment | Owens, Joe S. | |||||||||
02/08/2007 | Emergency Preparedness Information Activity | Owens, Joe S. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 02/08/2007 | ||||||||||
10/31/2006 | Attachment | Owens, Joe S. | |||||||||
10/31/2006 | Site Inspection Activity Closed | Ramsey, Timothy H | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 10/31/2006 | ||||||||||
Activity Closed Date: | 10/31/2006 | Activity Closed By: | RAMSEY_TH_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 10/31/2006 | User: | RAMSEY_TH_1 | ||||||||
Description: | DOCUMENTS REVIEWED: Placard current & displayed in Store - OK CFR form complete and updated - OK - FR record updated. RDRL Accepted - TANKS: Annual Tank Tite Test w/ DAILY csld atg test / PIPING: Visual inspection of sumps, spill buckets w/ Flappers positive shut-off, and disp. liner visual, MLLD annual testing. Site Diagram attached to Facility Attachemnts - OK Compliance Inspection Cover Page to contact. Monthly release detection records - ATG w/CSLD printouts complete and all indicate PASS on all products. FILL ports have FLapper positive shut off drop for overfill prevention. Spill buckets clean and dry - All (3) appear sound w/ trace of new fuel indicative of recent fuel drop - contact removed trace fuel -OK Previous TCI date: 8/2005 Date range for Inspection records:8/2005 - present Reviewed monthly C/W bailing results- for release detection of S/W tanks - no product indicated. Facility has a documented clean-up score of 10 - presently not in funding range for clean-up. ADVISED CONTACT OF FOLLOWING: MLLD required testing due: 4/2007 Tank Insurance Renewal: 1/2007 Placard Registration renewal due: 6/2007 Annual Tank Tghtness test- 10/2007 Operability test of leak sensors - 10/2007 REMINDER FOR SINGLE-WALL TANK OWNERS - UPGRADE DEADLINE 12/2009. Visual inspection of (3) sumps, spill buckets, (2) disp. liners all dry and clean. Performed operability test of sump elect. leak sensors for piping - PASSED | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/31/2006 | User: | RAMSEY_TH_1 | ||||||||
Description: | Inspection performed by J. OWens - Documented on T. Ramsey laptop. | ||||||||||
10/31/2006 | Site Inspection Activity Closed | Ramsey, Timothy H | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 10/31/2006 | ||||||||||
Activity Closed Date: | 10/31/2006 | Activity Closed By: | RAMSEY_TH_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 10/31/2006 | User: | RAMSEY_TH_1 | ||||||||
Description: | DOCUMENTS REVIEWED: Placard current & displayed in Store - OK CFR form complete and updated - OK - FR record updated. RDRL Accepted - TANKS: Annual Tank Tite Test w/ DAILY csld atg test / PIPING: Visual inspection of sumps, spill buckets w/ Flappers positive shut-off, and disp. liner visual, MLLD annual testing. Site Diagram attached to Facility Attachemnts - OK Compliance Inspection Cover Page to contact. Monthly release detection records - ATG w/CSLD printouts complete and all indicate PASS on all products. FILL ports have FLapper positive shut off drop for overfill prevention. Spill buckets clean and dry - All (3) appear sound w/ trace of new fuel indicative of recent fuel drop - contact removed trace fuel -OK Previous TCI date: 8/2005 Date range for Inspection records:8/2005 - present Reviewed monthly C/W bailing results- for release detection of S/W tanks - no product indicated. Facility has a documented clean-up score of 10 - presently not in funding range for clean-up. ADVISED CONTACT OF FOLLOWING: MLLD required testing due: 4/2007 Tank Insurance Renewal: 1/2007 Placard Registration renewal due: 6/2007 Annual Tank Tghtness test- 10/2007 Operability test of leak sensors - 10/2007 REMINDER FOR SINGLE-WALL TANK OWNERS - UPGRADE DEADLINE 12/2009. Visual inspection of (3) sumps, spill buckets, (2) disp. liners all dry and clean. Performed operability test of sump elect. leak sensors for piping - PASSED | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/31/2006 | User: | RAMSEY_TH_1 | ||||||||
Description: | Inspection performed by J. OWens - Documented on T. Ramsey laptop. | ||||||||||
10/31/2006 | Site Inspection Activity Closed | Owens, Joe S. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 10/31/2006 | ||||||||||
Activity Closed Date: | 10/31/2006 | Activity Closed By: | OWENS_JS_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 10/31/2006 | User: | OWENS_JS_1 | ||||||||
Description: | Tank # 4 - Closed in Place - filled with Foam by Petroleum Aids Inc. & Southern Foam Insulation Inc. This tank has been out of service and Lewis Oil Co. was not prepared to remove the tank at present. Tank was empty and has been for a while. Limited Closure Summary Report received. Tank filled with foam and visible portion of fill pipe (to brim) filled and capped. State EQ-505 - foam used per foam company rep. Photos taken of fill port following foam installation. Requested Tank Registration Form be completed and forwarded to ACEPD & FDEP. | ||||||||||
10/31/2006 | Attachment | Owens, Joe S. | |||||||||
10/31/2006 | Attachment | Owens, Joe S. | |||||||||
09/22/2006 | Emergency Preparedness Information Activity | Owens, Joe S. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 09/22/2006 | ||||||||||
08/18/2005 | Legacy Activity | Ramsey, Timothy H | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
Completion Notes: | MLLD TEST 4/28/05, ANNUAL OPERABILITY TEST 8/18/05 | ||||||||||
10/12/2004 | Legacy Activity | Ramsey, Timothy H | |||||||||
Activity Name: | RESPONSE RECEIVED BY DEPARTMENT | Activity Status: | Closed | ||||||||
Completion Notes: | RECEIVED TANK TIGHTNESS TEST RESULTS DATED 10/1/04 | ||||||||||
08/12/2004 | Violation Closed | Ramsey, Timothy H | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 640(3)(c)4 | ||||||||||
08/12/2004 | Legacy Activity | Ramsey, Timothy H | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
Completion Notes: | LLD TEST 4/27/04, ANNUAL OPERABILITY TEST 8/12/04 | ||||||||||
10/23/2003 | Legacy Activity | Ramsey, Timothy H | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
Completion Notes: | LLD TEST 4/22/03, OPERABILITY TEST 10/23/03, ANNUAL TANK TIGHT TEST 11/13/03 | ||||||||||
11/21/2002 | Legacy Activity | Ramsey, Timothy H | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
Completion Notes: | LLD TEST 4/22/02, OPERABILITY TEST 11/21/02 | ||||||||||
10/16/2001 | Legacy Activity | Ramsey, Timothy H | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
Completion Notes: | COMPLIANCE INSPECTION | ||||||||||
10/31/2000 | Legacy Activity | Ramsey, Timothy H | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
Completion Notes: | COMPLIANCE INSPECTION | ||||||||||
12/02/1999 | Legacy Activity | Buono, Mike | |||||||||
Activity Name: | TANK COMPLIANCE RE-INSPECTION | Activity Status: | Closed | ||||||||
Completion Notes: | CHANDLER_D | ||||||||||
10/06/1999 | Violation Closed | Buono, Mike | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 710(1) | ||||||||||
Comments: | |||||||||||
Comment Date: | 01/23/2007 | User: | SNIPES_SR_1 | ||||||||
Description: | TANK: 6,000 GALLON SINGLE WALL STEEL UST THAT IS CATHODICALLY PROTECTED BY IMPRESSED CURRENT. BALL CHECK VALVES FOR OVERFILL PROTECTION. STREET BOXES FOR SUMPS. SPILL CONTAINMENT BUCKETS WITH TIGHT FILL CONNECTORS. FIBERGLASS POURED UNIT DISPENSER LINERS (EQ#115) WITH SHEAR VALVES ANCHORED IN PLACE. MECHANICAL IN-LINE LEAK DETECTORS. SINGLE WALL STEEL PIPING THAT IS CATHODICALLY PROTECTED BY IMPRESSED CURRENT. RELEASE DETECTION: MONTHLY VISUAL INSPECTIONS INCLUDING SUMPS, DISPENSER LINERS, AND SPILL CONTAINMENT BUCKETS. ATG MECHANICAL IN-LINE LEAK DETECTORS/ ANNUAL LINE TIGHTNESS TESTING | ||||||||||
10/06/1999 | Legacy Activity | Buono, Mike | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
06/14/1999 | Violation Closed | Buono, Mike | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 800(4)(d) | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/03/2004 | User: | UNKNOWN | ||||||||
Description: | GENERAL: PIPING: SINGLE WALL STEEL ABOVE GROUND INSIDE SECONDARY CONTAINMENT CORROSION PROTECTED. | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/04/2006 | User: | UNKNOWN | ||||||||
Description: | GENERAL: PIPING: ABOVEGROUND SINGLE WALL STEEL. | ||||||||||
06/14/1999 | Legacy Activity | Buono, Mike | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
06/14/1999 | Violation Closed | Buono, Mike | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 800(4)(d) | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/03/2004 | User: | UNKNOWN | ||||||||
Description: | GENERAL: PIPING: SINGLE WALL STEEL ABOVE GROUND INSIDE SECONDARY CONTAINMENT CORROSION PROTECTED. | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/04/2006 | User: | UNKNOWN | ||||||||
Description: | GENERAL: PIPING: ABOVEGROUND SINGLE WALL STEEL. | ||||||||||
05/26/1999 | Legacy Activity | Buono, Mike | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
04/27/1999 | Legacy Activity | Buono, Mike | |||||||||
Activity Name: | TANK INSTALLATION - FINAL INSPECTION | Activity Status: | Closed | ||||||||
04/07/1999 | Legacy Activity | Buono, Mike | |||||||||
Activity Name: | TANK CLOSURE INSPECTION | Activity Status: | Closed | ||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | SNC-A | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/14/2007 | User: | BRAZILE_DO_1 | ||||||||
Description: | 2000 Gl. Single walled, steel, AST-located inside of a concrete secondary containment (no EQ). Piping- Steel, Aboveground Release Detection - Monthly Visual Inspection Overfill Protection - Concrete Secondary Containment/pop-up sight tube 1000 Gl. Single walled, steel, AST-located inside of a concrete secondary containment (no EQ). Piping- Steel, Aboveground Release Detection - Monthly Visual Inspection Overfill Protection - Concrete Secondary Containment/pop-up sight tube. #3. - 1000 Gl. Convault DW AST - (EQ 201). Dispenser pump located next to the AST. Release Detection - I/S space DW tank/pop-up site tube/Monthly visuals. Overfill Protection -Manual Tank gauging/pop-up site tube. | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | SNC-A | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Since the tank had been closed in place prior to the closure assessment requirements, and because results of groundwater samples from an NPDES permit indicated no contaminants present, a closure assessment was not required. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | The storage tanks had been closed in place in June of 1990. While running a sewer line for a new Walmart store, the contractors (White-Spunner) encountered the old waste oil tank. Gallet & Associates who are the consultant of record contacted the ECHD. | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | SNC-A | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Since the tank had been closed in place prior to the closure assessment requirements, and because results of groundwater samples from an NPDES permit indicated no contaminants present, a closure assessment was not required. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | The storage tanks had been closed in place in June of 1990. While running a sewer line for a new Walmart store, the contractors (White-Spunner) encountered the old waste oil tank. Gallet & Associates who are the consultant of record contacted the ECHD. | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/20/2018 | User: | FRENCH_EC_1 | ||||||||
Description: | Phone(850)856-9095 | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/31/2000 | User: | UNKNOWN | ||||||||
Description: | COMPLIANCE: SNC ENFORCEMENT | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/11/2005 | User: | UNKNOWN | ||||||||
Description: | REGISTRATION: FORMER GREENSBORO HWY. /AWM | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/20/2018 | User: | FRENCH_EC_1 | ||||||||
Description: | Phone(850)856-9095 | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/31/2000 | User: | UNKNOWN | ||||||||
Description: | COMPLIANCE: SNC ENFORCEMENT | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/11/2005 | User: | UNKNOWN | ||||||||
Description: | REGISTRATION: FORMER GREENSBORO HWY. /AWM | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/20/2018 | User: | FRENCH_EC_1 | ||||||||
Description: | Phone(850)856-9095 | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/31/2000 | User: | UNKNOWN | ||||||||
Description: | COMPLIANCE: SNC ENFORCEMENT | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/11/2005 | User: | UNKNOWN | ||||||||
Description: | REGISTRATION: FORMER GREENSBORO HWY. /AWM | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Oz Baruch (504) 232-8111. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Facility under new ownership. Facility now called OZ Holdings #2. New owners Garges Purtee & Oz Baruch. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Mark Purtee (813) 514-3804. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/29/2015 | User: | FOXWORTH_S_1 | ||||||||
Description: | POC is Abu T. Mridha, Property Owner and Operator, almridha@sbcglobal.net Store Manager is Rizwan Bakhshi, rizwan.bakhshi@cellularamerica.com or store Phone is 850-862-4241. The Southeastern Energy Corp POC is Jeff McConnell - jeff@secqv.net | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Oz Baruch (504) 232-8111. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Facility under new ownership. Facility now called OZ Holdings #2. New owners Garges Purtee & Oz Baruch. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Mark Purtee (813) 514-3804. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/29/2015 | User: | FOXWORTH_S_1 | ||||||||
Description: | POC is Abu T. Mridha, Property Owner and Operator, almridha@sbcglobal.net Store Manager is Rizwan Bakhshi, rizwan.bakhshi@cellularamerica.com or store Phone is 850-862-4241. The Southeastern Energy Corp POC is Jeff McConnell - jeff@secqv.net | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Oz Baruch (504) 232-8111. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Facility under new ownership. Facility now called OZ Holdings #2. New owners Garges Purtee & Oz Baruch. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Mark Purtee (813) 514-3804. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/29/2015 | User: | FOXWORTH_S_1 | ||||||||
Description: | POC is Abu T. Mridha, Property Owner and Operator, almridha@sbcglobal.net Store Manager is Rizwan Bakhshi, rizwan.bakhshi@cellularamerica.com or store Phone is 850-862-4241. The Southeastern Energy Corp POC is Jeff McConnell - jeff@secqv.net | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Oz Baruch (504) 232-8111. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Facility under new ownership. Facility now called OZ Holdings #2. New owners Garges Purtee & Oz Baruch. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/19/2006 | User: | THAYER_JD_1 | ||||||||
Description: | Mark Purtee (813) 514-3804. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/29/2015 | User: | FOXWORTH_S_1 | ||||||||
Description: | POC is Abu T. Mridha, Property Owner and Operator, almridha@sbcglobal.net Store Manager is Rizwan Bakhshi, rizwan.bakhshi@cellularamerica.com or store Phone is 850-862-4241. The Southeastern Energy Corp POC is Jeff McConnell - jeff@secqv.net | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/31/2000 | User: | UNKNOWN | ||||||||
Description: | COMPLIANCE: SNC ENFORCEMENT | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | SNC-B | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
09/23/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/05/2021 | User: | MATHERLY_H | ||||||||
Description: | Facility Contacts Jimmy White - Vice President Deep South Crane Rentals, Inc. (850) 982-1679 Erik Jaspers erik@deepsouthcranes.com (850) 876-9509 | ||||||||||
09/23/1998 | Legacy Activity | Buono, Mike | |||||||||
Activity Name: | UST ROUTINE COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||