DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/30/2025        Last Data Refresh: 04/29/2025        Report Generated from DOPPLER
 
Facility ID: 8500457
Facility Name: SHARATH INC.
 
04/21/2025 Document Management Activity Gillman, Mark
Activity Title: Short Form Consent Order Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 04/29/2025
Comment: Finished
Attachments:
Attachment Date: 04/21/2025 User: GILLMAN_M
Description: Executed Short-Form Consent Order
View Attachment
04/08/2025 Document Management Activity Gillman, Mark
Activity Title: Short Form Consent Order Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 04/08/2025
Comment: Finished
Attachments:
Attachment Date: 04/08/2025 User: GILLMAN_M
Description: Issued Short-form Consent Order
View Attachment
03/07/2025 Electronic Communication Activity Gillman, Mark
Activity Closed Date: 03/07/2025 Activity Status: Closed
Date: 03/07/2025
Recipient: Mr. Vinjamara
Sender: Mark Gillman
Subject: These emails include a response by Mr. Vinjamara to the Notice of Violation, and a response from Mark Gillman explaining the options.
Message: See email string in attachments.
Events:
Event Type: Activity has been finished Date: 03/07/2025
Comment: Finished
Attachments:
Attachment Date: 03/07/2025 User: GILLMAN_M
Description: Response to NOV and return response
View Attachment
03/04/2025 Electronic Communication Activity Gillman, Mark
Activity Closed Date: 03/04/2025 Activity Status: Closed
Date: 03/04/2025
Recipient: Vijay Kumar Vinjamara
Sender: Mark Gillman
Subject: Follow-up to Mr. Vinjamara's response to receiving the NOV.
Message: See attachments
Events:
Event Type: Activity has been finished Date: 03/04/2025
Comment: Finished
Attachments:
Attachment Date: 03/04/2025 User: GILLMAN_M
Description: Email correspondence
View Attachment
02/24/2025 Document Management Activity Gillman, Mark
Activity Title: Notice Of Violation Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/24/2025
Comment: Finished
Attachments:
Attachment Date: 02/24/2025 User: GILLMAN_M
Description: Issued Notice of Violation
View Attachment
01/29/2025 Document Management Activity Elliott, Emily
Activity Title: Closure Document Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/29/2025
Comment: Finished
Attachments:
Attachment Date: 01/29/2025 User: ELLIOTT_EV_1
Description: Closure Assessment Report
View Attachment
01/29/2025 Editable Letter Activity Elliott, Emily
Activity Title: Closure Assessment Report (Complete) Activity Status: Closed
Description: In Compliance Letter
Events:
Event Type: Document has been sent Date: 01/30/2025
Comment: Sent
Events:
Event Type: Activity has been finished Date: 01/30/2025
Comment: Finished
Attachments:
Attachment Date: 01/30/2025 User: MCLEOD_SL_1
Description: Closure Assessment Report (Complete)
View Attachment
01/29/2025 TCAR Activity Elliott, Emily
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 01/29/2025
Events:
Event Type: Activity has been finished Date: 01/29/2025
Comment: Finished
10/31/2024 Electronic Communication Activity Gillman, Mark
Activity Closed Date: 10/31/2024 Activity Status: Closed
Date: 10/31/2024
Recipient: Brooke Proffitt/Mark Gillman
Sender: Vijay Kumar Vinjamara
Subject: Email response to compliance assistance email.
Message: See attachment
Events:
Event Type: Activity has been finished Date: 10/31/2024
Comment: Finished
Attachments:
Attachment Date: 10/31/2024 User: GILLMAN_M
Description: Incoming email correspondence
View Attachment
10/31/2024 Electronic Communication Activity Gillman, Mark
Activity Closed Date: 10/31/2024 Activity Status: Closed
Date: 10/31/2024
Recipient: Mark Gillman
Sender: Vijay Kumar Vinjamara
Subject: Correspondence following Mr. Vijamara's response to compliance assistance email.
Message: See attachment
Events:
Event Type: Activity has been finished Date: 10/31/2024
Comment: Finished
Attachments:
Attachment Date: 10/31/2024 User: GILLMAN_M
Description: Incoming email correspondence
View Attachment
10/02/2024 Editable Letter Activity Proffitt, Brooke
Activity Title: Warning Letter Activity Status: Closed
Description: 2021-09-22 Documentation via E-mail.
Events:
Event Type: Activity has been finished Date: 10/02/2024
Comment: Finished
Attachments:
Attachment Date: 10/02/2024 User: PROFFITT_B
Description: Warning Letter
View Attachment
09/24/2024 Electronic Communication Activity Proffitt, Brooke
Activity Closed Date: 09/24/2024 Activity Status: Closed
Date: 09/24/2024
Recipient: Mr. Vinjamara
Sender: Brooke Proffitt
Subject: Update on INF investigation 9-23-24
Message: Mr Vinjamara emailed back to my request for an update on the INF investigation stating that the primary boots will need to be replaced, which requires the reinstallation of the primary piping, and dispensers and transition sumps. They are working on getting a quote.
Events:
Event Type: Activity has been finished Date: 09/24/2024
Comment: Finished
Attachments:
Attachment Date: 09/24/2024 User: PROFFITT_B
Description: Email Update
View Attachment
09/06/2024 Incident Activity Proffitt, Brooke
Activity Status: Open
Attachments:
Attachment Date: 09/06/2024 User: PROFFITT_B
Description: Incident Notification Form
View Attachment
09/06/2024 Electronic Communication Activity Proffitt, Brooke
Activity Closed Date: 09/06/2024 Activity Status: Closed
Date: 09/06/2024
Recipient: Brooke Proffitt
Sender: Jhonny Kirchman
Subject: Response to compliance assistance email
Message: See attached
Events:
Event Type: Activity has been finished Date: 09/06/2024
Comment: Finished
Attachments:
Attachment Date: 09/06/2024 User: PROFFITT_B
Description: Incoming email
View Attachment
09/06/2024 Document Management Activity Proffitt, Brooke
Activity Title: Incident Notification Form Activity Status: Closed
Description: 2021/08/16, E-mail
Events:
Event Type: Activity has been finished Date: 09/06/2024
Comment: Finished
Attachments:
Attachment Date: 09/06/2024 User: PROFFITT_B
Description: INF
View Attachment
09/04/2024 Electronic Communication Activity Proffitt, Brooke
Activity Closed Date: 09/04/2024 Activity Status: Closed
Date: 09/04/2024
Recipient: Mr. Vinjamara
Sender: Brooke Proffitt
Subject: Response to initial contact email
Message: See attachment
Events:
Event Type: Activity has been finished Date: 09/04/2024
Comment: Finished
09/04/2024 Electronic Communication Activity Proffitt, Brooke
Activity Closed Date: 09/10/2024 Activity Status: Closed
Date: 09/04/2024
Recipient: Mr. Vinjamara
Sender: Brooke Proffitt
Subject: First email contact
Message: See attachment
Events:
Event Type: Activity has been finished Date: 09/10/2024
Comment: Finished
Attachments:
Attachment Date: 09/04/2024 User: PROFFITT_B
Description: First email contact
View Attachment
09/04/2024 Electronic Communication Activity Proffitt, Brooke
Activity Closed Date: 09/10/2024 Activity Status: Closed
Date: 09/04/2024
Recipient: Mr. Vinjamara
Sender: Brooke Proffitt
Subject: Response to first email contact
Message: See attachment
Events:
Event Type: Activity has been finished Date: 09/10/2024
Comment: Finished
Attachments:
Attachment Date: 09/04/2024 User: PROFFITT_B
Description: Response to first email contact
View Attachment
08/27/2024 Enforcement Tracking Activity Gillman, Mark
OGC Case Number: 250154 Activity Status: Open
Attachments:
Attachment Date: 03/19/2025 User: GILLMAN_M
Description: Penalty Computation Worksheet (approved)
View Attachment
08/20/2024 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 08/27/2024
Events:
Event Type: Activity/Document was acknowledged on this date Date: 08/20/2024
Comment: Acknowledged and Assigned by EVAN M. CATO
Events:
Event Type: Activity has been submitted for approval Date: 08/20/2024
Comment: Submitted for approval by: Muhammad Rafique Khan: SIX VIOATIONS ARE STILL OPEN,NO RESPONSE IS RECEIVED AS OF 8-20-2024
Events:
Event Type: Activity has been assigned Date: 08/20/2024
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity has been finished Date: 08/27/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 08/27/2024
Comment: Accepted by Mark Gillman: Accepted
Comments:
Comment Date: 08/20/2024 User: KHAN_MR_1
Description: SIX VIOATIONS ARE STILL OPEN,NO RESPONSE IS RECEIVED AS OF 8-20-2024
Comments:
Comment Date: 08/20/2024 User: KHAN_MR_1
Description: SIX VIOATIONS ARE STILL OPEN,NO RESPONSE IS RECEIVED AS OF 8-20-2024
08/20/2024 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 08/27/2024
Events:
Event Type: Activity/Document was acknowledged on this date Date: 08/20/2024
Comment: Acknowledged and Assigned by EVAN M. CATO
Events:
Event Type: Activity has been submitted for approval Date: 08/20/2024
Comment: Submitted for approval by: Muhammad Rafique Khan: SIX VIOATIONS ARE STILL OPEN,NO RESPONSE IS RECEIVED AS OF 8-20-2024
Events:
Event Type: Activity has been assigned Date: 08/20/2024
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity has been finished Date: 08/27/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 08/27/2024
Comment: Accepted by Mark Gillman: Accepted
Comments:
Comment Date: 08/20/2024 User: KHAN_MR_1
Description: SIX VIOATIONS ARE STILL OPEN,NO RESPONSE IS RECEIVED AS OF 8-20-2024
Comments:
Comment Date: 08/20/2024 User: KHAN_MR_1
Description: SIX VIOATIONS ARE STILL OPEN,NO RESPONSE IS RECEIVED AS OF 8-20-2024
05/16/2024 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 05/16/2024
Comment: Finished
Events:
Event Type: Document has been sent Date: 05/16/2024
Comment: Sent
Attachments:
Attachment Date: 05/16/2024 User: KHAN_MR_1
Description: Compliance Assistance Offer Letter
View Attachment
05/03/2024 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6056
Rule: 62-761.600(1)(d), 62-761.600(1)(e), 62-761.600(1)(g)
05/03/2024 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6056
Rule: 62-761.600(1)(d), 62-761.600(1)(e), 62-761.600(1)(g)
05/03/2024 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6063
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2
05/03/2024 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
05/03/2024 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6015
Rule: 62-761.430(4), 62-761.430(5)
05/03/2024 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6009
Rule: 62-761.405(3)
05/03/2024 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6024
Rule: 62-761.500(1)(b)4, 62-761.500(1)(b)5, 62-761.500(1)(b)6, 62-761.500(1)(b)7
03/17/2024 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: VIJAY Activity Closed Date: 05/03/2024
Events:
Event Type: Activity has been finished Date: 05/03/2024
Comment: Finished
03/14/2024 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: Sharath.speedway@gmail.com Activity Closed Date: 05/16/2024
Events:
Event Type: Activity has been finished Date: 05/16/2024
Comment: Finished
Comments:
Comment Date: 05/16/2024 User: KHAN_MR_1
Description: After review, Disp 3/4 faileed testing 03/06/2024 performed by A Phelps. Issuing violation for: 1. Submit INF for failed Disp 3/4 Testing. 2. Incident Investigation (closure report). 3. Repair Disp 3/4 to be liquid tight. 4. Re-issuing Monthlys to provide May & June with Veeder-Root print outs for each month and keep on file. 5. Provide Annual Spill Bucket Gauge Operability testing.
02/19/2024 Phone Conversation Activity Khan, Muhammad Rafique
Call Type: Outgoing Activity Status: Closed
Phone Number: (646) 422-9487 Activity Closed Date: 02/19/2024
Subject: 6464229487 called vasue for tci on 4-6-2024
Events:
Event Type: Activity has been finished Date: 02/19/2024
Comment: Finished
02/19/2024 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/19/2024
Comment: Finished
Events:
Event Type: Document has been sent Date: 02/19/2024
Comment: Sent
Attachments:
Attachment Date: 02/19/2024 User: KHAN_MR_1
Description: Compliance Assistance Offer Letter
View Attachment
02/06/2024 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6056
Rule: 62-761.600(1)(d), 62-761.600(1)(e), 62-761.600(1)(g)
02/06/2024 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/06/2024
Activity Closed Date: 02/19/2024 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 02/19/2024
Comment: Finished
Comments:
Comment Date: 02/15/2024 User: KHAN_MR_1
Description: TANK: Tank #7 - 12000 Gl. Two Compartment, Double Wall NewBerry PermaTank (EQ 733) installed January 2010. PIPING: Franklin Fueling Systems Model XP (EQ 618) - 70 Ft. - Installed from the new tank to the south east Existing Environ Dispenser Liner (EQ 439). The existing Environ Double Wall Piping (EQ 511) between the existing dispenser pumps was used with the installation upgade. VENT PIPING:Smith Fiberglass Red Thread IIA (EQ 252). SPILL CONTAINMENT: EMCO Wheaton Double Wall (EQ 594) OVERFILL PROTECTION: OPW 61SO Overfill Protection Valve/Embarco EMC 130 with Overfill Alarm. STP SUMPS: Advanced Polymer Technology, APT Tank Sump - (EQ 423) DISPENSER SUMPS: Environ Products, Inc., Dispenser Sump Liner (EQ-439) RELEASE DETECTION: Tank IM sensor is monitored by a Embarco EMC ATG (EQ-130). Red Jacket Pumps, Mechanical Leak Detectors (EQ 373). Monthly visual inspections of all tank related equipment is completed. Sensor status tape and alarm history is printed monthly.
02/06/2024 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6024
Rule: 62-761.500(1)(b)4, 62-761.500(1)(b)5, 62-761.500(1)(b)6, 62-761.500(1)(b)7
02/06/2024 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
02/06/2024 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6013
Rule: 62-761.420(3), 62-761.420(4), 62-761.420(8)
02/06/2024 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
02/06/2024 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
10/18/2022 Editable Letter Activity Tomas, Morgan E
Activity Title: Return to Compliance Letter Activity Status: Open
08/03/2022 Editable Letter Activity Tomas, Morgan E
Activity Title: Warning Letter Activity Status: Closed
Description: 2020/12/08, E-mail with closure
Events:
Event Type: Activity has been finished Date: 08/03/2022
Comment: Finished
Attachments:
Attachment Date: 08/03/2022 User: TOMAS_M
Description: Issued Warning Letter
View Attachment
07/22/2022 Enforcement Tracking Activity Gillman, Mark
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 10/18/2022
Events:
Event Type: Activity has been finished Date: 10/18/2022
Comment: Finished
07/19/2022 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: vijay Activity Closed Date: 07/19/2022
Events:
Event Type: Activity has been finished Date: 07/19/2022
Comment: Finished
Comments:
Comment Date: 07/19/2022 User: KHAN_MR_1
Description: called vijay about violatons,he said katunti will call me,enforcement date was 7/12,inspector was on vacation,inspector is waiting for call,if hear nothing,it would to sent to enforcement. called also a phelps,he provided overfill test done on3-8-2022 only and picture of spill bucket.howard said some testing was done,but some one is sick(i guess someone else might have more testing) it is being submitted to enforcement now
07/19/2022 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 07/22/2022
Events:
Event Type: Activity/Document was acknowledged on this date Date: 07/22/2022
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity/Document was accepted on this date Date: 07/22/2022
Comment: Accepted by Mark Gillman: Accepted
Events:
Event Type: Activity has been assigned Date: 07/22/2022
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity has been finished Date: 07/22/2022
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 07/19/2022
Comment: Submitted for approval by: Muhammad Rafique Khan: called vijay about violatons,he said katunti will call me,enforcement date was 7/12,inspector was on vacation,inspector is waiting for call,if hear nothing,it would to sent to enforcement. called also a phelps,he provided overfill test done on3-8-2022 only and picture of spill bucket.howard said some testing was done,but some one is sick(i guess someone else might have more testing) it is being submitted to enforcement now
Comments:
Comment Date: 07/19/2022 User: KHAN_MR_1
Description: called vijay about violatons,he said katunti will call me,enforcement date was 7/12,inspector was on vacation,inspector is waiting for call,if hear nothing,it would to sent to enforcement. called also a phelps,he provided overfill test done on3-8-2022 only and picture of spill bucket.howard said some testing was done,but some one is sick(i guess someone else might have more testing) it is being submitted to enforcement now
Comments:
Comment Date: 07/19/2022 User: KHAN_MR_1
Description: called vijay about violatons,he said katunti will call me,enforcement date was 7/12,inspector was on vacation,inspector is waiting for call,if hear nothing,it would to sent to enforcement. called also a phelps,he provided overfill test done on3-8-2022 only and picture of spill bucket.howard said some testing was done,but some one is sick(i guess someone else might have more testing) it is being submitted to enforcement now
07/19/2022 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 07/22/2022
Events:
Event Type: Activity/Document was acknowledged on this date Date: 07/22/2022
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity/Document was accepted on this date Date: 07/22/2022
Comment: Accepted by Mark Gillman: Accepted
Events:
Event Type: Activity has been assigned Date: 07/22/2022
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity has been finished Date: 07/22/2022
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 07/19/2022
Comment: Submitted for approval by: Muhammad Rafique Khan: called vijay about violatons,he said katunti will call me,enforcement date was 7/12,inspector was on vacation,inspector is waiting for call,if hear nothing,it would to sent to enforcement. called also a phelps,he provided overfill test done on3-8-2022 only and picture of spill bucket.howard said some testing was done,but some one is sick(i guess someone else might have more testing) it is being submitted to enforcement now
Comments:
Comment Date: 07/19/2022 User: KHAN_MR_1
Description: called vijay about violatons,he said katunti will call me,enforcement date was 7/12,inspector was on vacation,inspector is waiting for call,if hear nothing,it would to sent to enforcement. called also a phelps,he provided overfill test done on3-8-2022 only and picture of spill bucket.howard said some testing was done,but some one is sick(i guess someone else might have more testing) it is being submitted to enforcement now
Comments:
Comment Date: 07/19/2022 User: KHAN_MR_1
Description: called vijay about violatons,he said katunti will call me,enforcement date was 7/12,inspector was on vacation,inspector is waiting for call,if hear nothing,it would to sent to enforcement. called also a phelps,he provided overfill test done on3-8-2022 only and picture of spill bucket.howard said some testing was done,but some one is sick(i guess someone else might have more testing) it is being submitted to enforcement now
04/22/2022 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: sharath.speedway@gmail.com; vasu.itc007@gmail.com Activity Closed Date: 04/22/2022
Events:
Event Type: Activity has been finished Date: 04/22/2022
Comment: Finished
Comments:
Comment Date: 04/22/2022 User: WILSON_ML_1
Description: Greetings, I have attached the above referenced facility’s Compliance Assistance Offer Letter and Inspection Report. Please be sure to submit the information needed to resolve the violations to this office by 07/12/2022 to avoid possible penalties. Please feel free to contact this office should you have any questions or concerns. Kind Regards, Monica L. Wilson Planning Consultant I Florida Department of Health in Escambia County Environment Health Division 1300 W Gregory Street, Pensacola, Florida 32502 Phone: 850-595-6700 ext 2004 Cell: 850-554-4315 Fax: 850-595-6774 www.EscambiaHealth.com Follow us on Twitter: @HealthyEscambia The Department’s mission is to protect, and improve the health of all people in Florida through integrated state, county, and community efforts NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
04/19/2022 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
04/19/2022 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 04/22/2022
Comment: Sent
Events:
Event Type: Activity has been finished Date: 04/22/2022
Comment: Finished
Attachments:
Attachment Date: 04/22/2022 User: WILSON_ML_1
Description: Compliance Assistance Offer Letter
View Attachment
04/19/2022 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
04/19/2022 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6056
Rule: 62-761.600(1)(d), 62-761.600(1)(e), 62-761.600(1)(g)
04/19/2022 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
04/19/2022 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6002
Rule: 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2, 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7)
04/19/2022 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6011
Rule: 62-761.420(2)
04/19/2022 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
04/19/2022 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6063
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2
04/13/2022 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 04/13/2022
Activity Closed Date: 04/19/2022 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 04/19/2022
Comment: Finished
Comments:
Comment Date: 04/13/2022 User: KHAN_MR_1
Description: TANKS: ONE NEW TANK WAS INSTALLED ON 2010/01/20, Tank #7 - 12000 Gl. Two Compartment, Double Wall New Berry Perma Tank (EQ 733). PIPING: Franklin Fueling Systems Model XP (EQ 618) - 70 Ft. - Installed from the new tank to the south east, Existing Environ Dispenser Liner (EQ 439). The existing Environ Double Wall Piping (EQ 511) between the existing dispenser pumps was used with the installation upgade , The Vent piping is Smith Fiberglass Red Thread IIA (EQ 252).. STP SUMPS: APT - (EQ 423). SPILL CONTAINMENTEMCO Wheaton Double Wall (EQ 594). OVERFILL PROTECTIONOPW 61SO Overfill Protection Valve The existing Double Wall, Environ Piping (EQ 511) between the three dispenser pumps was utilized with the Existing Environ Dispenser Liners (EQ 439) for the New Tank Upgrade Activity. DISPENSERS: Used Three Existing Environ Liners (EQ 439). RELEASE DETECTION: Veeder root TLS Interstitial Space Double Wall Tank
04/13/2022 Phone Conversation Activity Khan, Muhammad Rafique
Call Type: Outgoing Activity Status: Closed
Phone Number: (646) 422-9487 Activity Closed Date: 04/19/2022
Subject: called SRINAVAS for tci on 4/13/2022
Events:
Event Type: Activity has been finished Date: 04/19/2022
Comment: Finished
06/19/2020 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: sharath.speedway@gmail.com; Petro Flow Inc. Activity Closed Date: 06/19/2020
Events:
Event Type: Activity has been finished Date: 06/19/2020
Comment: Finished
Comments:
Comment Date: 06/19/2020 User: WILSON_ML_1
Description: Greetings, I have attached the above referenced facility’s In Compliance Letter and Inspection Report. I have also attached the Limited Closure Report Form mentioned in the inspection Report. Please feel free to contact this office should you have any questions or concerns. Kind Regards, Monica L. Wilson Planning Consultant I Florida Department of Health in Escambia County Environment Health Division 1300 W Gregory Street, Pensacola, Florida 32502 Phone: 850-595-6700 ext 2004 Cell: 850-554-4315 Fax: 850-595-6774 www.EscambiaHealth.com Follow us on Twitter: @HealthyEscambia The Department’s mission is to protect, and improve the health of all people in Florida through integrated state, county, and community efforts NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
06/19/2020 Editable Letter Activity Wilson, Monica L
Activity Title: In Compliance Letter Activity Status: Closed
Description: 2020-02-24 Mobil-Wauchula #419 CAO Letter.
Events:
Event Type: Document has been sent Date: 06/19/2020
Comment: Sent
Events:
Event Type: Activity has been finished Date: 06/19/2020
Comment: Finished
Attachments:
Attachment Date: 06/19/2020 User: WILSON_ML_1
Description: In Compliance Letter
View Attachment
05/08/2020 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/30/2020
Activity Closed Date: 06/19/2020 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 06/19/2020
Comment: Finished
Comments:
Comment Date: 05/08/2020 User: KHAN_MR_1
Description: Description of work: To remove and replace premium spill bucket. New Equipment: EMCO Wheaton DW Spill Bucket Model A1004 - EQ 524 Location: T&N EXPRESS, 3000 W HWY 98, PANAMA CITY, FL 32401 PSSC Contractor: Petro Flow INC (License # 1256798) petroflowinc@gmail.com Owner: NELLY MCDONOUGH Email: SHARATH.SPEEDWAY@GMAIL.COM Phone: (850) 769-5727 The Premium spill bucket failed initial integrity testing. At that time, Petro Flow noted a breech in the primary spill bucket due to corroded components. A hydrostatic test was performed on the Premium's secondary bucket on 04/14/2020 and the secondary passed hydrostatic testing. This information was submitted with the Closure Integrity Evaluation Form. Met onsite with Tim Jordan from Petro Flow Inc for this component install inspection. Petro Flow Inc. Replaced the damaged premium bucket with a new EMCO Wheaton Double Wall spill bucket (EQ - 524). After the new spill bucket was installed it was hydrostatic tested and verified as passing by our department. The Premium Spill Bucket was later vacuum tested by Petro Flow. Note: During inspector's visit spill bucket was not painted at that time. A Limited Closure Report Form for USTs is due to this office within 60 days.
Comments:
Comment Date: 05/08/2020 User: KHAN_MR_1
Description: Spoke with Petro Flow's main office and asked that they provide the post installation vacuum and hydrostatic testing for the premium spill bucket. Spoke with the facility operator, Vijay, and asked for the current insurance financial mechanism forms for review.
05/08/2020 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 05/08/2020
Activity Closed Date: 05/08/2020 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 05/08/2020
Comment: Finished
Comments:
Comment Date: 05/08/2020 User: KHAN_MR_1
Description: Closure Description of work: To remove premium spill bucket due to primary spill bucket breached .Spill bucket components were corroded and primary spill bucket is not replaceable without removing concrete. Component Install Inspection approved by Curran, Kimberley Kimberley.Curran@FloridaDEP.gov with DEP NW District office. Location: 8500457 District: NWD Facility Name: T&N EXPRESS County: BAY Address: 3000 W HWY 98 PANAMA CITY, FL 32401 PSSC Contractor: Petro Flow INC (License # 1256798) petroflowinc@gmail.com Consultant: none Owner: NELLY MCDONOUGH Address: 3000 W HWY 98 PANAMA CITY, FL 32401 Email: SHARATH.SPEEDWAY@GMAIL.COM Phone: (850) 769-5727 . Old premium Spill bucket was hydrostatic tested by Tim Jordon. Integrity test was provided by Petro Flow to our office. Old premium Spill bucket was removed,
05/08/2020 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/30/2020
Activity Closed Date: 06/19/2020 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 06/19/2020
Comment: Finished
Comments:
Comment Date: 05/08/2020 User: KHAN_MR_1
Description: Description of work: To remove and replace premium spill bucket. New Equipment: EMCO Wheaton DW Spill Bucket Model A1004 - EQ 524 Location: T&N EXPRESS, 3000 W HWY 98, PANAMA CITY, FL 32401 PSSC Contractor: Petro Flow INC (License # 1256798) petroflowinc@gmail.com Owner: NELLY MCDONOUGH Email: SHARATH.SPEEDWAY@GMAIL.COM Phone: (850) 769-5727 The Premium spill bucket failed initial integrity testing. At that time, Petro Flow noted a breech in the primary spill bucket due to corroded components. A hydrostatic test was performed on the Premium's secondary bucket on 04/14/2020 and the secondary passed hydrostatic testing. This information was submitted with the Closure Integrity Evaluation Form. Met onsite with Tim Jordan from Petro Flow Inc for this component install inspection. Petro Flow Inc. Replaced the damaged premium bucket with a new EMCO Wheaton Double Wall spill bucket (EQ - 524). After the new spill bucket was installed it was hydrostatic tested and verified as passing by our department. The Premium Spill Bucket was later vacuum tested by Petro Flow. Note: During inspector's visit spill bucket was not painted at that time. A Limited Closure Report Form for USTs is due to this office within 60 days.
Comments:
Comment Date: 05/08/2020 User: KHAN_MR_1
Description: Spoke with Petro Flow's main office and asked that they provide the post installation vacuum and hydrostatic testing for the premium spill bucket. Spoke with the facility operator, Vijay, and asked for the current insurance financial mechanism forms for review.
04/30/2020 Editable Letter Activity Decker, Kylie
Activity Title: Warning Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 05/04/2020
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 05/01/2020
Comment: Approved by Mark Gillman: approved
Events:
Event Type: Activity has been submitted for approval Date: 04/30/2020
Comment: Submitted for approval by: Kylie Decker
Attachments:
Attachment Date: 04/30/2020 User: DECKER_K
Description: Warning Letter
View Attachment
02/24/2020 Electronic Communication Activity Decker, Kylie
Activity Closed Date: 02/24/2020 Activity Status: Closed
Date: 02/24/2020
Recipient: Vijay Vinjamara
Sender: Kylie Decker
Subject: Notice of First Contact
Message: See attachment
Events:
Event Type: Activity has been finished Date: 02/24/2020
Comment: Finished
Attachments:
Attachment Date: 02/24/2020 User: DECKER_K
Description: First Contact Email
View Attachment
09/16/2019 Enforcement Tracking Activity Gillman, Mark
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 07/07/2020
Events:
Event Type: Activity has been finished Date: 07/07/2020
Comment: Finished
07/01/2019 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 09/16/2019
Events:
Event Type: Activity has been submitted for approval Date: 07/01/2019
Comment: Submitted for approval by: Muhammad Rafique Khan: petroflow sent email on 6/26/2019 and 6/27/2019 received atg test results and illd test results on 6/26 and 6/27/2019.so two violations would be cleared. email was sent on 6/24/2019,got no response till 7/1/2019 Good morning Do you any update for open violations for the facility which were addressed on 3/26/2019 inspection report. Enforcement date is 7/1/2019 if violations are still not resolved.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 09/16/2019
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been assigned Date: 09/16/2019
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity has been finished Date: 09/16/2019
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 09/16/2019
Comment: Accepted by Mark Gillman: Accepted
Comments:
Comment Date: 07/29/2019 User: KHAN_MR_1
Description: have not received any more test results as of yet.
Comments:
Comment Date: 07/01/2019 User: KHAN_MR_1
Description: petroflow sent email on 6/26/2019 and 6/27/2019 received atg test results and illd test results on 6/26 and 6/27/2019.so two violations would be cleared. email was sent on 6/24/2019,got no response till 7/1/2019 Good morning Do you any update for open violations for the facility which were addressed on 3/26/2019 inspection report. Enforcement date is 7/1/2019 if violations are still not resolved.
Comments:
Comment Date: 07/01/2019 User: KHAN_MR_1
Description: petroflow sent email on 6/26/2019 and 6/27/2019 received atg test results and illd test results on 6/26 and 6/27/2019.so two violations would be cleared. email was sent on 6/24/2019,got no response till 7/1/2019 Good morning Do you any update for open violations for the facility which were addressed on 3/26/2019 inspection report. Enforcement date is 7/1/2019 if violations are still not resolved.
07/01/2019 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 09/16/2019
Events:
Event Type: Activity has been submitted for approval Date: 07/01/2019
Comment: Submitted for approval by: Muhammad Rafique Khan: petroflow sent email on 6/26/2019 and 6/27/2019 received atg test results and illd test results on 6/26 and 6/27/2019.so two violations would be cleared. email was sent on 6/24/2019,got no response till 7/1/2019 Good morning Do you any update for open violations for the facility which were addressed on 3/26/2019 inspection report. Enforcement date is 7/1/2019 if violations are still not resolved.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 09/16/2019
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been assigned Date: 09/16/2019
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity has been finished Date: 09/16/2019
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 09/16/2019
Comment: Accepted by Mark Gillman: Accepted
Comments:
Comment Date: 07/29/2019 User: KHAN_MR_1
Description: have not received any more test results as of yet.
Comments:
Comment Date: 07/01/2019 User: KHAN_MR_1
Description: petroflow sent email on 6/26/2019 and 6/27/2019 received atg test results and illd test results on 6/26 and 6/27/2019.so two violations would be cleared. email was sent on 6/24/2019,got no response till 7/1/2019 Good morning Do you any update for open violations for the facility which were addressed on 3/26/2019 inspection report. Enforcement date is 7/1/2019 if violations are still not resolved.
Comments:
Comment Date: 07/01/2019 User: KHAN_MR_1
Description: petroflow sent email on 6/26/2019 and 6/27/2019 received atg test results and illd test results on 6/26 and 6/27/2019.so two violations would be cleared. email was sent on 6/24/2019,got no response till 7/1/2019 Good morning Do you any update for open violations for the facility which were addressed on 3/26/2019 inspection report. Enforcement date is 7/1/2019 if violations are still not resolved.
07/01/2019 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 09/16/2019
Events:
Event Type: Activity has been submitted for approval Date: 07/01/2019
Comment: Submitted for approval by: Muhammad Rafique Khan: petroflow sent email on 6/26/2019 and 6/27/2019 received atg test results and illd test results on 6/26 and 6/27/2019.so two violations would be cleared. email was sent on 6/24/2019,got no response till 7/1/2019 Good morning Do you any update for open violations for the facility which were addressed on 3/26/2019 inspection report. Enforcement date is 7/1/2019 if violations are still not resolved.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 09/16/2019
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been assigned Date: 09/16/2019
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity has been finished Date: 09/16/2019
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 09/16/2019
Comment: Accepted by Mark Gillman: Accepted
Comments:
Comment Date: 07/29/2019 User: KHAN_MR_1
Description: have not received any more test results as of yet.
Comments:
Comment Date: 07/01/2019 User: KHAN_MR_1
Description: petroflow sent email on 6/26/2019 and 6/27/2019 received atg test results and illd test results on 6/26 and 6/27/2019.so two violations would be cleared. email was sent on 6/24/2019,got no response till 7/1/2019 Good morning Do you any update for open violations for the facility which were addressed on 3/26/2019 inspection report. Enforcement date is 7/1/2019 if violations are still not resolved.
Comments:
Comment Date: 07/01/2019 User: KHAN_MR_1
Description: petroflow sent email on 6/26/2019 and 6/27/2019 received atg test results and illd test results on 6/26 and 6/27/2019.so two violations would be cleared. email was sent on 6/24/2019,got no response till 7/1/2019 Good morning Do you any update for open violations for the facility which were addressed on 3/26/2019 inspection report. Enforcement date is 7/1/2019 if violations are still not resolved.
06/26/2019 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: petroflow Activity Closed Date: 07/08/2019
Events:
Event Type: Activity has been finished Date: 07/08/2019
Comment: Finished
Comments:
Comment Date: 07/08/2019 User: KHAN_MR_1
Description: received atg test results and illd test results on 6/26 and 6/27/2019.so two violations would be cleared.
04/02/2019 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 04/02/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 04/02/2019
Comment: Finished
Attachments:
Attachment Date: 04/02/2019 User: WILSON_ML_1
Description: Compliance Assistance Offer Letter
View Attachment
04/02/2019 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: sharath.speedway@gmail.com Activity Closed Date: 04/02/2019
Events:
Event Type: Activity has been finished Date: 04/02/2019
Comment: Finished
03/26/2019 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 4067
Rule: 62-761.600(4)
03/26/2019 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 4077
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1., 62-761.700(3)(b)2.
03/26/2019 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 4057
Rule: 62-761.500(7)(e)
03/26/2019 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 4066
Rule: 62-761.600(3), 62-761.600(3)(a), 62-761.600(3)(b), 62-761.600(3)(b)1., 62-761.600(3)(b)2., 62-761.600(3)(b)3.
03/26/2019 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
03/25/2019 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 03/26/2019
Activity Closed Date: 04/02/2019 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 04/02/2019
Comment: Finished
Comments:
Comment Date: 03/26/2019 User: KHAN_MR_1
Description: jTANKS: ONE NEW TANK WAS INSTALLED ON 2010/01/20, Tank #7 - 12000 Gl. Two Compartment, Double Wall New Berry Perma Tank (EQ 733). PIPING : Franklin Fueling Systems Model XP (EQ 618) - 70 Ft. - Installed from the new tank to the south east , Existing Environ Dispenser Liner (EQ 439). The existing Environ Double Wall Piping (EQ 511) between the existing dispenser pumps was used with the installation upgade , The Vent piping is Smith Fiberglass Red Thread IIA (EQ 252).. STP SUMPS: APT - (EQ 423). SPILL CONTAINMENTEMCO Wheaton Double Wall (EQ 594). OVERFILL PROTECTIONOPW 61SO Overfill Protection Valve/Embarco EMC 130 with Overfill Alarm. . The existing Double Wall, Environ Piping (EQ 511) between the three dispenser pumps was utilized with the Existing Environ Dispenser Liners (EQ 439) for the New Tank Upgrade Activity. DISPENSERS: Used Three Existing Environ Liners (EQ 439). RELEASE DETECTION: Embarco EMC (130)/Interstitial Space Double Wall Tank
03/25/2019 Phone Conversation Activity Khan, Muhammad Rafique
Call Type: Outgoing Activity Status: Closed
Phone Number: (850) 769-5727 Activity Closed Date: 04/01/2019
Subject: called for Vijay for tci on 3/26/2019 spoke to one manager.also m.srinivasa reddy 646 422 9487
Events:
Event Type: Activity has been finished Date: 04/01/2019
Comment: Finished
10/22/2018 Site Inspection Activity Closed Brock, Samantha Nicole
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/17/2018
Activity Closed Date: 10/22/2018 Activity Closed By: BROCK_SN_1
Events:
Event Type: Activity has been finished Date: 10/22/2018
Comment: Finished
Comments:
Comment Date: 10/22/2018 User: BROCK_SN_1
Description: Complaint Inspection conducted per direction of FDEP Tank Division SERT Mission (FL-027613) as a follow-up to Hurricane Michael. See attachments section for the field Hurricane Michael Facility Impact Questionnaire.
02/03/2017 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: Shelly Taunton A. Phelps Petroleum of NW FL, Inc Activity Closed Date: 02/03/2017
Events:
Event Type: Activity has been finished Date: 02/03/2017
Comment: Finished
12/23/2016 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
12/23/2016 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/05/2017
Comment: Finished
Attachments:
Attachment Date: 01/05/2017 User: WILSON_ML_1
Description: First Non-Compliance Letter
View Attachment
12/23/2016 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1103
Rule: 62-761.640(4)(a)1., 62-761.640(4)(a)2., 62-761.640(4)(a)3., 62-761.640(4)(a)4.
Comments: Installation - verify that the line leak detector has been installed during the final installation inspection. Compliance - check to see that the unit is present. Examine the annual function test data - a pass alone is not sufficient. The tester must demonstrate 3.0 gph discharge detection for the mechanical (flow restrictor). Note that the electronic (auto shut off) line leak detector does not need an annual test, but must still be able to detect a 0.2 gph leak after it has been tripped at 150% line operating pressure. Replacements - unit must be tested out of the box - function must be proven. 3.0 gph = 185.4 ml/min (To convert milliliters/minute to gallons/hour, multiple the milliliters by 0.0162162; or, 1 gph equals 61.8 ml/min). Values greater than 186 ml/min fail. Values less than 185 ml/min mean that the line leak detector will activate at a more restrictive rate.
12/23/2016 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
12/22/2016 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 12/22/2016
Activity Closed Date: 12/23/2016 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 12/23/2016
Comment: Finished
Comments:
Comment Date: 12/23/2016 User: KHAN_MR_1
Description: TANKS: ONE NEW TANK WAS INSTALLED ON 2010/01/20, Tank #7 - 12000 Gl. Two Compartment, Double Wall New Berry Perma Tank (EQ 733). PIPING : Franklin Fueling Systems Model XP (EQ 618) - 70 Ft. - Installed from the new tank to the south east , Existing Environ Dispenser Liner (EQ 439). The existing Environ Double Wall Piping (EQ 511) between the existing dispenser pumps was used with the installation upgade , The Vent piping is Smith Fiberglass Red Thread IIA (EQ 252).. STP SUMPS: APT - (EQ 423). SPILL CONTAINMENTEMCO Wheaton Double Wall (EQ 594). OVERFILL PROTECTIONOPW 61SO Overfill Protection Valve/Embarco EMC 130 with Overfill Alarm. . The existing Double Wall, Environ Piping (EQ 511) between the three dispenser pumps was utilized with the Existing Environ Dispenser Liners (EQ 439) for the New Tank Upgrade Activity. DISPENSERS: Used Three Existing Environ Liners (EQ 439). RELEASE DETECTION: Embarco EMC (130)/Interstitial Space Double Wall Tank/Double Wall Piping/Mechanical Leak Detectors (EQ 373)/Monthly Visual Inspection Of Sumps and Dispenser Liners Documentation
05/29/2015 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/29/2015
Activity Closed Date: 06/05/2015 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 06/05/2015
Comment: Finished
Comments:
Comment Date: 06/05/2015 User: KHAN_MR_1
Description: Re-Inspection:5/29/2015 Met on-site vijay k vinjamara 5408310930,operator for 8500457 - T&N EXPRESS Inspection report was sent by email Current FR, placard and RDRL are posted. This was a Re-Inspection of the issues found during the Tank Compliance Inspection conducted on 04/02/2015 ISSUE: Spill containment, dispenser liners and piping sumps accessible; water and regulated substances not removed. Corrective Action: Upon inspection Regular product (with ethanol) tank sump (STP) had excess liquid. Please get the excess liquid out of Regular product (with ethanol) tank sump (STP) and call 850 258 8546 for a re-inspection Upon inspection Regular product (with NO ethanol) tank sump (STP) had excess liquid.Please get the excess liquid out of Regular product (with no ethanol) tank sump (STP) and call 850 258 8546 for a re-inspection RESOLUTION: water was removed from all above components.
05/14/2015 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: Jennifer Hernandez Compliance sent the test,test was done on 4/14/2015 Activity Closed Date: 05/14/2015
Events:
Event Type: Activity has been finished Date: 05/14/2015
Comment: Finished
Comments:
Comment Date: 05/14/2015 User: KHAN_MR_1
Description: Jennifer Hernandez Compliance sent the test,test was done on 4/14/2015
05/14/2015 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: phelps petroleum Activity Closed Date: 05/14/2015
Events:
Event Type: Activity has been finished Date: 05/14/2015
Comment: Finished
Comments:
Comment Date: 05/14/2015 User: KHAN_MR_1
Description: Jennifer Hernandez Compliance Coordinator Clemens Fuel Systems 850/265-8881 sent this message. ttached are the BOI testing results fojavascript:;r the above location. test was done on 4-17-2015
05/13/2015 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: RECEIVED ATG TEST FROM CLEMENS.DONE ON 4/14/2015 BY PHELPS Activity Closed Date: 05/13/2015
Events:
Event Type: Activity has been finished Date: 05/13/2015
Comment: Finished
Comments:
Comment Date: 05/13/2015 User: KHAN_MR_1
Description: RECEIVED ATG TEST FROM CLEMENS.DONE ON 4/14/2015 BY PHELPS
04/07/2015 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 04/08/2015
Comment: Sent on Wed Apr 08 00:00:00 EDT 2015
Events:
Event Type: Activity has been finished Date: 04/08/2015
Comment: Finished
Attachments:
Attachment Date: 04/08/2015 User: WILSON_ML_1
Description: 1st Non-Compliance Letter
View Attachment
04/07/2015 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 04/07/2015
Events:
Event Type: Activity has been finished Date: 04/07/2015
Comment: Finished
04/02/2015 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1020
Rule: 62-761.500(1)(d)5.
Comments: The breach of integrity test is intended for closed interstices only. A closed interstice has no unsecured or unsealed opening to the outside. Double-walled piping without a boot connector, or if the boot has a bleed valve (for tightness testing), is considered an open interstice. The breach of integrity test may be performed by using at least one of the following methods: a. A continuous hydrostatic system b. A continuous vacuum system c. Testing of the interstice for liquid tightness in accordance with manufacturer's installation instructions; or d. Another method in accordance with subsection 62-761.850(2). How the breach of integrity test is performed or to what degree can depend on the depth to groundwater at each facility. When the tank and or piping are fully submerged, the lack of water intrusion into the secondary containment may be considered a verification of its integrity. However, when total submersion is not the case, one of the rule stipulated options must be used. The breach of integrity test should not be confused with a precision tightness test, which tests the primary tank or piping only. The breach of integrity test will test the secondary and primary shells, but is not a precision test.
04/02/2015 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/02/2015
Activity Closed Date: 04/07/2015 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 04/07/2015
Comment: Finished
Comments:
Comment Date: 04/07/2015 User: KHAN_MR_1
Description: 8500457 - T&N EXPRESS TCI 4/2/2015 Met on site with vijay vinnamara 540 831 0930,operatot, 8500457 - T&N EXPRESS Inspection report was emailed.. Current FR, placard and RDRL are posted. TANKS: ONE NEW TANK WAS INSTALLED ON 2010/01/20, Tank #7 - 12000 Gl. Two Compartment, Double Wall NewBerry PermaTank (EQ 733). PIPING : Franklin Fueling Systems Model XP (EQ 618) - 70 Ft. - Installed from the new tank to the south east , Existing Environ Dispenser Liner (EQ 439). The existing Environ Double Wall Piping (EQ 511) between the existing dispenser pumps was used with the installation upgade , The Vent piping is Smith Fiberglass Red Thread IIA (EQ 252).. STP SUMPS: APT - (EQ 423). SPILL CONTAINMENTEMCO Wheaton Double Wall (EQ 594). OVERFILL PROTECTIONOPW 61SO Overfill Protection Valve/Embarco EMC 130 with Overfill Alarm. . The existing Double Wall, Environ Piping (EQ 511) between the three dispenser pumps was utilized with the Existing Environ Dispenser Liners (EQ 439) for the New Tank Upgrade Activity. DISPENSERS:Used Three Existing Environ Liners (EQ 439). RELEASE DETECTIONEmbarco EMC (130)/Interstitial Space Double Wall Tank/Double Wall Piping/Mechanical Leak Detectors (EQ 373)/Monthly Visual Inspection Of Sumps and Dispenser Liners Documentation
04/02/2015 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1103
Rule: 62-761.640(4)(a)1., 62-761.640(4)(a)2., 62-761.640(4)(a)3., 62-761.640(4)(a)4.
Comments: Installation - verify that the line leak detector has been installed during the final installation inspection. Compliance - check to see that the unit is present. Examine the annual function test data - a pass alone is not sufficient. The tester must demonstrate 3.0 gph discharge detection for the mechanical (flow restrictor). Note that the electronic (auto shut off) line leak detector does not need an annual test, but must still be able to detect a 0.2 gph leak after it has been tripped at 150% line operating pressure. Replacements - unit must be tested out of the box - function must be proven. 3.0 gph = 185.4 ml/min (To convert milliliters/minute to gallons/hour, multiple the milliliters by 0.0162162; or, 1 gph equals 61.8 ml/min). Values greater than 186 ml/min fail. Values less than 185 ml/min mean that the line leak detector will activate at a more restrictive rate.
04/02/2015 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
04/02/2015 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
04/02/2015 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
11/16/2012 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 11/16/2012
Events:
Event Type: Activity has been finished Date: 11/16/2012
Comment: Finished
11/15/2012 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/15/2012
Activity Closed Date: 11/15/2012 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 11/15/2012
Comment: Finished
Comments:
Comment Date: 11/15/2012 User: KHAN_MR_1
Description: 8500457 - T&N EXPRESS TCI 11-15-2012 QA/RK/DB/TCI,on Thursday. . ONE NEW TANK WAS INSTALLED ON 2010/01/20 - Tank #7 - 12000 Gl. Two Compartment, Double Wall NewBerry PermaTank (EQ 733). Piping - Franklin Fueling Systems Model XP (EQ 618) - 70 Ft. - Installed from the new tank to the south east , Existing Environ Dispenser Liner (EQ 439). The existing Environ Double Wall Piping (EQ 511) between the existing dispenser pumps was used with the installation upgade , The Vent piping is Smith Fiberglass Red Thread IIA (EQ 252). Dispenser Liners - Used Three Existing Environ Liners (EQ 439). Spill Buckets - EMCO Wheaton Double Wall (EQ 594). Tank Sumps - APT - (EQ 423). Release Detection - Embarco EMC (130)/Interstitial Space Double Wall Tank/Double Wall Piping/Mechanical Leak Detectors (EQ 373)/Monthly Visual Inspection Of Sumps and Dispenser Liners Documentation. Overfill Protection - OPW 61SO Overfill Protection Valve/Embarco EMC 130 with Overfill Alarm. . The existing Double Wall, Environ Piping (EQ 511) between the three dispenser pumps was utilized with the Existing Environ Dispenser Liners (EQ 439) for the New Tank Upgrade Activity. Contractor - PetroFlow Inc. - PCC # 1256798 and Gary Lawson (PCC 051751) and the Consultant is CD & G Engineers. This is an EDI Site - Active Score = 10 NOTE: 70 Ft. of Franklin Fueling Systems Model XP Piping was used during the Installation (EQ 618) and was connected from the new storage tank to the South East Environ Dispenser Liner (EQ 439). 1-24-2012.ALL PAPERWORK WAS OK, NO LEAKS WERE SEEN. Miss niley said that premium bucket had bubble and was relaced by petroflow on October 7,2011.our department was not informed of the new installation. Both STPs,spill bucket and 3 dispensers were opened,all hoses.nozzles looked ok.
02/22/2012 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/22/2012
Activity Closed Date: 02/28/2012 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 02/28/2012
Comment: Finished
Comments:
Comment Date: 02/27/2012 User: BRAZILE_DO_1
Description: 2012/02/22 - Closure of the APT Premium Product Tank Sump (EQ 423) due to a manufacturer defect (small crack) i n the bottom of the sump. There was no visual contamination observed during the replacement of the sump.
02/22/2012 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/22/2012
Activity Closed Date: 02/28/2012 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 02/28/2012
Comment: Finished
Comments:
Comment Date: 02/27/2012 User: BRAZILE_DO_1
Description: 2012/02/22 - Install of the APT Premium Product Tank Sump (EQ 423) only. This was due to a structural defect (small crack) in the bottom of the sump, from the Manufacturer.There was no visual contamination observed during the replacement of the sump. This is an EDI Site - Active Score = 10 2010/01/20 - Install Tank #7 - 12000 Gl. Two Compartment, Double Wall NewBerry PermaTank (EQ 733) Piping - Franklin Fueling Systems Model XP (EQ 618) - 70 Ft. - Installed from the new tank to the south east Existing Environ Dispenser Liner (EQ 439). The existing Environ Double Wall Piping (EQ 511) between the existing dispenser pumps was used with the installation upgade The Vent piping is Smith Fiberglass Red Thread IIA (EQ 252). Dispenser Liners - Used Three Existing Environ Liners (EQ 439) Spill Buckets - EMCO Wheaton Double Wall (EQ 594) Tank Sumps - APT - (EQ 423) Release Detection - Embarco EMC (130)/Interstitial Space Double Wall Tank/Double Wall Piping/Mechanical Leak Detectors (EQ 373)/Monthly Visual Inspection Of Sumps and Dispenser Liners Documentation. Overfill Protection - OPW 61SO Overfill Protection Valve/Embarco EMC 130 with Overfill Alarm. A Limited Closure Summary Report was received on 1/28/2010, for tank #4, #5, & #6 - Each 8,000 Gl., STIp3 - Single Wall USTs (No EQ) that were removed from site on 01/12/2010. The Tanks were Taken To Emerald Coast Recycling for Scrap Metal. The existing Double Wall, Environ Piping (EQ 511) between the three dispenser pumps was utilized with the Existing Environ Dispenser Liners (EQ 439) for the New Tank Upgrade Activity. Contractor - PetroFlow Inc. - PCC # 1256798 and Gary Lawson (PCC 051751) and the Consultant is CD & G Engineers. This is an EDI Site - Active Score = 10 NOTE: 70 Ft. of Franklin Fueling Systems Model XP Piping was used during the Installation (EQ 618) and was connected from the new storage tank to the South East Environ Dispenser Liner (EQ 439).
01/24/2012 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/24/2012
Activity Closed Date: 01/24/2012 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 01/24/2012
Comment: Finished
Comments:
Comment Date: 01/24/2012 User: KHAN_MR_1
Description: 8500457 - T&N EXPRESS TCI 1-24-2012 LATE AFTERNOON 3-30 pm.Tuesday. ONE NEW TANK WAS INSTALLED ON 2010/01/20 - Tank #7 - 12000 Gl. Two Compartment, Double Wall NewBerry PermaTank (EQ 733). Piping - Franklin Fueling Systems Model XP (EQ 618) - 70 Ft. - Installed from the new tank to the south east , Existing Environ Dispenser Liner (EQ 439). The existing Environ Double Wall Piping (EQ 511) between the existing dispenser pumps was used with the installation upgade , The Vent piping is Smith Fiberglass Red Thread IIA (EQ 252). Dispenser Liners - Used Three Existing Environ Liners (EQ 439). Spill Buckets - EMCO Wheaton Double Wall (EQ 594). Tank Sumps - APT - (EQ 423). Release Detection - Embarco EMC (130)/Interstitial Space Double Wall Tank/Double Wall Piping/Mechanical Leak Detectors (EQ 373)/Monthly Visual Inspection Of Sumps and Dispenser Liners Documentation. Overfill Protection - OPW 61SO Overfill Protection Valve/Embarco EMC 130 with Overfill Alarm. . The existing Double Wall, Environ Piping (EQ 511) between the three dispenser pumps was utilized with the Existing Environ Dispenser Liners (EQ 439) for the New Tank Upgrade Activity. Contractor - PetroFlow Inc. - PCC # 1256798 and Gary Lawson (PCC 051751) and the Consultant is CD & G Engineers. This is an EDI Site - Active Score = 10 NOTE: 70 Ft. of Franklin Fueling Systems Model XP Piping was used during the Installation (EQ 618) and was connected from the new storage tank to the South East Environ Dispenser Liner (EQ 439). 1-24-2012.ALL PAPERWORK WAS OK, NO LEAKS WERE SEEN. Miss niley said that premium bucket had bubble and was relaced by petroflow on October 7,2011.our department was not informed of the new installation.
11/18/2010 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/18/2010
Activity Closed Date: 11/21/2010 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 11/21/2010
Comment: Finished
Comments:
Comment Date: 11/21/2010 User: KHAN_MR_1
Description: 8500457 - T&N EXPRESS TCI 11-18-2010 LATE AFTERNOON.Thursday( car battery got dead,left he light on) ONE NEW TANK WAS INSTALLED ON 2010/01/20 - Tank #7 - 12000 Gl. Two Compartment, Double Wall NewBerry PermaTank (EQ 733). Piping - Franklin Fueling Systems Model XP (EQ 618) - 70 Ft. - Installed from the new tank to the south east , Existing Environ Dispenser Liner (EQ 439). The existing Environ Double Wall Piping (EQ 511) between the existing dispenser pumps was used with the installation upgade , The Vent piping is Smith Fiberglass Red Thread IIA (EQ 252). Dispenser Liners - Used Three Existing Environ Liners (EQ 439). Spill Buckets - EMCO Wheaton Double Wall (EQ 594). Tank Sumps - APT - (EQ 423). Release Detection - Embarco EMC (130)/Interstitial Space Double Wall Tank/Double Wall Piping/Mechanical Leak Detectors (EQ 373)/Monthly Visual Inspection Of Sumps and Dispenser Liners Documentation. Overfill Protection - OPW 61SO Overfill Protection Valve/Embarco EMC 130 with Overfill Alarm. . The existing Double Wall, Environ Piping (EQ 511) between the three dispenser pumps was utilized with the Existing Environ Dispenser Liners (EQ 439) for the New Tank Upgrade Activity. Contractor - PetroFlow Inc. - PCC # 1256798 and Gary Lawson (PCC 051751) and the Consultant is CD & G Engineers. This is an EDI Site - Active Score = 10 NOTE: 70 Ft. of Franklin Fueling Systems Model XP Piping was used during the Installation (EQ 618) and was connected from the new storage tank to the South East Environ Dispenser Liner (EQ 439). 11-18-2010.ALL PAPERWORK WAS OK, NO LEAKS WERE SEEN.
02/10/2010 Editable Letter Activity Pierce, Linda L.
Activity Title: Limited Closure Summary Report (Complete) Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/10/2010
Comment: Finished
Events:
Event Type: Document has been sent Date: 02/10/2010
Comment: Sent on Wed Feb 10 00:00:00 EST 2010
Attachments:
Attachment Date: 02/10/2010 User: PIERCE_LL_1
Description: Limited Closure Summary Letter
View Attachment
01/29/2010 TCAR Activity Brazile, David
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 01/29/2010
Events:
Event Type: Activity has been finished Date: 01/29/2010
Comment: Finished
Comments:
Comment Date: 01/29/2010 User: BRAZILE_DO_1
Description: A Limited Closure Summary Report was received on 1/28/2010, for tank #4, #5, & #6 - Each 8,000 Gl., STIp3 - Single Wall USTs (No EQ) that were removed from site on 01/12/2010. The Tanks were Taken To Emerald Coast Recycling for Scrap Metal. The existing Environ Piping (EQ 511) between the dispensers was utilized with the Existing Environ Dispensers (EQ 439) for the New Tank Upgrade Activity. The Contractor was PetroFlow Inc. - PCC # 1256798 and the Consultant is CD & G Engineers. This is an EDI Site - Active Score = 10 NOTE: 70 Ft. of Franklin Fueling Systems Model XP Piping was used during the Installation (EQ 618) and was connected from the new storage tank to the South East Dispenser Liner. The Vent Piping is Smith Fiberglass Red Thread II A - EQ 252.
01/22/2010 Attachment Brazile, David
01/22/2010 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/22/2010
Activity Closed Date: 02/08/2010 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 02/08/2010
Comment: Finished
Comments:
Comment Date: 02/08/2010 User: BRAZILE_DO_1
Description: 2010/01/20 - Install Tank #7 - 12000 Gl. Two Compartment, Double Wall NewBerry PermaTank (EQ 733) Piping - Franklin Fueling Systems Model XP (EQ 618) - 70 Ft. - Installed from the new tank to the south east Existing Environ Dispenser Liner (EQ 439). The existing Environ Double Wall Piping (EQ 511) between the existing dispenser pumps was used with the installation upgade The Vent piping is Smith Fiberglass Red Thread IIA (EQ 252). Dispenser Liners - Used Three Existing Environ Liners (EQ 439) Spill Buckets - EMCO Wheaton Double Wall (EQ 594) Tank Sumps - APT - (EQ 423) Release Detection - Embarco EMC (130)/Interstitial Space Double Wall Tank/Double Wall Piping/Mechanical Leak Detectors (EQ 373)/Monthly Visual Inspection Of Sumps and Dispenser Liners Documentation. Overfill Protection - OPW 61SO Overfill Protection Valve/Embarco EMC 130 with Overfill Alarm. A Limited Closure Summary Report was received on 1/28/2010, for tank #4, #5, & #6 - Each 8,000 Gl., STIp3 - Single Wall USTs (No EQ) that were removed from site on 01/12/2010. The Tanks were Taken To Emerald Coast Recycling for Scrap Metal. The existing Double Wall, Environ Piping (EQ 511) between the three dispenser pumps was utilized with the Existing Environ Dispenser Liners (EQ 439) for the New Tank Upgrade Activity. Contractor - PetroFlow Inc. - PCC # 1256798 and Gary Lawson (PCC 051751) and the Consultant is CD & G Engineers. This is an EDI Site - Active Score = 10 NOTE: 70 Ft. of Franklin Fueling Systems Model XP Piping was used during the Installation (EQ 618) and was connected from the new storage tank to the South East Environ Dispenser Liner (EQ 439).
01/13/2010 Attachment Brazile, David
01/12/2010 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/12/2010
Activity Closed Date: 01/22/2010 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 01/22/2010
Comment: Finished
Comments:
Comment Date: 01/22/2010 User: BRAZILE_DO_1
Description: 2010/01/12 - Closure By Removal - Tank #4, #5, & #6 - Each 8,000 Gl., STIp3 - Single Wall USTs (No EQ). The Tanks were Taken To Emerald Coast Recycling for Scrap Metal. Piping - The Existing Piping will be utilized with the Existing Dispensers for the New Tank Upgrade Activity. Contractor - PetroFlow Inc. - PCC # 1256798 Consultant - CD & G Engineers. This is an EDI Site - Active Score = 10
07/09/2009 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/09/2009
Activity Closed Date: 07/09/2009 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 07/09/2009 User: KHAN_MR_1
Description: T&N Express with PETRO FLOW/MR.MCDONOUGH.MRS.NELLY 7-9-2009 THU.SUNNY Petroflow was removing water from all stps and two dispenser liners this money when RK arrived.(rain water) Tanks csld =3 unknown dispenser liner = 3,Environ EQ # 439. Spill bucket =3-DRY holding Stp = environ eq # 540 2, 3rd small is piping sump.all did not have water now,petroflow emptied this morning during the inspection. Piping = Environ EQ # 511 Release detection = Gilbarco EMC EQ # = 130 Overfill protection = Flappers. Tank test n/r = csld Illd test = Annually=CURRENT Atg op test = annually=CURRENT Piping test = NOT REQUIRED/ DW PIpes. CP = every 3 years.=CURRENT No sensors in dispensers or in stp's.stp's had water from rain , was taken out by petroflow today. Ins,visual,printouts,test results,hoses,nozzles,stp's,disp liners =all ok. Dispenser liner were dry now Facility is in compliance at this time. Spill buckets=dry=3. -------------------------- TI T2,TWO TANKS ARE MANIFOLDED TOGETHER,T3 IS SECOND TANK. fax=769-5727 ----------------------- ALLSTP'S,SPILL BUCKETS,DISPENSER WERE OK NOW , NO LEAK SEEN. --------------------------------------------------------------------------- last TCI =12-19-08 -----------------------
07/09/2009 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 07/09/2009
12/19/2008 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/19/2008
Activity Closed Date: 12/22/2008 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 12/19/2008 User: KHAN_MR_1
Description: TCI =12-19-08 t&n express with MRMCDONOUGH tank csld =3 dispenser liner = 3,environ eq #439. spill bucket =3 stp = environ eq # 540 2, 3rd small is piping sump. piping = environ eq # 511 release detection = gilbarco emc eq # = 130 overfill protection = flappers. tank test n/r = csld illd test = annually atg op test = annually piping test = n/r dw pipe. cp = every 3 years. no sensors in dispensers or in stp's.stp's had water from rain per nelly, was taken out by petroflow(andy) ins,visual,printouts,test results,hoses,nozzles,stp's,disp liners =all ok. spill buckets are being freshly painted. dispenser liner were dry. facility is in compliance at this time. --------------------------TI T2,TWO TANKS ARE MANIFOLDED TOGETHER,T3 IS SECOND TANK. fax=769-5727 ----------------------- ALLSTP'S,SPILL BUCKETS,DISPENSER WERE OK, NO LEAK SEEN.
Comments:
Comment Date: 04/06/2009 User: KHAN_MR_1
Description: 2009-4-3 I CALLED AND RCD INFO ABOUT INSURANCE=NOW EXPIRES ON=12-24-09
12/19/2008 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 12/19/2008
12/19/2008 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/19/2008
Activity Closed Date: 12/22/2008 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 12/19/2008 User: KHAN_MR_1
Description: TCI =12-19-08 t&n express with MRMCDONOUGH tank csld =3 dispenser liner = 3,environ eq #439. spill bucket =3 stp = environ eq # 540 2, 3rd small is piping sump. piping = environ eq # 511 release detection = gilbarco emc eq # = 130 overfill protection = flappers. tank test n/r = csld illd test = annually atg op test = annually piping test = n/r dw pipe. cp = every 3 years. no sensors in dispensers or in stp's.stp's had water from rain per nelly, was taken out by petroflow(andy) ins,visual,printouts,test results,hoses,nozzles,stp's,disp liners =all ok. spill buckets are being freshly painted. dispenser liner were dry. facility is in compliance at this time. --------------------------TI T2,TWO TANKS ARE MANIFOLDED TOGETHER,T3 IS SECOND TANK. fax=769-5727 ----------------------- ALLSTP'S,SPILL BUCKETS,DISPENSER WERE OK, NO LEAK SEEN.
Comments:
Comment Date: 04/06/2009 User: KHAN_MR_1
Description: 2009-4-3 I CALLED AND RCD INFO ABOUT INSURANCE=NOW EXPIRES ON=12-24-09
04/14/2008 Emergency Preparedness Information Activity Brazile, David
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 04/14/2008
12/24/2007 Attachment Khan, Muhammad Rafique
12/20/2007 Comment Khan, Muhammad Rafique
Description: no change in info.
12/20/2007 Attachment Khan, Muhammad Rafique
12/18/2007 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/18/2007
Activity Closed Date: 12/20/2007 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 12/18/2007 User: KHAN_MR_1
Description: TCI =12-17-07 t&n express tci = 2-27-07 tank csld =3 dispenser liner = 3,environ eq #439. spill bucket =3 stp = environ eq # 540 2, 3rd small is piping sump. piping = environ eq # 511 release detection = gilbarco emc eq # = 130 overfill protection = flappers. tank test n/r = csld illd test = annually atg op test = annually piping test = n/r dw pipe. cp = every 3 years. no sensors in dispensers or in stp's.stp's had water from rain per nelly, was taken out by petroflow(andy) ins,visual,printouts,test results,hoses,nozzles,stp's,disp liners =all ok. spill buckets are being freshly painted. dispenser liner were dry. facility is in compliance at this time. --------------------------TI T2,TWO TANKS ARE MANIFOLDED TOGETHER,T3 IS SECOND TANK. fax=769-5727
02/27/2007 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/27/2007
Activity Closed Date: 02/27/2007 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 02/27/2007 User: KHAN_MR_1
Description: t&n express tci = 2-27-07 tank csld =3 dispenser liner = 3,environ eq #439. spill bucket =3 stp = environ eq # 540 2,3rd small is piping sump. piping = environ eq # 511 release detection = gilbarco emc eq # = 130 overfill protection = flappers. tank test n/r = csld illd test = annually atg op test = annually piping test = n/r dw pipe. cp = every 3 years. no sensors in dispensers or in stp's. ins,visual,printouts,test results,hoses,nozzles,stp's,disp liners =all ok. spill buckets are being freshly painted right now. dispenser liner had little rain water at the bottom below piping, they will remove it facility is in compliance at this time.soon.
02/07/2007 Emergency Preparedness Information Activity Brazile, David
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/07/2007
02/07/2007 Emergency Preparedness Information Activity Brazile, David
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/07/2007
09/19/2006 Emergency Preparedness Information Activity Brazile, David
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/19/2006
02/20/2006 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
02/01/2006 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.700(1)(a)1
02/01/2006 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/17/2005 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: PIPING: ENVIRON
02/10/2005 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.700(1)(a)1
02/10/2005 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: PIPING: ENVIRON
02/11/2004 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: PIPING: ENVIRON
02/10/2004 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)1
Comments:
Comment Date: 03/02/2017 User: CRUZ_I_2
Description: The tank make/model could not be located at this time therefore the correct EQ# could not be found.
02/10/2004 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: PIPING: ENVIRON
08/04/2003 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: PIPING: ENVIRON
02/10/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 640(3)(d)
Comments:
Comment Date: 06/25/2008 User: JARRETT_SE
Description: Release Detection: - Tanks: Statistical Inventory Reconciliations (SIR) with tank tightness tests every three years; - SIR Provider: Teledata; Version: Tankmate 3.12 (EQ # 466); - Piping: Visual monitoring of piping interstice and mechanical line leak detectors with annual 3 gph leak tests; - Visual inspections of STP sumps, dispensers/liners and spill containment buckets; Tanks/STP Sumps/Piping: (3) 10,000-gallon, single-walled, fiberglass USTs; underground piping is Ameron III, double-walled, flexible piping. Tanks are equipped with: - (3) Total Containment STP sumps; Unknown
Comments:
Comment Date: 06/12/2007 User: JARRETT_SE
Description: 06/07/2007 Underground piping is Ameron III Direct Burial, double-walled, flexible piping (No DEP EQ #).
02/10/2003 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/10/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)3
02/10/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)1
02/10/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 640(3)(d)
Comments:
Comment Date: 06/25/2008 User: JARRETT_SE
Description: Release Detection: - Tanks: Statistical Inventory Reconciliations (SIR) with tank tightness tests every three years; - SIR Provider: Teledata; Version: Tankmate 3.12 (EQ # 466); - Piping: Visual monitoring of piping interstice and mechanical line leak detectors with annual 3 gph leak tests; - Visual inspections of STP sumps, dispensers/liners and spill containment buckets; Tanks/STP Sumps/Piping: (3) 10,000-gallon, single-walled, fiberglass USTs; underground piping is Ameron III, double-walled, flexible piping. Tanks are equipped with: - (3) Total Containment STP sumps; Unknown
Comments:
Comment Date: 06/12/2007 User: JARRETT_SE
Description: 06/07/2007 Underground piping is Ameron III Direct Burial, double-walled, flexible piping (No DEP EQ #).
04/08/2002 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
03/18/2002 Legacy Activity Godwin, Christine
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
02/11/2002 Legacy Activity Pinkovsky, Dennis D.
Activity Name: DISCHARGE SUSPECTED - NO RELEASE FOUND Activity Status: Closed
Completion Notes: PASSING LINE TEST RESULTS
02/11/2002 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
02/01/2002 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 450(2)(a)
02/01/2002 Legacy Activity Pinkovsky, Dennis D.
Activity Name: INCIDENT REPORT FORM RECEIVED Activity Status: Closed
Completion Notes: FUEL SEEN IN REGULAR UNLEAD PIPING/TANK SUMP
02/01/2002 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/01/2002 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 710(2)
02/01/2002 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)1
Comments:
Comment Date: 09/17/2012 User: PUCCI_SA_1
Description: Tank: probably Owens Corning since the sump is (EQ-191) Sump: Owens Corning Piping: Ameron D/W Red piping Veeder Root TLS-350 (EQ-033)
02/01/2002 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(a)1
04/25/2001 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
04/18/2001 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 610(4)(c)
04/18/2001 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
02/28/2001 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
02/07/2001 Violation Closed Godwin, Christine
Significance: SNC-B Status: Closed
Rule: 400(3)
02/07/2001 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/07/2001 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 710(2)
02/07/2001 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)3
02/07/2001 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)1
05/31/2000 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
05/08/2000 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)1
05/08/2000 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
02/22/2000 Violation Closed Godwin, Christine
Significance: SNC-B Status: Closed
Rule: 600(1)(d)
Comments:
Comment Date: 04/26/2017 User: PERRY_JF_2
Description: Facility email is tracy@daytonawrecker.com
02/22/2000 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/22/2000 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)1
02/26/1999 Legacy Activity Pinkovsky, Dennis D.
Activity Name: TANK CLOSURE INSPECTION Activity Status: Closed
02/19/1999 Legacy Activity Pinkovsky, Dennis D.
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
02/02/1999 Legacy Activity Pinkovsky, Dennis D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
05/08/1998 Legacy Activity Tolar, Nancy J.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
05/06/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 10/31/2000 User: UNKNOWN
Description: COMPLIANCE: PETROLEUM CONTAMINATION
Comments:
Comment Date: 04/30/2007 User: KHAN_MR_1
Description: 8518653 - RITZ FOOD STORE #24. LOCATEDA AT 11214 FRONT BEACH RD. TANKS =1 DW UST TANKS MANUFACTURER=HIGHLAND/20 K TANK TANKS EQ #506 PIPING=AMERON DW LCX 3000EQ-291 RELEASE DETECTION =TLS 300C EQ-196 OVERFILL PROTECTION=BALL FLOATS DISPENSER LINER=APT EQ-423 STP=APT EQ-423
Attachments:
Attachment Date: 03/17/2025 User: GARTIN_D
Description: Facility photograph 3-05-2025
View Attachment
05/06/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 10/31/2000 User: UNKNOWN
Description: COMPLIANCE: PETROLEUM CONTAMINATION
Comments:
Comment Date: 04/30/2007 User: KHAN_MR_1
Description: 8518653 - RITZ FOOD STORE #24. LOCATEDA AT 11214 FRONT BEACH RD. TANKS =1 DW UST TANKS MANUFACTURER=HIGHLAND/20 K TANK TANKS EQ #506 PIPING=AMERON DW LCX 3000EQ-291 RELEASE DETECTION =TLS 300C EQ-196 OVERFILL PROTECTION=BALL FLOATS DISPENSER LINER=APT EQ-423 STP=APT EQ-423
Attachments:
Attachment Date: 03/17/2025 User: GARTIN_D
Description: Facility photograph 3-05-2025
View Attachment
05/06/1998 Legacy Activity Tolar, Nancy J.
Activity Name: UST ROUTINE COMPLIANCE INSPECTION Activity Status: Closed