Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 04/20/2025 Last Data Refresh: 04/19/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 8510599 | ||||||||||
Facility Name: | TRI-COUNTY OIL DISTRIBUTORS INC | ||||||||||
05/03/2024 | Enforcement Tracking Activity | Paul, Jennifer | |||||||||
Activity Status: | Open | ||||||||||
05/31/2023 | Electronic Communication Activity | Keim, Michael J | |||||||||
Activity Closed Date: | 05/31/2023 | Activity Status: | Closed | ||||||||
Date: | 05/31/2023 | ||||||||||
Recipient: | Todd Tucker | ||||||||||
Sender: | M Keim | ||||||||||
Subject: | TCI report | ||||||||||
Message: | Storage tank inspection report and compliance letter sent via e-mail to Todd Tucker, Todd@tricountyoil.com | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/31/2023 | ||||||||
Comment: | Finished | ||||||||||
05/31/2023 | Editable Letter Activity | Keim, Michael J | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Description: | Inspection notification 4.8.21 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/31/2023 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 05/31/2023 | ||||||||
Comment: | Sent | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 05/31/2023 | User: | KEIM_MJ_1 | ||||||||
Description: | CAO Letter | ||||||||||
View Attachment | |||||||||||
05/16/2023 | Electronic Communication Activity | Ramsey, Timothy H | |||||||||
Activity Closed Date: | 05/16/2023 | Activity Status: | Closed | ||||||||
Date: | 05/16/2023 | ||||||||||
Recipient: | Mike Doerr | ||||||||||
Sender: | Tim Ramsey | ||||||||||
Subject: | Source Removal Report Review Email | ||||||||||
Message: | Sent Review Letter by email | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/16/2023 | ||||||||
Comment: | Finished | ||||||||||
05/16/2023 | Editable Letter Activity | Ramsey, Timothy H | |||||||||
Activity Title: | Closure Assessment Report (Complete) | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/16/2023 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 05/16/2023 | ||||||||
Comment: | Sent | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 05/16/2023 | User: | RAMSEY_TH_1 | ||||||||
Description: | Source Removal Report Review | ||||||||||
View Attachment | |||||||||||
05/16/2023 | TCAR Activity | Ramsey, Timothy H | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 05/16/2023 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/16/2023 | ||||||||
Comment: | Finished | ||||||||||
05/16/2023 | Document Management Activity | Ramsey, Timothy H | |||||||||
Activity Title: | Closure Document | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/16/2023 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 05/16/2023 | User: | RAMSEY_TH_1 | ||||||||
Description: | Source Removal Report | ||||||||||
View Attachment | |||||||||||
05/15/2023 | Site Inspection Activity Closed | Keim, Michael J | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 04/13/2023 | ||||||||||
Activity Closed Date: | 05/31/2023 | Activity Closed By: | KEIM_MJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/31/2023 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/31/2023 | User: | KEIM_MJ_1 | ||||||||
Description: | Storage tank inspection report and compliance letter sent via e-mail to Todd Tucker, Todd@tricountyoil.com | ||||||||||
02/27/2023 | Enforcement Referral Activity | Ramsey, Timothy H | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 05/03/2024 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 02/27/2023 | ||||||||
Comment: | Submitted for approval by: Timothy H Ramsey: Facility referred since violation not resolved | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 02/29/2024 | ||||||||
Comment: | Acknowledged and Assigned by Brierra Mack | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 02/29/2024 | ||||||||
Comment: | Assigned to MaryAnne Mills | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 05/03/2024 | ||||||||
Comment: | Accepted by Jennifer Paul: accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/03/2024 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 02/27/2023 | User: | RAMSEY_TH_1 | ||||||||
Description: | Facility referred since violation not resolved | ||||||||||
Comments: | |||||||||||
Comment Date: | 02/27/2023 | User: | RAMSEY_TH_1 | ||||||||
Description: | Facility referred since violation not resolved | ||||||||||
02/27/2023 | Enforcement Referral Activity | Ramsey, Timothy H | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 05/03/2024 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 02/27/2023 | ||||||||
Comment: | Submitted for approval by: Timothy H Ramsey: Facility referred since violation not resolved | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 02/29/2024 | ||||||||
Comment: | Acknowledged and Assigned by Brierra Mack | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 02/29/2024 | ||||||||
Comment: | Assigned to MaryAnne Mills | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 05/03/2024 | ||||||||
Comment: | Accepted by Jennifer Paul: accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/03/2024 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 02/27/2023 | User: | RAMSEY_TH_1 | ||||||||
Description: | Facility referred since violation not resolved | ||||||||||
Comments: | |||||||||||
Comment Date: | 02/27/2023 | User: | RAMSEY_TH_1 | ||||||||
Description: | Facility referred since violation not resolved | ||||||||||
06/16/2020 | Record Document Activity | Keim, Michael J | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Todd Tucker | Activity Closed Date: | 06/16/2020 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/16/2020 | ||||||||
Comment: | Finished | ||||||||||
06/12/2020 | Violation Closed | Keim, Michael J | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 4076 | ||||||||||
Rule: | 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2. | ||||||||||
06/12/2020 | Editable Letter Activity | Keim, Michael J | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 06/12/2020 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/12/2020 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 06/12/2020 | User: | KEIM_MJ_1 | ||||||||
Description: | CAO Letter | ||||||||||
View Attachment | |||||||||||
06/12/2020 | Violation Closed | Keim, Michael J | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 4057 | ||||||||||
Rule: | 62-761.500(7)(e) | ||||||||||
06/12/2020 | Violation Open | Keim, Michael J | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 5101 | ||||||||||
Rule: | 62-762.601(4), 62-762.601(4)(a), 62-762.601(4)(b), 62-762.601(4)(b)1., 62-762.601(4)(b)2., 62-762.601(4)(b)3. | ||||||||||
06/03/2020 | Electronic Communication Activity | Keim, Michael J | |||||||||
Activity Closed Date: | 06/03/2020 | Activity Status: | Closed | ||||||||
Date: | 06/03/2020 | ||||||||||
Recipient: | Todd Tucker | ||||||||||
Sender: | M Keim | ||||||||||
Subject: | TCI report | ||||||||||
Message: | Storage tank inspection report and compliance letter sent via e-mail to Todd Tucker, todd@tricountyoil.com | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/03/2020 | ||||||||
Comment: | Finished | ||||||||||
05/14/2020 | Site Inspection Activity Closed | Keim, Michael J | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 05/14/2020 | ||||||||||
Activity Closed Date: | 06/12/2020 | Activity Closed By: | KEIM_MJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/12/2020 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/03/2020 | User: | KEIM_MJ_1 | ||||||||
Description: | Storage tank inspection report and compliance letter sent via e-mail to Todd Tucker, todd@tricountyoil.com | ||||||||||
11/30/2017 | Issue Document Activity | Keim, Michael J | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Todd Tucker | Activity Closed Date: | 11/30/2017 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 11/30/2017 | ||||||||
Comment: | Finished | ||||||||||
11/30/2017 | Phone Conversation Activity | Keim, Michael J | |||||||||
Call Type: | Incoming | Activity Status: | Closed | ||||||||
Phone Number: | (352) 274-5569 | Activity Closed Date: | 11/30/2017 | ||||||||
Subject: | Spoke with Todd Tucker regarding TCI schedule and records needed. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 11/30/2017 | ||||||||
Comment: | Finished | ||||||||||
11/30/2017 | Electronic Communication Activity | Keim, Michael J | |||||||||
Activity Closed Date: | 11/30/2017 | Activity Status: | Closed | ||||||||
Date: | 11/30/2017 | ||||||||||
Recipient: | Todd Tucker | ||||||||||
Sender: | M Keim | ||||||||||
Subject: | TCI report | ||||||||||
Message: | Tank compliance inspection report sent via e-mail to Todd Tucker, todd@tricountyoil.com | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 11/30/2017 | ||||||||
Comment: | Finished | ||||||||||
11/17/2017 | Site Inspection Activity Closed | Keim, Michael J | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 11/17/2017 | ||||||||||
Activity Closed Date: | 11/30/2017 | Activity Closed By: | KEIM_MJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 11/30/2017 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 11/30/2017 | User: | KEIM_MJ_1 | ||||||||
Description: | Tank compliance inspection report sent via e-mail to Todd Tucker, todd@tricountyoil.com Compliance assist with Phil. | ||||||||||
06/18/2015 | Issue Document Activity | Holtkamp, John Joseph | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | RPK / John Holtkamp FDOH Columbia CHD | Activity Closed Date: | 06/18/2015 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/18/2015 | ||||||||
Comment: | Finished | ||||||||||
06/10/2015 | Site Inspection Activity Closed | Shulaw, Benjamin J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/03/2015 | ||||||||||
Activity Closed Date: | 06/10/2015 | Activity Closed By: | SHULAW_BJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/10/2015 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/10/2015 | User: | SHULAW_BJ_1 | ||||||||
Description: | Dispenser liners, and spill containment gave been emptied. The cracks in the secondary containment have been sealed and the shear valve secured. | ||||||||||
04/06/2015 | Editable Letter Activity | Shulaw, Benjamin J. | |||||||||
Activity Title: | County Subsequent Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/06/2015 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 04/06/2015 | User: | SHULAW_BJ_1 | ||||||||
Description: | 6Apr15 Sec NCL | ||||||||||
View Attachment | |||||||||||
10/27/2014 | Editable Letter Activity | Shulaw, Benjamin J. | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
Description: | DEP Enforcement Referrals | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/27/2014 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 10/27/2014 | User: | SHULAW_BJ_1 | ||||||||
Description: | 27Oct14 NCL | ||||||||||
View Attachment | |||||||||||
10/27/2014 | Emergency Preparedness Information Activity | Shulaw, Benjamin J. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 10/27/2014 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/27/2014 | ||||||||
Comment: | Finished | ||||||||||
10/21/2014 | Site Inspection Activity Closed | Shulaw, Benjamin J. | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 10/20/2014 | ||||||||||
Activity Closed Date: | 10/27/2014 | Activity Closed By: | SHULAW_BJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/27/2014 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/27/2014 | User: | SHULAW_BJ_1 | ||||||||
Description: | New Violations: The walls and floor of the concrete secondary in the fuel truck dispensing area have cracks in them. Seal the cracks with an approved sealant and call for a re-inspection. Some of the dispenser pans and the remote fill containment are holding some product. It should be removed. Dispenser ½ has a shear valve that is not properly secured. Secure the valve and call for a re-inspection. Comments: Six SW steel ASTs with remote fill inside concrete secondary containment. There is above ground steel pipe suction system inside the containment transitioning to DW pressurized underground pipe to the dispensers with the exception of the off road dispenser. Hoses in good condition dispenser pans look tight, several are holding some product. There is also a top fill dispenser area for filling fuel trucks. This dispenser area has some cracks in the walls and floor that must be sealed. Visual monitoring of ASTs, pipe and secondaries. The horizontal ASTs have clock gauge monitoring for product level; the vertical ASTs have Moormann gauges. The ASTs share a sealed concrete secondary containment with a closed drain. The ASTs, piping and secondary are in good condition. The current registration placard was posted. The insurance policy, Certificate of Financial Responsibility and RDRL were in the log. Inspections were on time, but details of the inspections were not noted. A facility representative signed the attached notes after consultation. Discharge Information: EDI completed score 77 This report will be mailed via USPS. A non compliance letter citing the violations accompanies this inspection report; please find it attached. Please provide our office with documentation confirming the resolution of the cited violations within thirty days of receipt of this inspection report and attached non compliance letter. For more inspection details and information or if you have any questions please contact me at 386-758-2185, 386-697-7329 cell, fax 386-758-2187, or email Benjamin.Shulaw@flhealth.gov. | ||||||||||
10/21/2014 | Discharge Reporting Activity | Shulaw, Benjamin J. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 11/17/2015 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 11/17/2015 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/21/2014 | User: | DEFALCO_L | ||||||||
Description: | DRF received 10/13/14 for discharge that occurred 10/1/14. notice from State Watch Office to OER. OER will handle and report for cleanup will be reviewed by OER. | ||||||||||
10/21/2014 | Site Inspection Activity Closed | Shulaw, Benjamin J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 10/20/2014 | ||||||||||
Activity Closed Date: | 10/23/2014 | Activity Closed By: | SHULAW_BJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/23/2014 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 10/21/2014 | User: | SHULAW_BJ_1 | ||||||||
Description: | Comments: After receiving information of a discharge I visited the site 20Oct14 to do a discharge inspection. As told to this inspector by Mike Doerr, who was told by Sean Fugate, as was reported by the truck driver: According to a truck driver: At approximately 0400 on 1Oct14 the driver saw evidence of a discharge and reported this to his employer, Sean Fugate. An unknown driver pulled up to a self service dispenser and started fueling his truck. He set the lock on the nozzle to continue fueling and was not attending when either the nozzle fell out of the tank and continued dispensing fuel, or the nozzle didn¿t shut itself off after the tank was full. This driver eventually discovered the discharge, stopped it and drove away. The reporting driver arrived to fuel his truck some time afterward. It rained that night and into the day. It is unknown when this driver told Sean Fugate. Mr Fugate told Mike Doerr at approximately noon that day. Mr Doerr reported this to his consultant, George Foster of Creative Environmental Solutions either later that day or the following day. Mr Doerr left the reporting of the discharge to DEP to Mr Foster. He said it didn¿t immediately occur to him to report to DEP. Note that the requirement for reporting a discharge is within 24 hours or the next business day. Creative Environmental Solutions notified the State Watch Office who notified the Office of Emergency Response on 13Oct14. The Office of Emergency Response will track and review until further notice. Creative Environmental Solutions submitted a Discharge Reporting Form to DEP on 13Oct14. Creative Environmental Solutions will be overseeing the excavation and submit a Source Removal Report to the Office of Emergency Response within 60 days of completion. It¿s a short way, 40-60 feet down a definite paved, mostly impermeable slope to the ditch by SW 18th Ave. The ditch continues to slope down toward the south. By the time Mr Doerr found out about the discharge, the fuel had completely adsorbed into the soil. The pavement had been washed, and the fuel washed into the soil by the rain. At this time there is dead grass showing the path of the fuel terminating in a patch of sand. I stepped off about 60 yards long and 2-3 yards wide. The estimation of 100 gallons spilled was derived from the amount of fuel dispensed. Discharge Information: EDI score 77 completed This report will be sent via USPS. If you have any questions please contact me at 386-758-2185, 386-697-7329 cell, fax 386-758-2187, or email Benjamin.Shulaw@flhealth.gov | ||||||||||
10/20/2014 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2120 | ||||||||||
Rule: | 62-762.701(1)(c)1. | ||||||||||
Comments: | Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water". | ||||||||||
10/20/2014 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2110 | ||||||||||
Rule: | 62-762.701(1)(a)1.a., 62-762.701(1)(a)1.b., 62-762.701(1)(a)1.c., 62-762.701(1)(a)1.d. | ||||||||||
10/20/2014 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2131 | ||||||||||
Rule: | 62-762.701(6) | ||||||||||
Comments: | Refer to inspection items #2017-2022 for information on .501(1)(e) issues. | ||||||||||
07/31/2012 | Site Inspection Activity Closed | Oymayan, Avo J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 07/25/2012 | ||||||||||
Activity Closed Date: | 07/31/2012 | Activity Closed By: | OYMAYAN_AJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/31/2012 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 07/31/2012 | User: | OYMAYAN_AJ_1 | ||||||||
Description: | Violations Summary: There wes one violation cited at the time of the inspection. It was a leaky pipe in the farm diesel dispenser liner. This leak was repaired on 7/31/2012, by J & J Equipment. Additional Notes: All previous violations which were open at the time of this inspection were resolved (re-inspected during theis annual inspection). Discharge Information: There is no new information or obvious evidence of recent release or discharge, within the last year. For more detailed discharge information, please consult the Petroleum Clean Up Section at the F D E P H.Q. in Tallahassee; or the F D E P Northeast District Office in Jacksonville; or the official compliance facility file at the Columbia C H D, Environmental Health Section, in Lake City. Other Comments: For more inspection details and information; please see the copy of the inspection field notes, site schematic and system description that is electronically, as well as physically, attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058. Attachments (2) | ||||||||||
06/04/2012 | Editable Letter Activity | Shulaw, Benjamin J. | |||||||||
Activity Title: | County Subsequent Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/04/2012 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 06/04/2012 | User: | SHULAW_BJ_1 | ||||||||
Description: | 4Jun12 NCL | ||||||||||
View Attachment | |||||||||||
05/04/2012 | Attachment | Perea, Aurelio O. | |||||||||
01/09/2012 | Editable Letter Activity | Shulaw, Benjamin J. | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/09/2012 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 01/09/2012 | User: | SHULAW_BJ_1 | ||||||||
Description: | 9Jan12 NCL | ||||||||||
View Attachment | |||||||||||
01/09/2012 | Emergency Preparedness Information Activity | Shulaw, Benjamin J. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 01/09/2012 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/09/2012 | ||||||||
Comment: | Finished | ||||||||||
01/06/2012 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2131 | ||||||||||
Rule: | 62-762.701(6) | ||||||||||
Comments: | Refer to inspection items #2017-2022 for information on .501(1)(e) issues. | ||||||||||
01/06/2012 | Site Inspection Activity Closed | Shulaw, Benjamin J. | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 01/06/2012 | ||||||||||
Activity Closed Date: | 01/09/2012 | Activity Closed By: | SHULAW_BJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/09/2012 | ||||||||
Comment: | Finished | ||||||||||
01/06/2012 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2110 | ||||||||||
Rule: | 62-762.701(1)(a)1.a., 62-762.701(1)(a)1.b., 62-762.701(1)(a)1.c., 62-762.701(1)(a)1.d. | ||||||||||
05/25/2011 | Issue Document Activity | Defalco, Lynal | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | defalco | Activity Closed Date: | 05/25/2011 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/25/2011 | ||||||||
Comment: | Finished | ||||||||||
05/24/2011 | Site Inspection Activity Closed | Shulaw, Benjamin J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 05/24/2011 | ||||||||||
Activity Closed Date: | 05/24/2011 | Activity Closed By: | SHULAW_BJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/24/2011 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/24/2011 | User: | SHULAW_BJ_1 | ||||||||
Description: | There were no violations cited at the time of the inspection. Comments: All ASTs have been repainted. The spill bucket contained little product. Discharge Information: Completed There is no new information or obvious evidence of recent release. This facility is in compliance, it was referred to DEP for enforcement; if you have any questions please contact me at 386-623-0831 cell, fax 386-758-2187, or office 386-758-2140 or email Benjamin_Shulaw@doh.state.fl.us | ||||||||||
04/19/2011 | Enforcement Referral Activity | Shulaw, Benjamin J. | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 04/19/2011 | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 04/19/2011 | ||||||||
Comment: | Acknowledged and Assigned by: DOHANEY_T | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 04/19/2011 | ||||||||
Comment: | Assigned to DEFALCO_L | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 04/19/2011 | ||||||||
Comment: | Accepted by: DEFALCO_L | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/19/2011 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 04/19/2011 | ||||||||
Comment: | Submitted for approval by: SHULAW_BJ_1 | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/19/2011 | User: | SHULAW_BJ_1 | ||||||||
Description: | This facility is being referred for unresolved violations incurred during the annual compliance on 8Sep10. | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/19/2011 | User: | SHULAW_BJ_1 | ||||||||
Description: | This facility is being referred for unresolved violations incurred during the annual compliance on 8Sep10. | ||||||||||
04/19/2011 | Enforcement Tracking Activity | Defalco, Lynal | |||||||||
Activity Status: | Closed | ||||||||||
Activity Result: | Closed Without Enforcement | Activity Closed Date: | 05/25/2011 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/25/2011 | ||||||||
Comment: | Finished | ||||||||||
04/19/2011 | Enforcement Referral Activity | Shulaw, Benjamin J. | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 04/19/2011 | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 04/19/2011 | ||||||||
Comment: | Acknowledged and Assigned by: DOHANEY_T | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 04/19/2011 | ||||||||
Comment: | Assigned to DEFALCO_L | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 04/19/2011 | ||||||||
Comment: | Accepted by: DEFALCO_L | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/19/2011 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 04/19/2011 | ||||||||
Comment: | Submitted for approval by: SHULAW_BJ_1 | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/19/2011 | User: | SHULAW_BJ_1 | ||||||||
Description: | This facility is being referred for unresolved violations incurred during the annual compliance on 8Sep10. | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/19/2011 | User: | SHULAW_BJ_1 | ||||||||
Description: | This facility is being referred for unresolved violations incurred during the annual compliance on 8Sep10. | ||||||||||
04/13/2011 | Editable Letter Activity | Shulaw, Benjamin J. | |||||||||
Activity Title: | County Subsequent Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/13/2011 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 04/13/2011 | User: | SHULAW_BJ_1 | ||||||||
Description: | 13Apr11 Trd NCL | ||||||||||
View Attachment | |||||||||||
03/29/2011 | Site Inspection Activity Closed | Shulaw, Benjamin J. | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 03/29/2011 | ||||||||||
Activity Closed Date: | 04/13/2011 | Activity Closed By: | SHULAW_BJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/13/2011 | ||||||||
Comment: | Finished | ||||||||||
02/10/2011 | Editable Letter Activity | Shulaw, Benjamin J. | |||||||||
Activity Title: | County Subsequent Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/10/2011 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/10/2011 | User: | SHULAW_BJ_1 | ||||||||
Description: | 10Feb11 Sec NCL | ||||||||||
View Attachment | |||||||||||
09/16/2010 | Editable Letter Activity | Shulaw, Benjamin J. | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/16/2010 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 09/16/2010 | User: | SHULAW_BJ_1 | ||||||||
Description: | 16Sep10 NCL | ||||||||||
View Attachment | |||||||||||
09/08/2010 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2038 | ||||||||||
Rule: | 62-762.501(2)(c)3.d. | ||||||||||
Comments: | Secondary containment penetrations shall be sealed on the internal and external portions of the wall. | ||||||||||
09/08/2010 | Site Inspection Activity Closed | Shulaw, Benjamin J. | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 09/08/2010 | ||||||||||
Activity Closed Date: | 09/16/2010 | Activity Closed By: | SHULAW_BJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/16/2010 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 09/10/2010 | User: | SHULAW_BJ_1 | ||||||||
Description: | Rusting is bad, ASTs becoming pitted. Paint ASTs. Spill bucket is ~ 1/2 full of product and 2 diesel dispensers hold product. Promptly empty secondary containment of liquids. 1 dispenser is missing a shear valve braket bolt. Replace the bolt. The offroad diesel dispenser is not sealed around in- pipe. Seal around the pipe. The offroad diesel fillport is green. Color codes are as follows: Yellow for road diesel or yellow with a blue stripe for off-road diesel. It would be helpful to number ASTs and dispensers, so they could be referred to more easiliy. Discharge Information: Completed A non compliance letter citing the violations accompanies this inspection report; please find it attached. Please provide our office with documentation confirming the resolution of the cited violations within thirty days of receipt of this inspection report and attached non compliance letter. For more inspection details and information, please see the copy of the inspection field notes. If you have any questions please contact me at 386-623-0831 cell, fax 386-758-2187, or office 386-758-2140 or email Benjamin_Shulaw@doh.state.fl.us | ||||||||||
09/08/2010 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 1049 | ||||||||||
Rule: | 62-761.510(1)(b)3. | ||||||||||
Comments: | Refer to the color coded chart included in the API 1637 Reference Standard. Note that airport fuel identification is described in API Bulletin 1542. Other identification methods are: tag or decal on the surface adjacent to the fill, tag on the fillpipe adapter, or colored plastic identification card inside the spill containment unit. Major oil retailers often have their own specific color scheme. See rule 62-761.500(5)(a). | ||||||||||
09/08/2010 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2120 | ||||||||||
Rule: | 62-762.701(1)(c)1. | ||||||||||
Comments: | Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water". | ||||||||||
09/08/2010 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2014 | ||||||||||
Rule: | 62-762.501(1)(b) | ||||||||||
Comments: | Examine exterior surfaces for damage during shipping and installation. Has the on site applied exterior coating been applied according to the manufacturer's specifications? Light colored paints show fuel discoloration. Refer to item #2110 for Cat A, B system tank condition. | ||||||||||
09/08/2010 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2110 | ||||||||||
Rule: | 62-762.701(1)(a)1.a., 62-762.701(1)(a)1.b., 62-762.701(1)(a)1.c., 62-762.701(1)(a)1.d. | ||||||||||
08/05/2009 | Site Inspection Activity Closed | Shulaw, Benjamin J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/05/2009 | ||||||||||
Activity Closed Date: | 08/05/2009 | Activity Closed By: | SHULAW_BJ_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 08/05/2009 | User: | SHULAW_BJ_1 | ||||||||
Description: | The secondary containment sealant has been patched and appears tight. This facility is in compliance without enforcement; if you have any questions please call me at 386-623-0831 or email Benjamin_Shulaw @doh.state.fl.us . | ||||||||||
06/29/2009 | Editable Letter Activity | Kassees, Ramsey D. | |||||||||
Activity Title: | County Subsequent Non-Compliance Letter | Activity Status: | Closed | ||||||||
02/27/2009 | Violation Closed | Shulaw, Benjamin J. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2110 | ||||||||||
Rule: | 62-762.701(1)(a)1.a., 62-762.701(1)(a)1.b., 62-762.701(1)(a)1.c., 62-762.701(1)(a)1.d. | ||||||||||
02/27/2009 | Editable Letter Activity | Shulaw, Benjamin J. | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
02/20/2009 | Site Inspection Activity Closed | Shulaw, Benjamin J. | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 02/20/2009 | ||||||||||
Activity Closed Date: | 02/27/2009 | Activity Closed By: | SHULAW_BJ_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 02/27/2009 | User: | SHULAW_BJ_1 | ||||||||
Description: | There are cracks in the secondary containment; it has to be re-sealed. Tanks are showing some rust; they should be repainted. A non compliance letter citing the violations accompanies this inspection report; please find it attached. Please provide our office with documentation confirming the resolution of the cited violations, within thirty days of receipt of this inspection report and attached non compliance letter. If you have any questions or concerns, please feel free to contact me at (386) 758-2140. | ||||||||||
06/20/2008 | Site Inspection Activity Closed | Oymayan, Avo J. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/20/2008 | ||||||||||
Activity Closed Date: | 06/24/2008 | Activity Closed By: | OYMAYAN_AJ_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 06/20/2008 | User: | OYMAYAN_AJ_1 | ||||||||
Description: | RRBD on 6-16-2008 indicates that all product spilled areas have been properly cleaned. There are no more open violations at this facility.Therefore, this facility is in compliance without enforcement (CWOE). | ||||||||||
01/17/2008 | Attachment | Kassees, Ramsey D. | |||||||||
01/17/2008 | Editable Letter Activity | Kassees, Ramsey D. | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
01/08/2008 | Violation Closed | Kassees, Ramsey D. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2120 | ||||||||||
Rule: | 62-762.701(1)(c)1. | ||||||||||
Comments: | Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water". | ||||||||||
Comments: | |||||||||||
Comment Date: | 01/17/2008 | User: | KASSEES_RP_1 | ||||||||
Description: | Forgot to photograph the violation. | ||||||||||
01/08/2008 | Site Inspection Activity Closed | Kassees, Ramsey D. | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 01/08/2008 | ||||||||||
Activity Closed Date: | 01/17/2008 | Activity Closed By: | KASSEES_RP_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 01/08/2008 | User: | KASSEES_RP_1 | ||||||||
Description: | Violations Summary: There wes one violation cited at the time of the inspection. It is summarized as follows: 1). Failure to maintain the spill containment units spill free and clean; and failure to maintain the areas around the off road and on road diesel dispensers spill free. Please clean up all product spills in all area, as best as possible. A non compliance letter citing the violations accompanies this inspection report. Please find it attached. Please provide our office with documentation confirming the resolution of the cited violations, within thirty days of receipt of this inspection report and attached non compliance letter. Additional Notes: The secondary containment unit sealant is beginning to crack in a few places. Please take measures to repair and/or patch the sealant where necessary. Discharge Information: There is no new information or obvious evidence of recent release or discharge, within the last year. For more detailed discharge information, please consult the Petroleum Clean Up Section at the F D E P H.Q. in Tallahassee; or the F D E P Northeast District Office in Jacksonville; or the official compliance facility file at the Columbia C H D, Environmental Health Section, in Lake City. Other Comments: For more inspection details and information; please see the copy of the inspection field notes, site schematic and system description that is electronically, as well as physically, attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058. | ||||||||||
06/24/2007 | Site Inspection Activity Closed | Kassees, Ramsey D. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/24/2007 | ||||||||||
Activity Closed Date: | 06/25/2007 | Activity Closed By: | KASSEES_RP_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 06/24/2007 | User: | KASSEES_RP_1 | ||||||||
Description: | A reinspection at this facility, on May 30, 2007, confirmed that the following violations have been resolved. 1). The A S Ts' secondary containment unit has been adequately repaired and sealed using F D E P approved sealant. 2). Pump # 4/5 diesel dispenser containment unit has been emptied and cleaned. There are no more open violations at this facility. It is in compliance without enforcement (C W O E). | ||||||||||
05/24/2007 | Emergency Preparedness Information Activity | Kassees, Ramsey D. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 05/24/2007 | ||||||||||
02/26/2007 | Editable Letter Activity | Kassees, Ramsey D. | |||||||||
Activity Title: | Warning Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 02/26/2007 | ||||||||
Comment: | Sent on Mon Feb 26 00:00:00 EST 2007 | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/26/2007 | User: | KASSEES_RP_1 | ||||||||
Description: | Warning Letter Report | ||||||||||
View Attachment | |||||||||||
02/15/2007 | Emergency Preparedness Information Activity | Kassees, Ramsey D. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 02/15/2007 | ||||||||||
01/10/2007 | Attachment | Kassees, Ramsey D. | |||||||||
01/10/2007 | Editable Letter Activity | Kassees, Ramsey D. | |||||||||
Activity Title: | District Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 01/10/2007 | ||||||||
Comment: | Sent on Wed Jan 10 00:00:00 EST 2007 | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 01/10/2007 | User: | KASSEES_RP_1 | ||||||||
Description: | NCL Report | ||||||||||
View Attachment | |||||||||||
01/10/2007 | Violation Closed | Kassees, Ramsey D. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2120 | ||||||||||
Rule: | 62-762.701(1)(c)1. | ||||||||||
Comments: | Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water". | ||||||||||
01/10/2007 | Violation Closed | Kassees, Ramsey D. | |||||||||
Significance: | SNC-B | Status: | Closed | ||||||||
Criteria ID: | 2018 | ||||||||||
Rule: | 62-762.501(1)(e)3.a., 62-762.501(1)(e)3.b., 62-762.501(1)(e)3.c. | ||||||||||
Comments: | Shop-fabricated AST dike field areas must have met these standards by January 1, 2000. Category-A and B field-erected AST dike field areas need to meet containment standards in .501(1)(e) and .501(3)(c) by January 1, 2005. Concrete secondary containment must meet one of three standards: 1) the concrete must be poured to ACI standards; or 2) a liner applied (either from the approved equipment list or applied to NACE/SPCC standards); or 3) the containment must be designed by a PE. Facilities must provide documentation that the concrete was installed according to ACI standards, if this option is used. Note that ACI concrete must be mixed according to a formula which involves a monolith pour. Applied liners must be compatible to the product stored. For example, coal tar epoxies won't work with petroleum products. Look at the manufacturer's specifications for limitations on the product to be used. The PE must be registered in the State of Florida. See rule 762.701(1)(c)1 for upkeep and maintenance issues. | ||||||||||
01/10/2007 | Attachment | Kassees, Ramsey D. | |||||||||
01/10/2007 | Attachment | Kassees, Ramsey D. | |||||||||
12/01/2006 | Site Inspection Activity Closed | Kassees, Ramsey D. | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 12/01/2006 | ||||||||||
Activity Closed Date: | 01/10/2007 | Activity Closed By: | KASSEES_RP_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 01/09/2007 | User: | KASSEES_RP_1 | ||||||||
Description: | Violations Summary: There were three violations observed during the inspection. They were cited under two violation citations. They are collectively summarized as follows: 1). The secondary containment unit is severely compromised at the west end. Furthermore it is not adequately sealed. Please repair the damaged west end, thoroughly clean the entire unit. Patch all the cracks then reseal it using F D E P approved sealant. 2). The dispenser containment for pump # 4/5 is holding some product (about one inch). Please empty and clean the liner, then maintain all in similar manner (clean and dry). A non compliance letter citing the violations accompanies this inspection report. Please find it attached. Please provide our office with documentation confirming the resolution of the cited violations, within thirty days of receipt of this inspection report and attached non compliance letter. Additional Notes: The secondary containment unit is adequately sized. The hose on retail gas pump #2 is somewhat compromised (it is kinked). Please monitor the condition of the hose, and repair or replace it before a leak developes at the damaged portion. There are two other dispenser containment units that are holding slight amounts of Petroleum Contact Water (P C W). Please empty and clean them, then maintain all containment units empty and clean. Discharge Information: There is no new information or obvious evidence of recent release or discharge, within the last year. For more detailed discharge information, please consult the Petroleum Clean Up Section at the F D E P H.Q. in Tallahassee; or the F D E P Northeast District Office in Jacksonville; or the official compliance facility file at the Columbia C H D, Environmental Health Section, in Lake City. Other Comments: For more inspection details and information, please see the copy of the inspection field notes, site schematic and system description that is electronically, as well as physically, attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058. | ||||||||||
06/01/2005 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | TANK DISCHARGE INVESTIGATION | Activity Status: | Closed | ||||||||
Completion Notes: | DISCHARGE OCCURRED DUE TO CUSTOMER AT DISPENSER, NOT THRU EQUIPMENT FAILURE. REPORTED TO DEP EMERGENCY RESPONSE, JAMIE ROARLEO. CLEANUP BEGUN BY CREATIVE SOLUTIONS. | ||||||||||
05/17/2005 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
06/03/2004 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
05/29/2003 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
Completion Notes: | THE UNDERGROUND PORTION OF THE PIPING IS GREEN ENVIRON D/W FLEX | ||||||||||
05/16/2002 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
09/13/2001 | Legacy Activity | Defalco, Lynal | |||||||||
Activity Name: | RETURN TO COMPLIANCE FROM FORMAL ENFORCEMENT | Activity Status: | Closed | ||||||||
Completion Notes: | CASE CLOSED FULL PAYMENT RECEIVED FROM SFCO | ||||||||||
06/19/2001 | Legacy Activity | Dohaney, Tim | |||||||||
Activity Name: | PENALTY RECEIVED | Activity Status: | Closed | ||||||||
Completion Notes: | FULL PAYMENT RECEIVED $6,200 CASE CLOSED | ||||||||||
06/01/2001 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | TANK COMPLIANCE RE-INSPECTION | Activity Status: | Closed | ||||||||
05/10/2001 | Violation Closed | Sheffield, Cynthia K. | |||||||||
Significance: | SNC-A | Status: | Closed | ||||||||
Rule: | 510(3)(d) | ||||||||||
05/10/2001 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
05/02/2001 | Legacy Activity | Defalco, Lynal | |||||||||
Activity Name: | NON-COMPLIANCE LETTER ISSUED | Activity Status: | Closed | ||||||||
Completion Notes: | SEC.CONT NOT COATED, PIPING UPGRADES PERFORMED PEN. ASSESSED | ||||||||||
12/22/2000 | Violation Closed | Sheffield, Cynthia K. | |||||||||
Significance: | SNC-A | Status: | Closed | ||||||||
Rule: | 510(3)(d) | ||||||||||
12/22/2000 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | TANK INSTALLATION - FINAL INSPECTION | Activity Status: | Closed | ||||||||
05/25/2000 | Violation Closed | Sheffield, Cynthia K. | |||||||||
Significance: | SNC-A | Status: | Closed | ||||||||
Rule: | 510(3)(d) | ||||||||||
05/25/2000 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
05/25/2000 | Violation Closed | Sheffield, Cynthia K. | |||||||||
Significance: | SNC-B | Status: | Closed | ||||||||
Rule: | 600(1)(i) | ||||||||||
05/25/2000 | Violation Closed | Sheffield, Cynthia K. | |||||||||
Significance: | SNC-B | Status: | Closed | ||||||||
Rule: | 610(1)(a) | ||||||||||
04/22/1999 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | PROGRAM DISCRETION/NO ENFORCEMENT INITIATED | Activity Status: | Closed | ||||||||
01/27/1999 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | TANK INSTALLATION - FINAL INSPECTION | Activity Status: | Closed | ||||||||
04/21/1998 | Violation Closed | Unknown, User | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762 | ||||||||||
04/21/1998 | Legacy Activity | Sheffield, Cynthia K. | |||||||||
Activity Name: | AST ROUTINE COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||