DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/27/2025        Last Data Refresh: 04/26/2025        Report Generated from DOPPLER
 
Facility ID: 8510927
Facility Name: MOBIL-HOLMES BEACH #378
 
12/17/2024 Record Document Activity Shanberg, Vincent
Activity Status: Open
12/13/2024 Site Inspection Activity Open Shanberg, Vincent
Activity Status: Open
On-Site Start Date: 12/13/2024
Comments:
Comment Date: 12/13/2024 User: SHANBERG_VJ_1
Description: Facility ID#: 41 8510927 Inspection start date: 12/13/2024 Facility name: Mobil- Homes Beach #378 Complaint inspection Notes Received email from FDEP SW District on Site visit: 12/12/2024- Vincent Shanberg on-site at 10:am Met with business owner Mrs. Raham
09/05/2024 Editable Letter Activity hernandez, emmanuel
Activity Title: Warning Letter Activity Status: Closed
Description: 2021/09/07, Reply
Events:
Event Type: Activity/Document has been approved Date: 09/05/2024
Comment: Approved by Jayme Brock: Approved
Events:
Event Type: Activity has been submitted for approval Date: 09/05/2024
Comment: Submitted for approval by: emmanuel hernandez
Events:
Event Type: Activity has been finished Date: 01/07/2025
Comment: Finished
Attachments:
Attachment Date: 09/05/2024 User: HERNANDEZ_EMC
Description: WL24-181TK41SWD
View Attachment
08/01/2024 Enforcement Tracking Activity hernandez, emmanuel
Activity Status: Open
07/15/2024 Enforcement Referral Activity Shanberg, Vincent
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 08/01/2024
Events:
Event Type: Activity has been finished Date: 08/01/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 08/01/2024
Comment: Accepted by emmanuel hernandez: Accepted
Events:
Event Type: Activity has been submitted for approval Date: 07/15/2024
Comment: Submitted for approval by: Vincent Shanberg: Submitted for Approval
Events:
Event Type: Activity/Document was acknowledged on this date Date: 07/18/2024
Comment: Acknowledged and Assigned by Jayme Brock
Events:
Event Type: Activity has been assigned Date: 07/18/2024
Comment: Assigned to emmanuel hernandez
Comments:
Comment Date: 07/15/2024 User: SHANBERG_VJ_1
Description: Submitted for Approval
Attachments:
Attachment Date: 07/15/2024 User: SHANBERG_VJ_1
Description: 8510927_Mobil-Holmes Beach #378_MC Property Appraiser
View Attachment
Attachments:
Attachment Date: 07/15/2024 User: SHANBERG_VJ_1
Description: 8510927_Mobil-Holmes Beach #378_Sunbiz
View Attachment
Attachments:
Attachment Date: 07/15/2024 User: SHANBERG_VJ_1
Description: 8510927_Mobil-Holmes Beach #378_Enforcement Referral
View Attachment
04/12/2024 Attachment Trethewey, Mark B.
04/12/2024 Editable Letter Activity Trethewey, Mark B.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Description: Site plans
Events:
Event Type: Activity has been finished Date: 04/12/2024
Comment: Finished
Events:
Event Type: Document has been sent Date: 04/12/2024
Comment: Sent
Attachments:
Attachment Date: 04/12/2024 User: TRETHEWEY_MB_1
Description: CAO 2023-2024.057
View Attachment
04/12/2024 Violation Open Trethewey, Mark B.
Significance: SNC-B Status: Open
Criteria ID: 6060
Rule: 62-761.600(2), 62-761.600(2)(a), 62-761.600(2)(a)1, 62-761.600(2)(a)2, 62-761.600(2)(a)3, 62-761.600(2)(a)4, 62-761.600(2)(a)5, 62-761.600(2)(a)6, 62-761.600(2)(a)6.a, 62-761.600(2)(a)6.b, 62-761.600(2)(a)7, 62-761.600(2)(a)8
04/12/2024 Violation Open Trethewey, Mark B.
Significance: Minor Status: Open
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
04/12/2024 Violation Open Trethewey, Mark B.
Significance: Minor Status: Open
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
04/12/2024 Violation Open Trethewey, Mark B.
Significance: Minor Status: Open
Criteria ID: 6074
Rule: 62-761.710(1), 62-761.710(2), 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(3), 62-761.710(3)(a), 62-761.710(3)(b), 62-761.710(3)(c), 62-761.710(3)(d), 62-761.710(3)(e), 62-761.710(3)(f), 62-761.710(3)(g), 62-761.710(3)(h), 62-761.710(3)(i)
04/12/2024 Violation Open Trethewey, Mark B.
Significance: SNC-B Status: Open
Criteria ID: 6061
Rule: 62-761.600(3), 62-761.600(3)(a), 62-761.600(3)(b), 62-761.600(3)(b)1, 62-761.600(3)(b)2, 62-761.600(3)(b)3
04/10/2024 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 04/10/2024
Activity Closed Date: 04/12/2024 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 04/12/2024
Comment: Finished
Comments:
Comment Date: 04/12/2024 User: TRETHEWEY_MB_1
Description: RECORDS: #8510927, 4/10/2024 Placard: #667809; issued 7/6/2023, 2 tanks listed. Financial Responsibility: ACE Insurance, 2/6/2024 – 2/6/2025. CoFR: Provided with FR. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical line leak detectors are used for the primary piping along with monthly visual inspections of the tank interstice, double walled fills, dispensers/liners, and STP sumps. b. Facility’s monthly release detection results: Reviewed some monthly visual inspection records from 7/20/2022 to 3/19/2024. Visual inspections include the dispensers/liners, DW fills, STP sumps with tank and spill bucket interstitials. Release detection records were not provided for 11/2023 to 2/2024, 2/2023 to 6/2023, 9/2022 to 12/2022 8/2022 and none prior to 7/20/2022. Ensure that all records are retained for at least three years for review. Tests: a. Annual or periodic test results: 1. The last annual operability test of the mechanical line leak detectors provided was conducted on 9/28/2020 by Hy-Tech Petroleum Maintenance, Inc., The next tests were due by 9/28/2021, 9/28/2022 and 9/28/2023. Tests were not provided. Immediately provide Manatee County PNRD with copies of the required documents. 2. The last annual operability test of the overfill protection devices provided was conducted on 9/28/2020 by Hy-Tech Petroleum Maintenance, Inc., The next tests were due by 9/28/2021, 9/28/2022 and 9/28/2023. Tests were not provided. Immediately provide Manatee County PNRD with copies of the required documents. 3. Integrity tests of the Double walled spill buckets (vacuum) were conducted on 9/22/2021 by Hy-Tech Petroleum Maintenance, Inc., all passed. The next tests are due by 9/22/2024. 4. Integrity tests of the sumps and liners (hydrostatic) were conducted on 9/22/2021 by Hy-Tech Petroleum Maintenance, Inc., all passed. The next tests are due by 9/22/2024. PHYSICAL: Interstice: The Regular tank interstice contains approximately 16 inches of water; the release detection record of 109/2023 indicates one inch of water. Immediately remove all water and continue monitoring this interstice. If water reoccurs submit an INF and investigate the cause. The Premium interstice was not checked. STP Sumps: Both sumps contain PCW over one inch. Immediately remove and properly dispose of all PCW. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. The liner of dispenser 1/2 contains PCW less than one inch, recommend removal at time of other water removal. Fills: Covers are properly painted. Both interstitial are dry. Shear Valves: All shear valves are rigidly anchored.
04/03/2024 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Ali Ghasemi Activity Closed Date: 04/12/2024
Events:
Event Type: Activity has been finished Date: 04/12/2024
Comment: Finished
Attachments:
Attachment Date: 04/12/2024 User: TRETHEWEY_MB_1
Description: 4/3/2024 Notification Letter
View Attachment
07/31/2022 Meeting Activity Pedigo, Leslie
Activity Closed Date: 07/31/2022 Activity Status: Closed
Location: FDEP/SWD
Subject: See attached meeting agenda with meeting notes.
Events:
Event Type: Activity has been finished Date: 07/31/2022
Comment: Finished
Attachments:
Attachment Date: 07/31/2022 User: PEDIGO_L
Description: 8/6/2018 Meeting Agenda with Meeting Notes
View Attachment
01/21/2022 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/21/2022
Activity Closed Date: 01/24/2022 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 01/24/2022
Comment: Finished
Comments:
Comment Date: 01/21/2022 User: TRETHEWEY_MB_1
Description: RECORDS: #8510927, 1/21/2022 Unresolved Violations Cited at Compliance Inspection 11/15/2021: 1. Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2 Violation Text: Spill containment, dispenser liners, and piping sumps not accessible. Water or regulated substances not removed. Explanation: Both sumps contain PCW over one inch. All dispenser liners contain PCW over one inch. Corrective Action: Immediately remove and properly dispose of all PCW. Corrective Action Taken: Yes. Re-inspection confirms all PCW has been removed. PHYSICAL: STP Sumps: All PCW has been removed. Sumps are currently dry. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All PCW has been removed. Liners are are currently dry. NOTE: Facility has recently been purchased by former leasee. Ensure that Financial Responsibility is obtained within 90 days. Continue performing monthly visual inspections. A STRF has been sent for update. COMPLIANCE ASSISTANCE INSPECTION ONLY. Certain records and equipment associated with routine compliance inspections were not checked.
01/21/2022 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Ali Ghasemi Activity Closed Date: 01/21/2022
Events:
Event Type: Activity has been finished Date: 01/21/2022
Comment: Finished
Attachments:
Attachment Date: 01/21/2022 User: TRETHEWEY_MB_1
Description: 1/21/2022 Return to Compliance Letter
View Attachment
12/08/2021 Record Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 01/04/2022
Events:
Event Type: Activity has been finished Date: 01/04/2022
Comment: Finished
Attachments:
Attachment Date: 01/04/2022 User: TRETHEWEY_MB_1
Description: Received repair documents for DW Spill Buckets
View Attachment
Attachments:
Attachment Date: 01/04/2022 User: TRETHEWEY_MB_1
Description: Received passing tests performed on 9/22/2021
View Attachment
11/18/2021 Attachment Trethewey, Mark B.
11/18/2021 Electronic Communication Activity Trethewey, Mark B.
Activity Closed Date: 11/18/2021 Activity Status: Closed
Date: 11/18/2021
Recipient: Mark Trethewey
Sender: Mike Bateman
Subject: Agreed to reschedule
Message: Mark, I received your schedule request from Rick. Our schedule does not coincide with the dates you listed. Maybe you could rearrange your schedule with the following: • Nov 15 Monday - Meet at Skyway Marathon at 9:00, then go to Terra Ceia, Save On Citgo, Rivers Edge, Manatee Citgo, In & Out Marathon, Bradenton Mobil, and Holmes Beach. • Nov 18 Thursday - Meet at Lucky Mobil (closed) at 9:00. Let me know if you can make this work, thanks. Michael R. Bateman, P.G. Hy-Tech Environmental Services, Inc. o. (813)719-1596
Events:
Event Type: Activity has been finished Date: 11/18/2021
Comment: Finished
11/18/2021 Editable Letter Activity Trethewey, Mark B.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 11/18/2021
Comment: Sent
Events:
Event Type: Activity has been finished Date: 11/18/2021
Comment: Finished
Attachments:
Attachment Date: 11/18/2021 User: TRETHEWEY_MB_1
Description: COA 2021-2022.037
View Attachment
11/18/2021 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
11/18/2021 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
11/18/2021 Violation Closed Trethewey, Mark B.
Significance: SNC-B Status: Closed
Criteria ID: 6061
Rule: 62-761.600(3), 62-761.600(3)(a), 62-761.600(3)(b), 62-761.600(3)(b)1, 62-761.600(3)(b)2, 62-761.600(3)(b)3
11/18/2021 Violation Closed Trethewey, Mark B.
Significance: SNC-B Status: Closed
Criteria ID: 6057
Rule: 62-761.600(1)(f), 62-761.600(1)(f)1
11/15/2021 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 11/15/2021
Activity Closed Date: 11/18/2021 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 11/18/2021
Comment: Finished
Comments:
Comment Date: 11/18/2021 User: TRETHEWEY_MB_1
Description: RECORDS: #8510927, 11/15/2021 Placard: #613096; issued 6/22/2021, 2 tanks listed. Financial Responsibility: Valley Bank, Letter of Credit, 5/31/2020 - 1/31/2022. CoFR: Provided with FR. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical line leak detectors are used for the primary piping along with monthly visual inspections of the tank interstice, double walled fills, dispensers/liners, and STP sumps. b. Facility’s monthly release detection results: Reviewed the monthly visual inspection records from 7/16/2019 to 6/15/2021. Visual inspections include the dispensers/liners, DW fills, and STP sumps. Release detection was performed at least once a month not exceeding 35 days apart. NOTE: Records for 7/2021, 8/2021, 9/2021 and 10/2021 were not included the records provided. Ensure that all records are available for review. Tests: a. Annual or periodic test results: 1. The last annual operability test of the mechanical line leak detectors provided was conducted on 9/28/2020 by Hy-Tech Petroleum Maintenance, Inc., all passed. The next tests were due by 9/28/2021. Tests were not provided. Immediately provide Manatee County PNRD with copies of the required documents. Tests for 10/4/2019 were also provided. 2. The last annual operability test of the overfill protection devices provided was conducted on 9/28/2020 by Hy-Tech Petroleum Maintenance, Inc., all passed. The next tests were due by 9/28/2021. Tests were not provided. Immediately provide Manatee County PNRD with copies of the required documents. Tests for 10/4/2019 were also provided. 3. Integrity tests of the Double walled spill buckets (vacuum) were conducted on 10/12/2018 by Hy-Tech Petroleum Maintenance, Inc., all passed. The next tests were due by 10/12/2021. Tests were not provided. Immediately provide Manatee County PNRD with copies of the required tests. 4. Integrity tests of the sumps and liners (hydrostatic) were conducted on 10/12/2018 by Hy-Tech Petroleum Maintenance, Inc., all passed. The next tests were due by 10/12/2021. Tests were not provided. Immediately provide Manatee County PNRD with copies of the required tests. PHYSICAL: Interstice: Tank interstitials are dry. STP Sumps: Both sumps contain PCW over one inch. Immediately remove and properly dispose of all PCW. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners contain PCW over one inch. Immediately remove and properly dispose of all PCW. Fills: Covers are properly painted. Both interstitial ports are open to the environment, Regular interstitial has ½ inch of water, Premium interstitial has 1 ½ inches of water. Remove water& cap ports. Continue monitoring to ensure integrity. If water returns after securing ports, submit an INF and test spill buckets. Fills are unobstructed. Shear Valves: All shear valves are rigidly anchored.
10/12/2021 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 11/18/2021
Events:
Event Type: Activity has been finished Date: 11/18/2021
Comment: Finished
Attachments:
Attachment Date: 11/18/2021 User: TRETHEWEY_MB_1
Description: 10/12/2021 Notification Letter
View Attachment
01/08/2020 Attachment Trethewey, Mark B.
10/03/2019 Record Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 10/03/2019
Events:
Event Type: Activity has been finished Date: 10/03/2019
Comment: Finished
10/03/2019 Record Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 10/03/2019
Events:
Event Type: Activity has been finished Date: 10/03/2019
Comment: Finished
Attachments:
Attachment Date: 10/03/2019 User: TRETHEWEY_MB_1
Description: Received verification of PCW removal.
View Attachment
10/03/2019 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 10/03/2019
Events:
Event Type: Activity has been finished Date: 10/03/2019
Comment: Finished
Attachments:
Attachment Date: 10/03/2019 User: TRETHEWEY_MB_1
Description: 10/3/2019 Return to Compliance Letter
View Attachment
09/06/2019 Record Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 09/06/2019
Events:
Event Type: Activity has been finished Date: 09/06/2019
Comment: Finished
Attachments:
Attachment Date: 09/06/2019 User: TRETHEWEY_MB_1
Description: records & tests
View Attachment
Attachments:
Attachment Date: 09/06/2019 User: TRETHEWEY_MB_1
Description: records & tests
View Attachment
08/16/2019 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 4057
Rule: 62-761.500(7)(e)
08/16/2019 Electronic Communication Activity Trethewey, Mark B.
Activity Closed Date: 08/16/2019 Activity Status: Closed
Date: 08/16/2019
Recipient: Mark Trethewey
Sender: Michael Bateman
Subject: Reschedule
Message: Mark, We are scheduled to do these locations on August 15th. If you can change your inspection to that date we can meet you at Skyway Marathon at 9:00. Let me know if that works for you. Michael R. Bateman, P.G. Hy-Tech Environmental Services, Inc. o. (813)719-1596
Events:
Event Type: Activity has been finished Date: 08/16/2019
Comment: Finished
08/16/2019 Editable Letter Activity Trethewey, Mark B.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/16/2019
Comment: Finished
Events:
Event Type: Document has been sent Date: 08/16/2019
Comment: Sent
Attachments:
Attachment Date: 08/16/2019 User: TRETHEWEY_MB_1
Description: CAO 2019-2020.007
View Attachment
08/16/2019 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 4078
Rule: 62-761.710(1)
08/16/2019 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 4077
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1., 62-761.700(3)(b)2.
08/16/2019 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
08/16/2019 Violation Closed Trethewey, Mark B.
Significance: SNC-B Status: Closed
Criteria ID: 4066
Rule: 62-761.600(3), 62-761.600(3)(a), 62-761.600(3)(b), 62-761.600(3)(b)1., 62-761.600(3)(b)2., 62-761.600(3)(b)3.
08/15/2019 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 08/15/2019
Activity Closed Date: 08/16/2019 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 08/16/2019
Comment: Finished
Comments:
Comment Date: 08/16/2019 User: TRETHEWEY_MB_1
Description: RECORDS: #8510927, 8/15/2019 Placard: #561342; issued 6/19/2019, 2 tanks listed. Financial Responsibility: Last provided, Letter of Credit, 5/31/2018 - 5/31/2019.Current FR not provided. Immediately provide Manatee County PNRD with copies of the required documents. CoFR: Not provided. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical line leak detectors are used for the primary piping along with monthly visual inspections of the tank interstice, double walled fills, dispensers/liners, and STP sumps. b. Facility’s monthly release detection results: 1. The monthly visual inspection records 4/17/2017 to present were not provided. Immediately provide Manatee County PNRD with copies of the required documents. Tests: a. Annual or periodic test results: 1. The last annual operability test of the mechanical line leak detectors provided was conducted on10/20/2016 by Hy-Tech Petroleum Maintenance, Inc., all passed. The next tests were due by 10/20/2017 and 10/20/2018. Tests were not provided. Immediately provide Manatee County PNRD with copies of the required documents. 2. Double walled spill buckets must be integrity tested by October 13, 2018 and every 3 years thereafter. Tests were not provided. Immediately provide Manatee County PNRD with copies of the required documents. 3. Sumps and liners must be integrity (hydrostatically) tested by October 13, 2018 and every 3 years thereafter. Tests were not provided. Immediately provide Manatee County PNRD with copies of the required documents. 4. Overfill protection devices must be tested for operability prior to January 11, 2018 and every 12 months thereafter Tests were not provided. Immediately provide Manatee County PNRD with copies of the required documents. PHYSICAL: Interstice: Tank interstitials are dry. STP Sumps: Both sumps contain PCW over one inch. Immediately remove and properly dispose of all PCW. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners contain PCW over one inch. Immediately remove and properly dispose of all PCW. Fills: Covers are properly painted. Both interstitial ports are open to the environment, Regular interstitial has minor condensation. Recommend securing the interstitial ports. Fills are unobstructed. Shear Valves: All shear valves are rigidly anchored.
08/02/2019 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 08/16/2019
Events:
Event Type: Activity has been finished Date: 08/16/2019
Comment: Finished
Attachments:
Attachment Date: 08/16/2019 User: TRETHEWEY_MB_1
Description: 8/2/2019 Notification Letter
View Attachment
08/06/2018 Issue Document Activity Pedigo, Leslie
Activity Status: Closed
Contact Name: Leslie Pedigo, FDEP/SWD Activity Closed Date: 07/31/2022
Events:
Event Type: Activity has been finished Date: 07/31/2022
Comment: Finished
Attachments:
Attachment Date: 07/31/2022 User: PEDIGO_L
Description: Case Closure Memo
View Attachment
06/13/2018 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 06/13/2018
Events:
Event Type: Activity has been finished Date: 06/13/2018
Comment: Finished
Attachments:
Attachment Date: 06/13/2018 User: TRETHEWEY_MB_1
Description: 6-13-2018 Return to Compliance Letter
View Attachment
06/13/2018 Document Management Activity Trethewey, Mark B.
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/13/2018
Comment: Finished
Attachments:
Attachment Date: 06/13/2018 User: TRETHEWEY_MB_1
Description: 12-26-2017 INF
View Attachment
06/12/2018 Record Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 06/13/2018
Events:
Event Type: Activity has been finished Date: 06/13/2018
Comment: Finished
Attachments:
Attachment Date: 06/13/2018 User: TRETHEWEY_MB_1
Description: Verification of PCW removal.
View Attachment
06/11/2018 Issue Document Activity Pedigo, Leslie
Activity Status: Closed
Contact Name: William McKnight, Automated Petroleum & Energy Company, Inc. Activity Closed Date: 07/31/2022
Events:
Event Type: Activity has been finished Date: 07/31/2022
Comment: Finished
Attachments:
Attachment Date: 07/31/2022 User: PEDIGO_L
Description: 6/11/2018 Warning Letter #WL18-38TK-Multi-SWD
View Attachment
01/09/2018 Incident Activity Trethewey, Mark B.
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 01/09/2018
Events:
Event Type: Activity has been finished Date: 01/09/2018
Comment: Finished
Comments:
Comment Date: 01/09/2018 User: TRETHEWEY_MB_1
Description: Water in interstice was discovered at annual inspection. INF was requested at that time. INF was received 12/27/2017. Water in interstice was removed and cap was secured.
Attachments:
Attachment Date: 01/09/2018 User: TRETHEWEY_MB_1
Description: 12-26-2017 INF
View Attachment
01/05/2018 Enforcement Tracking Activity Pedigo, Leslie
OGC Case Number: 190008 Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 07/31/2022
Events:
Event Type: Activity has been finished Date: 07/31/2022
Comment: Finished
12/07/2017 Editable Letter Activity Trethewey, Mark B.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 12/07/2017
Comment: Finished
Events:
Event Type: Document has been sent Date: 12/07/2017
Comment: Sent
Attachments:
Attachment Date: 12/07/2017 User: TRETHEWEY_MB_1
Description: CAO 2017-2018.030
View Attachment
12/07/2017 Enforcement Referral Activity Trethewey, Mark B.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 01/05/2018
Events:
Event Type: Activity has been finished Date: 01/05/2018
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 01/05/2018
Comment: Accepted by Leslie Pedigo: OK
Events:
Event Type: Activity/Document was acknowledged on this date Date: 12/07/2017
Comment: Acknowledged and Assigned by Laurel Culbreth
Events:
Event Type: Activity has been assigned Date: 12/07/2017
Comment: Assigned to Leslie Pedigo
Events:
Event Type: Activity has been submitted for approval Date: 12/07/2017
Comment: Submitted for approval by: Mark B. Trethewey: Violations open greater than 90 days. No action taken.
Comments:
Comment Date: 12/07/2017 User: TRETHEWEY_MB_1
Description: Violations open greater than 90 days. No action taken.
Attachments:
Attachment Date: 01/09/2018 User: TRETHEWEY_MB_1
Description: SITE MAP 8510927
View Attachment
Attachments:
Attachment Date: 01/09/2018 User: TRETHEWEY_MB_1
Description: Prop Appr Info
View Attachment
Attachments:
Attachment Date: 01/09/2018 User: TRETHEWEY_MB_1
Description: ER Memo 1-4-2018
View Attachment
Attachments:
Attachment Date: 01/09/2018 User: TRETHEWEY_MB_1
Description: Corp Info
View Attachment
12/06/2017 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 12/06/2017
Activity Closed Date: 12/07/2017 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 12/07/2017
Comment: Finished
Comments:
Comment Date: 12/07/2017 User: TRETHEWEY_MB_1
Description: RECORDS: #8510927, 12/6/2017 Placard: #509489; issued 6/13/2017, 2 tanks listed. Financial Responsibility: Nautilus Insurance; 12/31/2016 - 12/31/2017. Violation Cited at Compliance Inspection 4/7/2017, remained open at TCR of 12/6/2017: 1. Type: Violation Significance: Minor Rule: 62-761.450(2)(a)7., 62-761.450(2)(a)6., 62-761.450(2)(a)5., 62-761.450(2)(a)4., 62-761.450(2)(a)3., 62-761.450(2)(a)2., 62-761.450(2)(a)1. Violation Text: Incident not reported within 24-hours or by next business day. Explanation: The Premium interstitial was found to have 5 inches of water at inspection. Corrective Action: Immediately investigate cause of interstitial breach. Remove all water from interstice. File an INF with findings. Corrective Action Taken: No. An INF was not submitted. Unknown if the issue was addressed in a timely manner, unknown cause of intrusion. NOTE: re-inspection confirms removal of water from the interstice, level is currently at 1 ½ inches.This is probably due to recharge. Recommend repumping interstice as needed. 2. Type: Violation Rule: 62-761.700(1)(c)1. Significance: Minor Violation Text: Spill containment, dispenser liners and piping sumps accessible; water and regulated substances not removed. Explanation: The Regular and Premium sumps contain PCW greater than one inch. Corrective Action: Immediately remove and properly dispose of all PCW. Corrective Action Taken: No. PCW remains in the Regular and Premium sumps, six inches in the Regular and two inches in the Premium. NOTE new test requirements: • Double walled spill buckets must be integrity tested by October 13, 2018 and every 3 years thereafter. • Single walled spill buckets must be integrity (hydrostatically) tested by January 11, 2018 and every 12 months thereafter. • Sumps must be integrity (hydrostatically) tested by March 13, 2018 and every 3 years thereafter. • Overfill protection devices must be tested for operability prior to January 11, 2018 and every 12 months thereafter. If a ball float fails, the operability test it cannot be replaced with another ball float. All ball floats must be replaced with an approved overfill device by October 13, 2018. RE-INSPECTION ONLY. Certain records and equipment associated with routine compliance inspections were not checked.
05/19/2017 Record Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 05/19/2017
Events:
Event Type: Activity has been finished Date: 05/19/2017
Comment: Finished
05/19/2017 Record Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 05/19/2017
Events:
Event Type: Activity has been finished Date: 05/19/2017
Comment: Finished
04/12/2017 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
04/12/2017 Editable Letter Activity Trethewey, Mark B.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 04/12/2017
Comment: Finished
Attachments:
Attachment Date: 04/12/2017 User: TRETHEWEY_MB_1
Description: NCL 2016-2017.036
View Attachment
04/12/2017 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 1010
Rule: 62-761.450(2)(a)1., 62-761.450(2)(a)2., 62-761.450(2)(a)3., 62-761.450(2)(a)4., 62-761.450(2)(a)5., 62-761.450(2)(a)6., 62-761.450(2)(a)7.
Comments: Multiple incidents occurring at the same time at the facility may be reported on one form. #1-3 - Evidence of these types of INF situations are generally found during the inspector's paperwork review. Ask the facility representative what action they took in response, and in what time frame. If the situations are resolved within 24 hours, the owner/operator is not required to submit an INF to the local program. However, the actions they took to resolve the issue must be documented. #4-5, and 7 - Evidence of these types of situations are generally found during the outside or physical portion of the inspection. Give the facility owner/operator 24 hours to resolve, provided they document their actions. If they can not resolve the issues then they must submit the INF, at which time the two week investigative window opens. #6 - Evidence of this type of situation may be found during the physical examination of the release detection device (e.g. alarm mode), or during the examination of the records associated with the method. Note: Inspectors may find events that qualify as incidents during their review of the facility's paperwork. Such issues must have been resolved within 24 hours if an INF was not submitted at the time of the event.
04/12/2017 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 1122
Rule: 62-761.710(1)
Comments: Was reasonable access to the facility granted? If not, document the circumstances. Were the records available within the specified time frame? If five day pre-inspection notice was not given by the inspector, this item can not be marked as a discrepancy. Make note of the missing documents, and arrange a review period.
04/12/2017 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 1103
Rule: 62-761.640(4)(a)1., 62-761.640(4)(a)2., 62-761.640(4)(a)3., 62-761.640(4)(a)4.
Comments: Installation - verify that the line leak detector has been installed during the final installation inspection. Compliance - check to see that the unit is present. Examine the annual function test data - a pass alone is not sufficient. The tester must demonstrate 3.0 gph discharge detection for the mechanical (flow restrictor). Note that the electronic (auto shut off) line leak detector does not need an annual test, but must still be able to detect a 0.2 gph leak after it has been tripped at 150% line operating pressure. Replacements - unit must be tested out of the box - function must be proven. 3.0 gph = 185.4 ml/min (To convert milliliters/minute to gallons/hour, multiple the milliliters by 0.0162162; or, 1 gph equals 61.8 ml/min). Values greater than 186 ml/min fail. Values less than 185 ml/min mean that the line leak detector will activate at a more restrictive rate.
04/11/2017 Electronic Communication Activity Trethewey, Mark B.
Activity Closed Date: 04/11/2017 Activity Status: Closed
Date: 04/11/2017
Recipient: Mark Trethewey
Sender: Rick Herweh
Subject: TCI reschedule after no-show
Message: Received request for April reschedule.
Events:
Event Type: Activity has been finished Date: 04/11/2017
Comment: Finished
04/11/2017 Electronic Communication Activity Trethewey, Mark B.
Activity Closed Date: 04/11/2017 Activity Status: Closed
Date: 04/11/2017
Recipient: Mark Trethewey
Sender: Mike Bateman
Subject: TCI reschedule after no-show
Message: Confirmed TCIs for 4/7/2017. Rick also CCed
Events:
Event Type: Activity has been finished Date: 04/11/2017
Comment: Finished
04/11/2017 Electronic Communication Activity Trethewey, Mark B.
Activity Closed Date: 04/11/2017 Activity Status: Closed
Date: 04/11/2017
Recipient: Rick Herweh
Sender: Mark Trethewey
Subject: TCI reschedule after no-show
Message: Good morning Rick, Let me know the soonest we can reschedule. Please forward any paperwork for review.
Events:
Event Type: Activity has been finished Date: 04/11/2017
Comment: Finished
04/07/2017 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/07/2017
Activity Closed Date: 04/12/2017 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 04/12/2017
Comment: Finished
Comments:
Comment Date: 04/12/2017 User: TRETHEWEY_MB_1
Description: RECORDS: #8510927, 4/7/2017 Placard: #490866; issued 7/8/2016, 2 tanks listed Financial Responsibility: Last provided, Liberty Surplus Insurance Corp., 12/31/2014 - 12/31/2015. Current FR not provided. Immediately provide Manatee County PNRD with copies of the required documents. CoFR: Not provided. New forms required upon expiration. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical line leak detectors are used for the primary piping along with monthly visual inspections of the tank interstice, double walled fills, dispensers/liners, and STP sumps. b. Facility’s monthly release detection results: 1. The monthly visual inspection records 3/16/2015 to present were not provided. Immediately provide Manatee County PNRD with copies of the required documents. Tests: a. Annual or periodic test results: 1. The last annual operability test of the mechanical line leak detectors provided was conducted on10/24/2014 by Hy-Tech Petroleum Maintenance, Inc. All passed. The next test was due by 10/24/2015 and 10/24/2016. Immediately provide Manatee County PNRD with copies of the required documents. 2. Breach of Integrity tests were performed on 10/26/2012 by Hy-Tech Petroleum Maintenance, Inc. All systems passed. Breach of Integrity testing every five years is no longer required for shop fabricated double wall systems. NOTE new test requirements: • Double walled spill buckets must be integrity tested by October 13, 2018 and every 3 years thereafter. • Single walled spill buckets must be integrity (hydrostatically) tested by January 11, 2018 and every 12 months thereafter. • Sumps must be integrity (hydrostatically) tested by March 13, 2018 and every 3 years thereafter. • Overfill protection devices must be tested for operability prior to January 11, 2018 and every 12 months thereafter. If a ball float fails the operability test it cannot be replaced with another ball float. All ball floats must be replaced with an approved overfill device by October 13, 2018. PHYSICAL: Interstice: The Premium interstice contains five inches of water. Immediately investigate the cause, submit an INF if not resolved within 72 hours. The Regular tank interstitial is dry. STP Sumps: Both sumps contain PCW over one inch. Immediately remove and properly dispose of all PCW. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners are dry. Fills: Covers are properly painted. Both interstitial ports are open to the environment, Regular interstitial has minor condensation. Recommend securing the interstitial ports. Fills are unobstructed. See test requirements above. Shear Valves: All shear valves are rigidly anchored.
02/09/2017 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 04/11/2017
Events:
Event Type: Activity has been finished Date: 04/11/2017
Comment: Finished
04/17/2015 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 04/17/2015
Events:
Event Type: Activity has been finished Date: 04/17/2015
Comment: Finished
04/13/2015 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/13/2015
Activity Closed Date: 04/17/2015 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 04/17/2015
Comment: Finished
Comments:
Comment Date: 04/17/2015 User: TRETHEWEY_MB_1
Description: RECORDS: #8510927, 4/13/2015 Placard: #430715; issued 6/19/2014, 2 tanks listed Financial Responsibility: Liberty Surplus Insurance Corp., 12/31/2014 - 12/31/2015. CoFR: Available, complete, and accurate. RDRL: With Release Detection Records. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical line leak detectors are used for the primary piping along with monthly visual inspections of the tank interstice, double walled fills, dispensers/liners, and STP sumps. b. Facility¿s monthly release detection results: 1. Reviewed the monthly visual inspection records from 9/11/2013 to 3/16/2015. Inspections include the condition of the tank interstice, DW fills, dispensers, liners, and STP sumps. Release detection was performed at least once per month not exceeding 35 days apart. Tests: a. Annual or periodic test results: 1. The annual operability test of the mechanical line leak detectors was conducted on 10/24/2014 by Hy-Tech Petroleum Maintenance, Inc. All passed. The next test is due by 10/24/2015. Passing tests were also provided for 10/24/2013. 2. Breach of Integrity tests were performed on 10/26/2012 by Hy-Tech Petroleum Maintenance, Inc. All systems passed. Next tests are due by 10/26/2017. PHYSICAL: Interstice: Both tanks interstitials are dry. STP Sumps: The Premium sump contains minor PCW. Recommend the removal and proper disposal of PCW at next maintenance event. The Regular sump is dry. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners are dry. Fills: Covers are properly painted. Fills are unobstructed. The Premium interstice is open to the environment, both appear dry. Recommend securing the interstitial port. Shear Valves: All shear valves are rigidly anchored.
10/18/2013 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 10/18/2013
Events:
Event Type: Activity has been finished Date: 10/18/2013
Comment: Finished
10/15/2013 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/15/2013
Activity Closed Date: 10/18/2013 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 10/18/2013
Comment: Finished
Comments:
Comment Date: 10/18/2013 User: TRETHEWEY_MB_1
Description: RECORDS: #8510927, 10/15/2013 Placard: #398301; issued 7/6/2012, 2 tanks listed Financial Responsibility: Liberty Surplus Insurance Corp., 12/31/2012 - 12/31/2013. CoFR: Available, complete, and accurate. RDRL: With Release Detection Records. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical line leak detectors are used for the primary piping along with monthly visual inspections of the tank interstice, double walled fills, dispensers/liners, and STP sumps. b. Facility¿s monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period 11/12/2012 through 9/11/2013. Visual inspections include the condition of the tank interstice, DW fills, dispensers, liners, and STP sumps. Release detection was performed at least once per month not exceeding 35 days apart. Tests: a. Annual or periodic test results: 1. The annual operability test of the mechanical line leak detectors was conducted on 10/26/2012 by Hy-Tech Petroleum Maintenance, Inc. All passed. The next test is due by 10/26/2013. 2. Breach of Integrity tests are not required due to tanks submersion in groundwater. Buoyancy calculations were supplied at installation. PHYSICAL: Interstice: Both tanks interstitials are dry. STP Sumps: The Regular and Premium sumps contain minor PCW. Recommend the removal and proper disposal of PCW at next maintenance event. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners are dry. There is damage to the panel of dispenser 1/2. Recommend repairs to the panel to limit exposure to the elements. Fills: Covers are properly painted. Fills are locked. Both interstices are open to the environment, both appear dry. Recommend securing the interstitial ports Shear Valves: All shear valves are rigidly anchored.
12/28/2012 Editable Letter Activity Trethewey, Mark B.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 12/28/2012
Comment: Finished
Attachments:
Attachment Date: 12/28/2012 User: TRETHEWEY_MB_1
Description: NCL 2012-2013.018
View Attachment
12/18/2012 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
12/18/2012 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 12/18/2012
Activity Closed Date: 12/28/2012 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 12/28/2012
Comment: Finished
Comments:
Comment Date: 12/28/2012 User: TRETHEWEY_MB_1
Description: RECORDS: #8510927, 12/18/2012 Placard: #398301; issued 7/6/2012, 2 tanks listed Financial Responsibility: Liberty Surplus Insurance Corp., 12/31/2011 - 12/31/2012. CoFR: Available, complete, and accurate. RDRL: With Release Detection Records. Release Detection: a.This Facility has the following release detection methods: 1.Mechanical line leak detectors are used for the primary piping along with monthly visual inspections of the tank interstice, double walled fills, dispensers/liners, and STP sumps. b. Facility¿s monthly release detection results: 1.Reviewed the monthly visual inspection records for the time period 1/12/2012 through 11/12/2012. Visual inspections include the condition of the tank interstice, DW fills, dispensers, liners, and STP sumps. Release detection was performed at least once per month not exceeding 35 days apart. Tests: a. Annual or periodic test results: 1.The annual operability test of the mechanical line leak detectors was conducted on 10/26/2012 by Hy-Tech Petroleum Maintenance, Inc. All passed. The next test is due by 10/26/2013. 2.Breach of Integrity tests are not required due to tanks submersion in groundwater. Buoyancy calculations were supplied at installation. PHYSICAL: Interstice: Both tanks interstitials are dry. STP Sumps: The Regular sump contains water over the piping; the Premium sump contains minor PCW. Immediately remove and properly dispose of all PCW. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners are dry. Fills: Covers are properly painted. Fills are locked. Both interstices are open to the environment, the Regular is dry, the Premium is full of PCW. Recommend removal of PCW, testing the spill buckets and securing the interstitial ports Shear Valves: All shear valves are rigidly anchored.
02/13/2012 Record Document Activity Mason, Steve
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 02/13/2012
Events:
Event Type: Activity has been finished Date: 02/13/2012
Comment: Finished
Comments:
Comment Date: 02/13/2012 User: MASON_RS_1
Description: Service call report detailing removal of water in sumps received by Manatee County NRD on 02/03/2012.
01/24/2012 Editable Letter Activity Mason, Steve
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/24/2012
Comment: Finished
Attachments:
Attachment Date: 01/24/2012 User: MASON_RS_1
Description: NCL 2011-2012.024
View Attachment
01/17/2012 Site Inspection Activity Closed Mason, Steve
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/17/2012
Activity Closed Date: 01/24/2012 Activity Closed By: MASON_RS_1
Events:
Event Type: Activity has been finished Date: 01/24/2012
Comment: Finished
Comments:
Comment Date: 01/20/2012 User: MASON_RS_1
Description: RECORDS: #8510927, 1/17/2012 Placard: #377242; issued 7/8/2011, 2 tanks listed Financial Responsibility: Liberty Surplus Insurance Corp., 12/31/2011 - 12/31/2012 CoFR: Available, complete, and accurate RDRL: With Release Detection Records Release Detection: a. This Facility has the following release detection methods: 1. Mechanical line leak detectors are used for the primary piping along with monthly visual inspections of the tank interstice, double walled fills, dispensers/liners, and STP sumps. b. Facility's monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period 12/10/2010 through 12/15/2011. Visual inspections include the condition of the tank interstice, DW fills, dispensers/liners, and STP sumps. Release detection was performed at least once per month and did not exceed 35 days apart. Tests: a. Annual or periodic test results: 1. An annual operability test of the mechanical line leak detectors was conducted on 10/27/2011 by Hy-Tech Petroleum Maintenance, Inc. The next test is due by 10/27/2012. PHYSICAL: STP Sumps: Both sumps contain water over the piping. Recommend immediate removal of this water and monitor for any problems related to the integrity of the sumps. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners are clean and dry. Fills: Covers are properly painted. Fills are locked. The Regular spill bucket contains water. Recommend removal of this water at the next maintenance event. The Premium spill bucket is dry. Shear Valves: All shear valves are rigidly anchored. Tank Interstice: The Regular tank interstitial space is dry. Unable to access the Premium interstitial; however, release detection results indicate no problems.
01/28/2011 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
Comments:
Comment Date: 01/20/2012 User: MASON_RS_1
Description: Water present at 01/17/2012 Annual Compliance Inspection. Water needs to be removed immediately.
01/28/2011 Editable Letter Activity Trethewey, Mark B.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/28/2011
Comment: Finished
Attachments:
Attachment Date: 01/28/2011 User: TRETHEWEY_MB_1
Description: NCL 2010-2011.051
View Attachment
01/28/2011 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/26/2011
Activity Closed Date: 01/28/2011 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 01/28/2011
Comment: Finished
Comments:
Comment Date: 01/28/2011 User: TRETHEWEY_MB_1
Description: RECORDS: # 8510927, 1/26/2011 Placard: #352286; issued 7/13/2011, 2 tanks listed. Financial Responsibility: Liberty Surplus, 12/31/2010 ¿ 12/31/2011. CoFR: Available, complete, and accurate. RDRL: With Release Detection Records. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical Line Leak Detectors for the primary piping and monthly visual inspections of the tank interstice, double walled fills, dispensers/liners, and STP sumps. b. Facility¿s monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period 2/4/2010 through 12/10/2010. Visual inspections include the condition of the tank interstice, DW fills, dispensers/liners, and STP sumps. Release detection was performed at least once a month not exceeding 35 days apart. Tests: a. Annual or periodic test results: 1. Annual operability tests of the Mechanical Line Leak Detectors were conducted 10/27/2010 by Hytech; next tests due by 10/27/2011. PHYSICAL: STP Sumps: Both sumps contain PCW over the piping, immediately remove and properly dispose of all PCW. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners are clean and dry. Fills: Covers properly painted. Fills are locked. The interstitial caps are missing from both spill buckets; each one has a sorbent pad in the port. Recommend repairs or replacement to ensure interstice integrity. There is minor condensation both interstices. Shear Valves: All shear valves are rigidly anchored. Tank Interstice: The Regular tank interstitial space is dry. Unable to access the Premium interstitial, RD indicates no problems. NOTE: This facility meets the upgrade standards of 12/31/2009.
05/28/2010 Record Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Rick Herweh Activity Closed Date: 05/28/2010
Events:
Event Type: Activity has been finished Date: 05/28/2010
Comment: Finished
04/16/2010 Editable Letter Activity Trethewey, Mark B.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 04/16/2010
Comment: Finished
Attachments:
Attachment Date: 04/16/2010 User: TRETHEWEY_MB_1
Description: NCL 2009-2010.065
View Attachment
04/15/2010 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
04/15/2010 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/06/2010
Activity Closed Date: 04/16/2010 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 04/16/2010
Comment: Finished
Comments:
Comment Date: 04/16/2010 User: TRETHEWEY_MB_1
Description: RECORDS: # 8510927, 4/6/2010 Placard: #331358; issued 8/5/2009, 2 tanks listed. Financial Responsibility: Liberty Surplus, 12/31/2009 ¿ 12/31/2010. CoFR: Available, complete, and accurate. RDRL: With Release Detection Records. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical Line Leak Detectors for the primary piping and monthly visual inspections of the tank interstice, double walled fills, dispensers/liners, and STP sumps. b. Facility¿s monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period 2/15/2009 through 2/4/2010. Visual inspections include the condition of the tank interstice, DW fills, dispensers/liners, and STP sumps. Inspections were greater than 35 days apart on one occasion (6/8/2009 to 7/14/2009). Ensure that release detection is performed at least once a month not exceeding 35 days apart. Tests: a. Annual or periodic test results: 1. Annual operability tests of the Mechanical Line Leak Detectors were conducted 10/27/2009 by Hytech; next tests due by 10/27/2010. PHYSICAL: STP Sumps: Both sumps contain PCW, immediately remove and properly dispose of all PCW. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners are clean and dry. Fills: Covers properly painted. Fills are locked. The interstitial cap was not in place in the Premium spill bucket upon inspection. There is minor condensation in the interstice, cap was reinstalled. Unable to access the Regular interstitial, bucket is holding liquid at this time. Shear Valves: All shear valves are rigidly anchored. Tank Interstice: All tanks interstitial spaces are dry. NOTE: This facility meets the upgrade standards of 12/31/2009.
04/07/2009 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/07/2009
Activity Closed Date: 04/07/2009 Activity Closed By: TRETHEWEY_MB_1
Comments:
Comment Date: 04/07/2009 User: TRETHEWEY_MB_1
Description: RECORDS: # 8510927, 4/7/2009 Placard: #307896; issued 7/2/2007, 2 tanks listed. Financial Responsibility: Zurich-American, 12/31/2008 ¿ 12/31/2009. CoFR: Available, complete, and accurate. RDRL: With Release Detection Records. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical Line Leak Detectors for the primary piping and monthly visual inspections of the tank interstice, single-wall fills, dispensers/liners, and STP sumps. b. Facility¿s monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period 3/19/2008 through 2/5/2009. Visual inspections include the condition of the tank interstice, SW fills, dispensers/liners, and STP sumps, no inspections were greater than 35 days apart. Tests: a. Annual or periodic test results: 1. Annual operability tests of the Mechanical Line Leak Detectors were conducted 8/22/2008 by Hytech; next tests due by 8/22/2009. PHYSICAL: STP Sumps: Both sumps are clean and dry. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners are clean and dry. Fills: Covers properly painted. Fills are unobstructed. Shear Valves: All shear valves are rigidly anchored. Tank Interstice: All tanks interstitial spaces are dry. NOTE: This facility meets the upgrade standards of 12/31/2009.
04/15/2008 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/15/2008
Activity Closed Date: 04/15/2008 Activity Closed By: TRETHEWEY_MB_1
Comments:
Comment Date: 04/15/2008 User: TRETHEWEY_MB_1
Description: RECORDS: # 8510927, 4/15/2008 Placard: 284960; issued 7/2/2007, 2 tanks listed. Financial Responsibility: Zurich-American, 12/31/2007 ¿ 12/31/2008. CoFR: Available, complete, and accurate. RDRL: With Release Detection Records. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical Line Leak Detectors for the primary piping and monthly visual inspections of the tank interstice, single-wall fills, dispensers/liners, and STP sumps. b. Facility¿s monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period 3/22/2007 through 3/19/2008. Visual inspections include the condition of the tank interstice, SW fills, dispensers/liners, and STP sumps, no inspections were greater than 35 days apart. Tests: a. Annual or periodic test results: 1. Annual operability tests of the Mechanical Line Leak Detectors were conducted 8/22/2007 by Hytech; next tests due by 8/22/2008. PHYSICAL: STP Sumps: Both sumps are clean and dry. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners are clean and dry. Fills: Covers properly painted. Fills are unobstructed. Shear Valves: All shear valves are rigidly anchored. Tank Interstice: All tanks interstitial spaces are dry. NOTE: This facility meets the upgrade standards of 12/31/2009.
04/20/2007 Attachment Trethewey, Mark B.
04/20/2007 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/20/2007
Activity Closed Date: 04/20/2007 Activity Closed By: TRETHEWEY_MB_1
Comments:
Comment Date: 04/20/2007 User: TRETHEWEY_MB_1
Description: RECORDS: # 8510927, 4-20-2007 Placard: 254282; issued 5/31/2006, 2 tanks listed. Financial Responsibility: Zurich-American, 12/31/2006 ¿ 12/31/2007. CoFR: Available, complete, and accurate. RDRL: With Release Detection Records. Release Detection: a. This Facility has the following release detection methods: 1. Mechanical Line Leak Detectors for the primary piping and monthly visual inspections of the tank interstice, single-wall fills, dispensers/liners, and STP sumps. Note: SIRs TankMate version 3.12 (EQ-466) was used prior to the installation of DW tanks. b. Facility¿s monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period 2/9/2006 through 3/22/2007. Visual inspections include the condition of the tank interstice, SW fills, dispensers/liners, and STP sumps. SIRs records from 4/2006 to 6/2006 all pass. Facility was not in operation 7/2006 and 8/2006 due to the installation of DFW tanks. No inspections were greater than 35 days apart. Tests: a. Annual or periodic test results: 1. Annual operability tests of the Mechanical Line Leak Detectors were conducted 8/22/2006 by Hytech; next tests due by 8/22/2007. PHYSICAL: STP Sumps: Both sumps are clean and dry. Dispenser Liners: Inspected Dispenser #s 1/2, 3/4 and 5/6. All liners are clean and dry. Fills: Covers properly painted. Fills are unobstructed. Shear Valves: All shear valves are rigidly anchored. Tank Interstice: All tanks Interstitial space are dry. NOTE: This facility meets the upgrade standards of 12/31/2009.
04/20/2007 Attachment Trethewey, Mark B.
04/20/2007 Attachment Trethewey, Mark B.
02/09/2007 Emergency Preparedness Information Activity Reeder, Jon H.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/09/2007
10/18/2006 TCAR Activity Reeder, Jon H.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 10/18/2006
Comments:
Comment Date: 10/18/2006 User: REEDER_JH_1
Description: CLOSURE REPORT: Too large to attach (>256 KB), sent to DEP/Tampa for entry into OCULUS.
09/22/2006 Emergency Preparedness Information Activity Reeder, Jon H.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/22/2006
08/21/2006 Attachment Reeder, Jon H.
08/09/2006 Attachment Reeder, Jon H.
08/09/2006 Site Inspection Activity Closed Reeder, Jon H.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/09/2006
Activity Closed Date: 08/09/2006 Activity Closed By: REEDER_JH_1
Comments:
Comment Date: 08/09/2006 User: REEDER_JH_1
Description: CLOSURE INSPECTION ONLY. Certain records and equipment associated with compliance inspections were not checked.
Comments:
Comment Date: 08/09/2006 User: REEDER_JH_1
Description: SITE VISITS: See attachment.
08/09/2006 Site Inspection Activity Closed Reeder, Jon H.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/09/2006
Activity Closed Date: 08/09/2006 Activity Closed By: REEDER_JH_1
Comments:
Comment Date: 08/09/2006 User: REEDER_JH_1
Description: CLOSURE INSPECTION ONLY. Certain records and equipment associated with compliance inspections were not checked.
Comments:
Comment Date: 08/09/2006 User: REEDER_JH_1
Description: SITE VISITS: See attachment.
08/09/2006 Site Inspection Activity Closed Reeder, Jon H.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/09/2006
Activity Closed Date: 08/21/2006 Activity Closed By: REEDER_JH_1
Comments:
Comment Date: 08/09/2006 User: REEDER_JH_1
Description: SITE VISITS: See attachment.
Comments:
Comment Date: 08/09/2006 User: REEDER_JH_1
Description: INSTALLATION INSPECTION ONLY. Certain records and equipment associated with compliance inspections were not checked.
08/09/2006 Site Inspection Activity Closed Reeder, Jon H.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/09/2006
Activity Closed Date: 08/21/2006 Activity Closed By: REEDER_JH_1
Comments:
Comment Date: 08/09/2006 User: REEDER_JH_1
Description: SITE VISITS: See attachment.
Comments:
Comment Date: 08/09/2006 User: REEDER_JH_1
Description: INSTALLATION INSPECTION ONLY. Certain records and equipment associated with compliance inspections were not checked.
07/10/2006 Record Document Activity Reeder, Jon H.
Activity Status: Closed
Contact Name: Dawn Kohlmeyer - Tanknology Activity Closed Date: 07/10/2006
Comments:
Comment Date: 08/21/2006 User: REEDER_JH_1
Description: Re-testing and re-certification not necessary as tank system was replaced 8/21/2006.
04/10/2006 Legacy Activity Trethewey, Mark B.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
07/12/2005 Legacy Activity Reeder, Jon H.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: RECEIVED CP TEST RESULTS: TEST COMPLETE 07/06/2005, PASS.
07/12/2005 Legacy Activity Reeder, Jon H.
Activity Name: COMPLIANCE W/O FORMAL ENFORCEMENT ACTION Activity Status: Closed
05/16/2005 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 761.700(1)(b)2a
Comments:
Comment Date: 12/07/2022 User: GRAJEDACARDENAS_CJ_1
Description: Release detection - Veeder Root TLS 350 Overfill protection - Morrison Bros Clock
05/16/2005 Legacy Activity Trethewey, Mark B.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/26/2004 Legacy Activity Sego, John R.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
01/16/2004 Violation Closed Sego, John R.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
Comments:
Comment Date: 04/17/2008 User: HAMBY_MB_1
Description: Tanks: Modern Welding Glasteel II USTs EQ #156 Piping: AO Smith Red Thread EQ #252 Sumps: Unknown make/model Dispenser liners: Unknown make/model Spill buckets: Unknown make/model Overfill: ball-floats present per installation plans. Release Detection: -Visual inspections of STP sumps, dispensers/liners, and spill containment buckets. =Tanks=Electronic monitoring of tank interstices. Pnuemercator LDE-700 panel (DEP EQ #519) monitors (3) tank interstices. =Piping=Visual inspections of STP sumps and mechanical in line leak detectors.
01/16/2004 Legacy Activity Sego, John R.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/04/2003 Legacy Activity Unknown, User
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
03/17/2003 Violation Closed Panik, Paul J.
Significance: Minor Status: Closed
Rule: 640(3)(d)
03/17/2003 Legacy Activity Panik, Paul J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/17/2003 Violation Closed Panik, Paul J.
Significance: Minor Status: Closed
Rule: 700(1)(c)1
03/17/2003 Violation Closed Panik, Paul J.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
06/18/2002 Legacy Activity Panik, Paul J.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
02/13/2002 Violation Closed Panik, Paul J.
Significance: Minor Status: Closed
Rule: 700(2)(e)
02/13/2002 Legacy Activity Panik, Paul J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/27/2001 Legacy Activity Panik, Paul J.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
03/14/2001 Violation Closed Panik, Paul J.
Significance: Minor Status: Closed
Rule: 640(3)(d)
03/14/2001 Legacy Activity Panik, Paul J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
07/22/1999 Legacy Activity Panik, Paul J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
10/21/1998 Legacy Activity Panik, Paul J.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
09/22/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
09/22/1998 Legacy Activity Panik, Paul J.
Activity Name: UST ROUTINE COMPLIANCE INSPECTION Activity Status: Closed