DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/30/2025        Last Data Refresh: 04/29/2025        Report Generated from DOPPLER
 
Facility ID: 8519422
Facility Name: SAVINGS STATION
 
12/18/2024 Enforcement Tracking Activity Snyder, Ryan B
Activity Status: Open
01/29/2024 Site Inspection Activity Closed Parks, Jeff S
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/29/2024
Activity Closed Date: 01/29/2024 Activity Closed By: PARKS_J_4
Events:
Event Type: Activity has been finished Date: 01/29/2024
Comment: Finished
Comments:
Comment Date: 01/29/2024 User: PARKS_J_4
Description: There are 3 (3) 8,000 gallon tanks that are out of service. The dispensers have been removed.
01/29/2024 Phone Conversation Activity Parks, Jeff S
Call Type: Outgoing Activity Status: Closed
Phone Number: (662) 842-7525 Activity Closed Date: 01/29/2024
Subject: scheduling
Events:
Event Type: Activity has been finished Date: 01/29/2024
Comment: Finished
01/29/2024 Editable Letter Activity Parks, Jeff S
Activity Title: In Compliance Letter Activity Status: Closed
Description: RCL 9700454, PERRY-FOLEY AIRPORT.
Events:
Event Type: Document has been sent Date: 01/29/2024
Comment: Sent
Events:
Event Type: Activity has been finished Date: 01/29/2024
Comment: Finished
Attachments:
Attachment Date: 01/29/2024 User: PARKS_J_4
Description: ICL
View Attachment
10/19/2023 Electronic Communication Activity Parks, Jeff S
Activity Closed Date: 10/19/2023 Activity Status: Closed
Date: 10/19/2023
Recipient: Jeff Parks
Sender: Tiffany Priest
Subject: CFR
Message: See Attached for 3 years of CFR documents.
Events:
Event Type: Activity has been finished Date: 10/19/2023
Comment: Finished
10/19/2023 Editable Letter Activity Parks, Jeff S
Activity Title: Return to Compliance Letter Activity Status: Closed
Description: 2021-05-26 Rust repainted
Events:
Event Type: Activity has been finished Date: 10/19/2023
Comment: Finished
Events:
Event Type: Document has been sent Date: 10/19/2023
Comment: Sent
Attachments:
Attachment Date: 10/19/2023 User: PARKS_J_4
Description: RCL
View Attachment
10/10/2023 Electronic Communication Activity Parks, Jeff S
Activity Closed Date: 10/10/2023 Activity Status: Closed
Date: 10/10/2023
Recipient: Tiffany Priest
Sender: Jeff Parks
Subject: 8519422 Savings Station Tank
Message: Tiffany Priest: I have been trying to reach you regarding the status of a petroleum storage tank located in Fort Myers that is registered and lists you as the contact. This tank is due for an annual inspection. There are many issues of non-compliance associated with this account. Please contact me to discuss these issues and schedule the next inspection. Thank you, Jeff Parks | Environmental Specialist Natural Resources 1500 Monroe Street, Fort Myers, FL 33901 office: (239) 841-5773 email: JParks@leegov.com web: www.leegov.com Connect With Us On Social Media
Events:
Event Type: Activity has been finished Date: 10/10/2023
Comment: Finished
10/03/2023 Phone Conversation Activity Parks, Jeff S
Call Type: Outgoing Activity Status: Closed
Phone Number: (662) 842-7525 Activity Closed Date: 10/03/2023
Subject: J. Parks called the above listed number in an attempt to reach Tiffany Priest concerning outstanding violations and an upcoming inspection. A person answered and connect to voicemail. A message was left
Events:
Event Type: Activity has been finished Date: 10/03/2023
Comment: Finished
05/10/2022 Enforcement Referral Activity Parks, Jeff S
Activity Status: Submitted
Events:
Event Type: Activity has been submitted for approval Date: 05/10/2022
Comment: Submitted for approval by: Jeff S Parks: Enforcement Referral
Comments:
Comment Date: 05/10/2022 User: PARKS_J_4
Description: Enforcement Referral
04/21/2022 Violation Closed Parks, Jeff S
Significance: SNC-A Status: Closed
Criteria ID: 6012
Rule: 62-761.420(2)
04/21/2022 Phone Conversation Activity Parks, Jeff S
Call Type: Outgoing Activity Status: Closed
Phone Number: (662) 842-7525 Activity Closed Date: 04/21/2022
Subject: J. Parks called and left a message notifying the recipient of the inspection.
Events:
Event Type: Activity has been finished Date: 04/21/2022
Comment: Finished
04/21/2022 Enforcement Referral Activity Parks, Jeff S
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 12/18/2024
Events:
Event Type: Activity has been submitted for approval Date: 08/01/2022
Comment: Submitted for approval by: Jeff S Parks: No CFR >180 days
Events:
Event Type: Activity/Document was acknowledged on this date Date: 09/02/2022
Comment: Acknowledged and Assigned by Rick R Roudebush
Events:
Event Type: Activity has been assigned Date: 09/02/2022
Comment: Assigned to Ryan B Snyder
Events:
Event Type: Activity has been withdrawn from submission by the requestor Date: 08/02/2022
Comment: Withdrawn by Jeff S Parks: wd
Events:
Event Type: Activity has been submitted for approval Date: 08/30/2022
Comment: Submitted for approval by: Jeff S Parks: Withdrawn
Events:
Event Type: Activity has been assigned Date: 04/21/2022
Comment: Assigned to Ryan B Snyder
Events:
Event Type: Activity has been submitted for approval Date: 04/21/2022
Comment: Submitted for approval by: Jeff S Parks: No CFR since inspection conducted in 2020.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 04/21/2022
Comment: Acknowledged and Assigned by Ryan B Snyder
Events:
Event Type: Activity/Document was returned on this date Date: 04/21/2022
Comment: Returned by Ryan B Snyder: There is no memorandum attached to the enforcement case as per Guidance Document G within the contract. Information that needs to be contained within the memo is listed in Guidance Document G. Please complete and attached the memo prior to submitting for referral.
Events:
Event Type: Activity/Document was accepted on this date Date: 12/18/2024
Comment: Accepted by Ryan B Snyder: a
Events:
Event Type: Activity has been finished Date: 12/18/2024
Comment: Finished
Comments:
Comment Date: 04/21/2022 User: PARKS_J_4
Description: No CFR since inspection conducted in 2020.
04/21/2022 Site Inspection Activity Closed Parks, Jeff S
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 04/21/2022
Activity Closed Date: 04/21/2022 Activity Closed By: PARKS_J_4
Events:
Event Type: Activity has been finished Date: 04/21/2022
Comment: Finished
Comments:
Comment Date: 04/21/2022 User: PARKS_J_4
Description: Jeff Parks from Lee County conducted the Compliance Inspection. TANKS: Inspected: one 16,000-gallon and two 8,000-gallon tank double-walled, brine fill, underground tanks that have been placed out of service. No documentation on site and not provided after phone request on 4/18/22. DISPENSERS CONTAINMENT: Dispensors and hoses have been removed from site RECORDS SHALL BE KEPT FOR THREE YEARS IN ACCORDANCE WITH RULE 62-761.710, F.A.C. Inspection Report sent by e-mail to: Oneoldguy@aol.com
05/21/2020 Violation Closed Kleinmann, Keith
Significance: Minor Status: Closed
Criteria ID: 4078
Rule: 62-761.710(1)
05/21/2020 Phone Conversation Activity Kleinmann, Keith
Call Type: Outgoing Activity Status: Closed
Phone Number: (239) 731-1600 Activity Closed Date: 05/21/2020
Subject: Informed them required paperwork not received.
Events:
Event Type: Activity has been finished Date: 05/21/2020
Comment: Finished
05/21/2020 Editable Letter Activity Kleinmann, Keith
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 07/01/2021
Comment: Finished
Attachments:
Attachment Date: 06/15/2020 User: KLEINMANN_K_1
Description: CAO
View Attachment
05/07/2020 Site Inspection Activity Closed Kleinmann, Keith
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 05/07/2020
Activity Closed Date: 05/21/2020 Activity Closed By: KLEINMANN_K_1
Events:
Event Type: Activity has been finished Date: 05/21/2020
Comment: Finished
Comments:
Comment Date: 05/07/2020 User: KLEINMANN_K_1
Description: Keith Kleinmann from Lee County met with facility representatives to conduct the Compliance Inspection. TANKS: Inspected: one 16,000-gallon and two 8,000-gallon tank double-walled, brine fill, underground tanks that have been placed out of service. No documentation on site and not provided after phone request on 5/7/20. DISPENSERS CONTAINMENT: Dispensors and hoses have been removed from site The Placard expiration date is: June 30, 2020. Storage tank registration fees are due to the Department each year by July 1. Ensure that your contact information is up-to-date with the Department in order to receive updates concerning your annual registration fees. Once fees are paid, you must print a copy of your placard from the Department's website: http://www.fldepportal.com/go/submit-registration/. RECORDS SHALL BE KEPT FOR THREE YEARS IN ACCORDANCE WITH RULE 62-761.710, F.A.C. Inspection Report sent by e-mail to: Oneoldguy@aol.com
05/07/2020 Phone Conversation Activity Kleinmann, Keith
Call Type: Outgoing Activity Status: Closed
Phone Number: (239) 731-1600 Activity Closed Date: 05/07/2020
Subject: bill marron or kelly
Events:
Event Type: Activity has been finished Date: 05/07/2020
Comment: Finished
04/18/2017 Site Inspection Activity Closed Zimmerman, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/18/2017
Activity Closed Date: 04/18/2017 Activity Closed By: ZIMMERMAN_CA_1
Events:
Event Type: Activity has been finished Date: 04/18/2017
Comment: Finished
Comments:
Comment Date: 04/18/2017 User: ZIMMERMAN_CA_1
Description: Checked required documentation (Visuals, insurance, maintenance records, etc..) along with required storage tank components (Tanks, lines, spill buckets, hoses, etc...) Updated registration info as needed. Alarm/Maintenance History: Nothing significant to note.
04/14/2015 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/14/2015
Activity Closed Date: 04/17/2015 Activity Closed By: JOHNSON_SG_1
Events:
Event Type: Activity has been finished Date: 04/17/2015
Comment: Finished
Comments:
Comment Date: 04/17/2015 User: JOHNSON_SG_1
Description: Alarm/Maintenance History -Nothing significant to note
Comments:
Comment Date: 04/17/2015 User: JOHNSON_SG_1
Description: Checked all documentation (visuals, RDRL, maintenance records, insurance, liquid status tapes, testing, placard, etc) along with required storage tank components(tanks, lines, sumps, fills, DW fills, dispensers, veedor-root, LLD, sensors, etc).
04/14/2015 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/14/2015
Activity Closed Date: 04/17/2015 Activity Closed By: JOHNSON_SG_1
Events:
Event Type: Activity has been finished Date: 04/17/2015
Comment: Finished
Comments:
Comment Date: 04/17/2015 User: JOHNSON_SG_1
Description: Alarm/Maintenance History -Nothing significant to note
Comments:
Comment Date: 04/17/2015 User: JOHNSON_SG_1
Description: Checked all documentation (visuals, RDRL, maintenance records, insurance, liquid status tapes, testing, placard, etc) along with required storage tank components(tanks, lines, sumps, fills, DW fills, dispensers, veedor-root, LLD, sensors, etc).
07/26/2012 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/26/2012
Activity Closed Date: 07/31/2012 Activity Closed By: JOHNSON_SG_1
Events:
Event Type: Activity has been finished Date: 07/31/2012
Comment: Finished
Comments:
Comment Date: 07/26/2012 User: JOHNSON_SG_1
Description: Only items associated with INF were checked at time of inspection.
Comments:
Comment Date: 07/26/2012 User: JOHNSON_SG_1
Description: Received INF due to damaged vent lines. Appears someone ran into vent lines and damaged underground fiberglass piping. Does not appear that product was released and repairs have since been made. INF will be closed and it appears that no discharge occured. See attachments for more details.
07/26/2012 Document Management Activity Johnson, Stephen G.
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 07/26/2012
Comment: Finished
Attachments:
Attachment Date: 07/26/2012 User: JOHNSON_SG_1
Description: 1. INF
View Attachment
07/26/2012 Discharge Reporting Activity Johnson, Stephen G.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 07/31/2012
Events:
Event Type: Activity has been finished Date: 07/31/2012
Comment: Finished
07/26/2012 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/26/2012
Activity Closed Date: 07/31/2012 Activity Closed By: JOHNSON_SG_1
Events:
Event Type: Activity has been finished Date: 07/31/2012
Comment: Finished
Comments:
Comment Date: 07/26/2012 User: JOHNSON_SG_1
Description: Only items associated with INF were checked at time of inspection.
Comments:
Comment Date: 07/26/2012 User: JOHNSON_SG_1
Description: Received INF due to damaged vent lines. Appears someone ran into vent lines and damaged underground fiberglass piping. Does not appear that product was released and repairs have since been made. INF will be closed and it appears that no discharge occured. See attachments for more details.
03/26/2012 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/26/2012
Activity Closed Date: 03/28/2012 Activity Closed By: JOHNSON_SG_1
Events:
Event Type: Activity has been finished Date: 03/28/2012
Comment: Finished
Comments:
Comment Date: 03/28/2012 User: JOHNSON_SG_1
Description: ALarm/Maintenance History -Nothing significant to note
Comments:
Comment Date: 03/28/2012 User: JOHNSON_SG_1
Description: All required documentation was inspected at time of inspection (Insurance, Placard, visuals, liquid status tapes, maintenance records, RDRL, testing, etc...) along with required storage tank components (Tank, lines, spill buckets, DW buckets, hoses, dispensers, sumps, shear valves, piping, breakaways, LLD, sensors, veeder-root, etc...)
Comments:
Comment Date: 03/28/2012 User: JOHNSON_SG_1
Description: NOTES: 1) Facility should update form to #dispenser on site and # product fills on site. 2) Facility is a category "c" system and will be required to preform a breach of integrity test on storage tanks in November 2013.
03/26/2012 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/26/2012
Activity Closed Date: 03/28/2012 Activity Closed By: JOHNSON_SG_1
Events:
Event Type: Activity has been finished Date: 03/28/2012
Comment: Finished
Comments:
Comment Date: 03/28/2012 User: JOHNSON_SG_1
Description: ALarm/Maintenance History -Nothing significant to note
Comments:
Comment Date: 03/28/2012 User: JOHNSON_SG_1
Description: All required documentation was inspected at time of inspection (Insurance, Placard, visuals, liquid status tapes, maintenance records, RDRL, testing, etc...) along with required storage tank components (Tank, lines, spill buckets, DW buckets, hoses, dispensers, sumps, shear valves, piping, breakaways, LLD, sensors, veeder-root, etc...)
Comments:
Comment Date: 03/28/2012 User: JOHNSON_SG_1
Description: NOTES: 1) Facility should update form to #dispenser on site and # product fills on site. 2) Facility is a category "c" system and will be required to preform a breach of integrity test on storage tanks in November 2013.
03/26/2012 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/26/2012
Activity Closed Date: 03/28/2012 Activity Closed By: JOHNSON_SG_1
Events:
Event Type: Activity has been finished Date: 03/28/2012
Comment: Finished
Comments:
Comment Date: 03/28/2012 User: JOHNSON_SG_1
Description: ALarm/Maintenance History -Nothing significant to note
Comments:
Comment Date: 03/28/2012 User: JOHNSON_SG_1
Description: All required documentation was inspected at time of inspection (Insurance, Placard, visuals, liquid status tapes, maintenance records, RDRL, testing, etc...) along with required storage tank components (Tank, lines, spill buckets, DW buckets, hoses, dispensers, sumps, shear valves, piping, breakaways, LLD, sensors, veeder-root, etc...)
Comments:
Comment Date: 03/28/2012 User: JOHNSON_SG_1
Description: NOTES: 1) Facility should update form to #dispenser on site and # product fills on site. 2) Facility is a category "c" system and will be required to preform a breach of integrity test on storage tanks in November 2013.
03/15/2011 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/15/2011
Activity Closed Date: 03/18/2011 Activity Closed By: JOHNSON_SG_1
Events:
Event Type: Activity has been finished Date: 03/18/2011
Comment: Finished
Comments:
Comment Date: 03/15/2011 User: JOHNSON_SG_1
Description: ALarm/Maintenance History -Nothing significant to note
Comments:
Comment Date: 03/15/2011 User: JOHNSON_SG_1
Description: All required documentation was inspected at time of inspection (Insurance, Placard, visuals, liquid status tapes, maintenance records, RDRL, testing, etc...) along with required storage tank components (Tank, lines, spill buckets, DW buckets, hoses, dispensers, sumps, shear valves, piping, breakaways, LLD, sensors, veeder-root, etc...)
Comments:
Comment Date: 03/18/2011 User: JOHNSON_SG_1
Description: Notes: 1) one of the diesel dispensers has dirt/debris along base making inspection of space difficult. Liner should be cleaned out prior to next compliance inspection. 2) Unleaded spill bucket is bubbled out. Nothing in interstice but an area of concern. Facility may want to check bleeder valve on interstitial port....may be cause. 3) Visuals need to be conducted within 35 days of one another. Couple months where that was not done.
03/15/2011 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/15/2011
Activity Closed Date: 03/18/2011 Activity Closed By: JOHNSON_SG_1
Events:
Event Type: Activity has been finished Date: 03/18/2011
Comment: Finished
Comments:
Comment Date: 03/15/2011 User: JOHNSON_SG_1
Description: ALarm/Maintenance History -Nothing significant to note
Comments:
Comment Date: 03/15/2011 User: JOHNSON_SG_1
Description: All required documentation was inspected at time of inspection (Insurance, Placard, visuals, liquid status tapes, maintenance records, RDRL, testing, etc...) along with required storage tank components (Tank, lines, spill buckets, DW buckets, hoses, dispensers, sumps, shear valves, piping, breakaways, LLD, sensors, veeder-root, etc...)
Comments:
Comment Date: 03/18/2011 User: JOHNSON_SG_1
Description: Notes: 1) one of the diesel dispensers has dirt/debris along base making inspection of space difficult. Liner should be cleaned out prior to next compliance inspection. 2) Unleaded spill bucket is bubbled out. Nothing in interstice but an area of concern. Facility may want to check bleeder valve on interstitial port....may be cause. 3) Visuals need to be conducted within 35 days of one another. Couple months where that was not done.
03/15/2011 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/15/2011
Activity Closed Date: 03/18/2011 Activity Closed By: JOHNSON_SG_1
Events:
Event Type: Activity has been finished Date: 03/18/2011
Comment: Finished
Comments:
Comment Date: 03/15/2011 User: JOHNSON_SG_1
Description: ALarm/Maintenance History -Nothing significant to note
Comments:
Comment Date: 03/15/2011 User: JOHNSON_SG_1
Description: All required documentation was inspected at time of inspection (Insurance, Placard, visuals, liquid status tapes, maintenance records, RDRL, testing, etc...) along with required storage tank components (Tank, lines, spill buckets, DW buckets, hoses, dispensers, sumps, shear valves, piping, breakaways, LLD, sensors, veeder-root, etc...)
Comments:
Comment Date: 03/18/2011 User: JOHNSON_SG_1
Description: Notes: 1) one of the diesel dispensers has dirt/debris along base making inspection of space difficult. Liner should be cleaned out prior to next compliance inspection. 2) Unleaded spill bucket is bubbled out. Nothing in interstice but an area of concern. Facility may want to check bleeder valve on interstitial port....may be cause. 3) Visuals need to be conducted within 35 days of one another. Couple months where that was not done.
03/02/2010 Site Inspection Activity Closed Zimmerman, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/02/2010
Activity Closed Date: 03/03/2010 Activity Closed By: ZIMMERMAN_CA_1
Events:
Event Type: Activity has been finished Date: 03/03/2010
Comment: Finished
Comments:
Comment Date: 03/03/2010 User: ZIMMERMAN_CA_1
Description: Inspection Notes: Dispensers are starting to accumulate some dirt & debris and should be clean out before the next annual compliance inspection. Also one of the diesel dispensers had a small amount of water, but was well below the piping. The whip hose for the reg unleaded on dispenser #1 is dry roted and should be replaced.
Comments:
Comment Date: 03/02/2010 User: ZIMMERMAN_CA_1
Description: Checked required documentation (RDRL, Visuals, insurance, maintenance records, etc..) along with required storage tank components (Tanks, lines, spill buckets, hoses, etc...) Updated registration info as needed.
Comments:
Comment Date: 03/02/2010 User: ZIMMERMAN_CA_1
Description: Alarm/Maintenance history Nothing significate to note
03/02/2010 Site Inspection Activity Closed Zimmerman, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/02/2010
Activity Closed Date: 03/03/2010 Activity Closed By: ZIMMERMAN_CA_1
Events:
Event Type: Activity has been finished Date: 03/03/2010
Comment: Finished
Comments:
Comment Date: 03/03/2010 User: ZIMMERMAN_CA_1
Description: Inspection Notes: Dispensers are starting to accumulate some dirt & debris and should be clean out before the next annual compliance inspection. Also one of the diesel dispensers had a small amount of water, but was well below the piping. The whip hose for the reg unleaded on dispenser #1 is dry roted and should be replaced.
Comments:
Comment Date: 03/02/2010 User: ZIMMERMAN_CA_1
Description: Checked required documentation (RDRL, Visuals, insurance, maintenance records, etc..) along with required storage tank components (Tanks, lines, spill buckets, hoses, etc...) Updated registration info as needed.
Comments:
Comment Date: 03/02/2010 User: ZIMMERMAN_CA_1
Description: Alarm/Maintenance history Nothing significate to note
03/02/2010 Site Inspection Activity Closed Zimmerman, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/02/2010
Activity Closed Date: 03/03/2010 Activity Closed By: ZIMMERMAN_CA_1
Events:
Event Type: Activity has been finished Date: 03/03/2010
Comment: Finished
Comments:
Comment Date: 03/03/2010 User: ZIMMERMAN_CA_1
Description: Inspection Notes: Dispensers are starting to accumulate some dirt & debris and should be clean out before the next annual compliance inspection. Also one of the diesel dispensers had a small amount of water, but was well below the piping. The whip hose for the reg unleaded on dispenser #1 is dry roted and should be replaced.
Comments:
Comment Date: 03/02/2010 User: ZIMMERMAN_CA_1
Description: Checked required documentation (RDRL, Visuals, insurance, maintenance records, etc..) along with required storage tank components (Tanks, lines, spill buckets, hoses, etc...) Updated registration info as needed.
Comments:
Comment Date: 03/02/2010 User: ZIMMERMAN_CA_1
Description: Alarm/Maintenance history Nothing significate to note
04/17/2009 Site Inspection Activity Closed Zimmerman, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/17/2009
Activity Closed Date: 04/20/2009 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 04/17/2009 User: ZIMMERMAN_CA_1
Description: Items on page 3/4 were checked to complete inspection. Only re-inspection items were checked at time of inspection.
03/27/2009 Editable Letter Activity Johnson, Stephen G.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
03/25/2009 Comment Johnson, Stephen G.
Description: *UPDATE*Facility has installed 3 DW USTs equipped with 3 sumps, MLLD, sensors in sumps and tank interstices, DW fiberglass piping, 8 dispensers, and a veeder-root. Facilities primary form of release detection is monthly visuals and liquid stauts.
03/25/2009 Violation Closed Johnson, Stephen G.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
03/25/2009 Violation Closed Johnson, Stephen G.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
03/25/2009 Attachment Johnson, Stephen G.
03/25/2009 Attachment Johnson, Stephen G.
03/24/2009 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/24/2009
Activity Closed Date: 03/27/2009 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Updated registration at time of inspection.
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Alarm/Maintenance history -Nothing Significant to note.
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: All required documentation was inspected at time of inspection (Insurance, Placard, visuals, liquid status tapes, maintenance records, RDRL, testing, etc...) along with required storage tank components (Tank, lines, DW buckets, hoses, dispensers, sumps, shear valves, piping, breakaways, LLD, sensors, veeder-root, etc...)
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Records -Reviewed old system records but did not include on page 3 due to tank upgrade and updating fields. - 4-1-08 thru 12-1-08 - Sensor status, PLLD reports, and CSLDs - all normal -4-1-08 thru 12-1-08 - Visuals of sumps, dispenser liners, and CP - all normal **11/26/08 - Last time CP was checked. Tanks closed in December/January.
03/24/2009 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/24/2009
Activity Closed Date: 03/27/2009 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Updated registration at time of inspection.
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Alarm/Maintenance history -Nothing Significant to note.
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: All required documentation was inspected at time of inspection (Insurance, Placard, visuals, liquid status tapes, maintenance records, RDRL, testing, etc...) along with required storage tank components (Tank, lines, DW buckets, hoses, dispensers, sumps, shear valves, piping, breakaways, LLD, sensors, veeder-root, etc...)
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Records -Reviewed old system records but did not include on page 3 due to tank upgrade and updating fields. - 4-1-08 thru 12-1-08 - Sensor status, PLLD reports, and CSLDs - all normal -4-1-08 thru 12-1-08 - Visuals of sumps, dispenser liners, and CP - all normal **11/26/08 - Last time CP was checked. Tanks closed in December/January.
03/24/2009 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/24/2009
Activity Closed Date: 03/27/2009 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Updated registration at time of inspection.
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Alarm/Maintenance history -Nothing Significant to note.
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: All required documentation was inspected at time of inspection (Insurance, Placard, visuals, liquid status tapes, maintenance records, RDRL, testing, etc...) along with required storage tank components (Tank, lines, DW buckets, hoses, dispensers, sumps, shear valves, piping, breakaways, LLD, sensors, veeder-root, etc...)
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Records -Reviewed old system records but did not include on page 3 due to tank upgrade and updating fields. - 4-1-08 thru 12-1-08 - Sensor status, PLLD reports, and CSLDs - all normal -4-1-08 thru 12-1-08 - Visuals of sumps, dispenser liners, and CP - all normal **11/26/08 - Last time CP was checked. Tanks closed in December/January.
03/24/2009 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/24/2009
Activity Closed Date: 03/27/2009 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Updated registration at time of inspection.
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Alarm/Maintenance history -Nothing Significant to note.
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: All required documentation was inspected at time of inspection (Insurance, Placard, visuals, liquid status tapes, maintenance records, RDRL, testing, etc...) along with required storage tank components (Tank, lines, DW buckets, hoses, dispensers, sumps, shear valves, piping, breakaways, LLD, sensors, veeder-root, etc...)
Comments:
Comment Date: 03/24/2009 User: JOHNSON_SG_1
Description: Records -Reviewed old system records but did not include on page 3 due to tank upgrade and updating fields. - 4-1-08 thru 12-1-08 - Sensor status, PLLD reports, and CSLDs - all normal -4-1-08 thru 12-1-08 - Visuals of sumps, dispenser liners, and CP - all normal **11/26/08 - Last time CP was checked. Tanks closed in December/January.
01/09/2009 Record Document Activity Zimmerman, Chris A.
Activity Status: Closed
Contact Name: JoAnne Shadroui Activity Closed Date: 01/09/2009
Comments:
Comment Date: 01/09/2009 User: ZIMMERMAN_CA_1
Description: Copy of complete closure report placed in file for review
01/09/2009 Issue Document Activity Zimmerman, Chris A.
Activity Status: Closed
Contact Name: Tammy Scott Activity Closed Date: 01/09/2009
Comments:
Comment Date: 01/09/2009 User: ZIMMERMAN_CA_1
Description: Copy of SAR letter placed in file for review
11/24/2008 Site Inspection Activity Closed Zimmerman, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/24/2008
Activity Closed Date: 01/05/2009 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete closure inspection.
Comments:
Comment Date: 01/05/2009 User: ZIMMERMAN_CA_1
Description: On 11/24/08 the old tanks were closed in place and filled with with foam DEP EQ #672.
Comments:
Comment Date: 01/05/2009 User: ZIMMERMAN_CA_1
Description: Copy of DEP approval documentation place in file for review
11/24/2008 Site Inspection Activity Closed Zimmerman, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/24/2008
Activity Closed Date: 01/05/2009 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete closure inspection.
Comments:
Comment Date: 01/05/2009 User: ZIMMERMAN_CA_1
Description: On 11/24/08 the old tanks were closed in place and filled with with foam DEP EQ #672.
Comments:
Comment Date: 01/05/2009 User: ZIMMERMAN_CA_1
Description: Copy of DEP approval documentation place in file for review
11/24/2008 Site Inspection Activity Closed Zimmerman, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/24/2008
Activity Closed Date: 01/05/2009 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete closure inspection.
Comments:
Comment Date: 01/05/2009 User: ZIMMERMAN_CA_1
Description: On 11/24/08 the old tanks were closed in place and filled with with foam DEP EQ #672.
Comments:
Comment Date: 01/05/2009 User: ZIMMERMAN_CA_1
Description: Copy of DEP approval documentation place in file for review
11/05/2008 Site Inspection Activity Closed Johnson, Bill
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/05/2008
Activity Closed Date: 12/12/2008 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/17/2008 User: ZIMMERMAN_CA_1
Description: 10/14/08 - Hydro was conduct on all sump and the 2 new diesel dispensers and transition sump. No visible signs of leaks at time of inspection. Note: the entry boots for the exciting electrical conduit in the transition sump had to be replaced as they were leaking during the first hydro test. The conduit takes a 90 degree bend right after it enters the dispenser (Now the transition sump). This may cause a problem in the future if there is any shift of the conduit
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of secondary lines. No visiable signs lof leaks
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Hydro on new diesel dispenser lines conducted on this date with no visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/06/2008 User: JOHNSON_BW_1
Description: Informed by PSSSC that the tank-set would have to be rescheduled for tomorrow. Due to some weight/delivery issues, the UST's would not be delivered on site untill approximately 11:00 AM tomorrow, November 07, 2008.
Comments:
Comment Date: 11/05/2008 User: JOHNSON_BW_1
Description: Ben with PSSSC, Petroleum Equipment Const. (PEC) #pcc 056723, called on 10-28-08 to request a UST (3) installation inspection (tank set) for Thursday afternoon, 11-05-08.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Contractor set 3 DW Glasteel 2 Tanks (EQ# EQ-222), (1) 16,000 tank (UL#R382580) and (2) 8,000 gal tanks (UL #'s UL#R-382581 & UL#R-382582)
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of new primary fiberglass lines(Red Thread IIA (EQ # EQ-252). Piping for the Prem & Reg unleaded was ran into an exciting dispenser and will be connected to the exciting DW flex piping. 2 new diesel dispenser (EQ # EQ-296) were installed and the same type of fiberglass piping was install and soap tested on this date. No visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete intallation inspection.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: 11/21/08-Conduct finial inspections: Vacuum 3 DW spill buckets. Tested sensors (3 sumps, 3 Interstitials, and 2 transition sumps.) Tripped the shear valves in the 2 new diesel dispensers and the dispenser where new piping was connected to exciting DW piping.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Finial test for Tanks, LLD and lines was conmducted by Tanknology, Inc
11/05/2008 Site Inspection Activity Closed Johnson, Bill
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/05/2008
Activity Closed Date: 12/12/2008 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/17/2008 User: ZIMMERMAN_CA_1
Description: 10/14/08 - Hydro was conduct on all sump and the 2 new diesel dispensers and transition sump. No visible signs of leaks at time of inspection. Note: the entry boots for the exciting electrical conduit in the transition sump had to be replaced as they were leaking during the first hydro test. The conduit takes a 90 degree bend right after it enters the dispenser (Now the transition sump). This may cause a problem in the future if there is any shift of the conduit
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of secondary lines. No visiable signs lof leaks
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Hydro on new diesel dispenser lines conducted on this date with no visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/06/2008 User: JOHNSON_BW_1
Description: Informed by PSSSC that the tank-set would have to be rescheduled for tomorrow. Due to some weight/delivery issues, the UST's would not be delivered on site untill approximately 11:00 AM tomorrow, November 07, 2008.
Comments:
Comment Date: 11/05/2008 User: JOHNSON_BW_1
Description: Ben with PSSSC, Petroleum Equipment Const. (PEC) #pcc 056723, called on 10-28-08 to request a UST (3) installation inspection (tank set) for Thursday afternoon, 11-05-08.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Contractor set 3 DW Glasteel 2 Tanks (EQ# EQ-222), (1) 16,000 tank (UL#R382580) and (2) 8,000 gal tanks (UL #'s UL#R-382581 & UL#R-382582)
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of new primary fiberglass lines(Red Thread IIA (EQ # EQ-252). Piping for the Prem & Reg unleaded was ran into an exciting dispenser and will be connected to the exciting DW flex piping. 2 new diesel dispenser (EQ # EQ-296) were installed and the same type of fiberglass piping was install and soap tested on this date. No visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete intallation inspection.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: 11/21/08-Conduct finial inspections: Vacuum 3 DW spill buckets. Tested sensors (3 sumps, 3 Interstitials, and 2 transition sumps.) Tripped the shear valves in the 2 new diesel dispensers and the dispenser where new piping was connected to exciting DW piping.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Finial test for Tanks, LLD and lines was conmducted by Tanknology, Inc
11/05/2008 Site Inspection Activity Closed Johnson, Bill
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/05/2008
Activity Closed Date: 12/12/2008 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/17/2008 User: ZIMMERMAN_CA_1
Description: 10/14/08 - Hydro was conduct on all sump and the 2 new diesel dispensers and transition sump. No visible signs of leaks at time of inspection. Note: the entry boots for the exciting electrical conduit in the transition sump had to be replaced as they were leaking during the first hydro test. The conduit takes a 90 degree bend right after it enters the dispenser (Now the transition sump). This may cause a problem in the future if there is any shift of the conduit
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of secondary lines. No visiable signs lof leaks
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Hydro on new diesel dispenser lines conducted on this date with no visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/06/2008 User: JOHNSON_BW_1
Description: Informed by PSSSC that the tank-set would have to be rescheduled for tomorrow. Due to some weight/delivery issues, the UST's would not be delivered on site untill approximately 11:00 AM tomorrow, November 07, 2008.
Comments:
Comment Date: 11/05/2008 User: JOHNSON_BW_1
Description: Ben with PSSSC, Petroleum Equipment Const. (PEC) #pcc 056723, called on 10-28-08 to request a UST (3) installation inspection (tank set) for Thursday afternoon, 11-05-08.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Contractor set 3 DW Glasteel 2 Tanks (EQ# EQ-222), (1) 16,000 tank (UL#R382580) and (2) 8,000 gal tanks (UL #'s UL#R-382581 & UL#R-382582)
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of new primary fiberglass lines(Red Thread IIA (EQ # EQ-252). Piping for the Prem & Reg unleaded was ran into an exciting dispenser and will be connected to the exciting DW flex piping. 2 new diesel dispenser (EQ # EQ-296) were installed and the same type of fiberglass piping was install and soap tested on this date. No visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete intallation inspection.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: 11/21/08-Conduct finial inspections: Vacuum 3 DW spill buckets. Tested sensors (3 sumps, 3 Interstitials, and 2 transition sumps.) Tripped the shear valves in the 2 new diesel dispensers and the dispenser where new piping was connected to exciting DW piping.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Finial test for Tanks, LLD and lines was conmducted by Tanknology, Inc
11/05/2008 Site Inspection Activity Closed Johnson, Bill
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/05/2008
Activity Closed Date: 12/12/2008 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/17/2008 User: ZIMMERMAN_CA_1
Description: 10/14/08 - Hydro was conduct on all sump and the 2 new diesel dispensers and transition sump. No visible signs of leaks at time of inspection. Note: the entry boots for the exciting electrical conduit in the transition sump had to be replaced as they were leaking during the first hydro test. The conduit takes a 90 degree bend right after it enters the dispenser (Now the transition sump). This may cause a problem in the future if there is any shift of the conduit
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of secondary lines. No visiable signs lof leaks
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Hydro on new diesel dispenser lines conducted on this date with no visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/06/2008 User: JOHNSON_BW_1
Description: Informed by PSSSC that the tank-set would have to be rescheduled for tomorrow. Due to some weight/delivery issues, the UST's would not be delivered on site untill approximately 11:00 AM tomorrow, November 07, 2008.
Comments:
Comment Date: 11/05/2008 User: JOHNSON_BW_1
Description: Ben with PSSSC, Petroleum Equipment Const. (PEC) #pcc 056723, called on 10-28-08 to request a UST (3) installation inspection (tank set) for Thursday afternoon, 11-05-08.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Contractor set 3 DW Glasteel 2 Tanks (EQ# EQ-222), (1) 16,000 tank (UL#R382580) and (2) 8,000 gal tanks (UL #'s UL#R-382581 & UL#R-382582)
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of new primary fiberglass lines(Red Thread IIA (EQ # EQ-252). Piping for the Prem & Reg unleaded was ran into an exciting dispenser and will be connected to the exciting DW flex piping. 2 new diesel dispenser (EQ # EQ-296) were installed and the same type of fiberglass piping was install and soap tested on this date. No visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete intallation inspection.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: 11/21/08-Conduct finial inspections: Vacuum 3 DW spill buckets. Tested sensors (3 sumps, 3 Interstitials, and 2 transition sumps.) Tripped the shear valves in the 2 new diesel dispensers and the dispenser where new piping was connected to exciting DW piping.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Finial test for Tanks, LLD and lines was conmducted by Tanknology, Inc
11/05/2008 Site Inspection Activity Closed Johnson, Bill
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/05/2008
Activity Closed Date: 12/12/2008 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/17/2008 User: ZIMMERMAN_CA_1
Description: 10/14/08 - Hydro was conduct on all sump and the 2 new diesel dispensers and transition sump. No visible signs of leaks at time of inspection. Note: the entry boots for the exciting electrical conduit in the transition sump had to be replaced as they were leaking during the first hydro test. The conduit takes a 90 degree bend right after it enters the dispenser (Now the transition sump). This may cause a problem in the future if there is any shift of the conduit
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of secondary lines. No visiable signs lof leaks
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Hydro on new diesel dispenser lines conducted on this date with no visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/06/2008 User: JOHNSON_BW_1
Description: Informed by PSSSC that the tank-set would have to be rescheduled for tomorrow. Due to some weight/delivery issues, the UST's would not be delivered on site untill approximately 11:00 AM tomorrow, November 07, 2008.
Comments:
Comment Date: 11/05/2008 User: JOHNSON_BW_1
Description: Ben with PSSSC, Petroleum Equipment Const. (PEC) #pcc 056723, called on 10-28-08 to request a UST (3) installation inspection (tank set) for Thursday afternoon, 11-05-08.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Contractor set 3 DW Glasteel 2 Tanks (EQ# EQ-222), (1) 16,000 tank (UL#R382580) and (2) 8,000 gal tanks (UL #'s UL#R-382581 & UL#R-382582)
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of new primary fiberglass lines(Red Thread IIA (EQ # EQ-252). Piping for the Prem & Reg unleaded was ran into an exciting dispenser and will be connected to the exciting DW flex piping. 2 new diesel dispenser (EQ # EQ-296) were installed and the same type of fiberglass piping was install and soap tested on this date. No visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete intallation inspection.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: 11/21/08-Conduct finial inspections: Vacuum 3 DW spill buckets. Tested sensors (3 sumps, 3 Interstitials, and 2 transition sumps.) Tripped the shear valves in the 2 new diesel dispensers and the dispenser where new piping was connected to exciting DW piping.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Finial test for Tanks, LLD and lines was conmducted by Tanknology, Inc
11/05/2008 Site Inspection Activity Closed Johnson, Bill
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/05/2008
Activity Closed Date: 12/12/2008 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/17/2008 User: ZIMMERMAN_CA_1
Description: 10/14/08 - Hydro was conduct on all sump and the 2 new diesel dispensers and transition sump. No visible signs of leaks at time of inspection. Note: the entry boots for the exciting electrical conduit in the transition sump had to be replaced as they were leaking during the first hydro test. The conduit takes a 90 degree bend right after it enters the dispenser (Now the transition sump). This may cause a problem in the future if there is any shift of the conduit
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of secondary lines. No visiable signs lof leaks
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Hydro on new diesel dispenser lines conducted on this date with no visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/06/2008 User: JOHNSON_BW_1
Description: Informed by PSSSC that the tank-set would have to be rescheduled for tomorrow. Due to some weight/delivery issues, the UST's would not be delivered on site untill approximately 11:00 AM tomorrow, November 07, 2008.
Comments:
Comment Date: 11/05/2008 User: JOHNSON_BW_1
Description: Ben with PSSSC, Petroleum Equipment Const. (PEC) #pcc 056723, called on 10-28-08 to request a UST (3) installation inspection (tank set) for Thursday afternoon, 11-05-08.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Contractor set 3 DW Glasteel 2 Tanks (EQ# EQ-222), (1) 16,000 tank (UL#R382580) and (2) 8,000 gal tanks (UL #'s UL#R-382581 & UL#R-382582)
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of new primary fiberglass lines(Red Thread IIA (EQ # EQ-252). Piping for the Prem & Reg unleaded was ran into an exciting dispenser and will be connected to the exciting DW flex piping. 2 new diesel dispenser (EQ # EQ-296) were installed and the same type of fiberglass piping was install and soap tested on this date. No visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete intallation inspection.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: 11/21/08-Conduct finial inspections: Vacuum 3 DW spill buckets. Tested sensors (3 sumps, 3 Interstitials, and 2 transition sumps.) Tripped the shear valves in the 2 new diesel dispensers and the dispenser where new piping was connected to exciting DW piping.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Finial test for Tanks, LLD and lines was conmducted by Tanknology, Inc
11/05/2008 Site Inspection Activity Closed Johnson, Bill
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/05/2008
Activity Closed Date: 12/12/2008 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/17/2008 User: ZIMMERMAN_CA_1
Description: 10/14/08 - Hydro was conduct on all sump and the 2 new diesel dispensers and transition sump. No visible signs of leaks at time of inspection. Note: the entry boots for the exciting electrical conduit in the transition sump had to be replaced as they were leaking during the first hydro test. The conduit takes a 90 degree bend right after it enters the dispenser (Now the transition sump). This may cause a problem in the future if there is any shift of the conduit
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of secondary lines. No visiable signs lof leaks
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Hydro on new diesel dispenser lines conducted on this date with no visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/06/2008 User: JOHNSON_BW_1
Description: Informed by PSSSC that the tank-set would have to be rescheduled for tomorrow. Due to some weight/delivery issues, the UST's would not be delivered on site untill approximately 11:00 AM tomorrow, November 07, 2008.
Comments:
Comment Date: 11/05/2008 User: JOHNSON_BW_1
Description: Ben with PSSSC, Petroleum Equipment Const. (PEC) #pcc 056723, called on 10-28-08 to request a UST (3) installation inspection (tank set) for Thursday afternoon, 11-05-08.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Contractor set 3 DW Glasteel 2 Tanks (EQ# EQ-222), (1) 16,000 tank (UL#R382580) and (2) 8,000 gal tanks (UL #'s UL#R-382581 & UL#R-382582)
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of new primary fiberglass lines(Red Thread IIA (EQ # EQ-252). Piping for the Prem & Reg unleaded was ran into an exciting dispenser and will be connected to the exciting DW flex piping. 2 new diesel dispenser (EQ # EQ-296) were installed and the same type of fiberglass piping was install and soap tested on this date. No visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete intallation inspection.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: 11/21/08-Conduct finial inspections: Vacuum 3 DW spill buckets. Tested sensors (3 sumps, 3 Interstitials, and 2 transition sumps.) Tripped the shear valves in the 2 new diesel dispensers and the dispenser where new piping was connected to exciting DW piping.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Finial test for Tanks, LLD and lines was conmducted by Tanknology, Inc
11/05/2008 Site Inspection Activity Closed Johnson, Bill
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/05/2008
Activity Closed Date: 12/12/2008 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/17/2008 User: ZIMMERMAN_CA_1
Description: 10/14/08 - Hydro was conduct on all sump and the 2 new diesel dispensers and transition sump. No visible signs of leaks at time of inspection. Note: the entry boots for the exciting electrical conduit in the transition sump had to be replaced as they were leaking during the first hydro test. The conduit takes a 90 degree bend right after it enters the dispenser (Now the transition sump). This may cause a problem in the future if there is any shift of the conduit
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of secondary lines. No visiable signs lof leaks
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Hydro on new diesel dispenser lines conducted on this date with no visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/06/2008 User: JOHNSON_BW_1
Description: Informed by PSSSC that the tank-set would have to be rescheduled for tomorrow. Due to some weight/delivery issues, the UST's would not be delivered on site untill approximately 11:00 AM tomorrow, November 07, 2008.
Comments:
Comment Date: 11/05/2008 User: JOHNSON_BW_1
Description: Ben with PSSSC, Petroleum Equipment Const. (PEC) #pcc 056723, called on 10-28-08 to request a UST (3) installation inspection (tank set) for Thursday afternoon, 11-05-08.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Contractor set 3 DW Glasteel 2 Tanks (EQ# EQ-222), (1) 16,000 tank (UL#R382580) and (2) 8,000 gal tanks (UL #'s UL#R-382581 & UL#R-382582)
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of new primary fiberglass lines(Red Thread IIA (EQ # EQ-252). Piping for the Prem & Reg unleaded was ran into an exciting dispenser and will be connected to the exciting DW flex piping. 2 new diesel dispenser (EQ # EQ-296) were installed and the same type of fiberglass piping was install and soap tested on this date. No visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete intallation inspection.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: 11/21/08-Conduct finial inspections: Vacuum 3 DW spill buckets. Tested sensors (3 sumps, 3 Interstitials, and 2 transition sumps.) Tripped the shear valves in the 2 new diesel dispensers and the dispenser where new piping was connected to exciting DW piping.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Finial test for Tanks, LLD and lines was conmducted by Tanknology, Inc
11/05/2008 Site Inspection Activity Closed Johnson, Bill
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/05/2008
Activity Closed Date: 12/12/2008 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/17/2008 User: ZIMMERMAN_CA_1
Description: 10/14/08 - Hydro was conduct on all sump and the 2 new diesel dispensers and transition sump. No visible signs of leaks at time of inspection. Note: the entry boots for the exciting electrical conduit in the transition sump had to be replaced as they were leaking during the first hydro test. The conduit takes a 90 degree bend right after it enters the dispenser (Now the transition sump). This may cause a problem in the future if there is any shift of the conduit
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of secondary lines. No visiable signs lof leaks
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Hydro on new diesel dispenser lines conducted on this date with no visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/06/2008 User: JOHNSON_BW_1
Description: Informed by PSSSC that the tank-set would have to be rescheduled for tomorrow. Due to some weight/delivery issues, the UST's would not be delivered on site untill approximately 11:00 AM tomorrow, November 07, 2008.
Comments:
Comment Date: 11/05/2008 User: JOHNSON_BW_1
Description: Ben with PSSSC, Petroleum Equipment Const. (PEC) #pcc 056723, called on 10-28-08 to request a UST (3) installation inspection (tank set) for Thursday afternoon, 11-05-08.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Contractor set 3 DW Glasteel 2 Tanks (EQ# EQ-222), (1) 16,000 tank (UL#R382580) and (2) 8,000 gal tanks (UL #'s UL#R-382581 & UL#R-382582)
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of new primary fiberglass lines(Red Thread IIA (EQ # EQ-252). Piping for the Prem & Reg unleaded was ran into an exciting dispenser and will be connected to the exciting DW flex piping. 2 new diesel dispenser (EQ # EQ-296) were installed and the same type of fiberglass piping was install and soap tested on this date. No visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete intallation inspection.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: 11/21/08-Conduct finial inspections: Vacuum 3 DW spill buckets. Tested sensors (3 sumps, 3 Interstitials, and 2 transition sumps.) Tripped the shear valves in the 2 new diesel dispensers and the dispenser where new piping was connected to exciting DW piping.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Finial test for Tanks, LLD and lines was conmducted by Tanknology, Inc
11/05/2008 Site Inspection Activity Closed Johnson, Bill
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/05/2008
Activity Closed Date: 12/12/2008 Activity Closed By: ZIMMERMAN_CA_1
Comments:
Comment Date: 11/17/2008 User: ZIMMERMAN_CA_1
Description: 10/14/08 - Hydro was conduct on all sump and the 2 new diesel dispensers and transition sump. No visible signs of leaks at time of inspection. Note: the entry boots for the exciting electrical conduit in the transition sump had to be replaced as they were leaking during the first hydro test. The conduit takes a 90 degree bend right after it enters the dispenser (Now the transition sump). This may cause a problem in the future if there is any shift of the conduit
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of secondary lines. No visiable signs lof leaks
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Hydro on new diesel dispenser lines conducted on this date with no visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/06/2008 User: JOHNSON_BW_1
Description: Informed by PSSSC that the tank-set would have to be rescheduled for tomorrow. Due to some weight/delivery issues, the UST's would not be delivered on site untill approximately 11:00 AM tomorrow, November 07, 2008.
Comments:
Comment Date: 11/05/2008 User: JOHNSON_BW_1
Description: Ben with PSSSC, Petroleum Equipment Const. (PEC) #pcc 056723, called on 10-28-08 to request a UST (3) installation inspection (tank set) for Thursday afternoon, 11-05-08.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Contractor set 3 DW Glasteel 2 Tanks (EQ# EQ-222), (1) 16,000 tank (UL#R382580) and (2) 8,000 gal tanks (UL #'s UL#R-382581 & UL#R-382582)
Comments:
Comment Date: 11/13/2008 User: ZIMMERMAN_CA_1
Description: Conducted soap test of new primary fiberglass lines(Red Thread IIA (EQ # EQ-252). Piping for the Prem & Reg unleaded was ran into an exciting dispenser and will be connected to the exciting DW flex piping. 2 new diesel dispenser (EQ # EQ-296) were installed and the same type of fiberglass piping was install and soap tested on this date. No visible signs of leaks at time of inspection.
Comments:
Comment Date: 11/07/2008 User: ZIMMERMAN_CA_1
Description: Items on pages 3 & 4 were checked to complete intallation inspection.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: 11/21/08-Conduct finial inspections: Vacuum 3 DW spill buckets. Tested sensors (3 sumps, 3 Interstitials, and 2 transition sumps.) Tripped the shear valves in the 2 new diesel dispensers and the dispenser where new piping was connected to exciting DW piping.
Comments:
Comment Date: 11/24/2008 User: ZIMMERMAN_CA_1
Description: Finial test for Tanks, LLD and lines was conmducted by Tanknology, Inc
03/13/2008 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/13/2008
Activity Closed Date: 03/13/2008 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Dirt/Debris build up in dispenser liners. May need to be removed prior to next compliance inspection to ensure space can be properly inspected.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facoility needs to remove "Annual Tightness Test" from written release detection response form.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Electrical conduct boots in sumps may need to be replaced at time of upgrade. Starting to show signs of failure.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Single-walled USts required to be upgraded to double-walled,replaced with double-walled, or closed by 12/31/2009.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facility missing January 2008 Visuals.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Annual operability test conducted by Tanknology(John Adams-Cert #10098).
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: T1/T2 fails in August 2007 and last week of march-first week of April. Multiple passes and PLLD passes before and after. T1/T2 connected by siphon line and tests run on both.
03/13/2008 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/13/2008
Activity Closed Date: 03/13/2008 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Dirt/Debris build up in dispenser liners. May need to be removed prior to next compliance inspection to ensure space can be properly inspected.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facoility needs to remove "Annual Tightness Test" from written release detection response form.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Electrical conduct boots in sumps may need to be replaced at time of upgrade. Starting to show signs of failure.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Single-walled USts required to be upgraded to double-walled,replaced with double-walled, or closed by 12/31/2009.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facility missing January 2008 Visuals.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Annual operability test conducted by Tanknology(John Adams-Cert #10098).
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: T1/T2 fails in August 2007 and last week of march-first week of April. Multiple passes and PLLD passes before and after. T1/T2 connected by siphon line and tests run on both.
03/13/2008 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/13/2008
Activity Closed Date: 03/13/2008 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Dirt/Debris build up in dispenser liners. May need to be removed prior to next compliance inspection to ensure space can be properly inspected.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facoility needs to remove "Annual Tightness Test" from written release detection response form.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Electrical conduct boots in sumps may need to be replaced at time of upgrade. Starting to show signs of failure.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Single-walled USts required to be upgraded to double-walled,replaced with double-walled, or closed by 12/31/2009.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facility missing January 2008 Visuals.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Annual operability test conducted by Tanknology(John Adams-Cert #10098).
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: T1/T2 fails in August 2007 and last week of march-first week of April. Multiple passes and PLLD passes before and after. T1/T2 connected by siphon line and tests run on both.
03/13/2008 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/13/2008
Activity Closed Date: 03/13/2008 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Dirt/Debris build up in dispenser liners. May need to be removed prior to next compliance inspection to ensure space can be properly inspected.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facoility needs to remove "Annual Tightness Test" from written release detection response form.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Electrical conduct boots in sumps may need to be replaced at time of upgrade. Starting to show signs of failure.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Single-walled USts required to be upgraded to double-walled,replaced with double-walled, or closed by 12/31/2009.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facility missing January 2008 Visuals.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Annual operability test conducted by Tanknology(John Adams-Cert #10098).
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: T1/T2 fails in August 2007 and last week of march-first week of April. Multiple passes and PLLD passes before and after. T1/T2 connected by siphon line and tests run on both.
03/13/2008 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/13/2008
Activity Closed Date: 03/13/2008 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Dirt/Debris build up in dispenser liners. May need to be removed prior to next compliance inspection to ensure space can be properly inspected.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facoility needs to remove "Annual Tightness Test" from written release detection response form.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Electrical conduct boots in sumps may need to be replaced at time of upgrade. Starting to show signs of failure.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Single-walled USts required to be upgraded to double-walled,replaced with double-walled, or closed by 12/31/2009.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facility missing January 2008 Visuals.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Annual operability test conducted by Tanknology(John Adams-Cert #10098).
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: T1/T2 fails in August 2007 and last week of march-first week of April. Multiple passes and PLLD passes before and after. T1/T2 connected by siphon line and tests run on both.
03/13/2008 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/13/2008
Activity Closed Date: 03/13/2008 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Dirt/Debris build up in dispenser liners. May need to be removed prior to next compliance inspection to ensure space can be properly inspected.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facoility needs to remove "Annual Tightness Test" from written release detection response form.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Electrical conduct boots in sumps may need to be replaced at time of upgrade. Starting to show signs of failure.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Single-walled USts required to be upgraded to double-walled,replaced with double-walled, or closed by 12/31/2009.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facility missing January 2008 Visuals.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Annual operability test conducted by Tanknology(John Adams-Cert #10098).
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: T1/T2 fails in August 2007 and last week of march-first week of April. Multiple passes and PLLD passes before and after. T1/T2 connected by siphon line and tests run on both.
03/13/2008 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/13/2008
Activity Closed Date: 03/13/2008 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Dirt/Debris build up in dispenser liners. May need to be removed prior to next compliance inspection to ensure space can be properly inspected.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facoility needs to remove "Annual Tightness Test" from written release detection response form.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Electrical conduct boots in sumps may need to be replaced at time of upgrade. Starting to show signs of failure.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Single-walled USts required to be upgraded to double-walled,replaced with double-walled, or closed by 12/31/2009.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Facility missing January 2008 Visuals.
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: Annual operability test conducted by Tanknology(John Adams-Cert #10098).
Comments:
Comment Date: 03/13/2008 User: JOHNSON_SG_1
Description: T1/T2 fails in August 2007 and last week of march-first week of April. Multiple passes and PLLD passes before and after. T1/T2 connected by siphon line and tests run on both.
08/16/2007 Record Document Activity Zimmerman, Chris A.
Activity Status: Closed
Contact Name: Tammy Scott Activity Closed Date: 04/14/2008
Comments:
Comment Date: 08/16/2007 User: ZIMMERMAN_CA_1
Description: Veeder Root leak test failed alarm
Comments:
Comment Date: 04/14/2008 User: ZIMMERMAN_CA_1
Description: Resolved during annual compliance inspection.
08/16/2007 Record Document Activity Zimmerman, Chris A.
Activity Status: Closed
Contact Name: Tammy Scott Activity Closed Date: 04/14/2008
Comments:
Comment Date: 08/16/2007 User: ZIMMERMAN_CA_1
Description: Veeder Root leak test failed alarm
Comments:
Comment Date: 04/14/2008 User: ZIMMERMAN_CA_1
Description: Resolved during annual compliance inspection.
05/02/2007 Attachment Zimmerman, Chris A.
04/26/2007 Comment Johnson, Stephen G.
Description: Facility has 3 SW USTs(unleadeds are Manifolded) equipped with DW APT piping, Sensors in sumps, Simplicity veeder-root, 3 sumps, 3 fills, 6 dispensers, PLLD, and an impressed current CP system. Facilities primary form or release detection is monthly visuals, liquid status, pllds, CP, and CSLD.
04/26/2007 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/26/2007
Activity Closed Date: 04/26/2007 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 04/26/2007 User: JOHNSON_SG_1
Description: Multiple T1/T2 fails on CSLD throughout year. Facility keeps daily CSLD tapes and has a compartmented system. Facility has shown at least 1 pass every month on CSLD tapes.
Comments:
Comment Date: 04/26/2007 User: JOHNSON_SG_1
Description: Facility to ensure release detection si conducted once a month, NOT TO EXCEED 35 DAYS.
04/26/2007 Site Inspection Activity Closed Johnson, Stephen G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/26/2007
Activity Closed Date: 04/26/2007 Activity Closed By: JOHNSON_SG_1
Comments:
Comment Date: 04/26/2007 User: JOHNSON_SG_1
Description: Multiple T1/T2 fails on CSLD throughout year. Facility keeps daily CSLD tapes and has a compartmented system. Facility has shown at least 1 pass every month on CSLD tapes.
Comments:
Comment Date: 04/26/2007 User: JOHNSON_SG_1
Description: Facility to ensure release detection si conducted once a month, NOT TO EXCEED 35 DAYS.
04/26/2007 Attachment Johnson, Stephen G.
04/26/2007 Attachment Johnson, Stephen G.
04/26/2007 Attachment Johnson, Stephen G.
04/26/2007 Attachment Johnson, Stephen G.
04/26/2007 Attachment Johnson, Stephen G.
04/26/2007 Attachment Johnson, Stephen G.
04/26/2007 Comment Johnson, Stephen G.
Description: Facility has 3 SW USTs(unleadeds are Manifolded) equipped with DW APT piping, Sensors in sumps, Simplicity veeder-root, 3 sumps, 3 fills, 6 dispensers, PLLD, and an impressed current CP system. Facilities primary form or release detection is monthly visuals, liquid status, pllds, CP, and CSLD.
04/26/2007 Comment Johnson, Stephen G.
Description: Facility has 3 SW USTs(unleadeds are Manifolded) equipped with DW APT piping, Sensors in sumps, Simplicity veeder-root, 3 sumps, 3 fills, 6 dispensers, PLLD, and an impressed current CP system. Facilities primary form or release detection is monthly visuals, liquid status, pllds, CP, and CSLD.
04/26/2007 Comment Johnson, Stephen G.
Description: Facility has 3 SW USTs(unleadeds are Manifolded) equipped with DW APT piping, Sensors in sumps, Simplicity veeder-root, 3 sumps, 3 fills, 6 dispensers, PLLD, and an impressed current CP system. Facilities primary form or release detection is monthly visuals, liquid status, pllds, CP, and CSLD.
02/05/2007 Emergency Preparedness Information Activity Zimmerman, Chris A.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/05/2007
10/20/2006 Record Document Activity Johnson, Stephen G.
Activity Status: Closed
Contact Name: Tammy Scott Activity Closed Date: 01/14/2008
Comments:
Comment Date: 10/20/2006 User: JOHNSON_SG_1
Description: Veeder-root dispatched a tank periodic leak test failed alarm on the regular product. JMP solutions will investigate the alarm condiction.
09/20/2006 Emergency Preparedness Information Activity Johnson, Stephen G.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/20/2006
Comments:
Comment Date: 09/20/2006 User: JOHNSON_SG_1
Description: Spoke with manager
09/13/2006 Record Document Activity Rupp, Siegfried
Activity Status: Closed
Contact Name: Tammy Scott Activity Closed Date: 01/14/2008
Comments:
Comment Date: 09/13/2006 User: RUPP_SS
Description: Veeder Root dispached a tank periodic leak test failed alarm on the regular product. JMP Solutions will investigate the alarm. The discovery date is 8/28/2006. I will notify you of their findings upon investigation.. All resolution documentation in file
09/13/2006 Record Document Activity Rupp, Siegfried
Activity Status: Closed
Contact Name: Tammy Scott Activity Closed Date: 01/14/2008
Comments:
Comment Date: 09/13/2006 User: RUPP_SS
Description: Veeder Root dispatched JMP Solutions on 9/07/2006 to investigate a sensor fuel alarm for the # 2 STP. Date of discovery is 9/08/2006 I will notify you of their findings upon inspection. All resolution documentation in file.
02/11/2006 Comment MIGRATION
Description: REGISTRATION: OPERATOR HAS INDICATED TANKS 1,2,AND 3 WILL HAVE OVERFILL PRO- TECTORS AND MONITORING DEVICES INSTALLED BY THE END OF 1986.
01/20/2006 Legacy Activity Johnson, Stephen G.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
01/18/2006 Violation Closed Unknown, User
Significance: Minor Status: Closed
Criteria ID: 1112
Rule: 62-761.700(1)(b)2.a.
Comments: Review documentation to confirm the test cycle. Has construction at the facility occurred in the area of the cathodic protection system? This activity may warrant testing of the system to ensure continued operation of the system. If a tank with factory installed anodes (such as a STI-P3), and cathodic protection was installed on the piping during installation, then the tank would need a structure to soil test every three years and the piping would be tested every year. Note that Florida does not have any equipment approval for piping with factory installed anodes.
Comments:
Comment Date: 03/26/2014 User: COLSON_NJ_1
Description: JRS, Inc. custom fabrication tank - EQ#497. Morrison Bros. spill bucket - EQ#345. Rochester level gauge for overfill protection. Madison M7000 sensors present for leak detection & high fuel level - EQ#682. Baldor generator panel monitors the status of the sensors.
01/18/2006 Violation Closed Unknown, User
Significance: Minor Status: Closed
Criteria ID: 1010
Rule: 62-761.450(2)(a)1., 62-761.450(2)(a)2., 62-761.450(2)(a)3., 62-761.450(2)(a)4., 62-761.450(2)(a)5., 62-761.450(2)(a)6., 62-761.450(2)(a)7.
Comments: Multiple incidents occurring at the same time at the facility may be reported on one form. #1-3 - Evidence of these types of INF situations are generally found during the inspector's paperwork review. Ask the facility representative what action they took in response, and in what time frame. If the situations are resolved within 24 hours, the owner/operator is not required to submit an INF to the local program. However, the actions they took to resolve the issue must be documented. #4-5, and 7 - Evidence of these types of situations are generally found during the outside or physical portion of the inspection. Give the facility owner/operator 24 hours to resolve, provided they document their actions. If they can not resolve the issues then they must submit the INF, at which time the two week investigative window opens. #6 - Evidence of this type of situation may be found during the physical examination of the release detection device (e.g. alarm mode), or during the examination of the records associated with the method. Note: Inspectors may find events that qualify as incidents during their review of the facility's paperwork. Such issues must have been resolved within 24 hours if an INF was not submitted at the time of the event.
Comments:
Comment Date: 09/13/2011 User: WINN_JP_1
Description: See attachments for components checklist.
01/18/2006 Violation Closed Unknown, User
Significance: SNC-B Status: Closed
Criteria ID: 1073
Rule: 62-761.610(1)(a)
Comments: Mark this as out of compliance if the storage tank system has a method of release detection available, but the method is improper. Some examples are: monitoring wells used without a site suitability determination; interstitial sensors improperly located, or no sensor at all; SIR contract signed but not performed; inventory control with annual tightness test listed as method, but no test results available or inventory records are incomplete, incorrect or missing; etc.
Comments:
Comment Date: 11/19/2015 User: DEZAYAS_A_1
Description: EQ#275
01/18/2006 Legacy Activity Johnson, Stephen G.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: PIPING - DW APT RD - MONTHLY VISUALS/LIQUID STATUS/CP 2/7/2005 - LINES,LLD, AND ATG TESTED/PASSED 1/8/2005 - CP TESTED/PASSED - RAY DAVIS
09/29/2004 Legacy Activity Johnson, Stephen G.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: PIPING- DW APT RDRL- CSLD, MONTHLY VISUALS
07/15/2003 Legacy Activity Demack, Paul J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: PIPING=DW APT FLEX RDRL=CSLD/MONTHLY VISUAL INSPECTIONS
07/18/2002 Legacy Activity Peck, Patrick
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
07/18/2001 Legacy Activity Unknown, User
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
07/25/2000 Legacy Activity Unknown, User
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: FACILITY NEEDS TO HAVE A INTERNAL TANK INSPECTION BY OCT. 2000
07/23/1999 Legacy Activity Unknown, User
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
07/06/1998 Legacy Activity Mele, Vince N.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed