Facility ID: 8520885
Facility Name: EXXON-OSPREY
 
11/12/2024 Enforcement Tracking Activity Chang, Louise
Activity Status: Open
06/05/2024 Site Inspection Activity Closed Tykoski, Bradley R
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/31/2024
Activity Closed Date: 06/12/2024 Activity Closed By: TYKOSKI_B_1
Events:
Event Type: Activity has been finished Date: 06/12/2024
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 06/12/2024
Comment: Approved by John Hickey: approved
Events:
Event Type: Activity has been submitted for approval Date: 06/06/2024
Comment: Submitted for approval by: Bradley R Tykoski
Attachments:
Attachment Date: 06/06/2024 User: TYKOSKI_B_1
Description: Premium Double-Wall Spill Bucket
View Attachment
Attachments:
Attachment Date: 06/06/2024 User: TYKOSKI_B_1
Description: Premium Spill Bucket Replacement Documents
View Attachment
06/05/2024 Site Inspection Activity Closed Tykoski, Bradley R
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/31/2024
Activity Closed Date: 07/09/2024 Activity Closed By: TYKOSKI_B_1
Events:
Event Type: Activity has been submitted for approval Date: 06/17/2024
Comment: Submitted for approval by: Bradley R Tykoski
Events:
Event Type: Activity/Document has been approved Date: 06/24/2024
Comment: Approved by John Hickey: approved
Events:
Event Type: Activity has been finished Date: 07/09/2024
Comment: Finished
05/31/2024 Violation Open Tykoski, Bradley R
Significance: Minor Status: Open
Criteria ID: 6066
Rule: 62-761.700(1)(c), 62-761.700(1)(c)1, 62-761.700(1)(c)2
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Regular STP
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Premium STP
View Attachment
05/31/2024 Site Inspection Activity Closed Tykoski, Bradley R
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/31/2024
Activity Closed Date: 06/24/2024 Activity Closed By: TYKOSKI_B_1
Events:
Event Type: Activity/Document has been approved Date: 06/24/2024
Comment: Approved by John Hickey: approved
Events:
Event Type: Activity has been finished Date: 06/24/2024
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 06/24/2024
Comment: Submitted for approval by: Bradley R Tykoski
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Dispenser #9/10 Sump
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Dispenser #7/8 Sump
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Tank Vent Stack Pipes
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Premium Tank Field
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Dispenser #3/4 Sump
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Dispenser #11/12 Sump
View Attachment
Attachments:
Attachment Date: 05/31/2024 User: TYKOSKI_B_1
Description: Testing Report August 2023
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Regular Vapor Port/Spill Bucket
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Premium STP/Sump
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Unleaded Tank Field
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Regular STP/Sump
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Dispenser #5/6 Sump
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Dispenser #1/2 Sump
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Regular Fill Port/Spill Bucket
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Premium Fill Port/Spill Bucket
View Attachment
05/31/2024 Violation Open Tykoski, Bradley R
Significance: Minor Status: Open
Criteria ID: 6008
Rule: 62-761.405(1), 62-761.405(1)(a), 62-761.405(1)(b), 62-761.405(1)(c), 62-761.405(2), 62-761.405(2)(a), 62-761.405(2)(b), 62-761.405(2)(c), 62-761.405(2)(d)
05/31/2024 Violation Open Tykoski, Bradley R
Significance: Minor Status: Open
Criteria ID: 6082
Rule: 62-761.800(3), 62-761.800(3)(a), 62-761.800(3)(a)1, 62-761.800(3)(a)2, 62-761.800(3)(a)3, 62-761.800(3)(a)4, 62-761.800(3)(a)5, 62-761.800(3)(a)6
05/31/2024 Violation Open Tykoski, Bradley R
Significance: SNC-B Status: Open
Criteria ID: 6080
Rule: 62-761.800(2)(b), 62-761.800(2)(b)1, 62-761.800(2)(b)2, 62-761.800(2)(b)3, 62-761.800(2)(b)4, 62-761.800(2)(b)5, 62-761.800(2)(b)6
05/31/2024 Violation Open Tykoski, Bradley R
Significance: SNC-B Status: Open
Criteria ID: 6084
Rule: 62-761.800(3)(c), 62-761.800(3)(c)1, 62-761.800(3)(c)2, 62-761.800(3)(c)3
05/31/2024 Violation Open Tykoski, Bradley R
Significance: Minor Status: Open
Criteria ID: 6004
Rule: 62-761.400(1)(c), 62-761.400(2)(b)
05/31/2024 Violation Open Tykoski, Bradley R
Significance: Minor Status: Open
Criteria ID: 6008
Rule: 62-761.405(1), 62-761.405(1)(a), 62-761.405(1)(b), 62-761.405(1)(c), 62-761.405(2), 62-761.405(2)(a), 62-761.405(2)(b), 62-761.405(2)(c), 62-761.405(2)(d)
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Premium Fill Port with OPV
View Attachment
Attachments:
Attachment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Regular Fill Port with OPV
View Attachment
05/30/2024 Enforcement Referral Activity Tykoski, Bradley R
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 11/12/2024
Events:
Event Type: Activity has been submitted for approval Date: 05/30/2024
Comment: Submitted for approval by: Bradley R Tykoski: Site being referred due to site still having outstanding violations and being Under Enforcement following May 2024 Routine Compliance Inspection.
Events:
Event Type: Activity has been finished Date: 11/12/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 11/12/2024
Comment: Accepted by Louise Chang: Case to be assigned to Lina Cerquera
Events:
Event Type: Activity/Document was acknowledged on this date Date: 11/12/2024
Comment: Acknowledged and Assigned by Louise Chang
Events:
Event Type: Activity has been assigned Date: 11/12/2024
Comment: Assigned to Louise Chang
Comments:
Comment Date: 05/30/2024 User: TYKOSKI_B_1
Description: Site being referred due to site still having outstanding violations and being Under Enforcement following May 2024 Routine Compliance Inspection.
Attachments:
Attachment Date: 05/30/2024 User: TYKOSKI_B_1
Description: Referral Letter
View Attachment
Attachments:
Attachment Date: 05/30/2024 User: TYKOSKI_B_1
Description: Referral Letter & 2024 Inspection Report EmailEmail
View Attachment
05/17/2024 Electronic Communication Activity Tykoski, Bradley R
Activity Closed Date: 05/17/2024 Activity Status: Closed
Date: 05/17/2024
Recipient: jallooilfl@gmail.com & JALLOOIL@GMAIL.COM
Sender: Brad Tykoski
Subject: Upcoming Mandatory Underground Storage Tank (UST) Compliance Inspection for EXXON-OSPREY (FAC ID: 8520885) 05/10/2024 at 9:30am
Message: See attachment.
Events:
Event Type: Activity has been finished Date: 05/17/2024
Comment: Finished
Attachments:
Attachment Date: 05/17/2024 User: TYKOSKI_B_1
Description: Inspection Notification Email
View Attachment
05/13/2024 Violation Open Tykoski, Bradley R
Significance: Minor Status: Open
Criteria ID: 6001
Rule: 62-761.100(3)
Comments:
Comment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Access provided on 31 May 2024.
05/13/2024 Phone Conversation Activity Tykoski, Bradley R
Call Type: Outgoing Activity Status: Closed
Phone Number: (813) 752-3190 Activity Closed Date: 05/13/2024
Subject: Brad Tykoski called Hy-Tech to request missing testing documents and coordinate when they will be on site so I can perform a visual of the sumps and spill buckets. Steven Zugg was out of the office and left voicemail.
Events:
Event Type: Activity has been finished Date: 05/13/2024
Comment: Finished
05/13/2024 Site Inspection Activity Closed Tykoski, Bradley R
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/13/2024
Activity Closed Date: 05/30/2024 Activity Closed By: TYKOSKI_B_1
Events:
Event Type: Activity has been submitted for approval Date: 05/28/2024
Comment: Submitted for approval by: Bradley R Tykoski
Events:
Event Type: Activity has not been approved Date: 05/28/2024
Comment: Not approved by John Hickey: As discussed, please get with Lina before we finalize this one.
Events:
Event Type: Activity has been submitted for approval Date: 05/29/2024
Comment: Submitted for approval by: Bradley R Tykoski
Events:
Event Type: Activity/Document has been approved Date: 05/30/2024
Comment: Approved by John Hickey: Approved
Events:
Event Type: Activity has been finished Date: 05/30/2024
Comment: Finished
Comments:
Comment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Testing paperwork incorrectly states both tanks are Regular Unleaded and are 12,000-gallons. One Tank is Premium and 10,000-gallons.
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: 1/20/2023-1/20/2024 Part D Page 3
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Veeder-Root 8/2/2022 by Hy-Tech Petroleum
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Service Call Report 8/2/2022 Hy-Tech Petroleum
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: ATG Operability 8/2/2022 by Hy-Tech Petroleum
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: 1/20/2023-1/20/2024 Part D Page 2
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: 1/20/2023-1/20/2024 Part P
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: INF Discovered 1/20/2022-form completed 8/4/2022
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Site View
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: 1/20/2023-1/20/2024 Policy Cover Page
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Tank Secondary Testing (both tanks) 8/3/2022 by Hy-Tech
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Tank Vent Stack Pipe
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Premium Tank Field
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Displayed Storage Tank Registration Placard
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Line Leak 8/16/2022 by Hy-Tech Petroleum
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: 1/20/2023-1/20/2024 Part D Page 1
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Overfill 8/3/2022 by Hy-Tech Petroleum
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Dispensers
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Alternative Procedure Form Page 2 Attachment
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Regular Tank Field
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Service Call Report 8/3/2022 Hy-Tech Petroleum
View Attachment
Attachments:
Attachment Date: 05/13/2024 User: TYKOSKI_B_1
Description: Unsigned Alternative Procedure Form
View Attachment
05/13/2024 Violation Open Tykoski, Bradley R
Significance: SNC-B Status: Open
Criteria ID: 6011
Rule: 62-761.420(2)
Comments:
Comment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Insurance Provider will not provide policy while tanks are still registered as out of service. Insurance provider agreed to back date policy to January 2024 once tanks are placed into service and new policy can be issued.
Comments:
Comment Date: 05/28/2024 User: TYKOSKI_B_1
Description: - No proof of current Financial Responsibility as of 1/20/2024. - No Financial Responsibility documents provided during or following the inspection to show coverage from 1/20/2024 to current. - Financial Responsibility forms (Part D – Certificate of Insurance and Part P - Financial Responsibility Form) were completed for 1/20/2023-1/20/2024 as required and provided during the inspection.
05/13/2024 Violation Open Tykoski, Bradley R
Significance: SNC-B Status: Open
Criteria ID: 6011
Rule: 62-761.420(2)
Comments:
Comment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Insurance Provider will not provide policy while tanks are still registered as out of service. Insurance provider agreed to back date policy to January 2024 once tanks are placed into service and new policy can be issued.
Comments:
Comment Date: 05/28/2024 User: TYKOSKI_B_1
Description: - No proof of current Financial Responsibility as of 1/20/2024. - No Financial Responsibility documents provided during or following the inspection to show coverage from 1/20/2024 to current. - Financial Responsibility forms (Part D – Certificate of Insurance and Part P - Financial Responsibility Form) were completed for 1/20/2023-1/20/2024 as required and provided during the inspection.
03/10/2023 Site Inspection Activity Open Cerquera, Lina
Activity Status: Open
On-Site Start Date: 03/10/2023
07/18/2022 Phone Conversation Activity Cerquera, Lina
Call Type: Outgoing Activity Status: Closed
Phone Number: (727) 366-1678 Activity Closed Date: 07/18/2022
Subject: Spoke to S. Jallo. Received the letter but has been out of the country and unable to make contact. Will call back on 7/14 or have her father Paul Jallo call back on 7/14/22.
Events:
Event Type: Activity has been finished Date: 07/18/2022
Comment: Finished
07/18/2022 Editable Letter Activity Cerquera, Lina
Activity Title: Warning Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/28/2022
Comment: Sent
Events:
Event Type: Activity has been finished Date: 07/18/2022
Comment: Finished
Attachments:
Attachment Date: 07/18/2022 User: CERQUERA_L
Description: Warning Letter
View Attachment
07/18/2022 Phone Conversation Activity Cerquera, Lina
Call Type: Outgoing Activity Status: Closed
Phone Number: (727) 366-1678 Activity Closed Date: 07/18/2022
Subject: Unable to speak to anyone but left voicemail requesting a call back. No call back received on 7/14/22 as agreed.
Events:
Event Type: Activity has been finished Date: 07/18/2022
Comment: Finished
03/18/2022 Enforcement Tracking Activity Snyder, Ryan B
Activity Status: Open
02/09/2022 Enforcement Referral Activity Murphy, Maggie A
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/18/2022
Events:
Event Type: Activity has been submitted for approval Date: 02/09/2022
Comment: Submitted for approval by: Maggie A Murphy: Please find the attached inspection report for enforcement per our discussion.
Events:
Event Type: Activity has been assigned Date: 03/18/2022
Comment: Assigned to Ryan B Snyder
Events:
Event Type: Activity/Document was accepted on this date Date: 03/18/2022
Comment: Accepted by Ryan B Snyder: accept
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/18/2022
Comment: Acknowledged and Assigned by Ryan B Snyder
Events:
Event Type: Activity has been finished Date: 03/18/2022
Comment: Finished
Comments:
Comment Date: 02/09/2022 User: MURPHY_MA_1
Description: This site is being submitted for enforcement per our discussion. The site is receiving gas without valid registration or placard and was previously out of service in excess of ten years.
Comments:
Comment Date: 02/09/2022 User: MURPHY_MA_1
Description: Please find the attached inspection report for enforcement per our discussion.
02/09/2022 Enforcement Referral Activity Murphy, Maggie A
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/18/2022
Events:
Event Type: Activity has been submitted for approval Date: 02/09/2022
Comment: Submitted for approval by: Maggie A Murphy: Please find the attached inspection report for enforcement per our discussion.
Events:
Event Type: Activity has been assigned Date: 03/18/2022
Comment: Assigned to Ryan B Snyder
Events:
Event Type: Activity/Document was accepted on this date Date: 03/18/2022
Comment: Accepted by Ryan B Snyder: accept
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/18/2022
Comment: Acknowledged and Assigned by Ryan B Snyder
Events:
Event Type: Activity has been finished Date: 03/18/2022
Comment: Finished
Comments:
Comment Date: 02/09/2022 User: MURPHY_MA_1
Description: This site is being submitted for enforcement per our discussion. The site is receiving gas without valid registration or placard and was previously out of service in excess of ten years.
Comments:
Comment Date: 02/09/2022 User: MURPHY_MA_1
Description: Please find the attached inspection report for enforcement per our discussion.
01/28/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6008
Rule: 62-761.405(1), 62-761.405(1)(a), 62-761.405(1)(b), 62-761.405(1)(c), 62-761.405(2), 62-761.405(2)(a), 62-761.405(2)(b), 62-761.405(2)(c), 62-761.405(2)(d)
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: Current Registered Owner (Osprey Amoco Inc) matches in FIRST, Property Appraiser, and SunBiz. Osprey Amoco Inc has a begin date of 8/9/2022 in FIRST. Tanks still registered as Out-Of-Service in FIRST.
01/28/2022 Record Document Activity Murphy, Maggie A
Activity Status: Closed
Contact Name: Stacy Jallos Activity Closed Date: 01/28/2022
Events:
Event Type: Activity has been finished Date: 01/28/2022
Comment: Finished
01/26/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6043
Rule: 62-761.500(4)(b)
Comments:
Comment Date: 05/28/2024 User: TYKOSKI_B_1
Description: Fill-Port covers marked in accordance with API Recommended Practice 1637, 4th Edition, April 2020.
01/26/2022 Electronic Communication Activity Murphy, Maggie A
Activity Closed Date: 01/28/2022 Activity Status: Closed
Date: 01/26/2022
Recipient: Sara.Vinas@oneCorpGlobal.com
Sender: Maggie Murphy
Subject: Initial scheduling email
Message: see attached.
Events:
Event Type: Activity has been finished Date: 01/28/2022
Comment: Finished
01/26/2022 Electronic Communication Activity Murphy, Maggie A
Activity Closed Date: 01/28/2022 Activity Status: Closed
Date: 01/26/2022
Recipient: Maggie Murphy
Sender: Stacy Jallo
Subject: Email reply from new owner
Message: see attached
Events:
Event Type: Activity has been finished Date: 01/28/2022
Comment: Finished
01/26/2022 Electronic Communication Activity Murphy, Maggie A
Activity Closed Date: 01/28/2022 Activity Status: Closed
Date: 01/26/2022
Recipient: stacy Jallo
Sender: Maggie Murphy
Subject: Osprey Store
Message: see attached emal
Events:
Event Type: Activity has been finished Date: 01/28/2022
Comment: Finished
01/26/2022 Electronic Communication Activity Murphy, Maggie A
Activity Closed Date: 01/28/2022 Activity Status: Closed
Date: 01/26/2022
Recipient: Maggie Murphy
Sender: Ricardo A. Gonzalez
Subject: Upcoming Mandatory Inpsection
Message: closing documents and bill of sale included in email outlining sale of site on December 17th 2020. see attached email
Events:
Event Type: Activity has been finished Date: 01/28/2022
Comment: Finished
01/26/2022 Electronic Communication Activity Murphy, Maggie A
Activity Closed Date: 01/28/2022 Activity Status: Closed
Date: 01/26/2022
Recipient: Stacy Jallo
Sender: Sara Vinas sara.vinas@onecorpglobal.com
Subject: 2021 STFRForm completed unsigned
Message: email exchange regarding registration please see attached email.
Events:
Event Type: Activity has been finished Date: 01/28/2022
Comment: Finished
01/25/2022 Violation Open Murphy, Maggie A
Significance: SNC-B Status: Open
Criteria ID: 6078
Rule: 62-761.800(1)(e)
Comments:
Comment Date: 05/21/2024 User: TYKOSKI_B_1
Description: During Routine Compliance Inspection on 5/13/2024 facility is actively using tanks while they are still showing out-of-service in FIRST.
01/25/2022 Site Inspection Activity Closed Murphy, Maggie A
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 01/20/2022
Activity Closed Date: 01/28/2022 Activity Closed By: MURPHY_MA_1
Events:
Event Type: Activity has been finished Date: 01/28/2022
Comment: Finished
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6003
Rule: 62-761.400(1)(b), 62-761.400(2), 62-761.400(2)(a), 62-761.400(3), 62-761.400(3)(a), 62-761.400(3)(b), 62-761.400(3)(c)
Comments:
Comment Date: 05/23/2024 User: TYKOSKI_B_1
Description: Current Registered Owner (Osprey Amoco Inc) matches in FIRST, Property Appraiser, and SunBiz. Osprey Amoco Inc has a begin date of 8/9/2022 in FIRST.
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6077
Rule: 62-761.800(1)(c), 62-761.800(1)(d)4
Comments:
Comment Date: 05/21/2024 User: TYKOSKI_B_1
Description: During Routine Compliance Inspection on 5/13/2024 Testing records for 8/22/2022 were on file. 2023-2024 records were not provided.
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: Site is operating as in service and has active tank liquid level probe to monitor level. All operability testing is current. Annual Integrity testing records: - Release Detection (Documents indicate site no longer conducts electronic monitoring) - Overfill Protection (Completed on 8/3/2022 and 8/1/2023 by Hy-Tech Petroleum) - Line Leak Detectors (Completed 8/16/2022 and 8/1/2023 by Hy-Tech Petroleum) - Regular Single-Wall Spill Bucket (Completed 1/25/2022 by SPATCO, & by Hy-Tech Petroleum on12/22/2022 and 1/20/2023 ) 3-year Integrity testing records: - Premium Double-Wall Spill Bucket (Completed 12/22/2022, 1/20/2023 by Hy-Tech Petroleum) - STP Sumps (Completed 1/25/2022 by SPATCO) - Dispenser Sumps (Completed 1/25/2022 by SPATCO) As Required testing records: - Tank Tightness (Completed 1/11/2022 by Adams Tank & Lift) - Tank Secondary (Completed 8/3/2022 by Hy-Tech Petroleum)
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6077
Rule: 62-761.800(1)(c), 62-761.800(1)(d)4
Comments:
Comment Date: 05/21/2024 User: TYKOSKI_B_1
Description: During Routine Compliance Inspection on 5/13/2024 Testing records for 8/22/2022 were on file. 2023-2024 records were not provided.
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: Site is operating as in service and has active tank liquid level probe to monitor level. All operability testing is current. Annual Integrity testing records: - Release Detection (Documents indicate site no longer conducts electronic monitoring) - Overfill Protection (Completed on 8/3/2022 and 8/1/2023 by Hy-Tech Petroleum) - Line Leak Detectors (Completed 8/16/2022 and 8/1/2023 by Hy-Tech Petroleum) - Regular Single-Wall Spill Bucket (Completed 1/25/2022 by SPATCO, & by Hy-Tech Petroleum on12/22/2022 and 1/20/2023 ) 3-year Integrity testing records: - Premium Double-Wall Spill Bucket (Completed 12/22/2022, 1/20/2023 by Hy-Tech Petroleum) - STP Sumps (Completed 1/25/2022 by SPATCO) - Dispenser Sumps (Completed 1/25/2022 by SPATCO) As Required testing records: - Tank Tightness (Completed 1/11/2022 by Adams Tank & Lift) - Tank Secondary (Completed 8/3/2022 by Hy-Tech Petroleum)
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
Comments:
Comment Date: 05/23/2024 User: TYKOSKI_B_1
Description: Report states ball valves replaced with OPW EQ#697 (unverified as no Component Closure/Install Inspection on record & no access during this inspection. Overfill Protection testing completed on 8/3/2022 by Hy-Tech Petroleum. Currently past due (8/31/2023).
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: Overfill Protection testing completed on 8/3/2022 and 8/1/2023 by Hy-Tech Petroleum. Service Report provided with EQ#s (EQ#-697). Verified during site visit on 5/31/2024 that Ball Vent Valves replaced with OPW Overfill Shut-Off Valves. Overfill Prevention provided and has current passing testing.
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
Comments:
Comment Date: 05/23/2024 User: TYKOSKI_B_1
Description: Report states ball valves replaced with OPW EQ#697 (unverified as no Component Closure/Install Inspection on record & no access during this inspection. Overfill Protection testing completed on 8/3/2022 by Hy-Tech Petroleum. Currently past due (8/31/2023).
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: Overfill Protection testing completed on 8/3/2022 and 8/1/2023 by Hy-Tech Petroleum. Service Report provided with EQ#s (EQ#-697). Verified during site visit on 5/31/2024 that Ball Vent Valves replaced with OPW Overfill Shut-Off Valves. Overfill Prevention provided and has current passing testing.
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
Comments:
Comment Date: 05/21/2024 User: TYKOSKI_B_1
Description: During Routine Compliance Inspection on 5/13/2024 no access was provided to STP Sumps, Dispenser Sumps, or Spill Buckets.
Comments:
Comment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Access to all sumps and spill buckets was provided on 31 May 2024. All sumps were dry or had less than 1". Dispenser sumps has some debris that should be removed for a better visual inspection. Debris could potentially cover up any cracks or damage to the sumps.
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
Comments:
Comment Date: 05/21/2024 User: TYKOSKI_B_1
Description: During Routine Compliance Inspection on 5/13/2024 no access was provided to STP Sumps, Dispenser Sumps, or Spill Buckets.
Comments:
Comment Date: 06/03/2024 User: TYKOSKI_B_1
Description: Access to all sumps and spill buckets was provided on 31 May 2024. All sumps were dry or had less than 1". Dispenser sumps has some debris that should be removed for a better visual inspection. Debris could potentially cover up any cracks or damage to the sumps.
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6072
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1, 62-761.700(3)(a)1.a, 62-761.700(3)(a)1.b, 62-761.700(3)(a)1.c, 62-761.700(3)(a)1.d, 62-761.700(3)(a)1.e, 62-761.700(3)(a)1.f, 62-761.700(3)(a)1.g, 62-761.700(3)(a)2
Comments:
Comment Date: 05/21/2024 User: TYKOSKI_B_1
Description: - Line Leak Detectors (Completed 8/16/2022 by Hy-Tech Petroleum) (Past Due 8/31/2023) - Single-Wall Spill Buckets (Completed 1/25/2022 by SPATCO & 1/20/2023 by Hy-Tech Petroleum) (Past Due 1/31/2024) - STP Sumps (Completed 1/25/2022 by SPATCO) (Due 1/31/2025) - Dispenser Sumps (Completed 1/25/2022 by SPATCO) (Due 1/31/2025) - Tank Tightness (Completed 1/11/2022 by Adams Tank & Lift) - Tank Secondary (Completed 8/3/2022 by Hy-Tech Petroleum)
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6062
Rule: 62-761.600(4)
Comments:
Comment Date: 05/21/2024 User: TYKOSKI_B_1
Description: During Routine Compliance Inspection on 5/13/2024 2022 inspection records were provided. The Annual ATG Operability test did NOT include annular space sensors. Service Report from 8/22/2022 from Hy-Tech states STP sump sensors removed and will be monitored manually.
01/25/2022 Violation Open Murphy, Maggie A
Significance: SNC-A Status: Open
Criteria ID: 6007
Rule: 62-761.400(7), 62-761.400(7)(a), 62-761.400(7)(b)
Comments:
Comment Date: 05/23/2024 User: TYKOSKI_B_1
Description: Site has a 2023-2024 Placard displayed on site.
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6067
Rule: 62-761.700(1)(d)
Comments:
Comment Date: 05/28/2024 User: TYKOSKI_B_1
Description: Annual Operability Testing Records - Release Detection (Documents indicate site no longer conducts electronic monitoring. No manual monitoring records provided) - Overfill Protection (Completed 8/3/2022 by Hy-Tech Petroleum) (Past Due 8/31/2023) - Line Leak Detectors (Completed 8/16/2022 by Hy-Tech Petroleum) (Past Due 8/31/2023) - Single-Wall Spill Buckets (Completed 1/25/2022 by SPATCO & 1/20/2023 by Hy-Tech Petroleum) (Past Due 1/31/2024) 3-year Integrity testing records - STP Sumps (Completed 1/25/2022 by SPATCO) (Due 1/31/2025) - Dispenser Sumps (Completed 1/25/2022 by SPATCO) (Due 1/31/2025) As Required testing records - Tank Tightness (Completed 1/11/2022 by Adams Tank & Lift) - Tank Secondary (Completed 8/3/2022 by Hy-Tech Petroleum)
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: All Operability Testing Current Annual Integrity testing records: - Release Detection (Documents indicate site no longer conducts electronic monitoring) - Overfill Protection (Completed on 8/3/2022 and 8/1/2023 by Hy-Tech Petroleum) - Line Leak Detectors (Completed 8/16/2022 and 8/1/2023 by Hy-Tech Petroleum) - Regular Single-Wall Spill Bucket (Completed 1/25/2022 by SPATCO, & by Hy-Tech Petroleum on12/22/2022 and 1/20/2023 ) 3-year Integrity testing records: - Premium Double-Wall Spill Bucket (Completed 12/22/2022, 1/20/2023 by Hy-Tech Petroleum) - STP Sumps (Completed 1/25/2022 by SPATCO) - Dispenser Sumps (Completed 1/25/2022 by SPATCO) As Required testing records: - Tank Tightness (Completed 1/11/2022 by Adams Tank & Lift) - Tank Secondary (Completed 8/3/2022 by Hy-Tech Petroleum)
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6067
Rule: 62-761.700(1)(d)
Comments:
Comment Date: 05/28/2024 User: TYKOSKI_B_1
Description: Annual Operability Testing Records - Release Detection (Documents indicate site no longer conducts electronic monitoring. No manual monitoring records provided) - Overfill Protection (Completed 8/3/2022 by Hy-Tech Petroleum) (Past Due 8/31/2023) - Line Leak Detectors (Completed 8/16/2022 by Hy-Tech Petroleum) (Past Due 8/31/2023) - Single-Wall Spill Buckets (Completed 1/25/2022 by SPATCO & 1/20/2023 by Hy-Tech Petroleum) (Past Due 1/31/2024) 3-year Integrity testing records - STP Sumps (Completed 1/25/2022 by SPATCO) (Due 1/31/2025) - Dispenser Sumps (Completed 1/25/2022 by SPATCO) (Due 1/31/2025) As Required testing records - Tank Tightness (Completed 1/11/2022 by Adams Tank & Lift) - Tank Secondary (Completed 8/3/2022 by Hy-Tech Petroleum)
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: All Operability Testing Current Annual Integrity testing records: - Release Detection (Documents indicate site no longer conducts electronic monitoring) - Overfill Protection (Completed on 8/3/2022 and 8/1/2023 by Hy-Tech Petroleum) - Line Leak Detectors (Completed 8/16/2022 and 8/1/2023 by Hy-Tech Petroleum) - Regular Single-Wall Spill Bucket (Completed 1/25/2022 by SPATCO, & by Hy-Tech Petroleum on12/22/2022 and 1/20/2023 ) 3-year Integrity testing records: - Premium Double-Wall Spill Bucket (Completed 12/22/2022, 1/20/2023 by Hy-Tech Petroleum) - STP Sumps (Completed 1/25/2022 by SPATCO) - Dispenser Sumps (Completed 1/25/2022 by SPATCO) As Required testing records: - Tank Tightness (Completed 1/11/2022 by Adams Tank & Lift) - Tank Secondary (Completed 8/3/2022 by Hy-Tech Petroleum)
01/25/2022 Violation Open Murphy, Maggie A
Significance: SNC-B Status: Open
Criteria ID: 6051
Rule: 62-761.500(7)(a)
Comments:
Comment Date: 05/23/2024 User: TYKOSKI_B_1
Description: Report states ball valves replaced with OPW EQ#697 (unverified as no Component Closure/Install Inspection on record & no access during this inspection. Overfill Protection testing completed on 8/3/2022 by Hy-Tech Petroleum. Currently past due (8/31/2023).
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: Overfill Protection testing completed on 8/3/2022 and 8/1/2023 by Hy-Tech Petroleum. Service Report provided with EQ#s. Verified during site visit on 5/31/2024 that Ball Vent Valves replaced with OPW Overfill Shut-Off Valves.
01/25/2022 Violation Open Murphy, Maggie A
Significance: SNC-B Status: Open
Criteria ID: 6051
Rule: 62-761.500(7)(a)
Comments:
Comment Date: 05/23/2024 User: TYKOSKI_B_1
Description: Report states ball valves replaced with OPW EQ#697 (unverified as no Component Closure/Install Inspection on record & no access during this inspection. Overfill Protection testing completed on 8/3/2022 by Hy-Tech Petroleum. Currently past due (8/31/2023).
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: Overfill Protection testing completed on 8/3/2022 and 8/1/2023 by Hy-Tech Petroleum. Service Report provided with EQ#s. Verified during site visit on 5/31/2024 that Ball Vent Valves replaced with OPW Overfill Shut-Off Valves.
01/25/2022 Violation Open Murphy, Maggie A
Significance: SNC-A Status: Open
Criteria ID: 6055
Rule: 62-761.600(1), 62-761.600(1)(a), 62-761.600(1)(b), 62-761.600(1)(c), 62-761.600(1)(i)
Comments:
Comment Date: 05/23/2024 User: TYKOSKI_B_1
Description: During Routine Compliance Inspection on 5/13/2024 monthly visual inspections and release detection logs were on file starting 9/14/2022 completed by Hy-Tech Petroleum. The months of February 2023 & September 2023 records were missing from the binder. All other months were completed as required and were provided during the inspection and kept in the binder. Missing records not provided following the inspection.
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: During Routine Compliance Inspection on 5/13/2024, 2022 inspection records were provided. Site now conducts manual monitoring and all Tank and STP Sump sensors have been removed/disconnected.
01/25/2022 Violation Open Murphy, Maggie A
Significance: SNC-A Status: Open
Criteria ID: 6055
Rule: 62-761.600(1), 62-761.600(1)(a), 62-761.600(1)(b), 62-761.600(1)(c), 62-761.600(1)(i)
Comments:
Comment Date: 05/23/2024 User: TYKOSKI_B_1
Description: During Routine Compliance Inspection on 5/13/2024 monthly visual inspections and release detection logs were on file starting 9/14/2022 completed by Hy-Tech Petroleum. The months of February 2023 & September 2023 records were missing from the binder. All other months were completed as required and were provided during the inspection and kept in the binder. Missing records not provided following the inspection.
Comments:
Comment Date: 06/05/2024 User: TYKOSKI_B_1
Description: During Routine Compliance Inspection on 5/13/2024, 2022 inspection records were provided. Site now conducts manual monitoring and all Tank and STP Sump sensors have been removed/disconnected.
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6024
Rule: 62-761.500(1)(b)4, 62-761.500(1)(b)5, 62-761.500(1)(b)6, 62-761.500(1)(b)7
Comments:
Comment Date: 05/23/2024 User: TYKOSKI_B_1
Description: Annual Operability Testing Records - Release Detection (Documents indicate site no longer conducts electronic monitoring. No manual monitoring records provided) - Overfill Protection (Completed 8/3/2022 by Hy-Tech Petroleum) (Past Due 8/31/2023) - Line Leak Detectors (Completed 8/16/2022 by Hy-Tech Petroleum) (Past Due 8/31/2023) - Single-Wall Spill Buckets (Completed 1/25/2022 by SPATCO & 1/20/2023 by Hy-Tech Petroleum) (Past Due 1/31/2024) 3-year Integrity testing records - STP Sumps (Completed 1/25/2022 by SPATCO) (Due 1/31/2025) - Dispenser Sumps (Completed 1/25/2022 by SPATCO) (Due 1/31/2025) As Required testing records - Tank Tightness (Completed 1/11/2022 by Adams Tank & Lift) - Tank Secondary (Completed 8/3/2022 by Hy-Tech Petroleum)
01/25/2022 Violation Open Murphy, Maggie A
Significance: Minor Status: Open
Criteria ID: 6006
Rule: 62-761.400(5)
Comments:
Comment Date: 05/23/2024 User: TYKOSKI_B_1
Description: Site has a 23-24 Placard displayed on site.
12/13/2019 Editable Letter Activity Neuhaus, Andrew
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 12/13/2019
Comment: Submitted for approval by: Andrew Neuhaus
Events:
Event Type: Document has been sent Date: 12/13/2019
Comment: Sent
Events:
Event Type: Activity/Document has been approved Date: 12/18/2019
Comment: Approved by John Hickey: Approved
Events:
Event Type: Activity has been finished Date: 12/18/2019
Comment: Finished
Attachments:
Attachment Date: 12/13/2019 User: NEUHAUS_AE_1
Description: ICL
View Attachment
10/17/2019 Electronic Communication Activity Neuhaus, Andrew
Activity Closed Date: 10/17/2019 Activity Status: Closed
Date: 10/17/2019
Recipient: Sara Vinas
Sender: Andrew Neuhaus
Subject: Close in place by 2021 notice.
Message: Attached.
Events:
Event Type: Activity has been finished Date: 10/17/2019
Comment: Finished
10/17/2019 Electronic Communication Activity Neuhaus, Andrew
Activity Closed Date: 10/17/2019 Activity Status: Closed
Date: 10/17/2019
Recipient: Sara Vinas
Sender: Andrew Neuhaus
Subject: Schedule Inspection.
Message: Attached.
Events:
Event Type: Activity has been finished Date: 10/17/2019
Comment: Finished
10/08/2019 Site Inspection Activity Closed Neuhaus, Andrew
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/08/2019
Activity Closed Date: 10/22/2019 Activity Closed By: NEUHAUS_AE_1
Events:
Event Type: Activity has been submitted for approval Date: 10/22/2019
Comment: Submitted for approval by: Andrew Neuhaus
Events:
Event Type: Activity/Document has been approved Date: 10/22/2019
Comment: Approved by John Hickey: Approved
Events:
Event Type: Activity has been finished Date: 10/22/2019
Comment: Finished
03/01/2018 Editable Letter Activity Murphy, Maggie A
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 03/01/2018
Comment: Submitted for approval by: Maggie A Murphy
Events:
Event Type: Activity/Document has been approved Date: 04/10/2018
Comment: Approved by John Hickey: approved
Events:
Event Type: Activity has been finished Date: 04/13/2018
Comment: Finished
Attachments:
Attachment Date: 03/01/2018 User: MURPHY_MA_1
Description: In compliance letter
View Attachment
01/29/2018 Site Inspection Activity Closed Murphy, Maggie A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/29/2018
Activity Closed Date: 01/31/2018 Activity Closed By: MURPHY_MA_1
Events:
Event Type: Activity/Document has been approved Date: 01/31/2018
Comment: Approved by John Hickey: Approved
Events:
Event Type: Activity has been submitted for approval Date: 01/29/2018
Comment: Submitted for approval by: Maggie A Murphy
Events:
Event Type: Activity has been submitted for approval Date: 01/29/2018
Comment: Submitted for approval by: Maggie A Murphy
Events:
Event Type: Activity has been finished Date: 01/31/2018
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 01/30/2018
Comment: Submitted for approval by: Maggie A Murphy
Events:
Event Type: Activity has not been approved Date: 01/30/2018
Comment: Not approved by John Hickey: Please add site comments
01/29/2018 Electronic Communication Activity Murphy, Maggie A
Activity Closed Date: 01/29/2018 Activity Status: Closed
Date: 01/29/2018
Recipient: Sara Vinas
Sender: Maggie Murphy
Subject: Scheduling email
Message: From: Margaret A. Murphy Sent: Wednesday, January 03, 2018 11:28 AM To: 'Slvonecorp@gmail.com' ; 'ytonecorp@gmail.com' Cc: Margaret A. Murphy Subject: Upcoming Compliance Inspection attn: Dockmaster Importance: High Good morning, I plan to perform a state petroleum storage tank compliance inspection at your facility, (Exxon- Osprey) on January 17th 2018 at 1:00 PM. I have attached the copy of the last tank inspection that our office performed at your facility. Please note the citations on the reports, which have been addressed and corrected so I do not need a response on those, but please check if any similar or other issues need corrected prior to this inspection. For information regarding the storage tank regulations and what we check during our inspections you can view the “Preparing for a Storage Tank Facility Inspection Information Video” for underground and aboveground tanks on the Florida Department of Environmental Protection’s Storage Tank Compliance web page: http://www.dep.state.fl.us/waste/categories/tanks/default.htm Also you may want to review this convenient list of general reminders for Regulated UST Owners and operators. Someone will need to be available at the inspection that can provide the required records for my review and can open the tank fill ports, piping sumps and dispensers. The following must be provided as part of the inspection but should it be easier can be supplied to me via email prior. 1. Registration Placard (see above note regarding) 2. Financial Responsibility/Certificate of Financial responsibility 3. Release Detection test (line leak detector test, interstice monitoring, and overfill protection) 4. Monthly records (visual inspections, equipment repair/replacement & maintenance log, print out for the electronic monitoring system) 5. Cathodic Protection test- if applicable 6. Inspector training certification Thank you for your attention and let me know if you have any questions I can address before my visit. Maggie Murphy Sarasota County Planning and Development Services Air and Water Quality Sarasota County Operations Center 1001 Sarasota Center Blvd Sarasota, FL 34240 941-202-3955 fax 941-861-6267 Email: mamurphy@scgov.net Website: www.scgov.net/PDS Your feedback is valuable to us: Customer Service Survey
Events:
Event Type: Activity has been finished Date: 01/29/2018
Comment: Finished
04/12/2016 Comment Ramsey, Timothy H
Description: Facility contact Yolanda Torres 954-499-8663 x 234 ytonecorp@gmail.com
04/11/2016 Site Inspection Activity Closed Ramsey, Timothy H
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/11/2016
Activity Closed Date: 04/11/2016 Activity Closed By: RAMSEY_TH_2
Events:
Event Type: Activity has been finished Date: 04/11/2016
Comment: Finished
04/11/2016 Phone Conversation Activity Ramsey, Timothy H
Call Type: Outgoing Activity Status: Closed
Phone Number: (954) 499-8663 Activity Closed Date: 04/11/2016
Subject: Contacted facility representative to discuss need to complete a routine tank compliance inspection. Requested financial responsibility records.
Events:
Event Type: Activity has been finished Date: 04/11/2016
Comment: Finished
04/11/2016 Electronic Communication Activity Ramsey, Timothy H
Activity Closed Date: 04/11/2016 Activity Status: Closed
Date: 04/11/2016
Recipient: Yolanda Torres
Sender: Tim Ramsey
Subject: Copy of Inspection Report
Message: Emailed copy of inspection report to facility representative
Events:
Event Type: Activity has been finished Date: 04/11/2016
Comment: Finished
07/22/2014 Site Inspection Activity Closed Wall, Kenneth
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/22/2014
Activity Closed Date: 07/23/2014 Activity Closed By: WALL_KD_1
Events:
Event Type: Activity has been finished Date: 07/23/2014
Comment: Finished
07/22/2014 Emergency Preparedness Information Activity Wall, Kenneth
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 07/22/2014
Events:
Event Type: Activity has been finished Date: 07/22/2014
Comment: Finished
10/08/2012 Attachment Wall, Kenneth
10/08/2012 Emergency Preparedness Information Activity Wall, Kenneth
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 10/08/2012
Events:
Event Type: Activity has been finished Date: 10/08/2012
Comment: Finished
10/08/2012 Site Inspection Activity Closed Wall, Kenneth
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/08/2012
Activity Closed Date: 10/08/2012 Activity Closed By: WALL_KD_1
Events:
Event Type: Activity has been finished Date: 10/08/2012
Comment: Finished
12/22/2011 Record Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: Sara Vinas Activity Closed Date: 12/22/2011
Events:
Event Type: Activity has been finished Date: 12/22/2011
Comment: Finished
12/21/2011 Electronic Communication Activity Wall, Kenneth
Activity Closed Date: 12/21/2011 Activity Status: Closed
Date: 12/21/2011
Recipient: Sarasota Co. AQ/STM
Sender: Sara Vinas
Subject: Financial Responsibility records and CFR for the UST systems.
Message: The 12/19/2011 email requesting FR records and the 12/20/2011 reply are attached.
Events:
Event Type: Activity has been finished Date: 12/21/2011
Comment: Finished
12/21/2011 Record Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: Sara Vinas Activity Closed Date: 12/21/2011
Events:
Event Type: Activity has been finished Date: 12/21/2011
Comment: Finished
12/20/2011 Editable Letter Activity Wall, Kenneth
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 12/22/2011
Comment: Finished
Events:
Event Type: Document has been sent Date: 12/22/2011
Comment: Sent on Thu Dec 22 00:00:00 EST 2011
Attachments:
Attachment Date: 12/22/2011 User: WALL_KD_1
Description: NCL
View Attachment
12/19/2011 Attachment Wall, Kenneth
12/19/2011 Site Inspection Activity Closed Wall, Kenneth
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 12/19/2011
Activity Closed Date: 12/20/2011 Activity Closed By: WALL_KD_1
Events:
Event Type: Activity has been finished Date: 12/20/2011
Comment: Finished
12/19/2011 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1006
Rule: 62-761.450(1)(a)2.
Comments: The local program should receive notice of listed tasks prior to the initiation of the work. Local program may accept less notice and still consider this item in compliance. This rule citation is not a requirement to submit construction plans. Notice can be accepted in these formats: Verbal Written Fax Email
12/19/2011 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1122
Rule: 62-761.710(1)
Comments: Was reasonable access to the facility granted? If not, document the circumstances. Were the records available within the specified time frame? If five day pre-inspection notice was not given by the inspector, this item can not be marked as a discrepancy. Make note of the missing documents, and arrange a review period.
12/19/2011 Violation Closed Wall, Kenneth
Significance: SNC-B Status: Closed
Criteria ID: 1004
Rule: 62-761.400(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2).
12/19/2011 Attachment Wall, Kenneth
08/25/2011 Issue Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: Hector Vinas Activity Closed Date: 08/25/2011
Events:
Event Type: Activity has been finished Date: 08/25/2011
Comment: Finished
08/25/2011 Editable Letter Activity Wall, Kenneth
Activity Title: Warning Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 03/27/2008
Comment: Sent on Thu Mar 27 00:00:00 EDT 2008
Events:
Event Type: Activity has been finished Date: 08/25/2011
Comment: Finished
Attachments:
Attachment Date: 08/25/2011 User: WALL_KD_1
Description: 3/27/2008 Warning Letter
View Attachment
08/25/2011 Record Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: Sara Vinas Activity Closed Date: 08/25/2011
Events:
Event Type: Activity has been finished Date: 08/25/2011
Comment: Finished
08/25/2011 Document Management Activity Wall, Kenneth
Activity Title: Short Form Consent Order Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/25/2011
Comment: Finished
Attachments:
Attachment Date: 08/25/2011 User: WALL_KD_1
Description: consent order
View Attachment
08/25/2011 Issue Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: Hector Vinas Activity Closed Date: 08/25/2011
Events:
Event Type: Activity has been finished Date: 08/25/2011
Comment: Finished
08/25/2011 Record Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: Hector Vinas Activity Closed Date: 08/25/2011
Events:
Event Type: Activity has been finished Date: 08/25/2011
Comment: Finished
08/16/2011 Attachment Wall, Kenneth
08/16/2011 Attachment Wall, Kenneth
01/26/2011 Site Inspection Activity Closed Wall, Kenneth
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/26/2011
Activity Closed Date: 02/15/2011 Activity Closed By: WALL_KD_1
Events:
Event Type: Activity has been finished Date: 02/15/2011
Comment: Finished
07/10/2009 Record Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: Sarah Vinas Activity Closed Date: 07/10/2009
06/05/2009 Site Inspection Activity Closed Wall, Kenneth
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 06/05/2009
Activity Closed Date: 06/05/2009 Activity Closed By: WALL_KD_1
Comments:
Comment Date: 06/05/2009 User: WALL_KD_1
Description: Guardian Fueling Technologies has repaired the damaged flex pipe in the facility's premium unleaded STP. The repaired segment of premium product piping (from the premium STP sump to the southwest dispenser) "passed" air testing (performed by the contrator). During the inspection the secondary pipe was pressurized to 5 psi - secondary pipe appears to be OK. Both STP sumps are filled with water for hydro-testing; Both STP sumps are liquid tight. The STP sumps have been pumped out, sensors have been reinstalled in the sumps, and secondary piping test boots have been opened. Several fuel hoses and fuel nozzles at the dispensers are being replaced (by request of the Dept. of Agriculture inspector). Guardian staff (Pete) performed the operability test on the Veeder-Root monitoring equipment on 6/4/2009; the bell sensor in the premium annnular UST needed to be replaced during the testing. Both gasoline USTs are being completely pumped out by Monarch Environmental Services in preparation for a delivery of gasoline scheduled for tomorrow. Guardian is to purge the product lines after the fuel delivery. Discovery Tank Testing is to tightness test the facility's primary product piping and the mechanical leak detectors before the UST systems are reopened. Please provide the tightness test records for the product lines, the mechanical leak detector test records, and the repair invoices from Guardian for the repairs performed within 10 days. The Veeder-Root TLS-350 tank monitor (EQ-033) indicates "normal" for all four interstitial sensors. The red and green indicator lights on the tank monitor are inoperative; Please repair the indicator lights ASAP.
03/10/2009 Meeting Activity Wall, Kenneth
Activity Closed Date: 03/10/2009 Activity Status: Closed
Location: Office of the County Attorney - Sarasota County Administration Building
Subject: Met with David Pierce, Assistant County Attorney, and discussed strategies to encourage the facility to return to compliance with Chapter 62-761, F.A.C. The County Attorney's office is to draft a letter to the facility's owner requesting a meeting to discuss and work toward resolution of all non-compliance issues. AQ/STM staff is to investigate details regarding referring the facility to the Special Master for enforcement. AQ/STM may prepare a Notice of Violation to initiate the enforcement process through the Sarasota County Code Enforcement Special Master.
02/26/2009 Editable Letter Activity Wall, Kenneth
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Comments:
Comment Date: 02/26/2009 User: WALL_KD_1
Description: FIRST generated NCL was not mailed - see attachments.
02/10/2009 Violation Closed Wall, Kenneth
Significance: SNC-B Status: Closed
Criteria ID: 1004
Rule: 62-761.400(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2).
02/10/2009 Site Inspection Activity Closed Wall, Kenneth
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/10/2009
Activity Closed Date: 02/10/2009 Activity Closed By: WALL_KD_1
Comments:
Comment Date: 02/10/2009 User: WALL_KD_1
Description: The business is closed and the building is locked. No records for the facility's UST systems were available during the inspection. GEC Florida Sarasota corporate office was contacted during the inspection to request operational records for the facility. A company representative did not answer, but a message was left on the company's answer machine requesting a call back. Fuel nozzles at the dispensers are bagged. Approximately 12-inches of gasoline was measured to be in the facility's premium UST and 9-inches of gasoline was present in the regular UST during the site visit. UST fill caps were not secured. Both of the facility's STP sumps contained excessive amounts of petroleum contact water, and one of the premium product pipes located in the premium STP sump was noted to be badly damaged. No additional UST equipment was evaluated during the site visit. Emergency preparedness information was not updated since the business was closed and facility contact information is unavailable.
02/10/2009 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1063
Rule: 62-761.600(1)(e)
Comments: The electronic monitoring unit is a system consisting of a sensor, wiring, and a panel. The sensor and the component that it monitors are exempt from the visual inspection process. However, the proper operation of the remainder of the electronic system must be verified on a monthly basis. One way to test is to activate the panel alarm switch. Depending on the system in place this test may check the alarm light, alarm horn, or the circuit continuity between the panel and the remote sensor. This test procedure must be documented by the facility, as required in rule 62-761.710(2). The remote verification feature meets this requirement, such as the Veeder-Root Simplicity system.
02/10/2009 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1091
Rule: 62-761.640(2)(e)
Comments: Note repair issues in rule 62-761.700(1)(a)1, 62-761.700(1)(a)2, 62-761.700(1)(a)3, 62-761.700(1)(a)4, 62-761.700(1)(a)5 & 62-761.700(1)(a)6. Also note record keeping problems in rules 62-761.710(1) & 62-761.710(2).
02/10/2009 Violation Closed Wall, Kenneth
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
02/10/2009 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
02/10/2009 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1122
Rule: 62-761.710(1)
Comments: Was reasonable access to the facility granted? If not, document the circumstances. Were the records available within the specified time frame? If five day pre-inspection notice was not given by the inspector, this item can not be marked as a discrepancy. Make note of the missing documents, and arrange a review period.
06/04/2008 Site Inspection Activity Closed Wall, Kenneth
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 06/04/2008
Activity Closed Date: 06/04/2008 Activity Closed By: WALL_KD_1
04/07/2008 Issue Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: Jaun Zorrilla, Registered Agent Activity Closed Date: 04/07/2008
03/25/2008 Site Inspection Activity Closed Wall, Kenneth
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 03/25/2008
Activity Closed Date: 03/25/2008 Activity Closed By: WALL_KD_1
Comments:
Comment Date: 03/25/2008 User: WALL_KD_1
Description: Single-wall spill buckets at the UST fill risers and vent riser are full of petroleum contact water (PCW). WITHIN 14 DAYS PLEASE REMOVE AND PROPERLY DISPOSE OF THE PCW IN ALL OF THE SPILL BUCKETS. The premium unleaded STP sump contains 23-inches of liquid - 16" of water and 7" of gasoline, and the regular STP sump contains approximately 1/2" of product. WITHIN 3-DAYS PLEASE REMOVE AND PROPERLY DISPOSE OF THE LIQUID IN BOTH STP SUMPS. Dispenser sumps were not evaluated during the inspection. Shear valves were not evaluated during the inspection. Fuel hoses, break-away fittings, whip hoses, and fuel nozzles were not evaluated during the inspection. The Veeder-Root TLS-350 tank monitor (EQ-033) indicates "normal" for three interstitial sensors, but the fourth sensor- premium STP sump sensor is indicating an "alarm". Alarm History Report indicates that the STP sump alarm has been on-going since 12/27/2007. Yellow & red indicator lights and the audible alarm at the tank monitor are operational. The green "power" indicator light is inoperative. WITHIN 30 DAYS PLEASE REPAIR THE GREEN INDICATOR LIGHT ON THE TANK MONITOR. No records were evaluated during the inspection. Currently the facility is out of fuel and is not dispensing gasoline - reportedly the facility ran out of fuel yesterday. A gas delivery is scheduled for this evening.
03/25/2008 Enforcement Tracking Activity Wall, Kenneth
Activity Status: Closed
Activity Result: Closed With Enforcement Activity Closed Date: 08/25/2011
Events:
Event Type: Activity has been finished Date: 08/25/2011
Comment: Finished
03/25/2008 Enforcement Referral Activity Wall, Kenneth
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/25/2008
Events:
Event Type: Activity/Document was accepted on this date Date: 03/25/2008
Comment: Warning Letter issued - see attachments.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/25/2008
Comment: Inadequate response received to 1/2/2008 NCL, and requested corrective action has not been taken. Warning Letter issued.
Events:
Event Type: Activity has been submitted for approval Date: 03/25/2008
Comment: See 3/25/2008 reinspection report and the 12/19/2007 annual inspection report for details.
Comments:
Comment Date: 03/25/2008 User: WALL_KD_1
Description: Warning Letter issued - see attachments.
Comments:
Comment Date: 03/25/2008 User: WALL_KD_1
Description: Inadequate response received to 1/2/2008 NCL, and requested corrective action has not been taken. Warning Letter issued.
Comments:
Comment Date: 03/25/2008 User: WALL_KD_1
Description: See 3/25/2008 reinspection report and the 12/19/2007 annual inspection report for details.
03/25/2008 Enforcement Referral Activity Wall, Kenneth
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/25/2008
Events:
Event Type: Activity/Document was accepted on this date Date: 03/25/2008
Comment: Warning Letter issued - see attachments.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/25/2008
Comment: Inadequate response received to 1/2/2008 NCL, and requested corrective action has not been taken. Warning Letter issued.
Events:
Event Type: Activity has been submitted for approval Date: 03/25/2008
Comment: See 3/25/2008 reinspection report and the 12/19/2007 annual inspection report for details.
Comments:
Comment Date: 03/25/2008 User: WALL_KD_1
Description: Warning Letter issued - see attachments.
Comments:
Comment Date: 03/25/2008 User: WALL_KD_1
Description: Inadequate response received to 1/2/2008 NCL, and requested corrective action has not been taken. Warning Letter issued.
Comments:
Comment Date: 03/25/2008 User: WALL_KD_1
Description: See 3/25/2008 reinspection report and the 12/19/2007 annual inspection report for details.
03/25/2008 Enforcement Referral Activity Wall, Kenneth
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/25/2008
Events:
Event Type: Activity/Document was accepted on this date Date: 03/25/2008
Comment: Warning Letter issued - see attachments.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/25/2008
Comment: Inadequate response received to 1/2/2008 NCL, and requested corrective action has not been taken. Warning Letter issued.
Events:
Event Type: Activity has been submitted for approval Date: 03/25/2008
Comment: See 3/25/2008 reinspection report and the 12/19/2007 annual inspection report for details.
Comments:
Comment Date: 03/25/2008 User: WALL_KD_1
Description: Warning Letter issued - see attachments.
Comments:
Comment Date: 03/25/2008 User: WALL_KD_1
Description: Inadequate response received to 1/2/2008 NCL, and requested corrective action has not been taken. Warning Letter issued.
Comments:
Comment Date: 03/25/2008 User: WALL_KD_1
Description: See 3/25/2008 reinspection report and the 12/19/2007 annual inspection report for details.
12/21/2007 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
12/21/2007 Editable Letter Activity Wall, Kenneth
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Comments:
Comment Date: 12/21/2007 User: WALL_KD_1
Description: FIRST generated NCL was not mailed. The NCL that was mailed is attached.
12/21/2007 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1063
Rule: 62-761.600(1)(e)
Comments: The electronic monitoring unit is a system consisting of a sensor, wiring, and a panel. The sensor and the component that it monitors are exempt from the visual inspection process. However, the proper operation of the remainder of the electronic system must be verified on a monthly basis. One way to test is to activate the panel alarm switch. Depending on the system in place this test may check the alarm light, alarm horn, or the circuit continuity between the panel and the remote sensor. This test procedure must be documented by the facility, as required in rule 62-761.710(2). The remote verification feature meets this requirement, such as the Veeder-Root Simplicity system.
12/21/2007 Violation Closed Wall, Kenneth
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
12/19/2007 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
12/19/2007 Site Inspection Activity Closed Wall, Kenneth
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 12/19/2007
Activity Closed Date: 12/21/2007 Activity Closed By: WALL_KD_1
12/19/2007 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
12/19/2007 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1080
Rule: 62-761.640(1)(a)1., 62-761.640(1)(a)2., 62-761.640(1)(a)3., 62-761.640(1)(a)4.
Comments: Mark this as out of compliance if the release detection method does not meet .640 standards. This should be a rare violation, since methods approved through .850 and are on approved equipment list already meet standards. The EQ number demonstrates that the release detection system meets standards. Check equipment approvals, and document EQ numbers if necessary.
12/19/2007 Violation Closed Wall, Kenneth
Significance: Minor Status: Closed
Criteria ID: 1058
Rule: 62-761.600(1)(a)1.
Comments: Mark this as out of compliance if the release detection method is not able to register or detect a new release. If you feel that the release detection system has lost its ability to detect a new release, document why in the inspection report. Examples include: a. An automatic tank gauge system already in alarm mode will not be able to detect a new release; b. sumps with water/product may impair detection abilities; c. monitoring wells at contaminated sites may also have impaired ability to detect new releases. See .640(2)(c)2. for further guidance on using contaminated monitoring wells for release detection.
11/30/2007 Editable Letter Activity Wall, Kenneth
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Comments:
Comment Date: 11/30/2007 User: WALL_KD_1
Description: FIRST generated NCL was not issued. The NCL that was mailed is attached.
02/06/2007 Emergency Preparedness Information Activity Wall, Kenneth
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/06/2007
02/02/2007 Site Inspection Activity Closed Wall, Kenneth
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/02/2007
Activity Closed Date: 02/06/2007 Activity Closed By: WALL_KD_1
Comments:
Comment Date: 02/02/2007 User: WALL_KD_1
Description: RDRL is satisfactory. Release detection methods are outlined on the RDRL attached on the General Facility Information screen. Certification of Financial Responsibility is satisfactory. Current registration placard is posted. Electronic and visual release detection records for January 2006 through December 2006 are satisfactory. The monthly records (and the Alarm History Report) indicate a couple of liquid alarms at each STP sump subsequent to the 7/6/2006 operability test. Annual operability tests for the Veeder-Root TLS-350 with 4 interstitial sensors and the MLLDs were performed on 7/6/2006 by Petroleum Compliance Solutions - Richard Parsons. Single-wall spill buckets & drop tubes appear to be satisfactory. Vapor extractor dry break fitting, vent riser, and vent cap are OK. STP sumps & dispenser liners are dry. Secondary piping test boots located in the STP sumps are open - OK. STP sump sensors are located below the product piping and near the bottom of each STP sump - OK. Shear valves are secured/anchored. All fuel hoses, break-away fittings, whip hoses, and fuel nozzles are satisfactory. The Veeder-Root TLS-350 tank monitor (EQ-033) indicates "normal" for all four interstitial sensors. Yellow & red indicator lights and the audible alarm at the tank monitor are operational. The green "power" indicator light is inoperative. Please repair the green "power" indicator light on the tank monitor.
09/20/2006 Emergency Preparedness Information Activity Telemeco-Anders, Debbie Y.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/20/2006
09/15/2006 Record Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: Danny Phillips Activity Closed Date: 09/15/2006
07/12/2006 Record Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: INF NFA letter Activity Closed Date: 07/12/2006
07/11/2006 Record Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: INF Resolution Activity Closed Date: 07/11/2006
07/11/2006 Record Document Activity Wall, Kenneth
Activity Status: Closed
Contact Name: 7/6/2006 INF Activity Closed Date: 07/11/2006
06/26/2006 Comment Telemeco-Anders, Debbie Y.
Description: Western coaxial flex piping at facility
06/21/2006 Site Inspection Activity Closed Telemeco-Anders, Debbie Y.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/21/2006
Activity Closed Date: 07/03/2006 Activity Closed By: ANDERS_DT_1
Comments:
Comment Date: 06/21/2006 User: ANDERS_DT_1
Description: * Guardian Fueling Technologies has replaced all weathered fuel hoses and a missing break away on dispenser #11. * The premium sump cover has been replaced and is tightly secured. * Current registration placard is posted (6/7/2006-6/30/2007). Placard 257244 was issued 6/7/2006, although FIRST does not have the placard being issued to date (see attachment). * Veeter Root TLS-350 tank monitor (EQ#-033) yellow and red indicator lights on the display panel are inoperable. Liquid Status indicates all sensors normal. * A CFR was left on site for completion. * Dispensers #1/#2 (6 fuel nozzels total) are bagged and temporarily out of service due to electronic display panal malfunctioning. NOTE 1: Repair alarm indicator lights on Veeter Root tank monitor display panel within 30 days. NOTE 2: Annual operbility and line leak detector tests are due by August 1, 2006.
05/16/2006 Comment Telemeco-Anders, Debbie Y.
Description: 5/16/06 "Site Inspection Report Activities" incorrectly list 9 USTs. There are 2 active USTs at this facility. The Data Base will not allow the info to be corrected.
05/15/2006 Comment Telemeco-Anders, Debbie Y.
Description: 5/12/06 Chris Amlicke, Guardian Fuel Technology 1-800-693-9499, called and said the facility is ready for re-inspection. The premium sump lid has been replaced, +15 fuel hoses and a break away on disp. #11 has been replaced.
03/21/2006 Comment MIGRATION
Description: COMMUNICATION: TO: MANGUM_BJ, SITE MANAGER Email: bmangum@scgov.net Email Date: 03/21/2006 ACTIVITY ID: 11706895 - TANK ANNUAL COMPLIANCE INSPECTION WAS PERFORMED AT FACILITY ID: 8520885 ON 03/16/2006 BY WALL. EVALUATION RESULT = MINOR OUT-OF-COMPLIANCE. ACTIVITY RECORDED ON 03/21/2006 USER: LINDA BENANTI OF SARASOTA COUNTY POLLUTION CONTROL
03/21/2006 Comment MIGRATION
Description: COMMUNICATION: TO: MANGUM_BJ, SITE MANAGER Email: bmangum@scgov.net Email Date: 03/21/2006 ACTIVITY ID: 11706895 - TANK ANNUAL COMPLIANCE INSPECTION WAS PERFORMED AT FACILITY ID: 8520885 ON 03/16/2006 BY WALL. EVALUATION RESULT = MINOR OUT-OF-COMPLIANCE. ACTIVITY RECORDED ON 03/21/2006 USER: LINDA BENANTI OF SARASOTA COUNTY POLLUTION CONTROL
03/21/2006 Comment MIGRATION
Description: COMMUNICATION: TO: MANGUM_BJ, SITE MANAGER Email: bmangum@scgov.net Email Date: 03/21/2006 ACTIVITY ID: 11706895 - TANK ANNUAL COMPLIANCE INSPECTION WAS PERFORMED AT FACILITY ID: 8520885 ON 03/16/2006 BY WALL. EVALUATION RESULT = MINOR OUT-OF-COMPLIANCE. ACTIVITY RECORDED ON 03/21/2006 USER: LINDA BENANTI OF SARASOTA COUNTY POLLUTION CONTROL
03/21/2006 Comment MIGRATION
Description: COMMUNICATION: TO: MANGUM_BJ, SITE MANAGER Email: bmangum@scgov.net Email Date: 03/21/2006 ACTIVITY ID: 11706895 - TANK ANNUAL COMPLIANCE INSPECTION WAS PERFORMED AT FACILITY ID: 8520885 ON 03/16/2006 BY WALL. EVALUATION RESULT = MINOR OUT-OF-COMPLIANCE. ACTIVITY RECORDED ON 03/21/2006 USER: LINDA BENANTI OF SARASOTA COUNTY POLLUTION CONTROL
03/21/2006 Comment MIGRATION
Description: COMMUNICATION: TO: MANGUM_BJ, SITE MANAGER Email: bmangum@scgov.net Email Date: 03/21/2006 ACTIVITY ID: 11706895 - TANK ANNUAL COMPLIANCE INSPECTION WAS PERFORMED AT FACILITY ID: 8520885 ON 03/16/2006 BY WALL. EVALUATION RESULT = MINOR OUT-OF-COMPLIANCE. ACTIVITY RECORDED ON 03/21/2006 USER: LINDA BENANTI OF SARASOTA COUNTY POLLUTION CONTROL
03/21/2006 Comment MIGRATION
Description: COMMUNICATION: TO: MANGUM_BJ, SITE MANAGER Email: bmangum@scgov.net Email Date: 03/21/2006 ACTIVITY ID: 11706895 - TANK ANNUAL COMPLIANCE INSPECTION WAS PERFORMED AT FACILITY ID: 8520885 ON 03/16/2006 BY WALL. EVALUATION RESULT = MINOR OUT-OF-COMPLIANCE. ACTIVITY RECORDED ON 03/21/2006 USER: LINDA BENANTI OF SARASOTA COUNTY POLLUTION CONTROL
03/21/2006 Comment MIGRATION
Description: COMMUNICATION: TO: MANGUM_BJ, SITE MANAGER Email: bmangum@scgov.net Email Date: 03/21/2006 ACTIVITY ID: 11706895 - TANK ANNUAL COMPLIANCE INSPECTION WAS PERFORMED AT FACILITY ID: 8520885 ON 03/16/2006 BY WALL. EVALUATION RESULT = MINOR OUT-OF-COMPLIANCE. ACTIVITY RECORDED ON 03/21/2006 USER: LINDA BENANTI OF SARASOTA COUNTY POLLUTION CONTROL
03/16/2006 Violation Closed Unknown, User
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
03/16/2006 Legacy Activity Benanti, Linda G.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
08/03/2005 Legacy Activity Starkey, Dorene M.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
05/25/2005 Legacy Activity Starkey, Dorene M.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 761.700(1)(a)1
03/08/2005 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 761.710(2)
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 761.761.710(1)
Comments:
Comment Date: 07/05/2013 User: ULRICH_CA_1
Description: Found in the paper file, a memo from Joanne Griffith to Doug Divers dated 5/27/2012: "a letter from Joe Glover Sr. (property owner at that time) to the City of Melbourne in 1977 stating that all tanks were removed from S. Babcock St., Melbourne, FL aka Subway Sandwich Shop." I have been on-site - there are no apparent tank sumps or fill buckets. Vents lines still exist attached to the building, they were never removed. Chris Ulrich, 7/5/2013.
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 761.700(1)(c)3
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 761.820(1)(a),(b),(c)
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 761.640(4)(a)
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 761.640(1)(a)
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: SNC-B Status: Closed
Rule: 761.610(1)(a)
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: SNC-B Status: Closed
Rule: 761.600(1)(d)
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 761.600(1)(a)2
03/08/2005 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 761.450(2)
Comments:
Comment Date: 11/14/2016 User: CRUZ_I_2
Description: EQ-371
03/02/2004 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/17/2003 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/01/2002 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
12/11/2001 Legacy Activity Starkey, Dorene M.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
11/14/2001 Violation Closed Starkey, Dorene M.
Significance: SNC-B Status: Closed
Rule: 500(1)(e)1,2
11/14/2001 Legacy Activity Starkey, Dorene M.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
11/14/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(c)1
11/14/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(a)1
11/14/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 600(1)(a)2
10/23/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(c)1
10/23/2001 Legacy Activity Starkey, Dorene M.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
10/23/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(a)1
10/23/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 600(1)(a)2
10/23/2001 Violation Closed Starkey, Dorene M.
Significance: SNC-B Status: Closed
Rule: 500(1)(e)1,2
10/23/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 710(1)
10/23/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
09/20/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
09/20/2001 Legacy Activity Starkey, Dorene M.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
09/20/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 710(1)
07/24/2001 Violation Closed Starkey, Dorene M.
Significance: SNC-B Status: Closed
Rule: 500(1)(e)1,2
07/24/2001 Legacy Activity Starkey, Dorene M.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
07/24/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 710(1)
07/24/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
07/24/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(c)1
07/24/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(a)1
07/24/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 600(1)(a)2
04/17/2001 Legacy Activity Starkey, Dorene M.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
04/13/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 400(2)(a)6
04/13/2001 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/13/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 710(1)
04/13/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
Comments:
Comment Date: 01/28/2016 User: COLSON_NJ_1
Description: Premium MLLD did NOT Fail on 10/13/2015. Deactivated erroneous record.
04/13/2001 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 600(1)(a)2
04/13/2001 Violation Closed Starkey, Dorene M.
Significance: SNC-B Status: Closed
Rule: 400(3)
05/25/2000 Legacy Activity Starkey, Dorene M.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
03/02/2000 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 600(1)(a)2
Comments:
Comment Date: 12/17/2020 User: WHITAKER_AJ_1
Description: Added update site diagram and reviewed photo.
03/02/2000 Legacy Activity Starkey, Dorene M.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
03/02/2000 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/02/2000 Violation Closed Starkey, Dorene M.
Significance: SNC-B Status: Closed
Rule: 610(1)(a)
03/02/2000 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 640(3)(d)1e
03/02/2000 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 640(3)(d)
03/02/2000 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(c)1
03/02/2000 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
03/02/2000 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 710(1)
Comments:
Comment Date: 08/30/2024 User: HARRINGTON_RD_1
Description: Anna C. Stoddard | Service & Tank Compliance Program Manager PowerSecure, Inc. – Environmental Compliance C: 336-264-3414 | anna.stoddard@powersecure.com
Comments:
Comment Date: 08/30/2024 User: HARRINGTON_RD_1
Description: Natalie Woodward | Customer Service Manager III | Distributed Infrastructure Office: (770) 721-7111 x 4059 | Direct: (470) 863-2509 | Cell: (470) 479-5875 | Email: nwoodward@powersecure.com
Comments:
Comment Date: 07/15/2018 User: HARRINGTON_RD_1
Description: Tank 1 was installed in 2012 at facility DEP# 9810102. The tank is in the same place in 2018, but has been registered at the current facility DEP# 9816232 (WM 1225). This was done to separate the Powersecure registrations from the Wal Mart registrations in order to avoid confusion.
Attachments:
Attachment Date: 09/09/2018 User: HARRINGTON_RD_1
Description: Tank 1- original install report.
View Attachment
Attachments:
Attachment Date: 11/22/2024 User: HARRINGTON_RD_1
Description: Tank 1... 2024-11-21
View Attachment
Attachments:
Attachment Date: 11/22/2024 User: HARRINGTON_RD_1
Description: Tank 1 label... 2024-11-21
View Attachment
03/02/2000 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 710(1)
Comments:
Comment Date: 08/30/2024 User: HARRINGTON_RD_1
Description: Anna C. Stoddard | Service & Tank Compliance Program Manager PowerSecure, Inc. – Environmental Compliance C: 336-264-3414 | anna.stoddard@powersecure.com
Comments:
Comment Date: 08/30/2024 User: HARRINGTON_RD_1
Description: Natalie Woodward | Customer Service Manager III | Distributed Infrastructure Office: (770) 721-7111 x 4059 | Direct: (470) 863-2509 | Cell: (470) 479-5875 | Email: nwoodward@powersecure.com
Comments:
Comment Date: 07/15/2018 User: HARRINGTON_RD_1
Description: Tank 1 was installed in 2012 at facility DEP# 9810102. The tank is in the same place in 2018, but has been registered at the current facility DEP# 9816232 (WM 1225). This was done to separate the Powersecure registrations from the Wal Mart registrations in order to avoid confusion.
Attachments:
Attachment Date: 09/09/2018 User: HARRINGTON_RD_1
Description: Tank 1- original install report.
View Attachment
Attachments:
Attachment Date: 11/22/2024 User: HARRINGTON_RD_1
Description: Tank 1... 2024-11-21
View Attachment
Attachments:
Attachment Date: 11/22/2024 User: HARRINGTON_RD_1
Description: Tank 1 label... 2024-11-21
View Attachment
03/02/2000 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 710(1)
Comments:
Comment Date: 08/30/2024 User: HARRINGTON_RD_1
Description: Anna C. Stoddard | Service & Tank Compliance Program Manager PowerSecure, Inc. – Environmental Compliance C: 336-264-3414 | anna.stoddard@powersecure.com
Comments:
Comment Date: 08/30/2024 User: HARRINGTON_RD_1
Description: Natalie Woodward | Customer Service Manager III | Distributed Infrastructure Office: (770) 721-7111 x 4059 | Direct: (470) 863-2509 | Cell: (470) 479-5875 | Email: nwoodward@powersecure.com
Comments:
Comment Date: 07/15/2018 User: HARRINGTON_RD_1
Description: Tank 1 was installed in 2012 at facility DEP# 9810102. The tank is in the same place in 2018, but has been registered at the current facility DEP# 9816232 (WM 1225). This was done to separate the Powersecure registrations from the Wal Mart registrations in order to avoid confusion.
Attachments:
Attachment Date: 09/09/2018 User: HARRINGTON_RD_1
Description: Tank 1- original install report.
View Attachment
Attachments:
Attachment Date: 11/22/2024 User: HARRINGTON_RD_1
Description: Tank 1... 2024-11-21
View Attachment
Attachments:
Attachment Date: 11/22/2024 User: HARRINGTON_RD_1
Description: Tank 1 label... 2024-11-21
View Attachment
06/23/1999 Legacy Activity Starkey, Dorene M.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
05/28/1999 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 710(1)
Comments:
Comment Date: 02/18/2009 User: BECKER_GT_1
Description: Zurich-January 15, 2009-January 15, 2010.
Comments:
Comment Date: 10/07/2005 User: UNKNOWN
Description: REGISTRATION: PER YORK CLAIMS SERVICE KIM CARPENTER, ADDITIONAL PROPERTY OWNER ADDRESS IS FOR NANCY JOHNSON AT 1604 ALABAMA DR APT #106, WINTER PARK, FL 32789.....KMW
Attachments:
Attachment Date: 03/04/2022 User: SHOCK_E_1
Description: Site view 20220216
View Attachment
05/28/1999 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 710(1)
Comments:
Comment Date: 02/18/2009 User: BECKER_GT_1
Description: Zurich-January 15, 2009-January 15, 2010.
Comments:
Comment Date: 10/07/2005 User: UNKNOWN
Description: REGISTRATION: PER YORK CLAIMS SERVICE KIM CARPENTER, ADDITIONAL PROPERTY OWNER ADDRESS IS FOR NANCY JOHNSON AT 1604 ALABAMA DR APT #106, WINTER PARK, FL 32789.....KMW
Attachments:
Attachment Date: 03/04/2022 User: SHOCK_E_1
Description: Site view 20220216
View Attachment
05/28/1999 Violation Closed Starkey, Dorene M.
Significance: SNC-B Status: Closed
Rule: 400(3)
Comments:
Comment Date: 06/08/2004 User: UNKNOWN
Description: GENERAL: PIPING: ABOVEGROUND SINGLE WALL HYDRAULIC.
05/28/1999 Violation Closed Starkey, Dorene M.
Significance: SNC-B Status: Closed
Rule: 600(1)(a)2
Comments:
Comment Date: 08/07/2006 User: REEDER_JH_1
Description: RELEASE DETECTION, as of 8/4/2006: a. STP sumps, dispenser liners, and tank interstice sensors wired to a Veeder-Root TLS-350R controller: L1: Plus tank (T1) interstitial float sensor. L2: Premium tank (T2) interstitial float sensor. L3: Regular tank (T3) interstitial float sensor. L4: Regular tank (T4), slave, interstitial float sensor - T3 and T4 are manifolded. S1: Dispenser 1/2 smart sensor. S2: Dispenser 3/4 smart sensor. S3: Dispenser 5/6 smart sensor. S4: Dispenser 7/8 smart sensor. S5: Plus STP sump smart sensor. S6: Premium STP sump smart sensor. S7: Regular STP sump smart sensor. S8: Regular slave manifold-piping sump smart sensor. b. Monthly visual inspections which includes interstitial monitoring of the double-walled spill buckets. Inspections shall also include the primary spill buckets and dispenser hoses. c. Mechanical line leak detectors.
Attachments:
Attachment Date: 10/30/2006 User: TRETHEWEY_MB_1
Description: SITE PHOTO (B) - 10/25/06
View Attachment
Attachments:
Attachment Date: 10/24/2013 User: TRETHEWEY_MB_1
Description: TIN 10/15/2013 Site Diagram & Equipment Location
View Attachment
Attachments:
Attachment Date: 10/24/2013 User: TRETHEWEY_MB_1
Description: TIN 10/15/2013 Tank Field.
View Attachment
Attachments:
Attachment Date: 11/03/2022 User: TRETHEWEY_MB_1
Description: TCI 11-1-2022 photo update
View Attachment
05/28/1999 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 600(1)(d)
Attachments:
Attachment Date: 12/26/2018 User: NATALINE_GE_1
Description: 2018 Site Photo
View Attachment
Attachments:
Attachment Date: 12/26/2018 User: NATALINE_GE_1
Description: 2018 Site Map
View Attachment
05/28/1999 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 600(1)(e)
05/28/1999 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 700(1)(c)1
05/28/1999 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed