11/28/2023 Enforcement Tracking Activity Paul, Jennifer
Activity Status: Open
11/22/2023 Document Management Activity Christian, Erich
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity/Document was rejected on this date Date: 11/22/2023
Comment: Rejected by Haley McArtor: resolve associated 6009 violation
Events:
Event Type: Activity has been submitted for approval Date: 11/22/2023
Comment: Submitted for approval by: Erich Christian
Events:
Event Type: Activity has been finished Date: 11/22/2023
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 11/22/2023
Comment: Approved by Haley McArtor: a
Events:
Event Type: Activity has been submitted for approval Date: 11/22/2023
Comment: Submitted for approval by: Erich Christian
Attachments:
Attachment Date: 11/22/2023 User: CHRISTIAN_ED_1
Description: INF Kerosene Spill Bucket
View Attachment
11/22/2023 Document Management Activity Christian, Erich
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 11/22/2023
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 11/22/2023
Comment: Approved by Haley McArtor: a
Events:
Event Type: Activity has been submitted for approval Date: 11/22/2023
Comment: Submitted for approval by: Erich Christian
Events:
Event Type: Activity/Document was rejected on this date Date: 11/22/2023
Comment: Rejected by Haley McArtor: resolve associated 6009 violation
Events:
Event Type: Activity has been submitted for approval Date: 11/22/2023
Comment: Submitted for approval by: Erich Christian
Attachments:
Attachment Date: 11/22/2023 User: CHRISTIAN_ED_1
Description: Kings INF L5 Unleaded Sensor
View Attachment
11/22/2023 Enforcement Referral Activity Gainey, Helen
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 11/28/2023
Events:
Event Type: Activity has been submitted for approval Date: 11/22/2023
Comment: Submitted for approval by: Helen Gainey: Violations cited during routine compliance inspection.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 11/28/2023
Comment: Acknowledged and Assigned by Jennifer Paul
Events:
Event Type: Activity has been finished Date: 11/28/2023
Comment: Finished
Events:
Event Type: Activity has been assigned Date: 11/28/2023
Comment: Assigned to Jennifer Paul
Events:
Event Type: Activity/Document was accepted on this date Date: 11/28/2023
Comment: Accepted by Jennifer Paul: Accepted
Comments:
Comment Date: 11/22/2023 User: GAINEY_H_1
Description: Violations cited during routine compliance inspection.
Attachments:
Attachment Date: 11/22/2023 User: GAINEY_H_1
Description: 8521795_CRDE Information Sheet_11-22-2023
View Attachment
11/22/2023 Document Management Activity Christian, Erich
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 11/22/2023
Comment: Submitted for approval by: Erich Christian
Events:
Event Type: Activity/Document has been approved Date: 11/22/2023
Comment: Approved by Haley McArtor: a
Events:
Event Type: Activity/Document was rejected on this date Date: 11/22/2023
Comment: Rejected by Haley McArtor: resolve associated 6009 violation
Events:
Event Type: Activity has been finished Date: 11/22/2023
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 11/22/2023
Comment: Submitted for approval by: Erich Christian
Attachments:
Attachment Date: 11/22/2023 User: CHRISTIAN_ED_1
Description: INF Unleaded and Kerosene STP Sumps
View Attachment
11/16/2023 Electronic Communication Activity Christian, Erich
Activity Closed Date: 11/16/2023 Activity Status: Closed
Date: 11/16/2023
Recipient: Robert Palmer and Hani Baskaron
Sender: Erich Christian
Subject: Final Violation Reminder
Message: See Attached.
Events:
Event Type: Activity has been finished Date: 11/16/2023
Comment: Finished
10/27/2023 Electronic Communication Activity Christian, Erich
Activity Closed Date: 10/27/2023 Activity Status: Closed
Date: 10/27/2023
Recipient: Robert Palmer and Hani Baskaron
Sender: Erich Christian
Subject: Violation Reminder Email
Message: See Attached.
Events:
Event Type: Activity has been finished Date: 10/27/2023
Comment: Finished
09/12/2023 Electronic Communication Activity Christian, Erich
Activity Closed Date: 09/12/2023 Activity Status: Closed
Date: 09/12/2023
Recipient: Robert Palmer and Hani Baskaron
Sender: Erich Christian
Subject: Violation Reminder Email
Message: See Attached.
Events:
Event Type: Activity has been finished Date: 09/12/2023
Comment: Finished
08/31/2023 Violation Open Christian, Erich
Significance: Minor Status: Open
Criteria ID: 6013
Rule: 62-761.420(3), 62-761.420(4), 62-761.420(8)
08/31/2023 Editable Letter Activity Christian, Erich
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 08/31/2023
Comment: Submitted for approval by: Erich Christian
Events:
Event Type: Activity/Document has been approved Date: 08/31/2023
Comment: Approved by Haley McArtor: a
Events:
Event Type: Activity has been finished Date: 08/31/2023
Comment: Finished
Events:
Event Type: Activity/Document was rejected on this date Date: 08/31/2023
Comment: Rejected by Haley McArtor: Change company name under Hani's name to "Jacksonville 76 Petroleum LLC"
Events:
Event Type: Document has been sent Date: 08/31/2023
Comment: Sent
Events:
Event Type: Activity has been submitted for approval Date: 08/31/2023
Comment: Submitted for approval by: Erich Christian
Attachments:
Attachment Date: 08/31/2023 User: CHRISTIAN_ED_1
Description: 8532795 Jacksonville 76 Petroleum CAO
View Attachment
08/31/2023 Violation Closed Christian, Erich
Significance: Minor Status: Closed
Criteria ID: 6009
Rule: 62-761.405(3)
08/28/2023 Violation Open Christian, Erich
Significance: SNC-B Status: Open
Criteria ID: 6014
Rule: 62-761.430(2)
08/28/2023 Incident Activity Christian, Erich
Activity Status: Open
08/28/2023 Incident Activity Christian, Erich
Activity Status: Open
08/28/2023 Incident Activity Christian, Erich
Activity Status: Open
08/28/2023 Violation Open Christian, Erich
Significance: SNC-B Status: Open
Criteria ID: 6014
Rule: 62-761.430(2)
08/28/2023 Violation Closed Christian, Erich
Significance: Minor Status: Closed
Criteria ID: 6075
Rule: 62-761.710(4)
08/28/2023 Violation Open Christian, Erich
Significance: SNC-B Status: Open
Criteria ID: 6063
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2
08/28/2023 Violation Closed Christian, Erich
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
08/28/2023 Violation Open Christian, Erich
Significance: Minor Status: Open
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
08/28/2023 Violation Closed Christian, Erich
Significance: Minor Status: Closed
Criteria ID: 6003
Rule: 62-761.400(1)(b), 62-761.400(2), 62-761.400(2)(a), 62-761.400(3), 62-761.400(3)(a), 62-761.400(3)(b), 62-761.400(3)(c)
08/28/2023 Violation Closed Christian, Erich
Significance: Minor Status: Closed
Criteria ID: 6009
Rule: 62-761.405(3)
08/28/2023 Violation Open Christian, Erich
Significance: Minor Status: Open
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
08/28/2023 Violation Closed Christian, Erich
Significance: Minor Status: Closed
Criteria ID: 6009
Rule: 62-761.405(3)
08/28/2023 Violation Open Christian, Erich
Significance: Minor Status: Open
Criteria ID: 6072
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1, 62-761.700(3)(a)1.a, 62-761.700(3)(a)1.b, 62-761.700(3)(a)1.c, 62-761.700(3)(a)1.d, 62-761.700(3)(a)1.e, 62-761.700(3)(a)1.f, 62-761.700(3)(a)1.g, 62-761.700(3)(a)2
08/28/2023 Violation Open Christian, Erich
Significance: Minor Status: Open
Criteria ID: 6015
Rule: 62-761.430(4), 62-761.430(5)
08/28/2023 Violation Closed Christian, Erich
Significance: Minor Status: Closed
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
08/28/2023 Violation Open Christian, Erich
Significance: Minor Status: Open
Criteria ID: 6015
Rule: 62-761.430(4), 62-761.430(5)
08/28/2023 Violation Open Christian, Erich
Significance: SNC-B Status: Open
Criteria ID: 6014
Rule: 62-761.430(2)
08/28/2023 Violation Open Christian, Erich
Significance: Minor Status: Open
Criteria ID: 6015
Rule: 62-761.430(4), 62-761.430(5)
08/24/2023 Site Inspection Activity Closed Christian, Erich
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 08/24/2023
Activity Closed Date: 08/31/2023 Activity Closed By: CHRISTIAN_ED_1
Events:
Event Type: Activity has been finished Date: 08/31/2023
Comment: Finished
Events:
Event Type: Activity has not been approved Date: 08/31/2023
Comment: Not approved by Haley McArtor: see email
Events:
Event Type: Activity has not been approved Date: 08/28/2023
Comment: Not approved by Haley McArtor: see email
Events:
Event Type: Activity has been submitted for approval Date: 08/28/2023
Comment: Submitted for approval by: Erich Christian
Events:
Event Type: Activity has been submitted for approval Date: 08/31/2023
Comment: Submitted for approval by: Erich Christian
Events:
Event Type: Activity has not been approved Date: 08/31/2023
Comment: Not approved by Haley McArtor: We are still missing at 6009, Cite 6009: Greater than an inch of liquid was found in tanks 5, and 7's STP sumps. Resolution: Submit an INF
Events:
Event Type: Activity has been submitted for approval Date: 08/31/2023
Comment: Submitted for approval by: Erich Christian
Events:
Event Type: Activity/Document has been approved Date: 08/31/2023
Comment: Approved by Haley McArtor: a
Events:
Event Type: Activity has been submitted for approval Date: 08/28/2023
Comment: Submitted for approval by: Erich Christian
07/21/2023 Electronic Communication Activity Christian, Erich
Activity Closed Date: 07/21/2023 Activity Status: Closed
Date: 07/21/2023
Recipient: Robert Palmer and Hani Baskaron
Sender: Erich Christian
Subject: CA Letter
Message: See attached.
Events:
Event Type: Activity has been finished Date: 07/21/2023
Comment: Finished
07/21/2023 Electronic Communication Activity Christian, Erich
Activity Closed Date: 07/21/2023 Activity Status: Closed
Date: 07/21/2023
Recipient: Robert Palmer and Hani Baskaron
Sender: Erich Christian
Subject: CA Email
Message: See Attached.
Events:
Event Type: Activity has been finished Date: 07/21/2023
Comment: Finished
07/17/2023 Comment McArtor, Haley
Description: Property owner: Marc Corker mc@multicor.us
03/03/2022 Editable Letter Activity Gainey, Helen
Activity Title: Closure Assessment Report (Complete) Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/03/2022
Comment: Finished
Attachments:
Attachment Date: 03/03/2022 User: GAINEY_H_1
Description: 8521795_Spill Bucket Closure Report Review_03-03-2022
View Attachment
02/24/2022 Editable Letter Activity Harris, Sarah B
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/28/2022
Comment: Finished
Attachments:
Attachment Date: 02/28/2022 User: HARRIS_SB
Description: 8521795 Return to Compliance
View Attachment
02/22/2022 Violation Closed Gregory, Hali M
Significance: Minor Status: Closed
Criteria ID: 6008
Rule: 62-761.405(1), 62-761.405(1)(a), 62-761.405(1)(b), 62-761.405(1)(c), 62-761.405(2), 62-761.405(2)(a), 62-761.405(2)(b), 62-761.405(2)(c), 62-761.405(2)(d)
02/22/2022 TCAR Activity Gainey, Helen
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 03/03/2022
Events:
Event Type: Activity has been finished Date: 03/03/2022
Comment: Finished
Attachments:
Attachment Date: 02/22/2022 User: GAINEY_H_1
Description: 8521795_ Spill Bucket Closure Assessment_01-13-2022
View Attachment
02/22/2022 Site Inspection Activity Closed Gregory, Hali M
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/22/2022
Activity Closed Date: 02/22/2022 Activity Closed By: GREGORY_HM_1
Events:
Event Type: Activity has been finished Date: 02/22/2022
Comment: Finished
02/22/2022 Site Inspection Activity Closed Gregory, Hali M
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/22/2022
Activity Closed Date: 02/22/2022 Activity Closed By: GREGORY_HM_1
Events:
Event Type: Activity has been finished Date: 02/22/2022
Comment: Finished
01/31/2022 Document Management Activity Harris, Sarah B
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/10/2022
Comment: Finished
Attachments:
Attachment Date: 01/31/2022 User: HARRIS_SB
Description: Incident Notification Form
View Attachment
01/31/2022 Document Management Activity Harris, Sarah B
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/10/2022
Comment: Finished
Attachments:
Attachment Date: 01/31/2022 User: HARRIS_SB
Description: Incident Notification Form
View Attachment
12/13/2021 Document Management Activity Harris, Sarah B
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/19/2022
Comment: Finished
Attachments:
Attachment Date: 12/13/2021 User: HARRIS_SB
Description: Incident Notification Form
View Attachment
12/13/2021 Incident Activity Harris, Sarah B
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 01/19/2022
Events:
Event Type: Activity has been finished Date: 01/19/2022
Comment: Finished
Comments:
Comment Date: 03/01/2022 User: GAINEY_H_1
Description: Revised INF submitted by Fegiste Consulting 2/28/2022 referencing both spill buckets in attachments below.
Comments:
Comment Date: 01/19/2022 User: HARRIS_SB
Description: New SB installed
12/13/2021 Incident Activity Harris, Sarah B
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 01/19/2022
Events:
Event Type: Activity has been finished Date: 01/19/2022
Comment: Finished
Comments:
Comment Date: 03/01/2022 User: GAINEY_H_1
Description: Revised INF submitted by Fegiste Consulting 2/28/2022 referencing both spill buckets in attachments below.
Comments:
Comment Date: 01/19/2022 User: HARRIS_SB
Description: New SB installed
11/30/2021 Editable Letter Activity Valenzuela, Shannon
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 11/30/2021
Comment: Submitted for approval by: Shannon Valenzuela
Events:
Event Type: Document has been sent Date: 11/30/2021
Comment: Sent
Events:
Event Type: Activity/Document has been approved Date: 11/30/2021
Comment: Approved by Jean Richards: Approved
Events:
Event Type: Activity has been finished Date: 11/30/2021
Comment: Finished
Attachments:
Attachment Date: 11/30/2021 User: VALENZUELA_S_1
Description: Compliance Offer Assistance Letter
View Attachment
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: SNC-B Status: Closed
Criteria ID: 6014
Rule: 62-761.430(2)
11/29/2021 Incident Activity Valenzuela, Shannon
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 02/22/2022
Events:
Event Type: Activity has been finished Date: 02/22/2022
Comment: Finished
11/29/2021 Incident Activity Valenzuela, Shannon
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 02/24/2022
Events:
Event Type: Activity has been finished Date: 02/24/2022
Comment: Finished
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: SNC-B Status: Closed
Criteria ID: 6011
Rule: 62-761.420(2)
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6072
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1, 62-761.700(3)(a)1.a, 62-761.700(3)(a)1.b, 62-761.700(3)(a)1.c, 62-761.700(3)(a)1.d, 62-761.700(3)(a)1.e, 62-761.700(3)(a)1.f, 62-761.700(3)(a)1.g, 62-761.700(3)(a)2
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6009
Rule: 62-761.405(3)
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: SNC-B Status: Closed
Criteria ID: 6014
Rule: 62-761.430(2)
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6015
Rule: 62-761.430(4), 62-761.430(5)
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6072
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1, 62-761.700(3)(a)1.a, 62-761.700(3)(a)1.b, 62-761.700(3)(a)1.c, 62-761.700(3)(a)1.d, 62-761.700(3)(a)1.e, 62-761.700(3)(a)1.f, 62-761.700(3)(a)1.g, 62-761.700(3)(a)2
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6015
Rule: 62-761.430(4), 62-761.430(5)
11/29/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6009
Rule: 62-761.405(3)
11/22/2021 Enforcement Tracking Activity Harris, Sarah B
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 02/28/2022
Events:
Event Type: Activity has been finished Date: 02/28/2022
Comment: Finished
11/17/2021 Enforcement Referral Activity Gainey, Helen
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 11/22/2021
Events:
Event Type: Activity has been assigned Date: 11/22/2021
Comment: Assigned to Sarah B Harris
Events:
Event Type: Activity/Document was acknowledged on this date Date: 11/22/2021
Comment: Acknowledged and Assigned by Kajani Cole
Events:
Event Type: Activity has been finished Date: 11/22/2021
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 11/22/2021
Comment: Accepted by Sarah B Harris: 11/22/2021
Events:
Event Type: Activity has been submitted for approval Date: 11/17/2021
Comment: Submitted for approval by: Helen Gainey: Violations cited during compliance inspection.
Comments:
Comment Date: 11/17/2021 User: GAINEY_H_1
Description: Violations cited during compliance inspection.
Attachments:
Attachment Date: 11/17/2021 User: GAINEY_H_1
Description: 8521795_CRDE Information Sheet_11-17-2021
View Attachment
11/15/2021 Site Inspection Activity Closed Valenzuela, Shannon
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 11/15/2021
Activity Closed Date: 11/30/2021 Activity Closed By: VALENZUELA_S_1
Events:
Event Type: Activity/Document has been approved Date: 11/30/2021
Comment: Approved by Jean Richards: Approved
Events:
Event Type: Activity has not been approved Date: 11/30/2021
Comment: Not approved by Jean Richards: Violations 6009, 6014, & 6015 need to be cited for both the spill buckets and STP sumps.
Events:
Event Type: Activity has not been approved Date: 11/29/2021
Comment: Not approved by Jean Richards: An Incident Activity needs to be opened, an INF requested, and violations cited for liquid in the premium & regular STP sumps. An Incident Activity needs to be opened, an INF requested, and violations cited for liquid in the spill bucket interstice for regular & kerosene . Violation 6073 for the spill buckets does not include liquid in the interstice of the regular & kerosene. Comments under STP SUMPS state "All were free of excessive corrosion" this should not be determined until the sumps are dry and can be fully viewed.
Events:
Event Type: Activity has been submitted for approval Date: 11/30/2021
Comment: Submitted for approval by: Shannon Valenzuela
Events:
Event Type: Activity has been finished Date: 11/30/2021
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 11/29/2021
Comment: Submitted for approval by: Shannon Valenzuela
Events:
Event Type: Activity has been submitted for approval Date: 11/29/2021
Comment: Submitted for approval by: Shannon Valenzuela
Comments:
Comment Date: 11/21/2021 User: VALENZUELA_S_1
Description: Signature not captured due to COVID-19 protocols. The inspection report and letter were completed off-site and emailed to Hani Baskaron at hsbpetro@yahoo.com. Violations that are not resolved within 90 days from the date cited will be referred to the Florida Department of Environmental Protection’s Northeast District Office and will be subject to a Consent Order with penalties.
11/09/2021 Electronic Communication Activity Valenzuela, Shannon
Activity Closed Date: 11/09/2021 Activity Status: Closed
Date: 11/09/2021
Recipient: HANI BASKARON
Sender: Shannon Valenzuela
Subject: resolving violations-and scheduling inspections
Message: see attachment
Events:
Event Type: Activity has been finished Date: 11/09/2021
Comment: Finished
11/05/2021 Electronic Communication Activity Valenzuela, Shannon
Activity Closed Date: 11/05/2021 Activity Status: Closed
Date: 11/05/2021
Recipient: HANI BASKARON
Sender: Shannon Valenzuela
Subject: resolving violations
Message: see attachment
Events:
Event Type: Activity has been finished Date: 11/05/2021
Comment: Finished
09/17/2021 Electronic Communication Activity Valenzuela, Shannon
Activity Closed Date: 09/20/2021 Activity Status: Closed
Date: 09/17/2021
Recipient: HANI BASKARON
Sender: Shannon Valenzuela
Subject: request for violation correction
Message: see attached
Events:
Event Type: Activity has been finished Date: 09/20/2021
Comment: Finished
08/26/2021 Editable Letter Activity Valenzuela, Shannon
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/26/2021
Comment: Finished
Events:
Event Type: Document has been sent Date: 08/26/2021
Comment: Sent
Events:
Event Type: Activity/Document has been approved Date: 08/26/2021
Comment: Approved by Jean Richards: Approved
Events:
Event Type: Activity has been submitted for approval Date: 08/26/2021
Comment: Submitted for approval by: Shannon Valenzuela
Attachments:
Attachment Date: 08/26/2021 User: VALENZUELA_S_1
Description: Compliance Offer Assistance Letter
View Attachment
08/23/2021 Attachment Valenzuela, Shannon
08/23/2021 Electronic Communication Activity Valenzuela, Shannon
Activity Closed Date: 08/23/2021 Activity Status: Closed
Date: 08/23/2021
Recipient: HANI BASKARON
Sender: Shannon Valenzuela
Subject: Compliance Outreach Email
Message: see attached
Events:
Event Type: Activity has been finished Date: 08/23/2021
Comment: Finished
08/23/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6074
Rule: 62-761.710(1), 62-761.710(2), 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(3), 62-761.710(3)(a), 62-761.710(3)(b), 62-761.710(3)(c), 62-761.710(3)(d), 62-761.710(3)(e), 62-761.710(3)(f), 62-761.710(3)(g), 62-761.710(3)(h), 62-761.710(3)(i)
08/18/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6075
Rule: 62-761.710(4)
08/18/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6006
Rule: 62-761.400(5)
08/18/2021 Violation Closed Valenzuela, Shannon
Significance: Minor Status: Closed
Criteria ID: 6001
Rule: 62-761.100(3)
08/17/2021 Site Inspection Activity Closed Valenzuela, Shannon
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 08/17/2021
Activity Closed Date: 08/26/2021 Activity Closed By: VALENZUELA_S_1
Events:
Event Type: Activity has been submitted for approval Date: 08/25/2021
Comment: Submitted for approval by: Shannon Valenzuela
Events:
Event Type: Activity has been submitted for approval Date: 08/24/2021
Comment: Submitted for approval by: Shannon Valenzuela
Events:
Event Type: Activity/Document has been approved Date: 08/26/2021
Comment: Approved by Jean Richards: Approved
Events:
Event Type: Activity has been submitted for approval Date: 08/26/2021
Comment: Submitted for approval by: Shannon Valenzuela
Events:
Event Type: Activity has not been approved Date: 08/26/2021
Comment: Not approved by Jean Richards: I started this with Haley yesterday and will discuss with everyone on Monday. For the System Tests entries for the overfill and release detection, include the types of devices or sensors that were tested. (i.e. Overfill - overfill protection valve, ball float valves; Release Detection - tank interstitial sensor, STP sump sensor, dispenser sensor, etc.) This will help to ensure that all testing is reviewed and make it clearer for the next inspector. This is not necessary for the spill bucket and sump testing since those are pretty straight forward, but it's useful to include just to make it clear what was tested.
Events:
Event Type: Activity has been finished Date: 08/26/2021
Comment: Finished
Events:
Event Type: Activity has not been approved Date: 08/25/2021
Comment: Not approved by Jean Richards: Returned to add system tests and explain how records were received.
08/12/2019 Editable Letter Activity Mondo, Patrick W
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 08/12/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 08/12/2019
Comment: Finished
Attachments:
Attachment Date: 08/12/2019 User: MONDO_PW_1
Description: 8521795_ In Compliance Letter_08-12-2019
View Attachment
08/02/2019 Site Inspection Activity Closed Mondo, Patrick W
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/02/2019
Activity Closed Date: 08/12/2019 Activity Closed By: MONDO_PW_1
Events:
Event Type: Activity has been finished Date: 08/12/2019
Comment: Finished
07/23/2019 Electronic Communication Activity Mondo, Patrick W
Activity Closed Date: 07/23/2019 Activity Status: Closed
Date: 07/23/2019
Recipient: Augusto Nascimento
Sender: EQD
Subject: Outreach email provided prior to Compliance Inspection.
Message: See attached.
Events:
Event Type: Activity has been finished Date: 07/23/2019
Comment: Finished
02/13/2019 Editable Letter Activity Gregory, Hali M
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/13/2019
Comment: Finished
Events:
Event Type: Document has been sent Date: 02/13/2019
Comment: Sent
Attachments:
Attachment Date: 02/13/2019 User: GREGORY_HM_1
Description: In Compliance letter
View Attachment
01/31/2019 Site Inspection Activity Closed Gregory, Hali M
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/31/2019
Activity Closed Date: 02/07/2019 Activity Closed By: GREGORY_HM_1
Events:
Event Type: Activity has been finished Date: 02/07/2019
Comment: Finished
09/18/2017 Electronic Communication Activity Gregory, Hali M
Activity Closed Date: 09/18/2017 Activity Status: Closed
Date: 09/18/2017
Recipient: Phillip Bujalski
Sender: Hali Gregory
Subject: FR and Annual Testing
Message: Emailed representative on 9/5/2017 about testing and FR for cited MNV facilities.
Events:
Event Type: Activity has been finished Date: 09/18/2017
Comment: Finished
09/18/2017 Electronic Communication Activity Gregory, Hali M
Activity Closed Date: 09/18/2017 Activity Status: Closed
Date: 09/18/2017
Recipient: Phillip Bujalski, Leticia Abreu and Sergio Delmico
Sender: Hali Gregory
Subject: FR and Annual Testing
Message: Emailed all three representatives on 9/7/2017 about testing and FR for cited MNV facilities.
Events:
Event Type: Activity has been finished Date: 09/18/2017
Comment: Finished
08/09/2017 Editable Letter Activity Richards, Jean
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 08/09/2017
Comment: Sent
Events:
Event Type: Activity has been finished Date: 08/09/2017
Comment: Finished
Attachments:
Attachment Date: 08/09/2017 User: RICHARDS_JE_1
Description: 8521795_RTC Letter_08-08-2017
View Attachment
07/31/2017 Site Inspection Activity Closed Gregory, Hali M
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/31/2017
Activity Closed Date: 08/08/2017 Activity Closed By: GREGORY_HM_1
Events:
Event Type: Activity has been finished Date: 08/08/2017
Comment: Finished
06/23/2017 Editable Letter Activity Richards, Jean
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/23/2017
Comment: Finished
Attachments:
Attachment Date: 06/23/2017 User: RICHARDS_JE_1
Description: 8521795_CSNCL Viol 1105_1105_1109_06-23-2017
View Attachment
03/20/2017 Electronic Communication Activity Gregory, Hali M
Activity Closed Date: 03/20/2017 Activity Status: Closed
Date: 03/20/2017
Recipient: Leticia Abreu
Sender: Hali Gregory
Subject: Compliance Report
Message: See attachment
Events:
Event Type: Activity has been finished Date: 03/20/2017
Comment: Finished
03/16/2017 Editable Letter Activity Gregory, Hali M
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: In Compliance Letter
Events:
Event Type: Activity has been finished Date: 03/16/2017
Comment: Finished
Attachments:
Attachment Date: 03/16/2017 User: RICHARDS_JE_1
Description: 8521795_1st County NCL Viol 1105_1105_1009_03-16-2017
View Attachment
03/14/2017 Violation Closed Gregory, Hali M
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
03/14/2017 Electronic Communication Activity Gregory, Hali M
Activity Closed Date: 03/14/2017 Activity Status: Closed
Date: 03/14/2017
Recipient: Leticia Abreu
Sender: Hali GRegory
Subject: Compliance assistance
Message: See attachment
Events:
Event Type: Activity has been finished Date: 03/14/2017
Comment: Finished
03/14/2017 Site Inspection Activity Closed Gregory, Hali M
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/14/2017
Activity Closed Date: 03/16/2017 Activity Closed By: GREGORY_HM_1
Events:
Event Type: Activity has been finished Date: 03/16/2017
Comment: Finished
Comments:
Comment Date: 03/15/2017 User: GREGORY_HM_1
Description: New upcoming due dates for: • overfill protection testing (by 1/11/18) • integrity testing of sumps and spill containment (sw spill buckets by 1/11/18 and sumps and dw spill buckets by 10/13/18) • certified operators (10/13/18) As of 1/11/2017, all records are to be kept for up to three years. You can access both rule chapters on the Announcement Page: http://www.dep.state.fl.us/waste/categories/shw/pages/announcements.htm
03/14/2017 Violation Closed Gregory, Hali M
Significance: Minor Status: Closed
Criteria ID: 1009
Rule: 62-761.450(1)(b)1., 62-761.450(1)(b)2., 62-761.450(1)(b)3., 62-761.450(1)(b)4.
Comments: Confirm ownership changes with the facility representative. If needed, research the new owner information with the facility's other licenses, especially alcoholic beverage and occupational. Note that new personnel or a change in name may just reflect the sale of the business rather than sale of the property. If a change of ownership has occurred, allow a reasonable time (a recommended time frame can be approximately 1-3 months) for the DEP database to be updated. Ask the facility to produce a dated registration form. Mark it as a discrepancy if a longer time frame has elapsed. Note: DEP Registration Section may change the ownership without receiving any additional proof, other than a registration form. Has the Certification of Financial Responsibility been revised?
03/14/2017 Violation Closed Gregory, Hali M
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
07/02/2015 Electronic Communication Activity Hill, Katrina L
Activity Closed Date: 07/02/2015 Activity Status: Closed
Date: 07/02/2015
Recipient: Kevin Kusmirek
Sender: Katrina Hill
Subject: Emailed Non-Compliance Inspection Report_06-25-2015_07-02-2015
Message: Emailed Non-Compliance Inspection Report_06-25-2015_07-02-2015
Events:
Event Type: Activity has been finished Date: 07/02/2015
Comment: Finished
06/29/2015 Electronic Communication Activity Hill, Katrina L
Activity Closed Date: 06/29/2015 Activity Status: Closed
Date: 06/29/2015
Recipient: Kevin Kusmirek; Amanda Mayor
Sender: Katrina Hill
Subject: Emailed 1st County NCL Viol 1040
Message: Emailed 1st County NCL Viol 1040
Events:
Event Type: Activity has been finished Date: 06/29/2015
Comment: Finished
06/25/2015 Site Inspection Activity Closed Hill, Katrina L
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/25/2015
Activity Closed Date: 07/02/2015 Activity Closed By: HILL_KL_1
Events:
Event Type: Activity has been finished Date: 07/02/2015
Comment: Finished
05/07/2015 Electronic Communication Activity Mayor, Amanda K
Activity Closed Date: 05/07/2015 Activity Status: Closed
Date: 05/07/2015
Recipient: Kevin Kusmirek
Sender: EQD
Subject: Emailed inspection report.
Message: See attachment.
Events:
Event Type: Activity has been finished Date: 05/07/2015
Comment: Finished
05/06/2015 Attachment Mayor, Amanda K
05/06/2015 Editable Letter Activity Mayor, Amanda K
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: Compliance Assistance Offer Letter
Events:
Event Type: Activity has been finished Date: 05/08/2015
Comment: Finished
Attachments:
Attachment Date: 05/07/2015 User: HILL_KL_1
Description: 8521795_1st County NCL Viol 1040
View Attachment
04/28/2015 Violation Closed Mayor, Amanda K
Significance: Minor Status: Closed
Criteria ID: 1040
Rule: 62-761.500(8)(c)1.
Comments: Mark this as out of compliance if the shear valves are not properly installed or anchored. The shear valve should be anchored to the dispenser frame in the ground. The valve should stay in place if the dispenser is knocked over. This is not intended to be the emergency fuel shut off system, and the emergency fuel shut off system already in place can not take the place of a shear valve. NFPA 30A Section 4-3.6 states: Small diameter piping systems connected to the dispenser should have a rigidly anchored automatically shutoff shear valve installed in accordance with the manufacturer's instructions. a. This valve should be at the base of each individual island type dispenser or at the inlet of each overhead dispensing device. b. This valve should incorporate a fusible link or other thermally activated device that will close the valve in the event of fire exposure. c. This valve should incorporate a mechanism to close the valve in the event of severe impact or displacement of the dispenser. d. The valve should be rigidly anchored so that the shear section functions as intended. An emergency shutoff valve incorporating a slip joint feature shall not be used. Note that NFPA 30A Section 4-3.6 suggests that shear valves be tested annually for functionality. However, Rule 761.500(8)(c)1 only requires installation standards to be met. You may recommend that the shear valves be tested annually but the Fire Marshall must enforce this. In an accident, as the dispenser is knocked over, these valves are intended to break and seal off the piping at the location of the valve to prevent a submersible pump from pumping out a geyser of fuel. It is both a fire hazard issue as well as environmental issue.
04/28/2015 Site Inspection Activity Closed Mayor, Amanda K
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/28/2015
Activity Closed Date: 05/06/2015 Activity Closed By: MAYOR_AK_1
Events:
Event Type: Activity has been finished Date: 05/06/2015
Comment: Finished
09/06/2013 Electronic Communication Activity Williams, April K.
Activity Closed Date: 09/06/2013 Activity Status: Closed
Date: 09/06/2013
Recipient: Scott Janashak, First Coast Energy, LLP
Sender: EQD
Subject: Emailed - Compliance Report
Message: See Attachment
Events:
Event Type: Activity has been finished Date: 09/06/2013
Comment: Finished
09/05/2013 Attachment Williams, April K.
09/05/2013 Emergency Preparedness Information Activity Williams, April K.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/05/2013
Events:
Event Type: Activity has been finished Date: 09/05/2013
Comment: Finished
09/05/2013 Attachment Williams, April K.
09/05/2013 Attachment Williams, April K.
09/05/2013 Attachment Williams, April K.
08/02/2013 Site Inspection Activity Closed Williams, April K.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/22/2013
Activity Closed Date: 09/05/2013 Activity Closed By: WILLIAMS_AK_1
Events:
Event Type: Activity has been finished Date: 09/05/2013
Comment: Finished
10/26/2011 Emergency Preparedness Information Activity Cain, Michael
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 10/26/2011
Events:
Event Type: Activity has been finished Date: 10/26/2011
Comment: Finished
10/11/2011 Site Inspection Activity Closed Cain, Michael
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/12/2011
Activity Closed Date: 10/26/2011 Activity Closed By: CAIN_M_1
Events:
Event Type: Activity has been finished Date: 10/26/2011
Comment: Finished
08/11/2010 Site Inspection Activity Closed Borisade, Charles
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/11/2010
Activity Closed Date: 08/27/2010 Activity Closed By: BORISADE_KA_1
Events:
Event Type: Activity has been finished Date: 08/27/2010
Comment: Finished
10/12/2009 Record Document Activity Parish, Kathy M.
Activity Status: Closed
Contact Name: R HENSON Activity Closed Date: 10/12/2009
10/02/2009 Record Document Activity Griffin, Tom
Activity Status: Closed
Contact Name: D J O'STEEN Activity Closed Date: 10/02/2009
10/01/2009 Attachment Parish, Kathy M.
10/01/2009 Attachment Parish, Kathy M.
09/15/2009 Violation Closed Parish, Kathy M.
Significance: Minor Status: Closed
Criteria ID: 1002
Rule: 62-761.400(2)(a)
Comments: Does STCM accurately reflect the tanks at the facility? This question concerns the registration process and payment of fees only - it is not about accurate registration. Check the number of tanks listed on the registration placard. Can the facility owner/operator produce a registration form to document submittal to DEP? Does STCM show that all DEP fees are paid? At the time of tank closure, a registration form should be submitted showing the change in tank codes.
09/15/2009 Editable Letter Activity Parish, Kathy M.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
08/30/2009 Site Inspection Activity Closed Parish, Kathy M.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/30/2009
Activity Closed Date: 08/30/2009 Activity Closed By: PARISH_KM_1
07/06/2009 Attachment Lunn, Raynald
06/18/2009 Attachment Lunn, Raynald
06/18/2009 Attachment Lunn, Raynald
06/09/2009 Attachment Allen, Eleanor
06/08/2009 TCAR Activity Holloway, Randall
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/08/2009
06/08/2009 Editable Letter Activity Holloway, Randall
Activity Title: Closure Review Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/08/2009
Comment: Sent on Mon Jun 08 07:29:06 EST 2009
04/17/2009 Site Inspection Activity Closed Lunn, Raynald
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/17/2009
Activity Closed Date: 04/17/2009 Activity Closed By: LUNN_RJ_1
04/17/2009 Site Inspection Activity Closed Lunn, Raynald
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/17/2009
Activity Closed Date: 06/15/2009 Activity Closed By: LUNN_RJ_1
07/31/2008 Emergency Preparedness Information Activity Parish, Kathy M.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 07/31/2008
Comments:
Comment Date: 07/31/2008 User: PARISH_KM_1
Description: Facility has 4 dual access dispensers.
06/27/2008 Site Inspection Activity Closed Parish, Kathy M.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/27/2008
Activity Closed Date: 07/31/2008 Activity Closed By: PARISH_KM_1
08/22/2007 Emergency Preparedness Information Activity Griffin, Tom
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 08/22/2007
08/20/2007 Site Inspection Activity Closed Griffin, Tom
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/20/2007
Activity Closed Date: 08/24/2007 Activity Closed By: WILLIAMS_AK_1
Comments:
Comment Date: 08/22/2007 User: GRIFFIN_TW_1
Description: 8521795 CHAPTER 62-761 FAC: UNDERGROUND STORAGE TANK NEED PHOTOGRAPHS: Photographs on file are accurate. Miscellaneous Proper notification was given prior to the inspection and proper identification was presented to the facility responsible party upon entry to the premises. ¿ The file review was conducted on 8/20/2007; and ¿ The site inspection was conducted on 8/22/2007. The method of release detection used at this facility is CSLD and visual inspection of secondary containment. The method of overfill protection used at this facility is spill buckets, flow shutoff & high level alarm. ¿ The site schematic has been reviewed for accuracy. The site schematic is fairly accurate. This system is scheduled for upgrade; therefore the schematic will remain as currently on file. ¿ The site equipment list has been reviewed for accuracy. ¿ The site photos have been reviewed for accuracy & relevancy. ¿ The facility coordinates in SWAP/Webpoint have been verified by office staff. ¿ The Emergency Preparedness information for this facility has been updated: YES Upgrade Notification: All single wall underground storage tank systems must be upgraded to double wall by 12/31/2009 Recordkeeping ¿ Required records made available within five working days (1122N): YES ¿ Required records have been kept for 2 yrs (1123): YES ¿ Required records have been kept for the life of the system. (1124N): YES Registration ¿ Registration Placard No: 286122 (4) ¿ All systems are registered and match Placard (1001N): YES - FOUR ¿ The Placard is current and the Registration fees paid (1002N): YES 2007 - 2008 ¿ The Placard kept in view (1003N): YES Note: Registration Fees are due and payable no later than June 30 of each year. Financial Responsibility ¿ The Financial Responsibility Records were current and made available for review (1004B): YES ¿ A Certificate of Financial Responsibility was made available (1004B): YES Financial Responsibility must be renewed before04/02/08 and a new Certificate of Responsibility completed. Equipment Approvals/Alternate Procedure ¿ Facility is in compliance with alternate procedure (2164N): THERE IS NO AP FOR THIS FACILITY ¿ Equipment is approved by Department (2165N): YES Notification & Reporting ¿ The facility responsibility party has reviewed the information on screens 1/13 & 3/13 for accuracy. There is no information change requiring the submittal of a Registration Form. Performance Standards Category A/B Integral Pipe ¿ Shears valves for pressurized systems installed properly on Category A/B (1047B): YES ¿ Fill box or tank marked with color code or contents for Category A/B (1049N): YES ¿ Kero is dull & needs touchup. Release Detection ¿ A release can be detected from any portion of system: 600(a) (1)1 - (1058N): YES ¿ The release detection system is operational: 600(1) (a) 2 - (1059N): YES ¿ Release detection performed monthly: 600(1) (1) d - (1062B): YES ¿ Is electronic leak detection system checked monthly: 600(1) (e) - (1063N): YES ¿ Release detection method for Category A/B: 610(2) ¿ (1075A): YES ¿ CSLD ¿ The RDRL matches the release detection method: 640(1) (c) (1082N): YES ¿ Problems found during monthly visual inspections noted: 640(2) (e) ¿ (1091N) YES ¿ Water fluctuations > 1.0 ¿not investigated or system tested: 640(3) (b) 4 - (1096N): NA ¿ ATG system in test mode every 30 days or operated continuously - 640(3) (d) (1099N): CSLD CONTINUOUS OPERATION Repairs Operation & Maintenance ¿ Piping sump - excess water or fuel removed (1115N): YES ¿ Release detection devices tested annually: 700(1) (3) c - (1117N): YES. SEE TEST SCHEDULE Incident & Discharge Response ¿ During the physical inspection of the facility, no evidence of a new product release was observed.
Comments:
Comment Date: 08/20/2007 User: GRIFFIN_TW_1
Description: 8521795_FCE 1037 UST TEST SCHEDULE: GENERAL The method of release detection used at this facility is continuous electronic monitoring of leak detection & visual inspection of secondary containment. The method of overfill protection used at this facility is alarm, spill bucket and flow shutoff. TANK Complete CSLD Tapes 62-761.610(1) (a) / (1073-B): YES ANNUAL LINE & LINE LEAK DETECTOR Pressurized Line Test - 62-761.610(3) (a) 2/ (1077B) (SW pipe in contact w/soil): (Able to detect a 0.1 gph leak 150% operating pressure) Last: 4/23/2007 Due: 4/23/2008 Line Leak Detector - 62-761.640(4) (a)/ (1103N): (Able to detect a 0.2 gph leak in the test mode/3 gph while in operation) Last: 4/23/2007 Due: 4/23/2008 ANNUAL OPERABILITY OF LEAK DETECTION DEVICES- 62-761.700(1) (c) 3 ATG: Veeder Root TLS 350 Last: 4/23/2007 Due: 4/23/2008 Tank Sensors: Last: 4/23/2007 Due: 4/23/2008 Interstitial Probe: NONE Sump Probe: NONE Dispenser Liner Probe: NONE CATHODIC PROTECTION: 62-761.700(1) (b) 2a: (1112N): NONE
08/20/2007 Emergency Preparedness Information Activity Griffin, Tom
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 08/20/2007
08/20/2007 Site Inspection Activity Closed Griffin, Tom
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/20/2007
Activity Closed Date: 08/24/2007 Activity Closed By: WILLIAMS_AK_1
Comments:
Comment Date: 08/22/2007 User: GRIFFIN_TW_1
Description: 8521795 CHAPTER 62-761 FAC: UNDERGROUND STORAGE TANK NEED PHOTOGRAPHS: Photographs on file are accurate. Miscellaneous Proper notification was given prior to the inspection and proper identification was presented to the facility responsible party upon entry to the premises. ¿ The file review was conducted on 8/20/2007; and ¿ The site inspection was conducted on 8/22/2007. The method of release detection used at this facility is CSLD and visual inspection of secondary containment. The method of overfill protection used at this facility is spill buckets, flow shutoff & high level alarm. ¿ The site schematic has been reviewed for accuracy. The site schematic is fairly accurate. This system is scheduled for upgrade; therefore the schematic will remain as currently on file. ¿ The site equipment list has been reviewed for accuracy. ¿ The site photos have been reviewed for accuracy & relevancy. ¿ The facility coordinates in SWAP/Webpoint have been verified by office staff. ¿ The Emergency Preparedness information for this facility has been updated: YES Upgrade Notification: All single wall underground storage tank systems must be upgraded to double wall by 12/31/2009 Recordkeeping ¿ Required records made available within five working days (1122N): YES ¿ Required records have been kept for 2 yrs (1123): YES ¿ Required records have been kept for the life of the system. (1124N): YES Registration ¿ Registration Placard No: 286122 (4) ¿ All systems are registered and match Placard (1001N): YES - FOUR ¿ The Placard is current and the Registration fees paid (1002N): YES 2007 - 2008 ¿ The Placard kept in view (1003N): YES Note: Registration Fees are due and payable no later than June 30 of each year. Financial Responsibility ¿ The Financial Responsibility Records were current and made available for review (1004B): YES ¿ A Certificate of Financial Responsibility was made available (1004B): YES Financial Responsibility must be renewed before04/02/08 and a new Certificate of Responsibility completed. Equipment Approvals/Alternate Procedure ¿ Facility is in compliance with alternate procedure (2164N): THERE IS NO AP FOR THIS FACILITY ¿ Equipment is approved by Department (2165N): YES Notification & Reporting ¿ The facility responsibility party has reviewed the information on screens 1/13 & 3/13 for accuracy. There is no information change requiring the submittal of a Registration Form. Performance Standards Category A/B Integral Pipe ¿ Shears valves for pressurized systems installed properly on Category A/B (1047B): YES ¿ Fill box or tank marked with color code or contents for Category A/B (1049N): YES ¿ Kero is dull & needs touchup. Release Detection ¿ A release can be detected from any portion of system: 600(a) (1)1 - (1058N): YES ¿ The release detection system is operational: 600(1) (a) 2 - (1059N): YES ¿ Release detection performed monthly: 600(1) (1) d - (1062B): YES ¿ Is electronic leak detection system checked monthly: 600(1) (e) - (1063N): YES ¿ Release detection method for Category A/B: 610(2) ¿ (1075A): YES ¿ CSLD ¿ The RDRL matches the release detection method: 640(1) (c) (1082N): YES ¿ Problems found during monthly visual inspections noted: 640(2) (e) ¿ (1091N) YES ¿ Water fluctuations > 1.0 ¿not investigated or system tested: 640(3) (b) 4 - (1096N): NA ¿ ATG system in test mode every 30 days or operated continuously - 640(3) (d) (1099N): CSLD CONTINUOUS OPERATION Repairs Operation & Maintenance ¿ Piping sump - excess water or fuel removed (1115N): YES ¿ Release detection devices tested annually: 700(1) (3) c - (1117N): YES. SEE TEST SCHEDULE Incident & Discharge Response ¿ During the physical inspection of the facility, no evidence of a new product release was observed.
Comments:
Comment Date: 08/20/2007 User: GRIFFIN_TW_1
Description: 8521795_FCE 1037 UST TEST SCHEDULE: GENERAL The method of release detection used at this facility is continuous electronic monitoring of leak detection & visual inspection of secondary containment. The method of overfill protection used at this facility is alarm, spill bucket and flow shutoff. TANK Complete CSLD Tapes 62-761.610(1) (a) / (1073-B): YES ANNUAL LINE & LINE LEAK DETECTOR Pressurized Line Test - 62-761.610(3) (a) 2/ (1077B) (SW pipe in contact w/soil): (Able to detect a 0.1 gph leak 150% operating pressure) Last: 4/23/2007 Due: 4/23/2008 Line Leak Detector - 62-761.640(4) (a)/ (1103N): (Able to detect a 0.2 gph leak in the test mode/3 gph while in operation) Last: 4/23/2007 Due: 4/23/2008 ANNUAL OPERABILITY OF LEAK DETECTION DEVICES- 62-761.700(1) (c) 3 ATG: Veeder Root TLS 350 Last: 4/23/2007 Due: 4/23/2008 Tank Sensors: Last: 4/23/2007 Due: 4/23/2008 Interstitial Probe: NONE Sump Probe: NONE Dispenser Liner Probe: NONE CATHODIC PROTECTION: 62-761.700(1) (b) 2a: (1112N): NONE
02/02/2007 Emergency Preparedness Information Activity Griffin, Tom
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/02/2007
09/23/2006 Emergency Preparedness Information Activity Carroll, Albert
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/23/2006
08/02/2006 Attachment Torsanko, Grace
08/02/2006 Attachment Torsanko, Grace
08/02/2006 Attachment Torsanko, Grace
08/02/2006 Attachment Torsanko, Grace
08/02/2006 Attachment Torsanko, Grace
07/27/2006 Site Inspection Activity Closed Torsanko, Grace
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/27/2006
Activity Closed Date: 08/02/2006 Activity Closed By: TORSANKO_G
Comments:
Comment Date: 08/02/2006 User: TORSANKO_G
Description: S T P sumps P C I , dry Disp.sumps A P T, dry, Shear valves anchored Vapor recovery coaxial with flapper valves for overfill protection Kerosene uses ball check valve for overfill protection Kerosene tank fill is a short fill pipe. (Short drop) Monthly line tests records good the day of inspection but records do not always have monthly tapes. Advised to obtain and keep with monthly maintenance records for two years. Placard posted R D R L at facility Registration information correct Records reviewed showed few minor problems. Overall good. No leaks found during inspection. System due for upgrade by 12-31-2009
Comments:
Comment Date: 08/02/2006 User: TORSANKO_G
Description: Release Detection C S L D U S Tank Alliance certified A T G - V R , T L S 350 U S Tank also tested lines and W P L L Ds.
07/27/2006 Site Inspection Activity Closed Torsanko, Grace
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/27/2006
Activity Closed Date: 08/02/2006 Activity Closed By: TORSANKO_G
Comments:
Comment Date: 08/02/2006 User: TORSANKO_G
Description: S T P sumps P C I , dry Disp.sumps A P T, dry, Shear valves anchored Vapor recovery coaxial with flapper valves for overfill protection Kerosene uses ball check valve for overfill protection Kerosene tank fill is a short fill pipe. (Short drop) Monthly line tests records good the day of inspection but records do not always have monthly tapes. Advised to obtain and keep with monthly maintenance records for two years. Placard posted R D R L at facility Registration information correct Records reviewed showed few minor problems. Overall good. No leaks found during inspection. System due for upgrade by 12-31-2009
Comments:
Comment Date: 08/02/2006 User: TORSANKO_G
Description: Release Detection C S L D U S Tank Alliance certified A T G - V R , T L S 350 U S Tank also tested lines and W P L L Ds.
08/29/2005 Legacy Activity Allen, Eleanor
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/08/2005 Legacy Activity Allen, Eleanor
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
12/17/2002 Legacy Activity Torsanko, Grace
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
08/28/2001 Legacy Activity Torsanko, Grace
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
07/10/2001 Violation Closed Torsanko, Grace
Significance: SNC-B Status: Closed
Rule: 500(2)(d)2
07/10/2001 Legacy Activity Torsanko, Grace
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
08/09/2000 Legacy Activity Cummings, Constance C.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
09/03/1999 Legacy Activity Cummings, Constance C.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/26/1999 Legacy Activity Cummings, Constance C.
Activity Name: COMPLIANCE W/O FORMAL ENFORCEMENT ACTION Activity Status: Closed
10/14/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 05/05/2009 User: BRAZILE_DO_1
Description: Emergency generator Petroleum storage tank- Publix Super Market #1241 -located at 11240 P C Beach Florida. Power Secure of North Carolina installed the emergency generator, and is also providing remote monitoring of the release detection. Release Detection- Interstitial Space alarm-Double walled Tank & Visual of AST System. Overfill protection - Battery powered alarm device which clamps onto the outside of the visual mount fuel level gauge. Tank #1 -AST is a Double Walled, Steel, Closed Top Diked Generator Base Tank built by JRS Custom Fab, EQ-497. A Caterpillar Emergency Generator Set in a custom enclosure is mounted on top of the tank. Piping consists of single-walled flexible synthetic fuel lines to the Diesel engine for the generator, entirely inside the enclosure. No sumps are installed; all required components are mounted directly on the tank. Release Detection consists of a liquid sensor in the tank interstice, connected to a separate NextGear switching unit which transmits an alarm signal via fiber optics to PowerSecure in North Carolina, who provides full-time monitoring. The sensor is NOT connected to the annunciator panel for the generator itself. PowerSecure also provides a contractor to perform monthly monitoring of the generator system, and who will maintain a log inside the door of each generator enclosure.
10/14/1998 Legacy Activity Cummings, Constance C.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
10/14/1998 Legacy Activity Puzak, Brent
Activity Name: UST ROUTINE COMPLIANCE INSPECTION Activity Status: Closed