DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/30/2025        Last Data Refresh: 04/29/2025        Report Generated from DOPPLER
 
Facility ID: 8521966
Facility Name: TUPPERWARE CORP
 
02/06/2025 Editable Letter Activity Mirajkar, Adam
Activity Title: Warning Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/07/2025
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 02/06/2025
Comment: Submitted for approval by: Adam Mirajkar
Events:
Event Type: Activity/Document has been approved Date: 02/06/2025
Comment: Approved by Jenny E Farrell: Approved
Attachments:
Attachment Date: 02/06/2025 User: MIRAJKAR_A
Description: Warning Letter 2/4/2025
View Attachment
05/16/2024 Enforcement Tracking Activity Puckett, Courtney K
Activity Status: Open
02/15/2024 Enforcement Referral Activity Becker, Glen
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 05/16/2024
Events:
Event Type: Activity has been finished Date: 05/16/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 05/16/2024
Comment: Accepted by Courtney K Puckett: Enforcement Case assigned and accepted by Courtney Puckett.
Events:
Event Type: Activity has been submitted for approval Date: 02/15/2024
Comment: Submitted for approval by: Glen Becker: Violations related to tank operation and tank removal. A Financial Responsibility violation should have been cited during the 5/31/2023 inspection.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 02/20/2024
Comment: Acknowledged and Assigned by DANIEL K HALL
Events:
Event Type: Activity has been assigned Date: 02/20/2024
Comment: Assigned to Courtney K Puckett
Comments:
Comment Date: 02/15/2024 User: BECKER_GT_1
Description: Violations related to tank operation and tank removal. A Financial Responsibility violation should have been cited during the 5/31/2023 inspection.
02/08/2024 Record Document Activity Perez, Erick
Activity Status: Closed
Contact Name: erick.perez@ocfl.net - 407-836-1435 Activity Closed Date: 02/08/2024
Events:
Event Type: Activity has been finished Date: 02/08/2024
Comment: Finished
02/07/2024 Record Document Activity Perez, Erick
Activity Status: Closed
Contact Name: erick.perez@ocfl.net - 407-836-1435 Activity Closed Date: 02/07/2024
Events:
Event Type: Activity has been finished Date: 02/07/2024
Comment: Finished
01/12/2024 Electronic Communication Activity Kidder, Matthew S
Activity Closed Date: 01/12/2024 Activity Status: Closed
Date: 01/12/2024
Recipient: matthew.kidder@ocfl.net
Sender: robertgordon@tupperware.com
Subject: Tom Huth
Message: Sorry I guess you need a number
Events:
Event Type: Activity has been finished Date: 01/12/2024
Comment: Finished
01/12/2024 Electronic Communication Activity Kidder, Matthew S
Activity Closed Date: 01/12/2024 Activity Status: Closed
Date: 01/12/2024
Recipient: matthew.kidder@ocfl.net
Sender: robertgordon@tupperware.com
Subject: * EXTERNAL EMAIL * Tupperware Corp Inspection Report/Compliance Assistance Letter
Message: Matthew the contact for the company that owns the property is O’Conner and their contact is Tom Huth. Reports attached let me know if you need anything else.
Events:
Event Type: Activity has been finished Date: 01/12/2024
Comment: Finished
06/07/2023 Phone Conversation Activity Kidder, Matthew S
Call Type: Outgoing Activity Status: Closed
Phone Number: (212) 546-0821 Activity Closed Date: 06/07/2023
Subject: Left a voicemail for Tom Huth. Requested that he returns my phone call in order to discuss the tank that has been removed.
Events:
Event Type: Activity has been finished Date: 06/07/2023
Comment: Finished
06/07/2023 Electronic Communication Activity Kidder, Matthew S
Activity Closed Date: 06/07/2023 Activity Status: Closed
Date: 06/07/2023
Recipient: robertgordon@tupperware.com
Sender: matthew.kidder@ocfl.net
Subject: * EXTERNAL EMAIL * Tupperware Corp Inspection Report/Compliance Assistance Letter
Message: Good morning Robert, Would you happen to have Tom Huth's email, or cell phone number? I will contact him about providing a limited closure form for the removal of tank 7. Tupperware will need to update their registration to reflect the fact that this tank is no longer your responsibility. Thank you for providing your monthly visual inspections. Still need to review your storage tank insurance policy, and annual operability testing records for the blacktop, and design tanks' overfill protection/release detection devices if you have them. Thanks
Events:
Event Type: Activity has been finished Date: 06/07/2023
Comment: Finished
06/05/2023 Electronic Communication Activity Kidder, Matthew S
Activity Closed Date: 06/05/2023 Activity Status: Closed
Date: 06/05/2023
Recipient: matthew.kidder@ocfl.net
Sender: robertgordon@tupperware.com
Subject: * EXTERNAL EMAIL * Tupperware Corp Inspection Report/Compliance Assistance Letter
Message: If you could call my cell 4073462773 Im not exactly sure what you are looking for. Thanks
Events:
Event Type: Activity has been finished Date: 06/05/2023
Comment: Finished
06/05/2023 Phone Conversation Activity Kidder, Matthew S
Call Type: Outgoing Activity Status: Closed
Phone Number: (407) 346-2773 Activity Closed Date: 06/05/2023
Subject: Spoke with Robert Gordon about what needs to take place in order to resolve the open violations. He did confirm that Tank#7 was removed within the past 6 months. The parcel of land that this tank was on was sold by Tupperware Corp a few years back. The new property owner will need to provide the limited closure form/removal documents. Mr. Gordon said he would share that entity's contact information.
Events:
Event Type: Activity has been finished Date: 06/05/2023
Comment: Finished
05/31/2023 Violation Open Kidder, Matthew S
Significance: Minor Status: Open
Criteria ID: 7103
Rule: 62-762.801(2)(b)8, 62-762.802(3)(b)8
05/31/2023 Editable Letter Activity Kidder, Matthew S
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/01/2023
Comment: Sent
Events:
Event Type: Compliance Assistance Offer Verbal Date: 06/01/2023
Comment: Compliance Assistance Offer Verbal
Events:
Event Type: Activity has been finished Date: 06/01/2023
Comment: Finished
Attachments:
Attachment Date: 05/31/2023 User: KIDDER_MS_1
Description: Compliance Assistance Letter
View Attachment
05/31/2023 Violation Open Kidder, Matthew S
Significance: Minor Status: Open
Criteria ID: 7094
Rule: 62-762.711(1)
05/31/2023 Violation Open Kidder, Matthew S
Significance: Minor Status: Open
Criteria ID: 7106
Rule: 62-762.801(3)(c), 62-762.801(3)(c)1, 62-762.801(3)(c)2, 62-762.801(3)(c)3, 62-762.802(4)(c), 62-762.802(4)(c)1, 62-762.802(4)(c)2, 62-762.802(4)(c)3
05/31/2023 Violation Open Kidder, Matthew S
Significance: Minor Status: Open
Criteria ID: 7005
Rule: 62-762.411(1)(b), 62-762.411(1)(c), 62-762.411(2)(a), 62-762.411(2)(b), 62-762.411(2)(c)
05/30/2023 Site Inspection Activity Closed Kidder, Matthew S
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 05/31/2023
Activity Closed Date: 05/31/2023 Activity Closed By: KIDDER_MS_1
Events:
Event Type: Activity has been finished Date: 05/31/2023
Comment: Finished
Attachments:
Attachment Date: 05/31/2023 User: KIDDER_MS_1
Description: 800 Gallon Customer Care Center AST
View Attachment
05/23/2023 Electronic Communication Activity Kidder, Matthew S
Activity Closed Date: 05/23/2023 Activity Status: Closed
Date: 05/23/2023
Recipient: matthew.kidder@ocfl.net
Sender: eahollier@tupperware.com
Subject: 8521966
Message: Good afternoon, A storage tank inspection is due for you facility mentioned in the subject header. I need to have this inspection completed by the end of the month. Can we please schedule a site visit in the coming days?
Events:
Event Type: Activity has been finished Date: 05/23/2023
Comment: Finished
05/23/2023 Electronic Communication Activity Kidder, Matthew S
Activity Closed Date: 05/23/2023 Activity Status: Closed
Date: 05/23/2023
Recipient: matthew.kidder@ocfl.net
Sender: eahollier@tupperware.com
Subject: * EXTERNAL EMAIL * 8521966 TUPPERWARE CORP
Message: I believe you spoke to Robert already and said he mentioned he was out of town on vacation. So can we schedule this for after 6/5?
Events:
Event Type: Activity has been finished Date: 05/23/2023
Comment: Finished
05/23/2023 Electronic Communication Activity Kidder, Matthew S
Activity Closed Date: 05/23/2023 Activity Status: Closed
Date: 05/23/2023
Recipient: eahollier@tupperware.com
Sender: matthew.kidder@ocfl.net
Subject: * EXTERNAL EMAIL * 8521966 TUPPERWARE CORP
Message: I believe that was my colleague Joseph Savoy. I will be doing the inspection on his behalf now. He did mention that he spoke with Mr. Gordon yesterday. The EPD needs to open an inspection activity prior to 05/31/2023 when our fiscal year ends. Is it possible for anyone to meet me on site before the 31st?
Events:
Event Type: Activity has been finished Date: 05/23/2023
Comment: Finished
06/09/2022 Electronic Communication Activity Becker, Glen
Activity Closed Date: 06/09/2022 Activity Status: Closed
Date: 06/09/2022
Recipient: Yjones@oconnorcp.com: cc: EAHollier@Tupperware.com; RobertGordon@Tupperware.com
Sender: Glen Becker
Subject: FW: Tupperware contact for Oconner Capital Partners #8521966
Message: Hello Ms. Jones, I represent the Florida Department of Environmental Protection (DEP) in the petroleum storage tank division. Our office is contracted by the DEP to inspect commercial fuel storage tanks in Central Florida (five counties). It has been brought to my attention that the property has changed ownership. Per the requirements of Florida Administrative Code Chapter 62-762.401(3)(a): (3) A completed Registration Form shall be submitted to the Department in paper or electronic format within 10 days of the following changes or discovery: (a) Any change in the owner or operator of a facility or of a storage tank system; Please see and complete the attached DEP Storage Tank Registration Form to update the C. REAL PROPERTY OWNER INFORMATION on the form. Also, before the 1,000-gal fuel tank is removed from the facility, our office is required to be notified via email 30-45 days and 48-72 hours prior to the removal of the tank. Our office is required to perform a tank closure inspection for the DEP. Here is a link to the DEP storage tank compliance webpage for more information. If you have any questions, please feel free to contact me. Thank you, Glen Becker Environmental Team Lead Orange County Environmental Protection Division Storage Tanks Compliance 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: 407-836-1453 Cell: 321-689-8389 Fax: 407-836-1499 Email: glen.becker@ocfl.net Web: www.ocepd.org From: Hollier, EA Sent: Thursday, June 9, 2022 1:33 PM To: Becker, Glen ; Gordon, Robert Subject: Tupperware contact for Oconner Capital Partners Hello Glen, Robert gave me your email you provided for me to send you our contact for Oconner Capital Partners Her name is Yvonne Jones and her email is: Yjones@oconnorcp.com Her phone number is (212) 546-0865 E.A. Rose Hollier's iPhone RID, NCIDQ Senior Project Specialist, Orlando Facilities Cell: (407) 308-6305 EAHollier@tupperware.com 14901 S. Orange Blossom Trail Orlando, FL 32837
Events:
Event Type: Activity has been finished Date: 06/09/2022
Comment: Finished
Comments:
Comment Date: 06/09/2022 User: BECKER_GT_1
Description: Attached STRF.
06/01/2022 Phone Conversation Activity Becker, Glen
Call Type: Outgoing Activity Status: Closed
Phone Number: (407) 346-2773 Activity Closed Date: 06/01/2022
Subject: I called and spoke to Mr. Robert Gordon, the facility contact, to ask why Tank #7 was being placed as 'out-of-service'. He stated that the facility is owned by a different party and in the process of being redeveloped. He stated that the tank isn't being used, but is half full. I stated that the tank needs to be emptied to be properly out-of-service. He stated he can't get to the tank due to remediation equipment in the way. He reiterated that they don't own the tanks anymore. I stated that the property ownership needs to be updated. He was frustrated at my call as I tried to explain the compliance requirements.
Events:
Event Type: Activity has been finished Date: 06/01/2022
Comment: Finished
06/01/2022 Electronic Communication Activity Becker, Glen
Activity Closed Date: 06/01/2022 Activity Status: Closed
Date: 06/01/2022
Recipient: TankRegistration@dep.state.fl.us; DEP_CD@dep.state.fl.us; Becker, Glen
Sender: no-reply@dep.state.fl.us
Subject: Storage Tank Registration Update
Message: see attached
Events:
Event Type: Activity has been finished Date: 06/01/2022
Comment: Finished
Attachments:
Attachment Date: 06/01/2022 User: BECKER_GT_1
Description: Registration email
View Attachment
01/11/2021 Electronic Communication Activity Becker, Glen
Activity Closed Date: 01/11/2021 Activity Status: Closed
Date: 01/11/2021
Recipient: Glen Becker
Sender: Gutreuter, Keith T
Subject: RE: Tupperware generator tank addition
Message: Glen, I hope this email finds you well. I just wanted to check with you to determine who the person would be that I need to notify on a new diesel fuel tank we will be adding at Tupperware (14901 Orange Blossom Trail, Orlando)? At this time if looks like it will be added the end of February. Can you assist me with that? Keith T. Gutreuter Duke Energy Florida, LLC - Energy Services 3300 Exchange Place – NP1D Lake Mary, FL 32746 o: 407-942-9364 | c: 407-463-1515| www.duke-energy.com/energyservices
Events:
Event Type: Activity has been finished Date: 01/11/2021
Comment: Finished
01/11/2021 Electronic Communication Activity Becker, Glen
Activity Closed Date: 01/11/2021 Activity Status: Closed
Date: 01/11/2021
Recipient: Gutreuter, Keith T
Sender: Becker, Glen
Subject: RE: Tupperware generator tank addition-#8521966, TUPPERWARE CORP >> Installation
Message: Hi Keith, Thank you for the email. Yes, we can count this email as the 30-45 day notification of installation. Please ensure to provide the 48-72 hour email notification prior to the setting of the unit. Is this the facility with the DEP registered address of 3175 N ORANGE BLOSSOM TRL, KISSIMMEE? Thank you, Glen Becker Environmental Team Lead Orange County Environmental Protection Division Storage Tanks Compliance 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: 407-836-1453 Cell: 321-689-8389 Fax: 407-836-1499 Email: glen.becker@ocfl.net Web: www.ocepd.org
Events:
Event Type: Activity has been finished Date: 01/11/2021
Comment: Finished
04/23/2019 Attachment Rauenzahn, Ruth
04/23/2019 Editable Letter Activity Rauenzahn, Ruth
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 04/23/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 04/23/2019
Comment: Finished
Attachments:
Attachment Date: 04/23/2019 User: RAUENZAHN_RA_1
Description: Return to Compliance Letter
View Attachment
04/23/2019 Electronic Communication Activity Rauenzahn, Ruth
Activity Closed Date: 04/23/2019 Activity Status: Closed
Date: 04/23/2019
Recipient: Ruth Rauenzahn
Sender: Edmond Baxley
Subject: Open violations
Message: Rcvd FR packet and photos of labeled tank. I questioned the address on the insurance policy and Kim Bauman responded indicating that the Tupperware facility is a very large campus with multiple address. She provided a map as supporting documentation.
Events:
Event Type: Activity has been finished Date: 04/23/2019
Comment: Finished
Attachments:
Attachment Date: 04/23/2019 User: RAUENZAHN_RA_1
Description: Photos and FR
View Attachment
04/23/2019 Electronic Communication Activity Rauenzahn, Ruth
Activity Closed Date: 04/23/2019 Activity Status: Closed
Date: 04/23/2019
Recipient: EdmondBaxley@Tupperware.com
Sender: Ruth Rauenzahn
Subject: Open Violations
Message: Emailed again requesting resolving documents. Email is attached.
Events:
Event Type: Activity has been finished Date: 04/23/2019
Comment: Finished
Attachments:
Attachment Date: 04/23/2019 User: RAUENZAHN_RA_1
Description: Email
View Attachment
04/18/2019 Electronic Communication Activity Rauenzahn, Ruth
Activity Closed Date: 04/18/2019 Activity Status: Closed
Date: 04/18/2019
Recipient: kimberlybauman@tupperware.com; SandraRobinson@Tupperware.com; mailto:EdmondBaxley@Tupperware.com
Sender: Ruth Rauenzahn
Subject: Open violations
Message: Emailed Tupperware staff to request documents to resolve outstanding violations. Email is attached.
Events:
Event Type: Activity has been finished Date: 04/18/2019
Comment: Finished
Attachments:
Attachment Date: 04/18/2019 User: RAUENZAHN_RA_1
Description: Email
View Attachment
04/18/2019 Electronic Communication Activity Rauenzahn, Ruth
Activity Closed Date: 04/18/2019 Activity Status: Closed
Date: 04/18/2019
Recipient: Ruth Rauenzahn
Sender: EdmondBaxley@Tupperware.com
Subject: Open Violations
Message: Edmond Baxley responded to my email indicating that he would send resolving documents on Tuesday, April 23, 2019. Email is attached.
Events:
Event Type: Activity has been finished Date: 04/18/2019
Comment: Finished
Attachments:
Attachment Date: 04/18/2019 User: RAUENZAHN_RA_1
Description: Email
View Attachment
04/15/2019 Comment Sanchez, Jose I
Description: Robert Gordon Tupperware Corp. 3175 N Orange Blossom Trl Kissimmee, FL 34744 (407) 826-5050 ext. 1846 robertgordon@tupperware.com
04/15/2019 Electronic Communication Activity Sanchez, Jose I
Activity Closed Date: 04/15/2019 Activity Status: Closed
Date: 04/15/2019
Recipient: robertgordon@tupperware.com & TroyAker@Tupperware.com
Sender: jose.sanchez@ocfl.net
Subject: RE: storage tank registration
Message: Good Morning Troy, Tupperware Corp will be referred for enforcement on 04/11/19. Please provide the following documentation to resolve open violations: 1. Annual operability test results for the interstitial gauge on tank 7. a. Thereafter, testing shall be performed annually not exceeding 12 months. 2. Install FDEP approved fuel level gauges on tanks 5, 6, & 7. a. OEM Econo Gauges (model 14495) on tanks 5 & 7 are approved. b. The approved Krueger fuel level gauge on tank 6 looks faded/damaged (should be replaced). c. Provide a work order describing the replacement of these components. i. An approved equipment list is attached. 3. Annual operability test results for overfill protection devices on tanks 5, 6 & 7. a. Newly installed fuel level gauges on tanks 5, 6 & 7 must be calibrated to 90%. b. Verify if the fuel alarm on tank 6 is the high or low level type. c. Thereafter, testing shall be performed annually not exceeding 12 months. i. A test form is attached also. 4. Current financial responsibility documents (insurance expired 02/15/2019). a. A Certificate of Financial Responsibility (CFR) must be completed by Tupperware Corp. b. A Certificate of Insurance (COI) must be completed by the insurance company. c. A signed insurance policy must be attached to the CFR & COI. d. A list of insured facilities must be attached to the CFR & COI. i. The financial references & requirements form describes this requirement. ii. The required forms are attached as well. 5. A fuel type label was not observed on tank 6. a. Place a diesel label/decal on tank 6. b. Provide pictures showing the tank is properly labeled. 6. Correct monitoring registration information for tank 5. a. Monitoring registration information was updated incorrectly to “not required.” b. Monitoring registration information should be corrected to “DEP approved monitoring.” i. Tank interstitials are monitored visually/externally with a tank gauging stick. If you wish to perform annual operability testing “in house”, complete the attached test forms for each individual FDEP approved overfill protection and/or release detection device. Attach manufacturer specifications to test forms. Provide a formal letter describing testing procedures for these components in accordance with PEI RP1200 & FAC 62-762. If you are uncomfortable with testing devices, it is highly recommended to hire a tester/contractor. Once documentation is received before 04/11/19, a return to compliance letter will be issued. Failure to provide this documentation before 04/11/19 will result in enforcement by the Florida Department of Environmental Protection (FDEP). If you have any questions, please feel free to contact me. Sincerely, Jose I Sanchez Environmental Specialist II Orange County Environmental Protection Division 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: (407) 558-0744 Email: jose.sanchez@ocfl.net Website: www.ocepd.org From: Aker, Troy Sent: Wednesday, February 6, 2019 9:53 AM To: Sanchez, Jose I Subject: storage tank registration Jose, I forgot to send the storage tank registration. Thanks Troy
Events:
Event Type: Activity has been finished Date: 04/15/2019
Comment: Finished
04/15/2019 Electronic Communication Activity Sanchez, Jose I
Activity Closed Date: 04/15/2019 Activity Status: Closed
Date: 04/15/2019
Recipient: TroyAker@Tupperware.com
Sender: jose.sanchez@ocfl.net
Subject: RE: * EXTERNAL EMAIL * RE: Tank Inspections
Message: Good Morning Troy, Do you have any of the required documentation now? Please let me know by today. If not, the facility will be referred for enforcement to FDEP. Sincerely, Jose I Sanchez Environmental Specialist II Orange County Environmental Protection Division 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: (407) 558-0744 Email: jose.sanchez@ocfl.net Website: www.ocepd.org From: Aker, Troy Sent: Friday, April 12, 2019 12:32 PM To: Sanchez, Jose I Subject: RE: * EXTERNAL EMAIL * RE: Tank Inspections Forgot to attach. From: Jose.Sanchez@ocfl.net [mailto:Jose.Sanchez@ocfl.net] Sent: Thursday, April 11, 2019 2:57 PM To: Aker, Troy Subject: RE: * EXTERNAL EMAIL * RE: Tank Inspections Hi Troy, Thank you very much for the fuel gauge pictures. I resolved both testing violations. It appears that the interstitial gauge for tank 7 should be changed soon. As of now, there two open violations: 1. Some financial responsibility documents are missing. a. CFR form needs to be filled out by Tupperware. b. Indian Harbor Insurance policy needs to be submitted. 2. Pictures of new fuel type labels on tank 6 are missing. a. Fuel type labels should be added on tank wall/fill box. Sincerely, Jose I Sanchez Environmental Specialist II Orange County Environmental Protection Division 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: (407) 558-0744 Email: jose.sanchez@ocfl.net Website: www.ocepd.org From: Aker, Troy Sent: Thursday, April 11, 2019 2:46 PM To: Sanchez, Jose I Subject: RE: * EXTERNAL EMAIL * RE: Tank Inspections Hi Jose, Ok that’s what I had called for. I will send as soon as I get them. I had to send the pictures separate. If you don’t get them let me know. Thanks Troy From: Jose.Sanchez@ocfl.net [mailto:Jose.Sanchez@ocfl.net] Sent: Thursday, April 11, 2019 2:41 PM To: Aker, Troy Subject: * EXTERNAL EMAIL * RE: Tank Inspections Hi Troy, Please provide the following documentation: 1. Complete the attached Certificate of Financial Responsibility (CFR) form. a. The CFR and certificate of insurance (COI) are NOT the same. i. I already have the COI form. b. The CFR & insurance policy are required to resolve the financial responsibility violation. 2. You need to provide pictures of three fuel level gauges. a. This is required to resolve the repair violation. Sincerely, Jose I Sanchez Environmental Specialist II Orange County Environmental Protection Division 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: (407) 558-0744 Email: jose.sanchez@ocfl.net Website: www.ocepd.org From: Aker, Troy Sent: Thursday, April 11, 2019 2:30 PM To: Sanchez, Jose I Subject: Tank Inspections Hi Jose, 1. I’ve attached the current CFR but I’m waiting on the actual policy. I will send as soon as I get it. 2. I have ordered new diesel labels for all tanks. 3. All overfill gauges were replaced with Krueger D-1 gauges: Tank #5 has two D-2-54, Tank #6 Has one D-2-24, and tank #7 has one D-2-42 all calibrated at 90%. 4. I have included an updated Overfill alarm Inspection. 5. The alarm on Tank #6 is a low level alarm which I installed a new alarm and new flex tubing. Let me know if there’s anything else you need. Files are to large so I’ll have to send images in another email. Thanks Troy PLEASE NOTE: Florida has a very broad public records law (F. S. 119). All e-mails to and from County Officials are kept as a public record. Your e-mail communications, including your e-mail address may be disclosed to the public and media at any time. PLEASE NOTE: Florida has a very broad public records law (F. S. 119). All e-mails to and from County Officials are kept as a public record. Your
Events:
Event Type: Activity has been finished Date: 04/15/2019
Comment: Finished
04/15/2019 Electronic Communication Activity Sanchez, Jose I
Activity Closed Date: 04/15/2019 Activity Status: Closed
Date: 04/15/2019
Recipient: TroyAker@Tupperware.com
Sender: jose.sanchez@ocfl.net
Subject: RE: * EXTERNAL EMAIL * RE: Tank Inspections
Message: Hi Troy, Thank you very much for the fuel gauge pictures. I resolved both testing violations. It appears that the interstitial gauge for tank 7 should be changed soon. As of now, there two open violations: 1. Some financial responsibility documents are missing. a. CFR form needs to be filled out by Tupperware. b. Indian Harbor Insurance policy needs to be submitted. 2. Pictures of new fuel type labels on tank 6 are missing. a. Fuel type labels should be added on tank wall/fill box. Sincerely, Jose I Sanchez Environmental Specialist II Orange County Environmental Protection Division 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: (407) 558-0744 Email: jose.sanchez@ocfl.net Website: www.ocepd.org From: Aker, Troy Sent: Thursday, April 11, 2019 2:46 PM To: Sanchez, Jose I Subject: RE: * EXTERNAL EMAIL * RE: Tank Inspections Hi Jose, Ok that’s what I had called for. I will send as soon as I get them. I had to send the pictures separate. If you don’t get them let me know. Thanks Troy From: Jose.Sanchez@ocfl.net [mailto:Jose.Sanchez@ocfl.net] Sent: Thursday, April 11, 2019 2:41 PM To: Aker, Troy Subject: * EXTERNAL EMAIL * RE: Tank Inspections Hi Troy, Please provide the following documentation: 1. Complete the attached Certificate of Financial Responsibility (CFR) form. a. The CFR and certificate of insurance (COI) are NOT the same. i. I already have the COI form. b. The CFR & insurance policy are required to resolve the financial responsibility violation. 2. You need to provide pictures of three fuel level gauges. a. This is required to resolve the repair violation. Sincerely, Jose I Sanchez Environmental Specialist II Orange County Environmental Protection Division 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: (407) 558-0744 Email: jose.sanchez@ocfl.net Website: www.ocepd.org From: Aker, Troy Sent: Thursday, April 11, 2019 2:30 PM To: Sanchez, Jose I Subject: Tank Inspections Hi Jose, 1. I’ve attached the current CFR but I’m waiting on the actual policy. I will send as soon as I get it. 2. I have ordered new diesel labels for all tanks. 3. All overfill gauges were replaced with Krueger D-1 gauges: Tank #5 has two D-2-54, Tank #6 Has one D-2-24, and tank #7 has one D-2-42 all calibrated at 90%. 4. I have included an updated Overfill alarm Inspection. 5. The alarm on Tank #6 is a low level alarm which I installed a new alarm and new flex tubing. Let me know if there’s anything else you need. Files are to large so I’ll have to send images in another email. Thanks Troy PLEASE NOTE: Florida has a very broad public records law (F. S. 119). All e-mails to and from County Officials are kept as a public record. Your e-mail communications, including your e-mail address may be disclosed to the public and media at any time.
Events:
Event Type: Activity has been finished Date: 04/15/2019
Comment: Finished
04/15/2019 Electronic Communication Activity Sanchez, Jose I
Activity Closed Date: 04/15/2019 Activity Status: Closed
Date: 04/15/2019
Recipient: robertgordon@tupperware.com & troyaker@tupperware.com
Sender: jose.sanchez@ocfl.net
Subject: Routine Inspection/CAO Letter - 8521966
Message: Good Afternoon Robert, Here is the official inspection report for Tupperware Corp (FCID: 8521966). A compliance assistance offer letter is attached. The facility was found to be in violation of storage tank regulations. Helpful documentation is attached for you to review. If you wish to perform annual operability testing “in house”, there are test forms at this web link: https://www.pei.org/rp1200. Attach manufacturer instructions to every test form completed. Testing for overfill protection and release detection shall occur every 12 months. Please resolve all violations within 90 days. If violations are not resolved by the deadline, the Florida Department of Environmental Protection (FDEP) will proceed with enforcement. If you have any questions, please feel free to contact me. Sincerely, Jose I Sanchez Environmental Specialist II Orange County Environmental Protection Division 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: (407) 558-0744 Email: jose.sanchez@ocfl.net Website: www.ocepd.org
Events:
Event Type: Activity has been finished Date: 04/15/2019
Comment: Finished
04/15/2019 Electronic Communication Activity Sanchez, Jose I
Activity Closed Date: 04/15/2019 Activity Status: Closed
Date: 04/15/2019
Recipient: TroyAker@Tupperware.com & RobertGordon@Tupperware.com
Sender: jose.sanchez@ocfl.net
Subject: RE: * EXTERNAL EMAIL * RE: storage tank registration
Message: Good Afternoon Troy, I will resolve the monitoring registration and interstitial gauge testing violations. However, the following open violations need to be resolved: 1. Some financial responsibility documents are MISSING (02/15/19-02/15/22). a. A Certificate of Financial Responsibility (CFR) must be completed by Tupperware Corp. b. A signed insurance policy from Indian Harbor Insurance must be provided. i. A list of insured facilities must be included. ii. This is required to demonstrate that data on forms correlates with the policy. iii. The required form is attached as well. 2. Fuel type labels NOT observed on tank 6. a. The submitted pictures show fire code labels on the tank walls. b. This satisfies some NFPA requirements, NOT FDEP requirements. c. Place diesel labels on the tank and spill bucket. 3. Installation documents & pictures of FDEP approved fuel level gauges on tanks 5, 6, & 7 NOT recieved. a. OEM Econo Gauges (model 14495) on tanks 5 & 7 are NOT approved by FDEP. i. Please install FDEP approved fuel level gauges on tanks 5 & 7. ii. Provide pictures of new fuel level gauges on tanks 5 & 7. b. The approved Krueger fuel level gauge on tank 6 looks faded/damaged (should be replaced). i. Please install an FDEP approved fuel level gauge on tank 6. ii. Provide a picture of the new fuel level gauge on tanks 6. c. Provide a work order, letter and pictures describing the replacement of these components. i. An approved equipment list is attached. 4. Test results for fuel level gauges on tanks 5, 6 & 7 are INCONSISTENT or INCOMPLETE. a. Pictures of new fuel level gauges on tanks 5, 6 & 7 were NOT provided. b. On the test form, it shows that ONLY one fuel gauge was tested on tank 5. i. Tank 5 has two fuel level gauges. ii. Testing for one fuel gauge CANNOT count for both. iii. Provide test results for both fuel gauges on tank 5. 1. A test form is attached as well. c. Verify if the fuel alarm on tank 6 is the high or low level type. d. Thereafter, testing shall be performed annually not exceeding 12 months. Please provide this documentation by tomorrow. Once the required documentation is received, a return to compliance letter will be issued. If you have any questions, please feel free to contact me. Sincerely, Jose I Sanchez Environmental Specialist II Orange County Environmental Protection Division 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: (407) 558-0744 Email: jose.sanchez@ocfl.net Website: www.ocepd.org From: Aker, Troy Sent: Monday, April 8, 2019 1:53 PM To: Sanchez, Jose I Cc: Gordon, Robert Subject: RE: * EXTERNAL EMAIL * RE: storage tank registration Hi Jose, Here is what you asked for. All Krueger gauges on tank 5, 6 and 7 have all been removed, replaced with new gauges and calibrated. Attached is the current Tank storage insurance policy. Labeling on tank #6 has been added picture attached. I called FDEP about the tank registration and she said everything looked ok. Sha said she would call you. Hope I have everything, if not let me know. Thanks Troy From: Jose.Sanchez@ocfl.net [mailto:Jose.Sanchez@ocfl.net] Sent: Tuesday, April 02, 2019 2:30 AM To: Aker, Troy Cc: Gordon, Robert Subject: * EXTERNAL EMAIL * RE: storage tank registration Good Morning Troy, Tupperware Corp will be referred for enforcement on 04/11/19. Please provide the following documentation to resolve open violations: 1. Annual operability test results for the interstitial gauge on tank 7. a. Thereafter, testing shall be performed annually not exceeding 12 months. 2. Install FDEP approved fuel level gauges on tanks 5, 6, & 7. a. OEM Econo Gauges (model 14495) on tanks 5 & 7 are approved. b. The approved Krueger fuel level gauge on tank 6 looks faded/damaged (should be replaced). c. Provide a work order describing the replacement of these components.
Events:
Event Type: Activity has been finished Date: 04/15/2019
Comment: Finished
04/11/2019 Document Management Activity Sanchez, Jose I
Activity Title: Map, Sketches And Drawings Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 04/11/2019
Comment: Submitted for approval by: Jose I Sanchez
Events:
Event Type: Activity has been finished Date: 04/12/2019
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 04/12/2019
Comment: Approved by Ruth Rauenzahn: ok
Attachments:
Attachment Date: 04/11/2019 User: SANCHEZ_JI_1
Description: 8521966 Fuel Gauge Test 2019
View Attachment
04/11/2019 Document Management Activity Sanchez, Jose I
Activity Title: Map, Sketches And Drawings Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 04/11/2019
Comment: Submitted for approval by: Jose I Sanchez
Events:
Event Type: Activity/Document has been approved Date: 04/12/2019
Comment: Approved by Ruth Rauenzahn: ok
Events:
Event Type: Activity has been finished Date: 04/12/2019
Comment: Finished
Attachments:
Attachment Date: 04/11/2019 User: SANCHEZ_JI_1
Description: 8521966 interstitial gauge test 2019
View Attachment
04/11/2019 Document Management Activity Sanchez, Jose I
Activity Title: Map, Sketches And Drawings Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 04/12/2019
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 04/12/2019
Comment: Approved by Ruth Rauenzahn: ok
Events:
Event Type: Activity has been submitted for approval Date: 04/11/2019
Comment: Submitted for approval by: Jose I Sanchez
Attachments:
Attachment Date: 04/11/2019 User: SANCHEZ_JI_1
Description: 8521966 Registration Update Email
View Attachment
01/14/2019 Editable Letter Activity Rauenzahn, Ruth
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Description: 8/3/2019-2020 policy docs
Events:
Event Type: Document has been sent Date: 01/14/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 01/14/2019
Comment: Finished
Attachments:
Attachment Date: 01/14/2019 User: RAUENZAHN_RA_1
Description: CAO
View Attachment
01/10/2019 Editable Letter Activity Sanchez, Jose I
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity/Document has been approved Date: 01/11/2019
Comment: Approved by Ruth Rauenzahn: ok
Events:
Event Type: Activity has been finished Date: 01/11/2019
Comment: Finished
Events:
Event Type: Document has been sent Date: 12/28/2018
Comment: Sent
Events:
Event Type: Activity has been submitted for approval Date: 01/10/2019
Comment: Submitted for approval by: Jose I Sanchez
Attachments:
Attachment Date: 01/10/2019 User: SANCHEZ_JI_1
Description: 2018 CAO Letter - 8521966
View Attachment
12/28/2018 Violation Closed Sanchez, Jose I
Significance: Minor Status: Closed
Criteria ID: 5003
Rule: 62-762.401(3), 62-762.401(3)(a), 62-762.401(3)(b), 62-762.401(3)(c)
12/28/2018 Site Inspection Activity Closed Sanchez, Jose I
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 12/28/2018
Activity Closed Date: 01/11/2019 Activity Closed By: SANCHEZ_JI_1
Events:
Event Type: Activity has been finished Date: 01/11/2019
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 01/10/2019
Comment: Submitted for approval by: Jose I Sanchez
Events:
Event Type: Activity/Document has been approved Date: 01/11/2019
Comment: Approved by Ruth Rauenzahn: ok
Comments:
Comment Date: 01/10/2019 User: SANCHEZ_JI_1
Description: A signed copy of this report was emailed to robertgordon@tupperware.com.
12/28/2018 Violation Closed Sanchez, Jose I
Significance: Minor Status: Closed
Criteria ID: 5102
Rule: 62-762.601(7)
12/28/2018 Violation Closed Sanchez, Jose I
Significance: SNC-B Status: Closed
Criteria ID: 5042
Rule: 62-762.501(2)(e), 62-762.501(2)(e)1., 62-762.501(2)(e)2., 62-762.501(2)(e)2.a., 62-762.501(2)(e)2.b., 62-762.501(2)(e)2.c., 62-762.501(2)(e)2.d., 62-762.501(2)(e)3.
12/28/2018 Violation Closed Sanchez, Jose I
Significance: Minor Status: Closed
Criteria ID: 5044
Rule: 62-762.501(2)(f)2.
12/28/2018 Violation Closed Sanchez, Jose I
Significance: Minor Status: Closed
Criteria ID: 5004
Rule: 62-762.401(4), 62-762.401(4)(a), 62-762.401(4)(a)1., 62-762.401(4)(a)2., 62-762.401(4)(b), 62-762.401(4)(c), 62-762.401(4)(d), 62-762.401(4)(e), 62-762.401(4)(f), 62-762.401(4)(g), 62-762.401(4)(h), 62-762.401(4)(i)
12/28/2018 Violation Closed Sanchez, Jose I
Significance: SNC-B Status: Closed
Criteria ID: 5011
Rule: 62-762.421(2)
08/21/2018 Electronic Communication Activity Becker, Glen
Activity Closed Date: 08/21/2018 Activity Status: Closed
Date: 08/21/2018
Recipient: Glen Becker
Sender: Bauman, Kimberly
Subject: RE: * EXTERNAL EMAIL * RE: TUPPERWARE BRANDS CORPORATION - DIESEL FUEL SPILL DOL: 08/14/2018
Message: see attached
Events:
Event Type: Activity has been finished Date: 08/21/2018
Comment: Finished
Attachments:
Attachment Date: 08/21/2018 User: BECKER_GT_1
Description: FR email
View Attachment
Attachments:
Attachment Date: 08/21/2018 User: BECKER_GT_1
Description: FR docs
View Attachment
08/20/2018 Electronic Communication Activity Becker, Glen
Activity Closed Date: 08/20/2018 Activity Status: Closed
Date: 08/20/2018
Recipient: Bauman, Kimberly
Sender: Glen Becker
Subject: FW: * EXTERNAL EMAIL * RE: TUPPERWARE BRANDS CORPORATION - DIESEL FUEL SPILL DOL: 08/14/2018
Message: see attached
Events:
Event Type: Activity has been finished Date: 08/20/2018
Comment: Finished
Attachments:
Attachment Date: 08/20/2018 User: BECKER_GT_1
Description: Discharge report email
View Attachment
08/20/2018 Electronic Communication Activity Becker, Glen
Activity Closed Date: 08/20/2018 Activity Status: Closed
Date: 08/20/2018
Recipient: Glen Becker
Sender: Bauman, Kimberly
Subject: TUPPERWARE BRANDS CORPORATION - DIESEL FUEL SPILL DOL: 08/14/2018
Message: see attached
Events:
Event Type: Activity has been finished Date: 08/20/2018
Comment: Finished
Attachments:
Attachment Date: 08/20/2018 User: BECKER_GT_1
Description: DRF email
View Attachment
Attachments:
Attachment Date: 08/20/2018 User: BECKER_GT_1
Description: DRF and other documents
View Attachment
08/20/2018 Electronic Communication Activity Becker, Glen
Activity Closed Date: 08/20/2018 Activity Status: Closed
Date: 08/20/2018
Recipient: Bauman, Kimberly
Sender: Glen Becker
Subject: RE: TUPPERWARE BRANDS CORPORATION - DIESEL FUEL SPILL DOL: 08/14/2018
Message: see attached
Events:
Event Type: Activity has been finished Date: 08/20/2018
Comment: Finished
Attachments:
Attachment Date: 08/20/2018 User: BECKER_GT_1
Description: DRF response email
View Attachment
08/17/2018 Site Inspection Activity Closed Becker, Glen
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 08/17/2018
Activity Closed Date: 01/14/2019 Activity Closed By: RAUENZAHN_RA_1
Events:
Event Type: Activity has been finished Date: 01/14/2019
Comment: Finished
Comments:
Comment Date: 08/20/2018 User: BECKER_GT_1
Description: Please provide all required current tank insurance documents and current tank system tests for this tank (leak gauge and overfill prevention devices) to OCEPD.
Comments:
Comment Date: 08/21/2018 User: BECKER_GT_1
Description: OCEPD received via email the current financial responsibility documentation.
08/17/2018 Site Inspection Activity Closed Becker, Glen
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 08/17/2018
Activity Closed Date: 01/14/2019 Activity Closed By: RAUENZAHN_RA_1
Events:
Event Type: Activity has been finished Date: 01/14/2019
Comment: Finished
Comments:
Comment Date: 08/20/2018 User: BECKER_GT_1
Description: Please provide all required current tank insurance documents and current tank system tests for this tank (leak gauge and overfill prevention devices) to OCEPD.
Comments:
Comment Date: 08/21/2018 User: BECKER_GT_1
Description: OCEPD received via email the current financial responsibility documentation.
08/14/2018 Document Management Activity Rauenzahn, Ruth
Activity Title: Discharge Report Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/14/2018
Comment: Finished
Attachments:
Attachment Date: 08/14/2018 User: RAUENZAHN_RA_1
Description: DRF
View Attachment
08/14/2018 Discharge Reporting Activity Rauenzahn, Ruth
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 07/05/2019
Events:
Event Type: Activity has been finished Date: 07/05/2019
Comment: Finished
05/19/2017 Document Management Activity Rauenzahn, Ruth
Activity Title: Discharge Report Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 05/19/2017
Comment: Finished
Attachments:
Attachment Date: 05/19/2017 User: RAUENZAHN_RA_1
Description: DRF
View Attachment
02/22/2017 Electronic Communication Activity Becker, Glen
Activity Closed Date: 02/22/2017 Activity Status: Closed
Date: 02/22/2017
Recipient: Glen Becker
Sender: Kimberly Bauman-Tupperware
Subject: FW: * EXTERNAL EMAIL * Diesel fuel discharge
Message: Hi Glen, Attached please find photos showing the corrosion on the fill port spill containment has been removed. We have also replaced the electrical part that failed on the day tank and re-routed the vent pipe back to the tank. I will forward invoices, work orders (where applicable) and photos on the same once received. Best regards, Kim Kimberly A. Bauman, ARM | Director, Risk Management | Tupperware Brands Corporation | Forbes Platinum 400 – America’s Best Big Companies | 2008 – 2015 Fortune World’s Most Admired Company | 14901 S. Orange Blossom Trail, Orlando, Florida 32837 | d: 407-847-1944 | f: 407-826-4510 | Email KimberlyBauman@Tupperware.com The contents, including attachments, are confidential to Tupperware Brands Corp. and its affiliates. From: Glen.Becker@ocfl.net [mailto:Glen.Becker@ocfl.net] Sent: Monday, February 13, 2017 3:25 PM To: Bauman, Kimberly Subject: RE: * EXTERNAL EMAIL * Diesel fuel discharge Thank you for the DRF. Attached is the discharge inspection. Please send all remediation/repair work to our office as soon as possible. Thank you, Glen Becker Environmental Team Lead Environmental Protection Division Storage Tanks Compliance 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: 407-836-1453 Cell: 321-689-8389 Fax: 407-836-1499 Email: glen.becker@ocfl.net Web: www.ocepd.org From: Bauman, Kimberly [mailto:KimberlyBauman@Tupperware.com] Sent: Monday, February 13, 2017 2:52 PM To: Becker, Glen Subject: RE: * EXTERNAL EMAIL * Diesel fuel discharge Hi Glen, Here you go. Best regards, Kim Kimberly A. Bauman, ARM | Director, Risk Management | Tupperware Brands Corporation | Forbes Platinum 400 – America’s Best Big Companies | 2008 – 2015 Fortune World’s Most Admired Company | 14901 S. Orange Blossom Trail, Orlando, Florida 32837 | d: 407-847-1944 | f: 407-826-4510 | Email KimberlyBauman@Tupperware.com The contents, including attachments, are confidential to Tupperware Brands Corp. and its affiliates. From: Glen.Becker@ocfl.net [mailto:Glen.Becker@ocfl.net] Sent: Monday, February 13, 2017 2:00 PM To: Bauman, Kimberly Subject: * EXTERNAL EMAIL * Diesel fuel disharge Hello Kim, Thank you for meeting me for the inspection today. I am working on completing the inspection report and noticed that our office has not received a FDEP Discharge Report Form (attached). Please complete and send back to me as soon as possible. If you have any questions, please feel free to contact me. Thank you, Glen Becker Environmental Team Lead Environmental Protection Division Storage Tanks Compliance 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: 407-836-1453 Cell: 321-689-8389 Fax: 407-836-1499 Email: glen.becker@ocfl.net Web: www.ocepd.org PLEASE NOTE: Florida has a very broad public records law (F. S. 119). All e-mails to and from County Officials are kept as a public record. Your e-mail communications, including your e-mail address may be disclosed to the public and media at any time. PLEASE NOTE: Florida has a very broad public records law (F. S. 119). All e-mails to and from County Officials are kept as a public record. Your e-mail communications, including your e-mail address may be disclosed to the public and media at any time.
Events:
Event Type: Activity has been finished Date: 02/22/2017
Comment: Finished
02/13/2017 Comment Becker, Glen
Description: Kimberlybauman@tupperware.com-Risk management director
02/13/2017 Discharge Reporting Activity Becker, Glen
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 05/22/2017
Events:
Event Type: Activity has been finished Date: 05/22/2017
Comment: Finished
02/13/2017 Document Management Activity Becker, Glen
Activity Title: Discharge Report Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/22/2017
Comment: Finished
Attachments:
Attachment Date: 02/13/2017 User: BECKER_GT_1
Description: 2/10/2017 DRF
View Attachment
02/13/2017 Document Management Activity Becker, Glen
Activity Title: Discharge Report Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/13/2017
Comment: Finished
Attachments:
Attachment Date: 02/13/2017 User: BECKER_GT_1
Description: State Watch Office incident email
View Attachment
02/13/2017 Document Management Activity Becker, Glen
Activity Title: Discharge Report Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/13/2017
Comment: Finished
Attachments:
Attachment Date: 02/13/2017 User: BECKER_GT_1
Description: Discharge report form request email
View Attachment
02/13/2017 Site Inspection Activity Closed Becker, Glen
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/13/2017
Activity Closed Date: 02/13/2017 Activity Closed By: BECKER_GT_1
Events:
Event Type: Activity has been finished Date: 02/13/2017
Comment: Finished
Comments:
Comment Date: 02/13/2017 User: BECKER_GT_1
Description: A FDEP Discharge Report Form (DRF) was received by OCEPD via email on February 13, 2017. Please provide to OCEPD all documentation relating to the discharge including waste/soil/water removal and disposal work orders and manifests, and work orders for the repair to the Day Tank level switch mechanism. Also, please maintain the coating on the 1,000-gal generator AST's fill port containment as corrosion is starting to occur. Please send all documentation to Glen Becker, OCEPD: glen.becker@ocfl.net, 321-689-8389.
04/06/2016 Site Inspection Activity Closed Jowett, John C.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/06/2016
Activity Closed Date: 04/06/2016 Activity Closed By: JOWETT_JC_1
Events:
Event Type: Activity has been finished Date: 04/06/2016
Comment: Finished
03/29/2016 Comment Jowett, John C.
Description: Troy Aker Tupperware Corp. 3175 N Orange Blossom Trl Kissimmee, FL 34744 (407) 334-5578 TroyAker@Tupperware.com
07/10/2014 Record Document Activity Moorhead, Seth B.
Activity Status: Closed
Contact Name: Mohamed Kachwalla Activity Closed Date: 07/10/2014
Events:
Event Type: Activity has been finished Date: 07/10/2014
Comment: Finished
02/18/2014 Site Inspection Activity Closed BOWERS, MIKE L
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/18/2014
Activity Closed Date: 02/18/2014 Activity Closed By: BOWERS_M_2
Events:
Event Type: Activity has been finished Date: 02/18/2014
Comment: Finished
Comments:
Comment Date: 02/18/2014 User: BOWERS_M_2
Description: A signed copy of this report was delived on site.
03/26/2012 Site Inspection Activity Closed Cottrell, Steve A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/26/2012
Activity Closed Date: 03/26/2012 Activity Closed By: COTTRELL_SA_1
Events:
Event Type: Activity has been finished Date: 03/26/2012
Comment: Finished
Comments:
Comment Date: 03/26/2012 User: COTTRELL_SA_1
Description: Annual Compliance Inspection Cover Page information verified Release detection is monthly electronic and visual inspections. Inspection report sent via e-mail to troyaker@tupperware.com
03/19/2012 Phone Conversation Activity Cottrell, Steve A.
Call Type: Outgoing Activity Status: Closed
Phone Number: (407) 334-4275 Activity Closed Date: 03/19/2012
Subject: Annual compliance inspection scheduled for Monday, March 26, 2012 at 1000 hours with Troy Aker.
Events:
Event Type: Activity has been finished Date: 03/19/2012
Comment: Finished
02/01/2011 Site Inspection Activity Closed Cottrell, Steve A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/01/2011
Activity Closed Date: 02/04/2011 Activity Closed By: COTTRELL_SA_1
Events:
Event Type: Activity has been finished Date: 02/04/2011
Comment: Finished
Comments:
Comment Date: 02/01/2011 User: COTTRELL_SA_1
Description: Annual Compliance Inspection Cover page information verified Release detection is electronic with monthly visual inspections.
01/21/2011 Phone Conversation Activity Cottrell, Steve A.
Call Type: Outgoing Activity Status: Closed
Phone Number: (407) 729-3969 Activity Closed Date: 01/21/2011
Subject: Annual compliance inspection scheduled for Tuesday, February 1, 2011 at 1300 hours with Mike Dahn.
Events:
Event Type: Activity has been finished Date: 01/21/2011
Comment: Finished
03/04/2010 Attachment Cottrell, Steve A.
03/04/2010 Site Inspection Activity Closed Cottrell, Steve A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/04/2010
Activity Closed Date: 03/04/2010 Activity Closed By: COTTRELL_SA_1
Events:
Event Type: Activity has been finished Date: 03/04/2010
Comment: Finished
Comments:
Comment Date: 03/04/2010 User: COTTRELL_SA_1
Description: Annual compliance inspection Cover page information verified Release detection is electronic with monthly visual inspections.
05/28/2009 Site Inspection Activity Closed Cottrell, Steve A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/28/2009
Activity Closed Date: 05/28/2009 Activity Closed By: COTTRELL_SA_1
Comments:
Comment Date: 05/28/2009 User: COTTRELL_SA_1
Description: annual compliance inspection cover page information Release detection electronic with monthy visual inspections.
05/15/2009 Phone Conversation Activity Gill, Mark A.
Activity Status: Closed
Phone Number: 407 729-6939 Activity Closed Date: 05/15/2009
Subject: The Annual Compliance INspection was schedule for 05/22/2009 at 1000
06/11/2008 Attachment Cottrell, Steve A.
06/11/2008 Attachment Cottrell, Steve A.
06/11/2008 Attachment Cottrell, Steve A.
04/11/2008 Site Inspection Activity Closed Cottrell, Steve A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/11/2008
Activity Closed Date: 04/11/2008 Activity Closed By: COTTRELL_SA_1
Comments:
Comment Date: 04/11/2008 User: COTTRELL_SA_1
Description: Annual compliance inspection. Cover page information verified. Release detection is electronic with monthly visual monitoring
04/03/2008 Phone Conversation Activity Cottrell, Steve A.
Activity Status: Closed
Phone Number: 407-729-3969 Activity Closed Date: 04/03/2008
Subject: Schedule annual compliance inspection for Friday, April 11 at 1PM.
04/09/2007 Record Document Activity Gill, Mark A.
Activity Status: Closed
Contact Name: Mohammad Kashwalla Activity Closed Date: 04/09/2007
03/30/2007 Violation Closed Gill, Mark A.
Significance: Minor Status: Closed
Criteria ID: 2133
Rule: 62-762.711(2)(a), 62-762.711(2)(b), 62-762.711(2)(c), 62-762.711(2)(d), 62-762.711(2)(e), 62-762.711(2)(f), 62-762.711(2)(g), 62-762.711(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-762.641(3)(b)1-2, 62-762.641(3)(b)3 and 62-762.701(1)(c)6 b. Repair, operation, and maintenance - rules 62-762.701(1)(a)1, 62-762.701(1)(a)4, 62-762.701(1)(a)6 and 62-762.701(1)(c)3 c. Release detection - rules 62-762.601(1)(e), 62-762.601(2)(g), 62-762.611(2)(b), 62-762.611(3)(b), 62-762.611(3)(d)2, 62-762.641(2)(c) and 62-762.641(2)(e) d. Release detection response level descriptions - rules 62-762.601(1)(b) and 62-762.641(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-762.611(3)(a)1 and 62-762.641(1)(a) f. Financial responsibility - rule 62-762.401(3) g. Repairs and replacements - rule 62-762.701(1)(a)6 The following are not issues for this rule: Rules 62-762.451(1)(a)2, 62-762.451(1)(a)3 and 62-762.451(1)(a)4 are verbal notices of activities that may also be written Rule 62-762.451(1)(b) is a registration issue Rules 62-762.451(2)(a), 62-762.451(3)(a) and 62-762.451(3)(b) are INF/DRF reporting issues Rules 62-762.601(1)(a)3 and 62-762.601(1)(f) are covered by 62-762.711(3) Anything with cathodic protection is covered by 62-762.711(3)
03/30/2007 Site Inspection Activity Closed Gill, Mark A.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/30/2007
Activity Closed Date: 03/30/2007 Activity Closed By: GILL_MA_1
Comments:
Comment Date: 03/30/2007 User: GILL_MA_1
Description: Annual Compliance Inspection. Facility contact information confirmed.
12/27/2005 Legacy Activity Gill, Mark A.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
11/10/2005 Violation Closed Gill, Mark A.
Significance: Minor Status: Closed
Rule: 762.711(2)
11/10/2005 Legacy Activity Gill, Mark A.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
10/26/2004 Legacy Activity Diaz, Nancy M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: FACILITY APPEARS TO BE IN COMPLIANCE
11/03/2003 Violation Closed Bradshaw, William L.
Significance: SNC-B Status: Closed
Rule: 400(3)
11/03/2003 Legacy Activity Gonzalez, Wendy
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: FACILITY OUT OF COMPLIANCE
11/03/2003 Legacy Activity Bradshaw, William L.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
11/12/2002 Legacy Activity Gonzalez, Wendy
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: FACILITY APPEARS TO BE IN COMPLIANCE
11/01/2001 Legacy Activity Bradshaw, William L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: FACILITY IN COMPLIANCE
12/07/2000 Legacy Activity Bradshaw, William L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: THIS FACILITY APPEARS TO BE IN COMPLIANCE
12/06/1999 Legacy Activity Bradshaw, William L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: IN COMPLIANCE
05/25/1999 Legacy Activity Unknown, User
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed