Report Run Date: 04/20/2025        Last Data Refresh: 04/19/2025        Report Generated from DOPPLER
 
Facility ID: 8623677
Facility Name: LIVING FAITH CHRISTIAN CENTER INC
 
10/24/2024 Electronic Communication Activity Proffitt, Brooke
Activity Closed Date: 10/24/2024 Activity Status: Closed
Date: 10/24/2024
Recipient: luckey7725@gmail.com
Sender: Brooke Proffitt
Subject: Delinquent Placard Notification
Message: See attachment
Events:
Event Type: Activity has been finished Date: 10/24/2024
Comment: Finished
Attachments:
Attachment Date: 10/24/2024 User: PROFFITT_B
Description: Delinquent Placard Notification
View Attachment
07/31/2024 Site Inspection Activity Open Payne, Charles L.
Activity Status: Open
On-Site Start Date: 07/30/2024
03/22/2023 Enforcement Tracking Activity Gillman, Mark
Activity Status: Open
Attachments:
Attachment Date: 04/28/2023 User: BRISTOL_S
Description: Warning Letter
View Attachment
03/09/2023 Enforcement Referral Activity Wilson, Monica L
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/22/2023
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/22/2023
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been finished Date: 03/22/2023
Comment: Finished
Events:
Event Type: Activity has been assigned Date: 03/22/2023
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity/Document was accepted on this date Date: 03/22/2023
Comment: Accepted by Mark Gillman: Accepted and assigned.
Events:
Event Type: Activity has been submitted for approval Date: 03/09/2023
Comment: Submitted for approval by: Monica L Wilson: 12/09/2022 - Sent Compliance Assistance Offer Letter to Gary Luckey (Luckey7725@gmail.com) with a response by 12/24/2022. 01/09/2023 - Mr. Luckey notified the office that the facility was going to do away with the generator and tank. It is no longer needed. We sent all the information that is required for the tank closure. - No Response. 02/10/2023 - Sent an email to Mr. Luckey asking about the status of the closure. - No Response.
Comments:
Comment Date: 03/09/2023 User: WILSON_ML_1
Description: 12/09/2022 - Sent Compliance Assistance Offer Letter to Gary Luckey (Luckey7725@gmail.com) with a response by 12/24/2022. 01/09/2023 - Mr. Luckey notified the office that the facility was going to do away with the generator and tank. It is no longer needed. We sent all the information that is required for the tank closure. - No Response. 02/10/2023 - Sent an email to Mr. Luckey asking about the status of the closure. - No Response.
Comments:
Comment Date: 03/09/2023 User: WILSON_ML_1
Description: 12/09/2022 - Sent Compliance Assistance Offer Letter to Gary Luckey (Luckey7725@gmail.com) with a response by 12/24/2022. 01/09/2023 - Mr. Luckey notified the office that the facility was going to do away with the generator and tank. It is no longer needed. We sent all the information that is required for the tank closure. - No Response. 02/10/2023 - Sent an email to Mr. Luckey asking about the status of the closure. - No Response.
03/09/2023 Enforcement Referral Activity Wilson, Monica L
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/22/2023
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/22/2023
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been finished Date: 03/22/2023
Comment: Finished
Events:
Event Type: Activity has been assigned Date: 03/22/2023
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity/Document was accepted on this date Date: 03/22/2023
Comment: Accepted by Mark Gillman: Accepted and assigned.
Events:
Event Type: Activity has been submitted for approval Date: 03/09/2023
Comment: Submitted for approval by: Monica L Wilson: 12/09/2022 - Sent Compliance Assistance Offer Letter to Gary Luckey (Luckey7725@gmail.com) with a response by 12/24/2022. 01/09/2023 - Mr. Luckey notified the office that the facility was going to do away with the generator and tank. It is no longer needed. We sent all the information that is required for the tank closure. - No Response. 02/10/2023 - Sent an email to Mr. Luckey asking about the status of the closure. - No Response.
Comments:
Comment Date: 03/09/2023 User: WILSON_ML_1
Description: 12/09/2022 - Sent Compliance Assistance Offer Letter to Gary Luckey (Luckey7725@gmail.com) with a response by 12/24/2022. 01/09/2023 - Mr. Luckey notified the office that the facility was going to do away with the generator and tank. It is no longer needed. We sent all the information that is required for the tank closure. - No Response. 02/10/2023 - Sent an email to Mr. Luckey asking about the status of the closure. - No Response.
Comments:
Comment Date: 03/09/2023 User: WILSON_ML_1
Description: 12/09/2022 - Sent Compliance Assistance Offer Letter to Gary Luckey (Luckey7725@gmail.com) with a response by 12/24/2022. 01/09/2023 - Mr. Luckey notified the office that the facility was going to do away with the generator and tank. It is no longer needed. We sent all the information that is required for the tank closure. - No Response. 02/10/2023 - Sent an email to Mr. Luckey asking about the status of the closure. - No Response.
12/09/2022 Editable Letter Activity Payne, Charles L.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 12/09/2022
Comment: Finished
Events:
Event Type: Document has been sent Date: 12/09/2022
Comment: Sent
Attachments:
Attachment Date: 12/09/2022 User: WILSON_ML_1
Description: Compliance Assistance Offer Letter
View Attachment
12/06/2022 Violation Open Payne, Charles L.
Significance: SNC-B Status: Open
Criteria ID: 7009
Rule: 62-762.421(2), 62-762.421(3)(c)
12/06/2022 Phone Conversation Activity Payne, Charles L.
Call Type: Outgoing Activity Status: Closed
Phone Number: (850) 778-5322 Activity Closed Date: 12/07/2022
Subject: Spoke with Pastor Gary and set TCI for 12/06/22.
Events:
Event Type: Activity has been finished Date: 12/07/2022
Comment: Finished
Events:
Event Type: Activity has been finished Date: 12/06/2022
Comment: Finished
12/06/2022 Electronic Communication Activity Payne, Charles L.
Activity Closed Date: 12/07/2022 Activity Status: Closed
Date: 12/06/2022
Recipient: pvhoward@bellsoth.net; almridha@sbcglobal.net
Sender: Charles.Payne@flhealth.gov
Subject: TCI
Message: Scheduled TCI with Patty Flores and AT Mridha for 12/06/2022.
Events:
Event Type: Activity has been finished Date: 12/06/2022
Comment: Finished
Events:
Event Type: Activity has been finished Date: 12/07/2022
Comment: Finished
12/06/2022 Site Inspection Activity Closed Payne, Charles L.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 12/06/2022
Activity Closed Date: 12/09/2022 Activity Closed By: PAYNE_CL_1
Events:
Event Type: Activity has been finished Date: 12/09/2022
Comment: Finished
Comments:
Comment Date: 12/08/2022 User: PAYNE_CL_1
Description: Met onsite with Gary Luckey (Associate Pastor) for this routine tank compliance inspection. This facility has been sold since the previous routine tank compliance inspection which was conducted in November of 2019. The new owner(s) acquired the facility in September of 2022 and were unaware of any regulations associated with the aboveground storage tank system. A copy of the inspection and compliance assistance offer letter will be emailed to Gary Luckey at luckey7725@gmail.com. During this inspection it was explained to Gary Luckey what is required to stay in compliance regarding the tank system. TANK: 1,000 gallon Double Wall (DW) Steel Convault AST installed in May 1999. The tank contains diesel fuel to supply an emergency generator. The tank exterior appears to be in good condition with no visible signs of deterioration or structural deficiencies although the exterior is covered in mold. RELEASE DETECTION: Tank Interstitial Monitoring (IM) sensor is connected to an Omntec OEL 8000 II tank monitor located on the adjacent building. Monthly visual inspections of all tank related equipment: spill containment, tank exterior, piping and alarm status of Tank IM sensor. Monthly visual inspections are not being conducted - violation issued. Omntec system did not appear to be working at time of inspection - violation issued. PIPING: Suction system. Aboveground single wall copper supply and return lines. An anti-siphon solenoid valve is installed on the tank top supply piping. The piping runs aboveground to the day tank. The day tank and emergency generator are located outside near the convault tank. SPILL CONTAINMENT: Spill containment was dry at time of inspection. OVERFILL PREVENTION: Omntec High Fuel Level alarm and a krueger fuel level gauge that is located adjacent to the spill containment. Annual testing of the overfill device is overdue - violation issued. NOTE: Please ensure any alarms associated with the day tank are in working condition.
12/06/2022 Violation Open Payne, Charles L.
Significance: Minor Status: Open
Criteria ID: 7072
Rule: 62-762.601(7), 62-762.602(7)
12/06/2022 Violation Open Payne, Charles L.
Significance: Minor Status: Open
Criteria ID: 7003
Rule: 62-762.401(4), 62-762.401(4)(a), 62-762.401(4)(a)1, 62-762.401(4)(a)2, 62-762.401(4)(b), 62-762.401(4)(c), 62-762.401(4)(d), 62-762.401(4)(e), 62-762.401(4)(f), 62-762.401(4)(g), 62-762.401(4)(h), 62-762.401(4)(i)
12/06/2022 Violation Open Payne, Charles L.
Significance: Minor Status: Open
Criteria ID: 7064
Rule: 62-762.601(1)(d), 62-762.602(1)(d), 62-762.601(1)(g), 62-762.602(1)(g)
12/06/2022 Violation Open Payne, Charles L.
Significance: Minor Status: Open
Criteria ID: 7041
Rule: 62-762.501(2)(e)3, 62-762.501(2)(e)3.a, 62-762.501(2)(e)3.b, 62-762.501(2)(e)4, 62-762.502(2)(e)4, 62-762.502(2)(e)4.a, 62-762.502(2)(e)4.b, 62-762.502(2)(e)5
10/25/2022 Record Document Activity Payne, Charles L.
Activity Status: Closed
Contact Name: Living Faith Christian Center Activity Closed Date: 11/02/2022
Events:
Event Type: Activity has been finished Date: 11/02/2022
Comment: Finished
11/18/2019 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: egregory@thejayodomgroup.com; dstuntz@thejayodomgroup.com Activity Closed Date: 11/18/2019
Events:
Event Type: Activity has been finished Date: 11/18/2019
Comment: Finished
11/18/2019 Editable Letter Activity Wilson, Monica L
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 11/18/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 11/18/2019
Comment: Finished
Attachments:
Attachment Date: 11/18/2019 User: WILSON_ML_1
Description: In Compliance Letter
View Attachment
11/12/2019 Site Inspection Activity Closed Payne, Charles L.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/12/2019
Activity Closed Date: 11/14/2019 Activity Closed By: PAYNE_CL_1
Events:
Event Type: Activity has been finished Date: 11/14/2019
Comment: Finished
Comments:
Comment Date: 11/14/2019 User: PAYNE_CL_1
Description: Met onsite with Emily Gregory (Property Manager, The Jay Odom Group) for this routine compliance inspection. A copy of the inspection and in compliance letter will be emailed to Emily Gregory at egregory@thejayodomgroup.com and Dawn Stuntz at dstuntz@thejayodomgroup.com. The property and tank were previously owned by Century Link. Currently the property is for lease and is owned by The Jay Odom Group (www.thejayodomgroup.com). TANK: 1,000 gallon Double Wall (DW) Steel Convault AST installed in May 1999. The tank contains diesel fuel to supply an emergency generator. The tank exterior appears to be in good condition with no visible signs of deterioration or structural deficiencies. RELEASE DETECTION: Tank Interstitial Monitoring (IM) sensor is connected to an Omntec OEL 8000 II tank monitor located in the adjacent building. The system is monitored locally and can be monitored remotely. Monthly visual inspections of all tank related equipment: spill containment, tank exterior, piping and alarm status of Tank IM sensor. Sensor status was normal and there were no alarms on ATG at time of inspection. PIPING: Suction system. Aboveground single wall copper supply and return lines. An anti-siphon solenoid valve is installed on the tank top supply piping. The piping runs aboveground to the day tank. The day tank and emergency generator are located outside near the convault tank. SPILL CONTAINMENT: Spill containment was clean and dry at time of inspection. OVERFILL PREVENTION: Omntec High Fuel Level alarm and a digital fuel level gauge that is located adjacent to the spill containment. NOTE: Please ensure any alarms associated with the day tank are in working condition.
11/12/2019 Electronic Communication Activity Payne, Charles L.
Activity Closed Date: 11/12/2019 Activity Status: Closed
Date: 11/12/2019
Recipient: EGregory@thejayodomgroup.com
Sender: Charles.Payne@flhealth.gov
Subject: Scedulinh TCI
Message: Sent Emily Gregory an email and set TCI for 11/12/2019.
Events:
Event Type: Activity has been finished Date: 11/12/2019
Comment: Finished
11/03/2017 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: Barbara.C.Oxendine@Centurylink.com Activity Closed Date: 11/06/2017
Events:
Event Type: Activity has been finished Date: 11/06/2017
Comment: Finished
Attachments:
Attachment Date: 11/06/2017 User: WILSON_ML_1
Description: In Compliance Letter
View Attachment
10/31/2017 Site Inspection Activity Closed Payne, Charles L.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/31/2017
Activity Closed Date: 11/02/2017 Activity Closed By: PAYNE_CL_1
Events:
Event Type: Activity has been finished Date: 11/02/2017
Comment: Finished
Comments:
Comment Date: 11/02/2017 User: PAYNE_CL_1
Description: Met on-site with Barbara Oxendine, Building and Land Manager, Barbara.Oxendine@centurylink.com or phone 850-664-3053. Inspection Report will be emailed. TANK: 1,000 gallon Double Wall (DW) Steel Convault AST installed in May 1999. The tank contains diesel for an emergency generator. The tank exterior appears to be in good condition. RELEASE DETECTION: Tank Interstitial Monitoring (IM) sensor is connected to an Omntec OEL 8000 II tank monitor located in the adjacent building. The system is monitored locally and remotely. Monthly visual inspections of all tank related equipment: spill containment, tank exterior, piping and alarm status of Tank IM sensor. Sensor status was normal and there were no alarms on ATG at time of inspection. PIPING: Suction. Aboveground single wall copper supply and return lines. An anti-siphon solenoid valve is installed on the tank top supply piping. The piping runs aboveground to the day tank. The day tank and emergency generator are located outside near the tank. SPILL CONTAINMENT: Spill containment was clean and dry at time of inspection. OVERFILL PREVENTION: Omntec High Fuel Level alarm and a digital fuel level gauge that is located adjacent to the spill containment. Area of Concern: Krueger Gauge is showing signs of wear. Replace Krueger Fuel Gauge as soon as possible.
10/24/2017 Phone Conversation Activity Payne, Charles L.
Call Type: Outgoing Activity Status: Closed
Phone Number: (850) 664-3053 Activity Closed Date: 10/24/2017
Subject: Set TCI with Barbara Oxendine for 10/31/17 at 10 AM.
Events:
Event Type: Activity has been finished Date: 10/24/2017
Comment: Finished
Comments:
Comment Date: 10/24/2017 User: PAYNE_CL_1
Description: Set TCI with Barbara Oxendine for 10/31/17 at 10 AM.
04/15/2015 Attachment Foxworth, Suzanne
04/15/2015 Site Inspection Activity Closed Foxworth, Suzanne
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/15/2015
Activity Closed Date: 04/19/2015 Activity Closed By: FOXWORTH_S_1
Events:
Event Type: Activity has been finished Date: 04/19/2015
Comment: Finished
Comments:
Comment Date: 04/15/2015 User: FOXWORTH_S_1
Description: Met on-site with Barbara Oxendine, Building and Land Repair Manager, Barbara.Oxendine@centurylink.com or phone 850-664-3053. Inspection Report will be emailed. TANK: 1,000 gallon Double Wall (DW) Steel Convault AST installed in May 1999. The tank contains diesel for an emergency generator. The tank exterior is in good condition. RELEASE DETECTION: Tank Interstitial Monitoring (IM) sensor is connected to an Omntec OEL 8000 II tank monitor located in the adjacent building. The system is monitored locally and remotely. Monthly visual inspections of all tank related equipment: spill containment, tank exterior, piping and alarm status of Tank IM sensor. Sensor status was normal and there were no alarms on ATG at time of inspection. PIPING: Suction. Aboveground single wall copper supply and return lines. An anti-siphon solenoid valve is installed on the tank top supply piping. The piping runs aboveground to the day tank. The day tank and emergency generator are located outside near the tank. SPILL CONTAINMENT: Spill containment was clean and dry at time of inspection. OVERFILL PREVENTION: Omntec High Fuel Level alarm and a digital fuel level gauge that is located adjacent to the spill containment.
01/16/2014 Comment Foxworth, Suzanne
Description: POC is Barbara.C.Oxendine@centurylink.com, 850-664-3053 or Lewis.Petteway@centurylink.com.
10/11/2012 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/11/2012
Activity Closed Date: 10/11/2012 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 10/11/2012
Comment: Finished
Comments:
Comment Date: 10/11/2012 User: BRAZILE_DO_1
Description: Tank #9 - Aboveground, Double Wall, concrete over steel primary, Convault tank (EQ-201,) with an E.F. digital level gauge and remote overfill alarm. Integral Piping is Single Wall steel aboveground to adjacent Daytank, 3/4-inch Supply with an anti-siphon solenoid valve and 1-inch return, suction system. Daytank is a Double Wall, SIMPLX Model SST-50B. No Sumps. Release Detection is Liquid Sensor in Aboveground Storage Tank Interstice monitored by OMNTEC OEL8000 II Automatic Tank Gauge (EQ-500) which is centrally remotely monitored by telemetry.
11/16/2010 Site Inspection Activity Closed Tissington, Arthur B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/15/2010
Activity Closed Date: 11/30/2010 Activity Closed By: TISSINGTON_AB_1
Events:
Event Type: Activity has been finished Date: 11/30/2010
Comment: Finished
Comments:
Comment Date: 11/16/2010 User: TISSINGTON_AB_1
Description: Release detection by monthly visual inspection and audible alarm in interstice using electronic probe. Records on computer sent to home office monthly. Copy of test in generator room with CFR, Placard and RDRL.
03/10/2010 Site Inspection Activity Closed Tissington, Arthur B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/10/2010
Activity Closed Date: 03/10/2010 Activity Closed By: TISSINGTON_AB_1
Events:
Event Type: Activity has been finished Date: 03/10/2010
Comment: Finished
Comments:
Comment Date: 03/10/2010 User: TISSINGTON_AB_1
Description: Facility uses visual inspection for release detection. All piping is above ground. Records kept on computer file. Did not have facility on list and had not loaded it before visit.
02/02/2009 Site Inspection Activity Closed Tissington, Arthur B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/02/2009
Activity Closed Date: 02/05/2009 Activity Closed By: TISSINGTON_AB_1
Comments:
Comment Date: 02/05/2009 User: TISSINGTON_AB_1
Description: Tank exterior in good condition All piping is above ground with no contact with soil Records kept on computer and transmitted monthly Site diagram and photo current
Comments:
Comment Date: 02/02/2009 User: TISSINGTON_AB_1
Description: Tank is a Convault DW with visual inspection of tank exterior and ATG to monitor tank interstice for Release detection.
02/02/2009 Site Inspection Activity Closed Tissington, Arthur B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/02/2009
Activity Closed Date: 02/05/2009 Activity Closed By: TISSINGTON_AB_1
Comments:
Comment Date: 02/05/2009 User: TISSINGTON_AB_1
Description: Tank exterior in good condition All piping is above ground with no contact with soil Records kept on computer and transmitted monthly Site diagram and photo current
Comments:
Comment Date: 02/02/2009 User: TISSINGTON_AB_1
Description: Tank is a Convault DW with visual inspection of tank exterior and ATG to monitor tank interstice for Release detection.
04/29/2008 Editable Letter Activity Stevenson, John
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
04/22/2008 Record Document Activity Stevenson, John
Activity Status: Closed
Contact Name: Jennifer Scarpino Activity Closed Date: 04/22/2008
04/10/2008 Attachment Stevenson, John
04/10/2008 Violation Closed Stevenson, John
Significance: Minor Status: Closed
Criteria ID: 2122
Rule: 62-762.701(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non discriminating, or tied into electrical circuits.
04/09/2008 Attachment Stevenson, John
04/07/2008 Site Inspection Activity Closed Stevenson, John
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/07/2008
Activity Closed Date: 04/10/2008 Activity Closed By: STEVENSON_JS
Comments:
Comment Date: 04/10/2008 User: STEVENSON_JS
Description: Inspectrion 04/08/2008. No physical violations; need annual ATG Opcheck. Release Detection is Liquid Sensor in AST Interstice monitored by OMNTEC OEL8000 II Automatic Tank Gauge (EQ-500) which is centrally remotely monitored by telemetry.
04/25/2007 Editable Letter Activity Thayer, Joseph
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 04/25/2007
Comment: Sent on Wed Apr 25 00:00:00 EST 2007
Comments:
Comment Date: 04/25/2007 User: THAYER_JD_1
Description: next test due 4-20-08
Attachments:
Attachment Date: 04/25/2007 User: THAYER_JD_1
Description: NCL Report
View Attachment
04/12/2007 Attachment Thayer, Joseph
04/12/2007 Site Inspection Activity Closed Thayer, Joseph
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/12/2007
Activity Closed Date: 04/12/2007 Activity Closed By: THAYER_JD_1
Comments:
Comment Date: 04/12/2007 User: THAYER_JD_1
Description: Note- ensure copy of tests kept at facility. SPCC plan on file. Inspection completed in office due to toughbook failure.
Comments:
Comment Date: 04/12/2007 User: THAYER_JD_1
Description: RD- Convault DW tank EQ#-201 w/ clock gauge and anti-syphon selenoid. Interstitial monitoring of space with Omntec ATG EQ#-500.
04/12/2007 Site Inspection Activity Closed Thayer, Joseph
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/12/2007
Activity Closed Date: 04/12/2007 Activity Closed By: THAYER_JD_1
Comments:
Comment Date: 04/12/2007 User: THAYER_JD_1
Description: Note- ensure copy of tests kept at facility. SPCC plan on file. Inspection completed in office due to toughbook failure.
Comments:
Comment Date: 04/12/2007 User: THAYER_JD_1
Description: RD- Convault DW tank EQ#-201 w/ clock gauge and anti-syphon selenoid. Interstitial monitoring of space with Omntec ATG EQ#-500.
04/12/2007 Violation Closed Thayer, Joseph
Significance: Minor Status: Closed
Criteria ID: 2122
Rule: 62-762.701(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non discriminating, or tied into electrical circuits.
04/12/2007 Attachment Thayer, Joseph
08/16/2005 Legacy Activity Pierce, Linda L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/01/2005 Comment MIGRATION
Description: REGISTRATION: ADDRESS CORRECTION PER CATHY STEPHENS. CHANGED FROM 630 DENTON TO 650 DENTON. 630 ADDRESS BELONGS TO FAC ID8630216 - LC
10/13/2004 Legacy Activity Pierce, Linda L.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
10/06/2004 Violation Closed Pierce, Linda L.
Significance: Minor Status: Closed
Rule: 762.711(1)
10/06/2004 Legacy Activity Pierce, Linda L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/23/2004 Legacy Activity Pierce, Linda L.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
12/19/2003 Violation Closed Pierce, Linda L.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
12/19/2003 Legacy Activity Pierce, Linda L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/19/2003 Violation Closed Pierce, Linda L.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
02/19/2003 Legacy Activity Pierce, Linda L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/23/2002 Legacy Activity Pierce, Linda L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/04/2001 Legacy Activity Pierce, Linda L.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
02/23/2001 Violation Closed Pierce, Linda L.
Significance: Minor Status: Closed
Rule: 400(2)(a)6
02/23/2001 Legacy Activity Pierce, Linda L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/10/2000 Legacy Activity Pierce, Linda L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/11/1999 Legacy Activity Pierce, Linda L.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
05/12/1999 Violation Closed Pierce, Linda L.
Significance: Minor Status: Closed
Rule: 450(1)(a)3
Comments:
Comment Date: 04/29/2005 User: UNKNOWN
Description: REGISTRATION: FAST FAC ID REQUEST - CLEANUP/NON TANK PER F. PEARSON, SEMINOLE CNTY. LM
05/12/1999 Violation Closed Pierce, Linda L.
Significance: Minor Status: Closed
Rule: 400(1)-(2)
Comments:
Comment Date: 04/05/2005 User: UNKNOWN
Description: REGISTRATION: PER DAN DASHTAKI, ORLO CI., THE GARDEN CLUB IS NOT AN ENTITY OF THE CITY, IT IS A PRIVATE ENTITY. TANK DISCOVERED ON CI R/W AND REMOVED/CLEANUP BY CITY IN PROCESS. LM
05/12/1999 Violation Closed Pierce, Linda L.
Significance: Minor Status: Closed
Rule: 450(1)(a)1
Comments:
Comment Date: 04/29/2005 User: UNKNOWN
Description: REGISTRATION: DISCHARGE ASSOCIATED W/ NON-REG TANK AT BLDG. C/GYM. CONTAMINATIN/DISCHARGE DATE: 4-22-2005 PER F PEARSON NEW # NEEDED BECAUSE THIS CONTAMINATION IS REMOTE FROM TANKS UNDER EXIST FAC 8520759, WHICH ALSO HAS CURRENT CLEANUP (3/2005) ASSOCATED WITH IT. LM
05/12/1999 Legacy Activity Pierce, Linda L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed