Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/20/2025        Last Data Refresh: 04/19/2025        Report Generated from DOPPLER
 
Facility ID: 8630395
Facility Name: SHELL-AVENUE
 
07/30/2024 Enforcement Tracking Activity Stamm, Trey
Activity Status: Open
03/01/2024 Enforcement Referral Activity Keim, Michael J
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 07/30/2024
Events:
Event Type: Activity has been submitted for approval Date: 03/01/2024
Comment: Submitted for approval by: Michael J Keim: This facility has (PUL) sump issues due to drainage from the parking area. The sump need to be raised t prevent rain run-off from entering the top of the sump.
Events:
Event Type: Activity has been assigned Date: 05/09/2024
Comment: Assigned to Jenny E Farrell
Events:
Event Type: Activity/Document was acknowledged on this date Date: 05/09/2024
Comment: Acknowledged and Assigned by DANIEL K HALL
Events:
Event Type: Activity/Document was accepted on this date Date: 07/30/2024
Comment: Accepted by Trey Stamm: Assigned to and Accepted by Trey Stamm
Events:
Event Type: Activity has been finished Date: 07/30/2024
Comment: Finished
Comments:
Comment Date: 03/01/2024 User: KEIM_MJ_1
Description: This facility has (PUL) sump issues due to drainage from the parking area. The sump need to be raised t prevent rain run-off from entering the top of the sump.
Comments:
Comment Date: 03/01/2024 User: KEIM_MJ_1
Description: Please accept this referral for enforcement. I have attached the last inspection report, referral memo, property card, and Sunbiz corporation information.
03/01/2024 Enforcement Referral Activity Keim, Michael J
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 07/30/2024
Events:
Event Type: Activity has been submitted for approval Date: 03/01/2024
Comment: Submitted for approval by: Michael J Keim: This facility has (PUL) sump issues due to drainage from the parking area. The sump need to be raised t prevent rain run-off from entering the top of the sump.
Events:
Event Type: Activity has been assigned Date: 05/09/2024
Comment: Assigned to Jenny E Farrell
Events:
Event Type: Activity/Document was acknowledged on this date Date: 05/09/2024
Comment: Acknowledged and Assigned by DANIEL K HALL
Events:
Event Type: Activity/Document was accepted on this date Date: 07/30/2024
Comment: Accepted by Trey Stamm: Assigned to and Accepted by Trey Stamm
Events:
Event Type: Activity has been finished Date: 07/30/2024
Comment: Finished
Comments:
Comment Date: 03/01/2024 User: KEIM_MJ_1
Description: This facility has (PUL) sump issues due to drainage from the parking area. The sump need to be raised t prevent rain run-off from entering the top of the sump.
Comments:
Comment Date: 03/01/2024 User: KEIM_MJ_1
Description: Please accept this referral for enforcement. I have attached the last inspection report, referral memo, property card, and Sunbiz corporation information.
12/19/2023 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Bob Wood Activity Closed Date: 02/28/2024
Events:
Event Type: Activity has been finished Date: 02/28/2024
Comment: Finished
11/30/2023 Violation Open Keim, Michael J
Significance: SNC-B Status: Open
Criteria ID: 6049
Rule: 62-761.500(6)(a)
11/30/2023 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 11/30/2023
Comment: Finished
Events:
Event Type: Document has been sent Date: 11/30/2023
Comment: Sent
Attachments:
Attachment Date: 11/30/2023 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
11/30/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 11/30/2023 Activity Status: Closed
Date: 11/30/2023
Recipient: Bob Wood
Sender: M Keim
Subject: TCI
Message: E-mail correspondence regarding request for inspection with Bob Wood including scheduling and records needed
Events:
Event Type: Activity has been finished Date: 11/30/2023
Comment: Finished
11/30/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 11/30/2023 Activity Status: Closed
Date: 11/30/2023
Recipient: Bob Wood
Sender: M Keim
Subject: TCI report
Message: Tank Compliance Inspection report and compliance letter sent via e-mail to Bob Wood, bobwoodspci@icloud.com (Authorized compliance contractor for this facility)
Events:
Event Type: Activity has been finished Date: 11/30/2023
Comment: Finished
11/30/2023 Violation Closed Keim, Michael J
Significance: SNC-B Status: Closed
Criteria ID: 6031
Rule: 62-761.500(1)(g), 62-761.500(1)(g)1, 62-761.500(1)(g)2
11/22/2023 Site Inspection Activity Closed Keim, Michael J
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 11/03/2023
Activity Closed Date: 11/30/2023 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 11/30/2023
Comment: Finished
Comments:
Comment Date: 11/30/2023 User: KEIM_MJ_1
Description: Tank Compliance Inspection report and compliance letter sent via e-mail to Bob Wood, bobwoodspci@icloud.com (Authorized compliance contractor for this facility) Compliance assist with Devin Nichols of Southeastern Petroleum
02/22/2023 Editable Letter Activity Keim, Michael J
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 02/22/2023
Comment: Sent
Events:
Event Type: Activity has been finished Date: 02/22/2023
Comment: Finished
Attachments:
Attachment Date: 02/22/2023 User: KEIM_MJ_1
Description: RTC Letter
View Attachment
11/21/2022 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Bob Wood Activity Closed Date: 02/22/2023
Events:
Event Type: Activity has been finished Date: 02/22/2023
Comment: Finished
06/01/2022 Violation Closed Keim, Michael J
Significance: SNC-B Status: Closed
Criteria ID: 6063
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2
06/01/2022 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 06/01/2022 Activity Status: Closed
Date: 06/01/2022
Recipient: Nainesh Patel
Sender: M Keim
Subject: TCI report
Message: Storage tank inspection report sent via e-mail to Nainesh Patel, nainesh65@yahoo.com
Events:
Event Type: Activity has been finished Date: 06/01/2022
Comment: Finished
06/01/2022 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/01/2022
Comment: Finished
Events:
Event Type: Document has been sent Date: 06/01/2022
Comment: Sent
Attachments:
Attachment Date: 06/01/2022 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
05/05/2022 Site Inspection Activity Closed Keim, Michael J
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/05/2022
Activity Closed Date: 06/01/2022 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 06/01/2022
Comment: Finished
Comments:
Comment Date: 06/01/2022 User: KEIM_MJ_1
Description: Storage tank inspection report sent via e-mail to Nainesh Patel, nainesh65@yahoo.com and Bob Wood, bobwoodspci@icloud.com Compliance assist with Bill McCagg of Southeastern Petroleum
03/24/2019 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
03/24/2019 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 03/24/2019 Activity Status: Closed
Date: 03/24/2019
Recipient: Nainesh Patel, Bob Wood
Sender: M Keim
Subject: TCI report
Message: Storage tank compliance report and compliance letter sent via e-mail to Nainesh Patel, nainesh65@yahoo.com and Bob Wood, bobwoodspci@icloud.com
Events:
Event Type: Activity has been finished Date: 03/24/2019
Comment: Finished
03/24/2019 Phone Conversation Activity Keim, Michael J
Call Type: Incoming Activity Status: Closed
Phone Number: (352) 572-6500 Activity Closed Date: 03/24/2019
Subject: Received phone call verifying scheduled TCI with records needed.
Events:
Event Type: Activity has been finished Date: 03/24/2019
Comment: Finished
03/24/2019 Editable Letter Activity Keim, Michael J
Activity Title: Return to Compliance Letter Activity Status: Closed
Description: In Compliance Letter
Events:
Event Type: Document has been sent Date: 03/24/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 03/24/2019
Comment: Finished
Attachments:
Attachment Date: 03/24/2019 User: KEIM_MJ_1
Description: RTC Letter
View Attachment
03/24/2019 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4067
Rule: 62-761.600(4)
03/24/2019 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
03/07/2019 Site Inspection Activity Closed Keim, Michael J
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/07/2019
Activity Closed Date: 03/24/2019 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 03/24/2019
Comment: Finished
Comments:
Comment Date: 03/24/2019 User: KEIM_MJ_1
Description: Storage tank compliance report and compliance letter sent via e-mail to Nainesh Patel, nainesh65@yahoo.com and Bob Wood, bobwoodspci@icloud.com Moving forward please schedule and maintain the required due dates for annual testing.
09/18/2018 Electronic Communication Activity Ramsey, Timothy H
Activity Closed Date: 09/18/2018 Activity Status: Closed
Date: 09/18/2018
Recipient: Nainesh Patel
Sender: Tim Ramsey
Subject: Outreach email to schedule Compliance Inspection
Message: Sent Outreach email to schedule Compliance Inspection
Events:
Event Type: Activity has been finished Date: 09/18/2018
Comment: Finished
12/15/2017 Comment Keim, Michael J
Description: Nainesh Patel (Nick), nainesh65@yahoo.com or 352-489-1494
12/15/2017 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 12/15/2017 Activity Status: Closed
Date: 12/15/2017
Recipient: Nainesh Patel
Sender: M Keim
Subject: Re-inspection compliance report
Message: Re-inspection compliance report sent via e-mail to Nainesh Patel, nainesh65@yahoo.com Also included: Return to Compliance Letter
Events:
Event Type: Activity has been finished Date: 12/15/2017
Comment: Finished
12/15/2017 Issue Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Nainesh Patel Activity Closed Date: 12/15/2017
Events:
Event Type: Activity has been finished Date: 12/15/2017
Comment: Finished
12/14/2017 Site Inspection Activity Closed Keim, Michael J
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/12/2017
Activity Closed Date: 12/15/2017 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 12/15/2017
Comment: Finished
Comments:
Comment Date: 12/14/2017 User: KEIM_MJ_1
Description: Re-inspection compliance report sent via e-mail to Nainesh Patel, nainesh65@yahoo.com Also included: Return to Compliance Letter
12/12/2017 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Melissa Knipp/ Nainesh Patel Activity Closed Date: 12/14/2017
Events:
Event Type: Activity has been finished Date: 12/14/2017
Comment: Finished
12/06/2017 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Nainesh Patel Activity Closed Date: 12/06/2017
Events:
Event Type: Activity has been finished Date: 12/06/2017
Comment: Finished
04/27/2017 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4067
Rule: 62-761.600(4)
04/27/2017 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 04/27/2017 Activity Status: Closed
Date: 04/27/2017
Recipient: Nainesh Patel
Sender: M Keim
Subject: TCI report
Message: sent TCI report to Nainesh Patel via e-mail, nainesh65@yahoo.com
Events:
Event Type: Activity has been finished Date: 04/27/2017
Comment: Finished
04/27/2017 Phone Conversation Activity Keim, Michael J
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 572-6500 Activity Closed Date: 04/27/2017
Subject: Spoke with Nainesh Patel regarding TCI scheduling.
Events:
Event Type: Activity has been finished Date: 04/27/2017
Comment: Finished
04/27/2017 Editable Letter Activity Keim, Michael J
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: INF received 12-18-18 for discovery date 11-28-18
Events:
Event Type: Activity has been finished Date: 04/27/2017
Comment: Finished
Attachments:
Attachment Date: 04/27/2017 User: KEIM_MJ_1
Description: NCL-1
View Attachment
04/27/2017 Site Inspection Activity Closed Keim, Michael J
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/27/2017
Activity Closed Date: 04/27/2017 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 04/27/2017
Comment: Finished
Comments:
Comment Date: 04/27/2017 User: KEIM_MJ_1
Description: Tank compliance inspection report sent via e-mail to Nainesh Patel, nainesh65@yahoo.com New CFR form provided Compliance assist with Nainesh
04/27/2017 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4068
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1., 62-761.700(1)(a)2.
04/27/2017 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4077
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1., 62-761.700(3)(b)2.
11/21/2014 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 11/21/2014
Events:
Event Type: Activity has been finished Date: 11/21/2014
Comment: Finished
11/17/2014 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/17/2014
Activity Closed Date: 11/21/2014 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 11/21/2014
Comment: Finished
Comments:
Comment Date: 11/17/2014 User: OWENS_JS_1
Description: TCI report delivered
10/22/2012 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/22/2012
Activity Closed Date: 10/22/2012 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 10/22/2012
Comment: Finished
Comments:
Comment Date: 10/22/2012 User: OWENS_JS_1
Description: Information for EPA operator training was conveyed and the CFR was completed.
12/23/2010 Site Inspection Activity Closed Gaidos, Daniel B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/23/2010
Activity Closed Date: 12/23/2010 Activity Closed By: GAIDOS_DB_1
Events:
Event Type: Activity has been finished Date: 12/23/2010
Comment: Finished
Comments:
Comment Date: 12/23/2010 User: GAIDOS_DB_1
Description: All open violations from previous inspection have found to have been resolved.
08/27/2010 Violation Closed Gaidos, Daniel B.
Significance: Minor Status: Closed
Criteria ID: 2003
Rule: 62-762.401(2)(a)6.
Comments: All federal facilities with USTs will have a placard. Federal facilities with only ASTs will not have a placard. Per FS 376.3077, "It is unlawful for any owner, operator, or supplier to pump or otherwise deposit any motor fuel into a tank required to be registered under section 376.303 FS, unless proof of valid registration is displayed on such tank itself or the dispensing or measuring device connected thereto or, where appropriate, in the office or kiosk of the facility where the tank is located." Penalties can be assessed to the facility owner for failure to properly register tank systems. Note that penalties can be assessed to the supplier that delivers motor fuel to an unregistered facility. Check the details on the placard. Do they agree with the location you are inspecting? Owners of multiple facilities may switch placards by mistake. Placards are not always issued or received in a timely manner at the change of year period (June and July). Provide the DEP Tallahassee phone number to the facility so they may resolve problems (850) 487-7077; (850) 488-3935. Check STCM in the registration/placard section for the date that the payment was made and the date that the placard was issued. The location of the placard in plain view can be subjective in interpretation: a. For vehicular fuel facilities, plain view is meant to allow the transport delivery driver to view the placard prior to delivering fuel. b. A legal definition is an exception to the general requirement of a valid search warrant to legitimize a search or seizure; a search implies prying into hidden places, and it is not a search to observe what is open to view.
08/27/2010 Editable Letter Activity Gaidos, Daniel B.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: Inspection notification 11.2.17
Events:
Event Type: Activity has been finished Date: 08/27/2010
Comment: Finished
Attachments:
Attachment Date: 08/27/2010 User: GAIDOS_DB_1
Description: Non Compliance Letter
View Attachment
08/27/2010 Site Inspection Activity Closed Gaidos, Daniel B.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 07/21/2010
Activity Closed Date: 08/27/2010 Activity Closed By: GAIDOS_DB_1
Events:
Event Type: Activity has been finished Date: 08/27/2010
Comment: Finished
Comments:
Comment Date: 08/27/2010 User: GAIDOS_DB_1
Description: Violations Summary: There were two violations observed at the time of the inspection; they are summarized in the following citations: 1). The most currect placard was not available during the inspection and was not submitted to our office for the inspection. Please submit a copy of the current tank registration placard to our office. 2). The insurance was not made available during the inspection and was not submitted to our office for this inspection. Please submit a copy of the current CFR and insurance to our office for review. Additional Notes: There are no additional notes, or observations, to document at this time. Discharge Information: There is no new information or obvious evidence of recent release or discharge, within the last year. For more detailed discharge information, please consult the Petroleum Clean Up Section at the F D E P H.Q. in Tallahassee; or the F D E P Central District Office in Orlando; or the official compliance facility file at the Columbia C H D, Environmental Health Section, in Lake City. Other Comments: For more inspection details and information; please see the copy of the inspection field notes, site schematic and system description that is electronically, as well as physically, attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058.
08/27/2010 Violation Closed Gaidos, Daniel B.
Significance: SNC-B Status: Closed
Criteria ID: 2004
Rule: 62-762.401(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-762.401(3).
09/17/2009 Site Inspection Activity Closed Gaidos, Daniel B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 09/17/2009
Activity Closed Date: 09/17/2009 Activity Closed By: GAIDOS_DB_1
Comments:
Comment Date: 09/17/2009 User: GAIDOS_DB_1
Description: Violations Summary: There were no violations cited at the time of the inspection. Additional Notes: Please make sure all monthly inspections are done within 35 days of each other. Discharge Information: There is no new information or obvious evidence of recent release or discharge, within the last year. For more detailed discharge information, please consult the Petroleum Clean Up Section at the F D E P H.Q. in Tallahassee; or the F D E P Central District Office in Orlando; or the official compliance facility file at the Columbia C H D, Environmental Health Section, in Lake City. Other Comments: For more inspection details and information; please see the copy of the inspection field notes, site schematic and system description that is electronically, as well as physically, attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058.
04/23/2009 Attachment Kassees, Ramsey D.
04/23/2009 Attachment Kassees, Ramsey D.
04/23/2009 Attachment Kassees, Ramsey D.
04/03/2009 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/03/2009
Activity Closed Date: 04/23/2009 Activity Closed By: KASSEES_RP_1
Comments:
Comment Date: 04/03/2009 User: KASSEES_RP_1
Description: This is an installation inspection report, for the installation of two D/W upgraded USTs that took place between February 09, 2009 and March 15, 2009. 02/09/2009: On this date two double wall D/W Metal Products (#EQ-333) USTs were installed. The drop took place without mishap. The vacuum gauge readings read -23" Hg and -24" Hg, upon initial installation. The contractor performing the installation was J & J Equipment of Brooksville, PSSSC #PCC050790. 02/10/2009: Inspector Avo Oymayan visited this site for the UST installation. The USTs vacuum readings were confirmed to be -23" Hg and -24" Hg. 02/20/2009: On this date D/W, co-axial, olive green rigid fiberglass Ameron, Dualoy 3000LCX (#EQ-3000L) was installed and pressurized to approximately 55 psi on the primary piping. The soap and pressure test was performed by inspector Avo Oymayan. There were no issues or problems, with the primary piping (tes/inspection) reported by inspector Oymayan. Also installed on this date were the following UST system components: The sump Containment units, they were NEF units by Metal Products (#EQ-627). The dispenser containment units, they were OPW Pisces (#EQ-318). The spill containment buckets, they were EMCO Wheaton (#EQ-594). Fill port flapper valves, OPW (#EQ-223). Red Jacket STPs with Red Jacket MLLDs (mechanical line leak detectors #EQ-373). 02/23/2009: On this date, the secondary piping pressure and soap test/inspection was to have occurred. It did not happen. There was a leak found in one of the secondary lines. Furthermore I observed that the piping installation was a sloppy installation with the piping crossing over one another in some spots and laying right upon one another in other spots. There was no soil bedding between any of the piping lines. They were just laying one upon the other with no cushion between them. I instructed the field foreman Kevin that in no shape, way or form would this be acceptable. I then contacted Melissa (presumeably the project manager) at the J & J Brooksville office and informed her of this situation. She asked to speak with Kevin, then she returned to me and told me that she had instructed Kevin to fix the problem to code stanadards as best as possible. Kevin and his crew then proceeded to bed down the piping runs, that were in contact with one another, with clean soil. Please see photos, of these piping runs, attached to page 8 of this (inspection) level. The USTs' vacuum gauges were still holding at approximately -20" Hg and -24" Hg. The primary piping lines pressures were holding at approximately 50 - 55 psi. 02/24/2009: On this date inspector Benjamin Shulaw performed the secondary piping pressure and soap test/inspection. His field notes indicate that the secondary was pressurized to 5psi each line. It all appeared to be tight. Also on this date, inspector Shula performed the sump and dispenser containment units' hydrostatic test/inspection. His field notes indicate that all units were tight except for dispenser containment units #1 and #5. There were slight leaks found. Repairs were made in the inspector's presence and the units were all passed. The primary piping was still prssurized as follows: Prem - 60 psi; desiel - 60 psi and reg - 50 psi. 03/02/009: On this date, inspector Benjamin shulaw performed the spill buckets' secondary contatainment vacuum tests. His field notes records the vacuum losses as such: Regular fillport spill bucket, no appreciable loss. Diesel fillport spill bucket, approximately 2.5" Hg loss within a minute (from -30" Hg to -27.5" Hg). This is still within the acceptable vacuum loss range within the minute (the tolerance is -4" Hg vacuum loss within a minute). Premium fillport spill bucket, approximately 2.0" Hg loss within a minute (from -30" Hg to -28" Hg). This is still within the acceptable vacuum loss range within the minute (the tolerance is -4" Hg vacuum loss within a minute).
Comments:
Comment Date: 04/23/2009 User: KASSEES_RP_1
Description: 03/16/2009: The start up inspection took place today. All components looked good. All precision tests were performed between 03/02/2009 and 03/05/2009, by J & J Equipment Brooksville and Petroleum Compliance Solutions Inc. Our office is in receipt of the precision tests results. The tested components all passed.
04/03/2009 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/03/2009
Activity Closed Date: 04/23/2009 Activity Closed By: KASSEES_RP_1
Comments:
Comment Date: 04/03/2009 User: KASSEES_RP_1
Description: This is an installation inspection report, for the installation of two D/W upgraded USTs that took place between February 09, 2009 and March 15, 2009. 02/09/2009: On this date two double wall D/W Metal Products (#EQ-333) USTs were installed. The drop took place without mishap. The vacuum gauge readings read -23" Hg and -24" Hg, upon initial installation. The contractor performing the installation was J & J Equipment of Brooksville, PSSSC #PCC050790. 02/10/2009: Inspector Avo Oymayan visited this site for the UST installation. The USTs vacuum readings were confirmed to be -23" Hg and -24" Hg. 02/20/2009: On this date D/W, co-axial, olive green rigid fiberglass Ameron, Dualoy 3000LCX (#EQ-3000L) was installed and pressurized to approximately 55 psi on the primary piping. The soap and pressure test was performed by inspector Avo Oymayan. There were no issues or problems, with the primary piping (tes/inspection) reported by inspector Oymayan. Also installed on this date were the following UST system components: The sump Containment units, they were NEF units by Metal Products (#EQ-627). The dispenser containment units, they were OPW Pisces (#EQ-318). The spill containment buckets, they were EMCO Wheaton (#EQ-594). Fill port flapper valves, OPW (#EQ-223). Red Jacket STPs with Red Jacket MLLDs (mechanical line leak detectors #EQ-373). 02/23/2009: On this date, the secondary piping pressure and soap test/inspection was to have occurred. It did not happen. There was a leak found in one of the secondary lines. Furthermore I observed that the piping installation was a sloppy installation with the piping crossing over one another in some spots and laying right upon one another in other spots. There was no soil bedding between any of the piping lines. They were just laying one upon the other with no cushion between them. I instructed the field foreman Kevin that in no shape, way or form would this be acceptable. I then contacted Melissa (presumeably the project manager) at the J & J Brooksville office and informed her of this situation. She asked to speak with Kevin, then she returned to me and told me that she had instructed Kevin to fix the problem to code stanadards as best as possible. Kevin and his crew then proceeded to bed down the piping runs, that were in contact with one another, with clean soil. Please see photos, of these piping runs, attached to page 8 of this (inspection) level. The USTs' vacuum gauges were still holding at approximately -20" Hg and -24" Hg. The primary piping lines pressures were holding at approximately 50 - 55 psi. 02/24/2009: On this date inspector Benjamin Shulaw performed the secondary piping pressure and soap test/inspection. His field notes indicate that the secondary was pressurized to 5psi each line. It all appeared to be tight. Also on this date, inspector Shula performed the sump and dispenser containment units' hydrostatic test/inspection. His field notes indicate that all units were tight except for dispenser containment units #1 and #5. There were slight leaks found. Repairs were made in the inspector's presence and the units were all passed. The primary piping was still prssurized as follows: Prem - 60 psi; desiel - 60 psi and reg - 50 psi. 03/02/009: On this date, inspector Benjamin shulaw performed the spill buckets' secondary contatainment vacuum tests. His field notes records the vacuum losses as such: Regular fillport spill bucket, no appreciable loss. Diesel fillport spill bucket, approximately 2.5" Hg loss within a minute (from -30" Hg to -27.5" Hg). This is still within the acceptable vacuum loss range within the minute (the tolerance is -4" Hg vacuum loss within a minute). Premium fillport spill bucket, approximately 2.0" Hg loss within a minute (from -30" Hg to -28" Hg). This is still within the acceptable vacuum loss range within the minute (the tolerance is -4" Hg vacuum loss within a minute).
Comments:
Comment Date: 04/23/2009 User: KASSEES_RP_1
Description: 03/16/2009: The start up inspection took place today. All components looked good. All precision tests were performed between 03/02/2009 and 03/05/2009, by J & J Equipment Brooksville and Petroleum Compliance Solutions Inc. Our office is in receipt of the precision tests results. The tested components all passed.
03/11/2009 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/11/2009
Activity Closed Date: 03/24/2009 Activity Closed By: SHULAW_BJ_1
Comments:
Comment Date: 03/13/2009 User: SHULAW_BJ_1
Description: 4Feb09: J&J Equipment of Brooksville PCC 050790 is pulling 4 10,000 gal Buffhide USTs. J&J will clean the tanks with shovels, pads and buckets. The site is reported to be in EDI and any contaminated soil found during the closure is to be returned to the tank pit. Lorrie, of Applied Science and Engineering is handling the assessment/ cleanup.The pipe being removed is single walled flex inside a blue corrugated chaser. There has previously been a cleanup system on the site. The tanks after being pulled were sold 2 each to 2 businesses, manfifests were forwarded. J&J Equipment will also be doing the new system installation.
08/28/2008 Editable Letter Activity Oymayan, Avo J.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
05/23/2008 Violation Closed Oymayan, Avo J.
Significance: SNC-B Status: Closed
Criteria ID: 1033
Rule: 62-761.500(5)(b)1., 62-761.500(5)(b)2., 62-761.500(5)(b)3., 62-761.500(5)(b)4., 62-761.500(5)(b)5.
Comments: Flow shut off device in the drop tube is visible when you look down the drop tube. For systems with flow shut off devices, lift the fill port cover, pop the cap, and view down the drop tube to verify the flow shut off exists. Has the overfill method been bypassed? (Look for broken off product sticks.) If an overfill event has occurred at the facility, check maximum product levels on the inventory records. Obtain the actual versus nominal tank volume. In general, metal tanks hold more product than their nominal rating, while FRP tanks hold less than their nominal rating. Recommend that the high level alarm system be function tested yearly. If the high level alarm is the declared overfill method, at what percentage of actual tank volume is it set to alarm? How does product transfer occur at the facility?
05/23/2008 Editable Letter Activity Oymayan, Avo J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
05/23/2008 Emergency Preparedness Information Activity Oymayan, Avo J.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 05/23/2008
05/23/2008 Violation Closed Oymayan, Avo J.
Significance: Minor Status: Closed
Criteria ID: 1100
Rule: 62-761.640(3)(e)1., 62-761.640(3)(e)2., 62-761.640(3)(e)3., 62-761.640(3)(e)4., 62-761.640(3)(e)5.
Comments: Mark this as out of compliance if SIR results are not calculated properly. Calculated Leak Rate [CLR]- a quantitative expression in gph, calculated to determine the leak status of a tank. A positive gph value may be indicative of product leaking out of the tank system and a negative gph value may be indicative of a volume gain to the tank. Leak Threshold [LT]- represents the action level portion of the leak rate. While the performance standard is 0.2 gph, the threshold is generally one half that rate. Examine the DEP Master Equipment book for the SIR version in use. Minimum Detectable Leak Rate [MDL]- is the smallest leak rate the vendor can determine for the data provided with a Pd of 95% or higher. If the CLR < LT and MDL < 0.2 gph, then the result is a PASS If the MDL > 0.2 gph and CLR < LT, then the result is an INCONCLUSIVE If the CLR > LT, then the result is a FAIL
05/15/2008 Site Inspection Activity Closed Oymayan, Avo J.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/15/2008
Activity Closed Date: 05/23/2008 Activity Closed By: OYMAYAN_AJ_1
Comments:
Comment Date: 05/23/2008 User: OYMAYAN_AJ_1
Description: Additional Notes: None at this time. Discharge Information: There is no new information or any evidence of a recent release or discharge. However, for more detailed information, please contact the FDEP Central District in Orlando; FDEP's HQ in Tallhassee; or the Columbia County Health Department's Environmental Health Section, in Lake City. Other Comments: Please be aware that this facility must upgrade its UST system by December 31, 2009; if it is to continue to operate as a fuel storage and dispensing facility. Also, please be aware that FDEP has never granted any extensions to any of its previous deadlines. For more inspection details and information, please see the copy of the inspection fieldnotes, that is electronically as well as physically attached to this inspection report. If you have any questions or concerns, please contact me at (386) 758-2140 or (386) 758-1058.
10/03/2007 Record Document Activity Jones, Fred H
Activity Status: Closed
Contact Name: Art Vetter, Phone 813-224-0822, Fax 8132240605 Activity Closed Date: 10/03/2007
06/19/2007 Editable Letter Activity McCranie, Pat
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/19/2007
Comment: Sent on Tue Jun 19 00:00:00 EST 2007
Attachments:
Attachment Date: 06/19/2007 User: MCCRANIE_P
Description: NCL Report
View Attachment
06/18/2007 Violation Closed McCranie, Pat
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
06/18/2007 Site Inspection Activity Closed McCranie, Pat
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 06/18/2007
Activity Closed Date: 06/18/2007 Activity Closed By: MCCRANIE_P
06/18/2007 Violation Closed McCranie, Pat
Significance: Minor Status: Closed
Criteria ID: 1122
Rule: 62-761.710(1)
Comments: Was reasonable access to the facility granted? If not, document the circumstances. Were the records available within the specified time frame? If five day pre-inspection notice was not given by the inspector, this item can not be marked as a discrepancy. Make note of the missing documents, and arrange a review period.
06/18/2007 Violation Closed McCranie, Pat
Significance: Minor Status: Closed
Criteria ID: 1049
Rule: 62-761.510(1)(b)3.
Comments: Refer to the color coded chart included in the API 1637 Reference Standard. Note that airport fuel identification is described in API Bulletin 1542. Other identification methods are: tag or decal on the surface adjacent to the fill, tag on the fillpipe adapter, or colored plastic identification card inside the spill containment unit. Major oil retailers often have their own specific color scheme. See rule 62-761.500(5)(a).
06/18/2007 Violation Closed McCranie, Pat
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
06/18/2007 Violation Closed McCranie, Pat
Significance: Minor Status: Closed
Criteria ID: 1102
Rule: 62-761.640(3)(f)1., 62-761.640(3)(f)2., 62-761.640(3)(f)3., 62-761.640(3)(f)4.
Comments: a. Tightness test method meets 0.1 gph performance standard. What is the pass/fail threshold? Look up the test method in the DEP Master Equipment book. Compare the threshold to the actual test data. b. The various test effects are compensated for by the test developer. Request a copy of the operation manual from the RQ tester or the test developer. While not specifically mentioned, the amount of water present in the tank at the start of the test is required to be recorded. c. Test methods generally test the: wetted portion of the tank (product), and the ullage (air space above the product). d. Define which test method is used: volumetric or non volumetric. e. The tester, especially with single-walled tanks, must know the depth to groundwater especially relative to the tank and the product level. The rule compensates for this by setting two minimum product volume values. 30% if depth actually known, 65% if unknown. f. Do overfill and spill containment devices interfere with the test method? This is something the RQ tester must determine, and they may remove these pieces of equipment.
06/18/2007 Violation Closed McCranie, Pat
Significance: Minor Status: Closed
Criteria ID: 1103
Rule: 62-761.640(4)(a)1., 62-761.640(4)(a)2., 62-761.640(4)(a)3., 62-761.640(4)(a)4.
Comments: Installation - verify that the line leak detector has been installed during the final installation inspection. Compliance - check to see that the unit is present. Examine the annual function test data - a pass alone is not sufficient. The tester must demonstrate 3.0 gph discharge detection for the mechanical (flow restrictor). Note that the electronic (auto shut off) line leak detector does not need an annual test, but must still be able to detect a 0.2 gph leak after it has been tripped at 150% line operating pressure. Replacements - unit must be tested out of the box - function must be proven. 3.0 gph = 185.4 ml/min (To convert milliliters/minute to gallons/hour, multiple the milliliters by 0.0162162; or, 1 gph equals 61.8 ml/min). Values greater than 186 ml/min fail. Values less than 185 ml/min mean that the line leak detector will activate at a more restrictive rate.
06/18/2007 Violation Closed McCranie, Pat
Significance: Minor Status: Closed
Criteria ID: 1100
Rule: 62-761.640(3)(e)1., 62-761.640(3)(e)2., 62-761.640(3)(e)3., 62-761.640(3)(e)4., 62-761.640(3)(e)5.
Comments: Mark this as out of compliance if SIR results are not calculated properly. Calculated Leak Rate [CLR]- a quantitative expression in gph, calculated to determine the leak status of a tank. A positive gph value may be indicative of product leaking out of the tank system and a negative gph value may be indicative of a volume gain to the tank. Leak Threshold [LT]- represents the action level portion of the leak rate. While the performance standard is 0.2 gph, the threshold is generally one half that rate. Examine the DEP Master Equipment book for the SIR version in use. Minimum Detectable Leak Rate [MDL]- is the smallest leak rate the vendor can determine for the data provided with a Pd of 95% or higher. If the CLR < LT and MDL < 0.2 gph, then the result is a PASS If the MDL > 0.2 gph and CLR < LT, then the result is an INCONCLUSIVE If the CLR > LT, then the result is a FAIL
02/07/2007 Emergency Preparedness Information Activity Sweeney, Angie
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/07/2007
Comments:
Comment Date: 02/07/2007 User: SWEENEY_A
Description: data collected by john lake
09/25/2006 Emergency Preparedness Information Activity Martin, Mary
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/25/2006
07/08/2005 Legacy Activity Sweeney, Angie
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
06/08/2005 Violation Closed Sweeney, Angie
Significance: SNC-B Status: Closed
Rule: 761.600(1)(d)
06/08/2005 Legacy Activity Sweeney, Angie
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/22/2005 Legacy Activity Johnson, Charles D.
Activity Name: COMPLIANCE W/O FORMAL ENFORCEMENT ACTION Activity Status: Closed
02/22/2005 Legacy Activity Johnson, Charles D.
Activity Name: TELEPHONE CONVERSATION Activity Status: Closed
Completion Notes: CALL TO JIM KRAUSS REQUESTED SIRS AND INV
02/22/2005 Legacy Activity Johnson, Charles D.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: DOCS SUBMITTED
02/21/2005 Legacy Activity Sweeney, Angie
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: NOW USING SIR'S FOR RELEASE DETECTION, MONTHLY VISUAL CHECKS STARTED
02/07/2005 Legacy Activity Johnson, Charles D.
Activity Name: TELEPHONE CONVERSATION Activity Status: Closed
Completion Notes: DOCUMENTATION REQUESTED SENT TO MARION COUNTY
02/03/2005 Legacy Activity Unknown, User
Activity Name: TELEPHONE CONVERSATION Activity Status: Closed
02/03/2005 Legacy Activity Johnson, Charles D.
Activity Name: LETTER Activity Status: Closed
05/28/2004 Violation Closed Sweeney, Angie
Significance: SNC-B Status: Closed
Rule: 600(1)(d)
05/28/2004 Legacy Activity Sweeney, Angie
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
05/28/2004 Violation Closed Sweeney, Angie
Significance: Minor Status: Closed
Rule: 640(2)(e)
05/28/2004 Violation Closed Sweeney, Angie
Significance: Minor Status: Closed
Rule: 700(1)(c)3
07/23/2003 Legacy Activity Sweeney, Angie
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
06/23/2003 Violation Closed Sweeney, Angie
Significance: Minor Status: Closed
Rule: 640(3)(d)
06/23/2003 Legacy Activity Sweeney, Angie
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/12/2002 Legacy Activity Sweeney, Angie
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/24/2001 Legacy Activity Sweeney, Angie
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/14/2000 Legacy Activity Sweeney, Angie
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: PLACARD 6/30/00, PURITY ENV TESTING UP TO 2/00, WILL FAX THE REST
07/27/1999 Legacy Activity Sweeney, Angie
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
07/12/1999 Violation Closed Sweeney, Angie
Significance: SNC-B Status: Closed
Rule: 400(3)
Comments:
Comment Date: 04/01/2009 User: MARTIN_JM
Description: The GPS coordinates for this site are LAT 28:16.288 LON 082:28.723
Comments:
Comment Date: 04/01/2009 User: MARTIN_JM
Description: This facility consists of one 1,000 gal. JRS Custom Fabricators double walled sub-based steel tank (EQ# 497) connected directly to a generator. The piping is D.E.P. approved piping.
07/12/1999 Legacy Activity Sweeney, Angie
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
07/12/1999 Violation Closed Sweeney, Angie
Significance: SNC-B Status: Closed
Rule: 400(3)
Comments:
Comment Date: 04/01/2009 User: MARTIN_JM
Description: The GPS coordinates for this site are LAT 28:16.288 LON 082:28.723
Comments:
Comment Date: 04/01/2009 User: MARTIN_JM
Description: This facility consists of one 1,000 gal. JRS Custom Fabricators double walled sub-based steel tank (EQ# 497) connected directly to a generator. The piping is D.E.P. approved piping.
08/26/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 08/28/2017 User: ZIMMERMAN_RA_2
Description: 7629 Sw Us Highway 27, Fort White, FL 32038
Comments:
Comment Date: 08/04/2008 User: STEVENSON_JS
Description: AST #3 is a SW steel tank by unidentified mfr, in a c/b-diked concrete containment, sealed on the inside surface. The tanks are pressure filled, and equipped with Morrison clock level gauges for overfill protection. The tank's bottom discharge pipe is equipped with a manual isolation valve and an electric solenoid valve. Integral piping is DW, 2-inch steel primary in an unidentified 4-inch, black, flexible PE secondary, suction system. Dispenser Sumps are Environ HDPE (EQ-439,) piped thru the bottom (no pipe interstice monitoring point in these sumps.) No transition sumps are installed at the tank end: the secondary pipe terminates 6-8 inches above the soil surface, and is not sealed. Release Detection is visual inspection of the ASTs and Containment, the Dispenser Sumps and the open ends of the piping secondary.
Comments:
Comment Date: 10/31/2000 User: UNKNOWN
Description: COMPLIANCE: CONTAMINATION
08/26/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 08/28/2017 User: ZIMMERMAN_RA_2
Description: 7629 Sw Us Highway 27, Fort White, FL 32038
Comments:
Comment Date: 08/04/2008 User: STEVENSON_JS
Description: AST #3 is a SW steel tank by unidentified mfr, in a c/b-diked concrete containment, sealed on the inside surface. The tanks are pressure filled, and equipped with Morrison clock level gauges for overfill protection. The tank's bottom discharge pipe is equipped with a manual isolation valve and an electric solenoid valve. Integral piping is DW, 2-inch steel primary in an unidentified 4-inch, black, flexible PE secondary, suction system. Dispenser Sumps are Environ HDPE (EQ-439,) piped thru the bottom (no pipe interstice monitoring point in these sumps.) No transition sumps are installed at the tank end: the secondary pipe terminates 6-8 inches above the soil surface, and is not sealed. Release Detection is visual inspection of the ASTs and Containment, the Dispenser Sumps and the open ends of the piping secondary.
Comments:
Comment Date: 10/31/2000 User: UNKNOWN
Description: COMPLIANCE: CONTAMINATION
08/26/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 08/28/2017 User: ZIMMERMAN_RA_2
Description: 7629 Sw Us Highway 27, Fort White, FL 32038
Comments:
Comment Date: 08/04/2008 User: STEVENSON_JS
Description: AST #3 is a SW steel tank by unidentified mfr, in a c/b-diked concrete containment, sealed on the inside surface. The tanks are pressure filled, and equipped with Morrison clock level gauges for overfill protection. The tank's bottom discharge pipe is equipped with a manual isolation valve and an electric solenoid valve. Integral piping is DW, 2-inch steel primary in an unidentified 4-inch, black, flexible PE secondary, suction system. Dispenser Sumps are Environ HDPE (EQ-439,) piped thru the bottom (no pipe interstice monitoring point in these sumps.) No transition sumps are installed at the tank end: the secondary pipe terminates 6-8 inches above the soil surface, and is not sealed. Release Detection is visual inspection of the ASTs and Containment, the Dispenser Sumps and the open ends of the piping secondary.
Comments:
Comment Date: 10/31/2000 User: UNKNOWN
Description: COMPLIANCE: CONTAMINATION
08/26/1998 Legacy Activity Sweeney, Angie
Activity Name: UST ROUTINE COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: 42