Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 04/27/2025 Last Data Refresh: 04/26/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 8631441 | ||||||||||
Facility Name: | Hontoon Landing Resort & Marina | ||||||||||
04/07/2025 | Electronic Communication Activity | Becker, Glen | |||||||||
Activity Closed Date: | 04/07/2025 | Activity Status: | Closed | ||||||||
Date: | 04/07/2025 | ||||||||||
Recipient: |
Becker, Glen |
||||||||||
Sender: |
Lori Cunniff |
||||||||||
Subject: | Re: Hontoon Landing Resort in Volusia - questions | ||||||||||
Message: |
Hi Glen,
More questions! Integrity testing for the dispenser and trans sump was done on Jan 31.2025. They plan to install a new smaller tank and will still have some underground lines. Integrity testing passed. Can I do a limited closer report?
If they install a smaller tank will they need a permit due to underground piping and over water (double walled) piping? I just could not remember the rules on piping and you are the expert and I am in the field so I am just asking. You can always tell me to go look it up. ¿
Thanks for your help.
Lori
On Thu, Apr 3, 2025 at 4:13¿PM Lori Cunniff |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/07/2025 | ||||||||
Comment: | Finished | ||||||||||
04/07/2025 | Electronic Communication Activity | Becker, Glen | |||||||||
Activity Closed Date: | 04/07/2025 | Activity Status: | Closed | ||||||||
Date: | 04/07/2025 | ||||||||||
Recipient: |
Lori Cunniff |
||||||||||
Sender: | Glen Becker | ||||||||||
Subject: | RE: Hontoon Landing Resort in Volusia - questions | ||||||||||
Message: | Good Morning, Sorry for the delayed reply. The Closure Integrity Evaluation (CIE) requirements state that the integrity tests and shall be performed and provided within 45 days before the closure of the tank system. Per the CIE requirements below, per 62-762-801(3)(a): 2. A Closure Integrity Evaluation for shop fabricated storage tank systems as defined in subsection 62-762.201(8), F.A.C., must be performed no more than 45 days prior to closure or replacement for all double-walled storage tanks, double-walled integral piping, piping sumps, dispenser sumps, and spill containment systems that are in contact with the soil. A Closure Integrity Report must be completed to document the findings of the Closure Integrity Evaluation. 5. The county must be provided with a copy of the Closure Integrity Report as part of the notification process pursuant to paragraph 62-762.411(2)(c), F.A.C. I understand that the facility will continue to use some of the underground piping (and containments?) with a smaller tank, but since a regulated tank is being closed (removed), the tank system falls under the closure requirements. They won’t need to register the smaller new tank, but I don’t know what permits Volusia Co./City of Deland will require. Thank you, Glen Becker Environmental Program Supervisor Orange County Environmental Protection Division Storage Tanks Compliance 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: 407-836-1453 Cell: 321-689-8389 Fax: 407-836-1499 Email: glen.becker@ocfl.net Web: www.ocepd.org | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/07/2025 | ||||||||
Comment: | Finished | ||||||||||
04/04/2025 | Electronic Communication Activity | Becker, Glen | |||||||||
Activity Closed Date: | 04/04/2025 | Activity Status: | Closed | ||||||||
Date: | 04/04/2025 | ||||||||||
Recipient: |
Becker, Glen |
||||||||||
Sender: |
Lori Cunniff |
||||||||||
Subject: | Re: Hontoon Landing Resort in Volusia - questions | ||||||||||
Message: |
Thanks for the clarification.
On Thu, Apr 3, 2025 at 4:04¿PM Becker, Glen |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/04/2025 | ||||||||
Comment: | Finished | ||||||||||
04/04/2025 | Electronic Communication Activity | Becker, Glen | |||||||||
Activity Closed Date: | 04/04/2025 | Activity Status: | Closed | ||||||||
Date: | 04/04/2025 | ||||||||||
Recipient: |
Becker, Glen |
||||||||||
Sender: |
Lori Cunniff |
||||||||||
Subject: | Re: Hontoon Landing Resort in Volusia - questions | ||||||||||
Message: |
Thanks for responding so quickly. I am thinking AOTC will probably do soil sampling so I am reviewing the "sampling requirements for closure of integral piping in contact with soil." Am I correct that if they sample the soil as required (per the Instructions for Conducting Sampling During AGT closure) and the results are clean, then a limited closure report would be acceptable instead of closure report?
Cheers, Lori
On Thu, Apr 3, 2025 at 3:39¿PM Becker, Glen |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/04/2025 | ||||||||
Comment: | Finished | ||||||||||
03/07/2025 | Electronic Communication Activity | Becker, Glen | |||||||||
Activity Closed Date: | 03/07/2025 | Activity Status: | Closed | ||||||||
Date: | 03/07/2025 | ||||||||||
Recipient: |
Becker, Glen |
||||||||||
Sender: | Jamie@hontoon.com | ||||||||||
Subject: | RE: Needing informant on a closer for a tank. #8631441-Hontoon Landing Resort & Marina | ||||||||||
Message: |
Thank you, I am Forwarding all this to John Moran.
From: Becker, Glen |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/07/2025 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 03/07/2025 | User: | BECKER_GT_1 | ||||||||
Description: | Email pdf | ||||||||||
View Attachment | |||||||||||
03/06/2025 | Electronic Communication Activity | Becker, Glen | |||||||||
Activity Closed Date: | 03/06/2025 | Activity Status: | Closed | ||||||||
Date: | 03/06/2025 | ||||||||||
Recipient: |
Jamie@hontoon.com; cc: DeVictoria, Faith |
||||||||||
Sender: | Glen Becker | ||||||||||
Subject: | FW: Needing informant on a closer for a tank. #8631441-Hontoon Landing Resort & Marina | ||||||||||
Message: | Hello Jamie, Thank you for your email and information. Attached is DEP guidance document on the steps to properly close the tank. The AST can either be removed or closed-in-place, as stated in the guidance document. Please note that the tank will need to be cleaned out so there are no more vapors/fumes. For the underground piping, piping transition sump, and the dispenser containment, either a Closure Integrity Evaluation (CIE-attached) shall be performed or a closure soil assessment shall be performed . If you choose to perform the Closure Integrity Evaluation, integrity tests shall be performed on the underground piping, piping transition sump, and the dispenser containment within 45 days prior to the closure of the tank system. The CIE form and integrity test documentation shall be provided to our office and DEP prior to the closure of the tank system. If a CIE is not performed, then a closure soil assessment shall be performed for those components and provided to our office and DEP within 60 days after the closure of the tank system. Email notifications shall be provided to our office and DEP 30-45 days and 48-72 hours prior to the closure of the tank system so our office can perform a closure inspection. If you have any questions, please feel free to contact me, and be sure to notify our office per the requirements prior to the tank removal. Thank you, Glen Becker Environmental Program Supervisor Orange County Environmental Protection Division Storage Tanks Compliance 3165 McCrory Place, Suite 200 Orlando, FL 32803 Office: 407-836-1453 Cell: 321-689-8389 Fax: 407-836-1499 Email: glen.becker@ocfl.net Web: www.ocepd.org | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/06/2025 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 03/06/2025 | User: | BECKER_GT_1 | ||||||||
Description: | Email PDF | ||||||||||
View Attachment | |||||||||||
03/06/2025 | Electronic Communication Activity | Becker, Glen | |||||||||
Activity Closed Date: | 03/06/2025 | Activity Status: | Closed | ||||||||
Date: | 03/06/2025 | ||||||||||
Recipient: | EPD@ocfl.ne | ||||||||||
Sender: |
Jamie@hontoon.com |
||||||||||
Subject: | Needing informant on a closer for a tank. | ||||||||||
Message: | Good afternoon, We are needing to get information on doing a closer of our current fuel holding tank. With plans to replace with a 500-gallon tank so we can continue operation, with our pontoon rentals/fuel sales. The tank we currently have, it’s just too much for our everyday needs on this property, I understand we need to have a Closure Integrity Evaluation report done to start. Who do I need to get in contact with to get this started? Also, do you have any recommendations on companies that can assist with hooking up the 500-gallon tank to the system that connect to the gas dock? Thanks for the information. Jamie Stomberg General Manager Hontoon Landing Resort 2317 River Ridge Rd. Deland, FL 32720 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/06/2025 | ||||||||
Comment: | Finished | ||||||||||
01/12/2024 | Editable Letter Activity | Jones, Jessica | |||||||||
Activity Title: | Warning Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity/Document has been approved | Date: | 01/15/2024 | ||||||||
Comment: | Approved by Jason Seyfert: approved | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 01/12/2024 | ||||||||
Comment: | Submitted for approval by: Jessica Jones | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 12/01/2023 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/06/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 01/12/2024 | User: | JONES_JEL | ||||||||
Description: | Warning Letter | ||||||||||
View Attachment | |||||||||||
Attachments: | |||||||||||
Attachment Date: | 01/12/2024 | User: | JONES_JEL | ||||||||
Description: | Warning Letter | ||||||||||
View Attachment | |||||||||||
04/07/2023 | Enforcement Tracking Activity | Useche, Viviana | |||||||||
Activity Status: | Open | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/06/2024 | User: | JONES_JEL | ||||||||
Description: | Certified Mail Signature | ||||||||||
View Attachment | |||||||||||
03/08/2023 | Enforcement Referral Activity | LaFon, Anthony | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 04/07/2023 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/07/2023 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 04/07/2023 | ||||||||
Comment: | Assigned to Viviana Useche | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 04/07/2023 | ||||||||
Comment: | Accepted by Viviana Useche: Accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 04/07/2023 | ||||||||
Comment: | Acknowledged and Assigned by Viviana Useche | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 03/08/2023 | ||||||||
Comment: | Submitted for approval by: Anthony LaFon: Enforcement referral submitted per DEP Contract # GC925 | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/08/2023 | User: | LAFON_AT_2 | ||||||||
Description: | Referral for enforcement per DEP Contract # GC925 | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/08/2023 | User: | LAFON_AT_2 | ||||||||
Description: | Enforcement referral submitted per DEP Contract # GC925 | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 03/08/2023 | User: | LAFON_AT_2 | ||||||||
Description: | Enforcement referral memo | ||||||||||
View Attachment | |||||||||||
03/08/2023 | Enforcement Referral Activity | LaFon, Anthony | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 04/07/2023 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/07/2023 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 04/07/2023 | ||||||||
Comment: | Assigned to Viviana Useche | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 04/07/2023 | ||||||||
Comment: | Accepted by Viviana Useche: Accepted | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 04/07/2023 | ||||||||
Comment: | Acknowledged and Assigned by Viviana Useche | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 03/08/2023 | ||||||||
Comment: | Submitted for approval by: Anthony LaFon: Enforcement referral submitted per DEP Contract # GC925 | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/08/2023 | User: | LAFON_AT_2 | ||||||||
Description: | Referral for enforcement per DEP Contract # GC925 | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/08/2023 | User: | LAFON_AT_2 | ||||||||
Description: | Enforcement referral submitted per DEP Contract # GC925 | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 03/08/2023 | User: | LAFON_AT_2 | ||||||||
Description: | Enforcement referral memo | ||||||||||
View Attachment | |||||||||||
01/05/2023 | Electronic Communication Activity | Finney, Brittany N | |||||||||
Activity Closed Date: | 01/05/2023 | Activity Status: | Closed | ||||||||
Date: | 01/05/2023 | ||||||||||
Recipient: | Jamie@hontoon.com | ||||||||||
Sender: | brittany.finney@ocfl.net | ||||||||||
Subject: | Hontoon Marina - Open Tank Violations | ||||||||||
Message: |
From: Finney, Brittany |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/05/2023 | ||||||||
Comment: | Finished | ||||||||||
12/19/2022 | Electronic Communication Activity | Finney, Brittany N | |||||||||
Activity Closed Date: | 12/19/2022 | Activity Status: | Closed | ||||||||
Date: | 12/19/2022 | ||||||||||
Recipient: | Jamie@hontoon.com | ||||||||||
Sender: | brittany.finney@ocfl.net | ||||||||||
Subject: | Hontoon Marina - Open Tank Violations | ||||||||||
Message: |
From: chris@hontoon.com |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/19/2022 | ||||||||
Comment: | Finished | ||||||||||
12/19/2022 | Electronic Communication Activity | Finney, Brittany N | |||||||||
Activity Closed Date: | 12/19/2022 | Activity Status: | Closed | ||||||||
Date: | 12/19/2022 | ||||||||||
Recipient: | CHRIS@HONTOON.COM | ||||||||||
Sender: | brittany.finney@ocfl.net | ||||||||||
Subject: | Hontoon Marina - Open Tank Violations | ||||||||||
Message: |
From: Finney, Brittany |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/19/2022 | ||||||||
Comment: | Finished | ||||||||||
11/28/2022 | Electronic Communication Activity | Finney, Brittany N | |||||||||
Activity Closed Date: | 11/28/2022 | Activity Status: | Closed | ||||||||
Date: | 11/28/2022 | ||||||||||
Recipient: | CHRIS@HONTOON.COM | ||||||||||
Sender: | brittany.finney@ocfl.net | ||||||||||
Subject: | Hontoon Marina - Open Tank Violations | ||||||||||
Message: |
From: Finney, Brittany |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 11/28/2022 | ||||||||
Comment: | Finished | ||||||||||
10/04/2022 | Electronic Communication Activity | Finney, Brittany N | |||||||||
Activity Closed Date: | 10/04/2022 | Activity Status: | Closed | ||||||||
Date: | 10/04/2022 | ||||||||||
Recipient: | brittany.finney@ocfl.net | ||||||||||
Sender: | chris@hontoon.com | ||||||||||
Subject: | Hontoon Marina Tank Inspection Report and Compliance Assistance Offer | ||||||||||
Message: |
From: Finney, Brittany
Sent: Monday, October 3, 2022 11:12 AM
To: Christopher White
Subject: Re: Hontoon Marina Tank Inspection Report and Compliance Assistance Offer
That's fine - no worries.
Facilities typically have approximately 90 days to provide corrective action.
If repairs cannot be made within that time, please just communicate with us that more time is needed so we can update our database.
Thank you!
Brittany Finney
From: Christopher White |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/04/2022 | ||||||||
Comment: | Finished | ||||||||||
10/03/2022 | Electronic Communication Activity | Finney, Brittany N | |||||||||
Activity Closed Date: | 10/03/2022 | Activity Status: | Closed | ||||||||
Date: | 10/03/2022 | ||||||||||
Recipient: | CHRIS@HONTOON.COM | ||||||||||
Sender: | brittany.finney@ocfl.net | ||||||||||
Subject: | Hontoon Marina Tank Inspection Report and Compliance Assistance Offer | ||||||||||
Message: | From: Finney, Brittany Sent: Monday, October 3, 2022 10:16 AM To: Christopher White Subject: Hontoon Marina Tank Inspection Report and Compliance Assistance Offer Hi Chris, I hope you guys did okay through the storm! Please see the attached tank inspection report and compliance assistance offer. I have also attached the pressurized piping diagram, if needed. Please work to address the open violations and supply corrective action once available. Please contact me with any questions. Thank you! Brittany Finney | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/03/2022 | ||||||||
Comment: | Finished | ||||||||||
09/28/2022 | Violation Open | Finney, Brittany N | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 7055 | ||||||||||
Rule: | 62-762.501(3)(a)5, 62-762.501(3)(a)6 | ||||||||||
09/28/2022 | Editable Letter Activity | Finney, Brittany N | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 09/28/2022 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Compliance Assistance Offer Verbal | Date: | 09/28/2022 | ||||||||
Comment: | Compliance Assistance Offer Verbal | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/03/2022 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 10/03/2022 | User: | PIERCE_BN_1 | ||||||||
Description: | Compliance Assistance Offer Letter | ||||||||||
View Attachment | |||||||||||
09/28/2022 | Violation Closed | Finney, Brittany N | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 7089 | ||||||||||
Rule: | 62-762.701(4), 62-762.701(4)(a), 62-762.701(4)(a)1, 62-762.701(4)(a)1.a, 62-762.701(4)(a)1.b, 62-762.701(4)(a)1.c, 62-762.701(4)(a)1.d, 62-762.701(4)(a)1.e, 62-762.701(4)(a)1.f, 62-762.701(4)(a)2, 62-762.702(4), 62-762.702(4)(a), 62-762.702(4)(a)1, 62-762.702(4)(a)1.a, 62-762.702(4)(a)1.b, 62-762.702(4)(a)1.c, 62-762.702(4)(a)1.d, 62-762.702(4)(a)2 | ||||||||||
Comments: | |||||||||||
Comment Date: | 11/13/2024 | User: | DEVICTORIA_F | ||||||||
Description: | passing testing rcvd 9-9-24 FD | ||||||||||
09/28/2022 | Violation Closed | Finney, Brittany N | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 7072 | ||||||||||
Rule: | 62-762.601(7), 62-762.602(7) | ||||||||||
Comments: | |||||||||||
Comment Date: | 11/13/2024 | User: | DEVICTORIA_F | ||||||||
Description: | Testing rcvd via Jamie@Hontoon.com on 9/9/24 - FD | ||||||||||
09/14/2022 | Site Inspection Activity Closed | Finney, Brittany N | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 09/14/2022 | ||||||||||
Activity Closed Date: | 09/28/2022 | Activity Closed By: | PIERCE_BN_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/28/2022 | ||||||||
Comment: | Finished | ||||||||||
09/06/2022 | Electronic Communication Activity | Finney, Brittany N | |||||||||
Activity Closed Date: | 09/07/2022 | Activity Status: | Closed | ||||||||
Date: | 09/06/2022 | ||||||||||
Recipient: | CHRIS@HONTOON.COM | ||||||||||
Sender: | brittany.finney@ocfl.net | ||||||||||
Subject: | Tank Inspection Due for FAC 8631441 Hontoon Landing Resort & Marina | ||||||||||
Message: | From: Finney, Brittany Sent: Wednesday, September 7, 2022 1:24 PM To: CHRIS@HONTOON.COM Subject: Tank Inspection Due for FAC 8631441 Hontoon Landing Resort & Marina Good afternoon, The storage tank compliance inspection is due for the facility listed below: HONTOON LANDING MARINA 2317 RIVER RIDGE RD DELAND, FL 32720-4321 I have the following dates available for scheduling the inspection: Sept. 13th at 12:30 PM or Sept. 14th at 11 AM Please confirm if a facility representative can be available to provide access to the tank & associated records on one of these dates. If needed, we can look into other dates for scheduling. Please supply the following records during the inspection (or provide electronically within 5 days of the inspection): the current registration placard should be posted onsite tank insurance documentation for 7/12/19 - present monthly visual inspections for Sept. 2019 - present Testing documentation: line leak detector testing for 2020 - present integrity testing of the transition sump and dispenser sumps I have also attached the Jan. 2019 tank inspection report as reminder of what the inspection consists of. Thank you! Brittany Finney | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/07/2022 | ||||||||
Comment: | Finished | ||||||||||
02/27/2019 | Electronic Communication Activity | Perry, Jacqueline | |||||||||
Activity Closed Date: | 02/27/2019 | Activity Status: | Closed | ||||||||
Date: | 02/27/2019 | ||||||||||
Recipient: | April@hontoon.com | ||||||||||
Sender: | Jackie Perry | ||||||||||
Subject: | Schedule up coming compliance inspection | ||||||||||
Message: | Notification for up coming compliance inspection. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/27/2019 | ||||||||
Comment: | Finished | ||||||||||
02/27/2019 | Editable Letter Activity | Perry, Jacqueline | |||||||||
Activity Title: | In Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 02/26/2019 | ||||||||
Comment: | Sent | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/27/2019 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/27/2019 | User: | PERRY_JF_2 | ||||||||
Description: | In compliance | ||||||||||
View Attachment | |||||||||||
02/26/2019 | Site Inspection Activity Closed | Perry, Jacqueline | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 02/26/2019 | ||||||||||
Activity Closed Date: | 02/27/2019 | Activity Closed By: | PERRY_JF_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/27/2019 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/26/2019 | User: | PERRY_JF_2 | ||||||||
Description: | Dispenser 1/2 on the dock | ||||||||||
View Attachment | |||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/26/2019 | User: | PERRY_JF_2 | ||||||||
Description: | Piping going under the dock over the water | ||||||||||
View Attachment | |||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/26/2019 | User: | PERRY_JF_2 | ||||||||
Description: | Piping transition sump | ||||||||||
View Attachment | |||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/26/2019 | User: | PERRY_JF_2 | ||||||||
Description: | Transition sump location | ||||||||||
View Attachment | |||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/26/2019 | User: | PERRY_JF_2 | ||||||||
Description: | Tank and containment | ||||||||||
View Attachment | |||||||||||
04/25/2016 | Site Inspection Activity Closed | Perry, Jacqueline | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 04/25/2016 | ||||||||||
Activity Closed Date: | 05/16/2016 | Activity Closed By: | PERRY_JF_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/16/2016 | ||||||||
Comment: | Finished | ||||||||||
09/26/2013 | Site Inspection Activity Closed | Perry, Jacqueline | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 09/26/2013 | ||||||||||
Activity Closed Date: | 09/26/2013 | Activity Closed By: | PERRY_JF_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/26/2013 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 09/26/2013 | User: | PERRY_JF_2 | ||||||||
Description: | Breakaways have been installed. Also the annual leak detector test have been successfully completed. Signature block not functional. Report sent via email. | ||||||||||
08/20/2013 | Violation Closed | Perry, Jacqueline | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 2028 | ||||||||||
Rule: | 62-762.501(2)(a)1., 62-762.501(2)(a)2. | ||||||||||
Comments: | Obtain and read the manufacturer's instructions. Make observations, record findings. It is a good practice to accumulate a library of tank system specifications for either your office or yourself. A PSSC is not required for any work involving an AST. Have a familiarity with these reference standards. Document your observations. NFPA 30 Chapters 2 and 3: Tank Storage, Piping Systems. NFPA 30A Chapters 2-4 and 10: Storage, piping, valves and fittings, fuel dispensing systems, marine service stations. PEI 200: Chapters 3, 4, 5, 6, 7, 8, 9, 10, 11, 13: Foundations, Supports, Anchorage, Dike Field Areas, Vaults and Special Enclosures, Tanks, Pumps and Valves, Fill Gauges and Vents, Pipes and Fittings, Corrosion Protection, Environmental Protection, and Testing. Be familiar with environmentally related issues in these referenced standards. You may want to contact the Fire Marshal regarding potential NFPA violations involving fire hazards [emergency power cutoff, securely mounted to island, etc.]. Personally verify as much of the installation process as possible. Refer to the installation inspection tasks described in the preface to this manual. If you are not able to verify certain aspects, get a written statement from the contractor that the standard was adhered to. Document. Document. Document. Verify and write down the make and model of all approved equipment installed. Note the date of each separate visit and what was observed at that time. Note items that pass or fail. | ||||||||||
08/20/2013 | Editable Letter Activity | Perry, Jacqueline | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/20/2013 | ||||||||
Comment: | Finished | ||||||||||
08/20/2013 | Emergency Preparedness Information Activity | Perry, Jacqueline | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 08/20/2013 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/20/2013 | ||||||||
Comment: | Finished | ||||||||||
08/20/2013 | Site Inspection Activity Closed | Perry, Jacqueline | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/20/2013 | ||||||||||
Activity Closed Date: | 08/20/2013 | Activity Closed By: | PERRY_JF_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/20/2013 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/20/2013 | User: | PERRY_JF_2 | ||||||||
Description: | On site for routine compliance inspection. Placard was posted and current. Monthly visual logs, CFR, and testing documents were available and current. Facility had one single wall AST inside a block containment. Containment did have a drain that was closed at time of inspection. Tank had a top mounted pump with single wall steel pipe aboveground at tank. Pipe transitioned to flexpipe going underground to dock and dispensers. Dispensers were in good condition, pans were dry, and shear valves secured. Remote fill quick connect is located inside block containment. System had manual visual check of containment and sticking for overfill. Registration appeared up to date. Breach of integrity test and EPA Op training not required for AST systems. Signature block not functional. Report emailed. Tank and containment are scheduled for cleaning and painting this fall. Currently it is the rainy season and unable to coat. Send pictures when completed. Leak detector test due at the end of the month. Hoses did not have break-a-ways. | ||||||||||
08/10/2011 | Site Inspection Activity Closed | Craft, Tom T. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/10/2011 | ||||||||||
Activity Closed Date: | 08/10/2011 | Activity Closed By: | CRAFT_TT_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/10/2011 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/10/2011 | User: | CRAFT_TT_1 | ||||||||
Description: | 2011.08.10 - Annual - The registration placard is current and available. The CFR and RDRL are current and available. All other required records are in proper order. The annual line leak detector test is current and passed. The tank is in good condition. The piping is in good condition and does not appear to be leaking. The containment area is in good condition. The dispensers are showing no signs of leakage. The dispenser liners are clean and dry. The hoses and nozzles are in good condition. The containment area drain valve is closed, (capped). | ||||||||||
08/05/2010 | Site Inspection Activity Closed | Craft, Tom T. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/05/2010 | ||||||||||
Activity Closed Date: | 08/19/2010 | Activity Closed By: | LEIGH_MM_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/19/2010 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/05/2010 | User: | CRAFT_TT_1 | ||||||||
Description: | 2010.08.05 - Annual - The registration placard is current and posted. The CFR and RDRL are current and on site. The monthly maintenance, visual and release detection records are in proper order. The annual line leak detector test is current and passed. A visual inspection showed the following: the tank is in good condition; the piping is in good condition and does not appear to be leaking; The containment area meets standards. The dispensers are in good condition. The dispenser liners are clean and dry. The hoses and nozzles are in good condition. The containment area drain valve is capped. | ||||||||||
04/02/2009 | Record Document Activity | Stafford, PJ | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | April Stomberg | Activity Closed Date: | 04/02/2009 | ||||||||
04/02/2009 | Record Document Activity | Stafford, PJ | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | April | Activity Closed Date: | 04/02/2009 | ||||||||
03/24/2009 | Editable Letter Activity | Leigh, Michelle M. | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
Comments: | |||||||||||
Comment Date: | 03/24/2009 | User: | LEIGH_MM_1 | ||||||||
Description: | Seperate non compliance letter issued by Volusia County Tanks Compliance Program. | ||||||||||
11/04/2008 | Violation Closed | Craft, Tom T. | |||||||||
Significance: | SNC-B | Status: | Closed | ||||||||
Criteria ID: | 2074 | ||||||||||
Rule: | 62-762.601(1)(i) | ||||||||||
Comments: | Note that there is an exemption: double-walled piping that uses a continuously operating interstitial monitoring method that can detect a 10 gallon release within one hour and shut the pump off, does not need a line leak detector. Note that this method is described in item #143. Also note that line leak detectors need 20 psi pressure to operate. Some pumps, such as centrifugal pumps, are not capable of delivering this pressure needed to operate a line leak detector. Indicate make and model of the line leak detector on the inspection report. | ||||||||||
11/04/2008 | Site Inspection Activity Closed | Craft, Tom T. | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 11/04/2008 | ||||||||||
Activity Closed Date: | 03/11/2009 | Activity Closed By: | LEIGH_MM_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 11/04/2008 | User: | CRAFT_TT_1 | ||||||||
Description: | 2008-11-04: Annual Registration placard is current and posted. CFR and RDRL are current and on site. Monthly maintenance, visual and release detection records are in proper order. The line leak detector has not been tested. A visual inspection showed the following: the tank is in good condition; the piping appears to be not leaking; The containment area meets standards. Dispensers are in good condition; liners are clean and dry. | ||||||||||
08/23/2007 | Site Inspection Activity Closed | Moser, Terry L. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/23/2007 | ||||||||||
Activity Closed Date: | 08/23/2007 | Activity Closed By: | MOSER_T | ||||||||
Comments: | |||||||||||
Comment Date: | 08/23/2007 | User: | MOSER_T | ||||||||
Description: | Required records and documents are available for inspection. Piping sump is clean and dry. Drain is closed. Dispensers are lined clean and dry. Tank is a SW steel ast in sealed block containment. SOme superficial cracking is noted in the containment. No violations noted. | ||||||||||
08/24/2006 | Attachment | Moser, Terry L. | |||||||||
08/24/2006 | Attachment | Moser, Terry L. | |||||||||
08/24/2006 | Attachment | Moser, Terry L. | |||||||||
08/24/2006 | Attachment | Moser, Terry L. | |||||||||
07/25/2006 | Attachment | Moser, Terry L. | |||||||||
07/19/2006 | Site Inspection Activity Closed | Moser, Terry L. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 07/19/2006 | ||||||||||
Activity Closed Date: | 07/19/2006 | Activity Closed By: | MOSER_T | ||||||||
07/21/2005 | Legacy Activity | Shields, Dan J. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
Completion Notes: | A CHANGE IN REGISTRATION SUBMITTED TO TALLA. REMOVING THE T AND CHANGING TO A U FOR IN SERVICE. | ||||||||||
03/28/2005 | Legacy Activity | Unknown, User | |||||||||
Activity Name: | TANK COMPLIANCE RE-INSPECTION | Activity Status: | Closed | ||||||||
03/21/2005 | Legacy Activity | Shields, Dan J. | |||||||||
Activity Name: | TANK INSTALLATION - FINAL INSPECTION | Activity Status: | Closed | ||||||||
Completion Notes: | PIPING INSTALLATION COMPLETE AT FACILITY. ALL TESTS INDICATED THE D/W LINE IS TIGHT. MEETS THE REQUIREMENT FOR D/W PIPING OVER WATER. | ||||||||||
03/21/2005 | Legacy Activity | Shields, Dan J. | |||||||||
Activity Name: | RESPONSE RECEIVED BY DEPARTMENT | Activity Status: | Closed | ||||||||
Completion Notes: | REPLACING PIPING RESOLVED PREVIOUS N/C ISSUE REFERENCING S/W PIPING. | ||||||||||
03/18/2005 | Legacy Activity | Shields, Dan J. | |||||||||
Activity Name: | TELEPHONE CONVERSATION | Activity Status: | Closed | ||||||||
Completion Notes: | RECEIVED MESSAGE FROM NANCY ROSE @ REMTECH STATING THE PIPING INSTALLED AT FACILITY IS READY FOR FINAL INSPECTION. | ||||||||||
07/06/2004 | Violation Closed | Edmondson, Emma Jean | |||||||||
Significance: | SNC-B | Status: | Closed | ||||||||
Rule: | 500(1)(e)3 | ||||||||||
07/06/2004 | Legacy Activity | Moser, Terry L. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
07/06/2004 | Violation Closed | Shields, Dan J. | |||||||||
Significance: | SNC-B | Status: | Closed | ||||||||
Rule: | 500(1)(c) | ||||||||||
07/06/2004 | Violation Closed | Shields, Dan J. | |||||||||
Significance: | SNC-A | Status: | Closed | ||||||||
Rule: | 510(3)(d) | ||||||||||
07/09/2003 | Legacy Activity | Shields, Dan J. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
08/22/2002 | Legacy Activity | Triantafylou, Georgia | |||||||||
Activity Name: | TANK COMPLIANCE - DISTRICT QA INSPECTION | Activity Status: | Closed | ||||||||
07/08/2002 | Legacy Activity | Unknown, User | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
07/10/2001 | Legacy Activity | Moser, Terry L. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
07/25/2000 | Legacy Activity | Moser, Terry L. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
08/03/1999 | Legacy Activity | Edmondson, Emma Jean | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||