DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/20/2025        Last Data Refresh: 04/19/2025        Report Generated from DOPPLER
 
Facility ID: 8840697
Facility Name: CIRCLE K #2708507
 
08/08/2024 Electronic Communication Activity Merritt, Sara
Activity Closed Date: 08/08/2024 Activity Status: Closed
Date: 08/08/2024
Recipient: Mike Sawkiewicz
Sender: Sara Merritt
Subject: All violations closed
Message: see attachment
Events:
Event Type: Activity has been finished Date: 08/08/2024
Comment: Finished
02/26/2024 Enforcement Tracking Activity Gillman, Mark
Activity Status: Open
Attachments:
Attachment Date: 07/11/2024 User: BRISTOL_S
Description: First Contact E-mail Notice
View Attachment
Attachments:
Attachment Date: 08/27/2024 User: BRISTOL_S
Description: Warning Letter
View Attachment
Attachments:
Attachment Date: 03/07/2025 User: BRISTOL_S
Description: CPAM and PCW
View Attachment
Attachments:
Attachment Date: 03/07/2025 User: BRISTOL_S
Description: Proposed SFCO
View Attachment
02/14/2024 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 02/26/2024
Events:
Event Type: Activity has been submitted for approval Date: 02/14/2024
Comment: Submitted for approval by: Muhammad Rafique Khan: ***It was not mentioned in the report but the Tank #3 will need to return to service by 12/01/2024 or the tank will need to be permanently closed. 11/20/2023 – Emailed CAO Letter to Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores. Response needed by 12/05/2023. 12/27/2023 – Emailed Chris regarding Fac ID# 9808435 Circle K #2721426. At that time he indicated that he would go through the inspections today and provide compliance packets for Rafiq’s inspections. He stated he knew there were a few of them and he was also working on gathering the information for the Escambia County sites as well. 12/28/2023 – Received Testing, monthly visual inspections, work order submitted 12/28/2023 to have water removed from STP Sumps and Dispenser sumps, A/B Operator Training, Guarantee FR Paperwork, and Liquid Status (no alarm history). 02/01/2024 – Notified to address any non compliance issues with Scott Janashak. 02/02/2024 – Sent email to Scott Janashak asking if he can assist with the information needed to get the facility in compliance. He added Mike Sawkiewicz to the email. Under a separate facility (8518599, Circle K #2709207) Circle K asked if they could get the information for all Circle K’s with outstanding violations. In a separate email under Facility 9818598 Circle K #2709101, Circle K could receive an extension for all facilities due to the circumstances of the contact that was sending information is no longer with the company. See email for explanation given (County does not have the authority to extend 90 day contracted agreement). Further more, the facility’s that are due to enforcement for Escambia County were also forwarded to both Scott Janashak and Mike Sawkiewicz per their request. **Please note that Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores were all 3 notified of the violations upon the first issuance of the CAO letter on 11/20/2023.
Events:
Event Type: Activity has been finished Date: 02/26/2024
Comment: Finished
Events:
Event Type: Activity/Document was acknowledged on this date Date: 02/26/2024
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been assigned Date: 02/26/2024
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity/Document was accepted on this date Date: 02/26/2024
Comment: Accepted by Mark Gillman: Accepted
Comments:
Comment Date: 02/14/2024 User: KHAN_MR_1
Description: ***It was not mentioned in the report but the Tank #3 will need to return to service by 12/01/2024 or the tank will need to be permanently closed. 11/20/2023 – Emailed CAO Letter to Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores. Response needed by 12/05/2023. 12/27/2023 – Emailed Chris regarding Fac ID# 9808435 Circle K #2721426. At that time he indicated that he would go through the inspections today and provide compliance packets for Rafiq’s inspections. He stated he knew there were a few of them and he was also working on gathering the information for the Escambia County sites as well. 12/28/2023 – Received Testing, monthly visual inspections, work order submitted 12/28/2023 to have water removed from STP Sumps and Dispenser sumps, A/B Operator Training, Guarantee FR Paperwork, and Liquid Status (no alarm history). 02/01/2024 – Notified to address any non compliance issues with Scott Janashak. 02/02/2024 – Sent email to Scott Janashak asking if he can assist with the information needed to get the facility in compliance. He added Mike Sawkiewicz to the email. Under a separate facility (8518599, Circle K #2709207) Circle K asked if they could get the information for all Circle K’s with outstanding violations. In a separate email under Facility 9818598 Circle K #2709101, Circle K could receive an extension for all facilities due to the circumstances of the contact that was sending information is no longer with the company. See email for explanation given (County does not have the authority to extend 90 day contracted agreement). Further more, the facility’s that are due to enforcement for Escambia County were also forwarded to both Scott Janashak and Mike Sawkiewicz per their request. **Please note that Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores were all 3 notified of the violations upon the first issuance of the CAO letter on 11/20/2023.
Comments:
Comment Date: 02/14/2024 User: KHAN_MR_1
Description: ***It was not mentioned in the report but the Tank #3 will need to return to service by 12/01/2024 or the tank will need to be permanently closed. 11/20/2023 – Emailed CAO Letter to Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores. Response needed by 12/05/2023. 12/27/2023 – Emailed Chris regarding Fac ID# 9808435 Circle K #2721426. At that time he indicated that he would go through the inspections today and provide compliance packets for Rafiq’s inspections. He stated he knew there were a few of them and he was also working on gathering the information for the Escambia County sites as well. 12/28/2023 – Received Testing, monthly visual inspections, work order submitted 12/28/2023 to have water removed from STP Sumps and Dispenser sumps, A/B Operator Training, Guarantee FR Paperwork, and Liquid Status (no alarm history). 02/01/2024 – Notified to address any non compliance issues with Scott Janashak. 02/02/2024 – Sent email to Scott Janashak asking if he can assist with the information needed to get the facility in compliance. He added Mike Sawkiewicz to the email. Under a separate facility (8518599, Circle K #2709207) Circle K asked if they could get the information for all Circle K’s with outstanding violations. In a separate email under Facility 9818598 Circle K #2709101, Circle K could receive an extension for all facilities due to the circumstances of the contact that was sending information is no longer with the company. See email for explanation given (County does not have the authority to extend 90 day contracted agreement). Further more, the facility’s that are due to enforcement for Escambia County were also forwarded to both Scott Janashak and Mike Sawkiewicz per their request. **Please note that Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores were all 3 notified of the violations upon the first issuance of the CAO letter on 11/20/2023.
02/14/2024 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 02/26/2024
Events:
Event Type: Activity has been submitted for approval Date: 02/14/2024
Comment: Submitted for approval by: Muhammad Rafique Khan: ***It was not mentioned in the report but the Tank #3 will need to return to service by 12/01/2024 or the tank will need to be permanently closed. 11/20/2023 – Emailed CAO Letter to Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores. Response needed by 12/05/2023. 12/27/2023 – Emailed Chris regarding Fac ID# 9808435 Circle K #2721426. At that time he indicated that he would go through the inspections today and provide compliance packets for Rafiq’s inspections. He stated he knew there were a few of them and he was also working on gathering the information for the Escambia County sites as well. 12/28/2023 – Received Testing, monthly visual inspections, work order submitted 12/28/2023 to have water removed from STP Sumps and Dispenser sumps, A/B Operator Training, Guarantee FR Paperwork, and Liquid Status (no alarm history). 02/01/2024 – Notified to address any non compliance issues with Scott Janashak. 02/02/2024 – Sent email to Scott Janashak asking if he can assist with the information needed to get the facility in compliance. He added Mike Sawkiewicz to the email. Under a separate facility (8518599, Circle K #2709207) Circle K asked if they could get the information for all Circle K’s with outstanding violations. In a separate email under Facility 9818598 Circle K #2709101, Circle K could receive an extension for all facilities due to the circumstances of the contact that was sending information is no longer with the company. See email for explanation given (County does not have the authority to extend 90 day contracted agreement). Further more, the facility’s that are due to enforcement for Escambia County were also forwarded to both Scott Janashak and Mike Sawkiewicz per their request. **Please note that Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores were all 3 notified of the violations upon the first issuance of the CAO letter on 11/20/2023.
Events:
Event Type: Activity has been finished Date: 02/26/2024
Comment: Finished
Events:
Event Type: Activity/Document was acknowledged on this date Date: 02/26/2024
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been assigned Date: 02/26/2024
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity/Document was accepted on this date Date: 02/26/2024
Comment: Accepted by Mark Gillman: Accepted
Comments:
Comment Date: 02/14/2024 User: KHAN_MR_1
Description: ***It was not mentioned in the report but the Tank #3 will need to return to service by 12/01/2024 or the tank will need to be permanently closed. 11/20/2023 – Emailed CAO Letter to Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores. Response needed by 12/05/2023. 12/27/2023 – Emailed Chris regarding Fac ID# 9808435 Circle K #2721426. At that time he indicated that he would go through the inspections today and provide compliance packets for Rafiq’s inspections. He stated he knew there were a few of them and he was also working on gathering the information for the Escambia County sites as well. 12/28/2023 – Received Testing, monthly visual inspections, work order submitted 12/28/2023 to have water removed from STP Sumps and Dispenser sumps, A/B Operator Training, Guarantee FR Paperwork, and Liquid Status (no alarm history). 02/01/2024 – Notified to address any non compliance issues with Scott Janashak. 02/02/2024 – Sent email to Scott Janashak asking if he can assist with the information needed to get the facility in compliance. He added Mike Sawkiewicz to the email. Under a separate facility (8518599, Circle K #2709207) Circle K asked if they could get the information for all Circle K’s with outstanding violations. In a separate email under Facility 9818598 Circle K #2709101, Circle K could receive an extension for all facilities due to the circumstances of the contact that was sending information is no longer with the company. See email for explanation given (County does not have the authority to extend 90 day contracted agreement). Further more, the facility’s that are due to enforcement for Escambia County were also forwarded to both Scott Janashak and Mike Sawkiewicz per their request. **Please note that Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores were all 3 notified of the violations upon the first issuance of the CAO letter on 11/20/2023.
Comments:
Comment Date: 02/14/2024 User: KHAN_MR_1
Description: ***It was not mentioned in the report but the Tank #3 will need to return to service by 12/01/2024 or the tank will need to be permanently closed. 11/20/2023 – Emailed CAO Letter to Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores. Response needed by 12/05/2023. 12/27/2023 – Emailed Chris regarding Fac ID# 9808435 Circle K #2721426. At that time he indicated that he would go through the inspections today and provide compliance packets for Rafiq’s inspections. He stated he knew there were a few of them and he was also working on gathering the information for the Escambia County sites as well. 12/28/2023 – Received Testing, monthly visual inspections, work order submitted 12/28/2023 to have water removed from STP Sumps and Dispenser sumps, A/B Operator Training, Guarantee FR Paperwork, and Liquid Status (no alarm history). 02/01/2024 – Notified to address any non compliance issues with Scott Janashak. 02/02/2024 – Sent email to Scott Janashak asking if he can assist with the information needed to get the facility in compliance. He added Mike Sawkiewicz to the email. Under a separate facility (8518599, Circle K #2709207) Circle K asked if they could get the information for all Circle K’s with outstanding violations. In a separate email under Facility 9818598 Circle K #2709101, Circle K could receive an extension for all facilities due to the circumstances of the contact that was sending information is no longer with the company. See email for explanation given (County does not have the authority to extend 90 day contracted agreement). Further more, the facility’s that are due to enforcement for Escambia County were also forwarded to both Scott Janashak and Mike Sawkiewicz per their request. **Please note that Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores were all 3 notified of the violations upon the first issuance of the CAO letter on 11/20/2023.
12/28/2023 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) Activity Closed Date: 02/14/2024
Events:
Event Type: Activity has been finished Date: 02/14/2024
Comment: Finished
Comments:
Comment Date: 02/14/2024 User: KHAN_MR_1
Description: 12/28/2023 – Received Testing, monthly visual inspections, work order submitted 12/28/2023 to have water removed from STP Sumps and Dispenser sumps, A/B Operator Training, Guarantee FR Paperwork, and Liquid Status (no alarm history). 02/01/2024 – Notified to address any non compliance issues with Scott Janashak. 02/02/2024 – Sent email to Scott Janashak asking if he can assist with the information needed to get the facility in compliance. He added Mike Sawkiewicz to the email. Under a separate facility (8518599, Circle K #2709207) Circle K asked if they could get the information for all Circle K’s with outstanding violations. In a separate email under Facility 9818598 Circle K #2709101, Circle K could receive an extension for all facilities due to the circumstances of the contact that was sending information is no longer with the company. See email for explanation given (County does not have the authority to extend 90 day contracted agreement). Further more, the facility’s that are due to enforcement for Escambia County were also forwarded to both Scott Janashak and Mike Sawkiewicz per their request. **Please note that Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkeiw@circlek.com) from Circle K Stores were all 3 notified of the violations upon the first issuance of the CAO letter on 11/20/2023.
11/21/2023 Phone Conversation Activity Khan, Muhammad Rafique
Call Type: Outgoing Activity Status: Closed
Phone Number: (919) 440-8377 Activity Closed Date: 11/21/2023
Subject: 11-8-2023called (919) 440-8377 jonathan smith for 4 tcis on 11-13-2023
Events:
Event Type: Activity has been finished Date: 11/21/2023
Comment: Finished
11/21/2023 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 11/22/2023
Comment: Sent
Events:
Event Type: Activity has been finished Date: 11/27/2023
Comment: Finished
Attachments:
Attachment Date: 11/27/2023 User: KHAN_MR_1
Description: Compliance Assistance Offer Letter
View Attachment
11/19/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
11/19/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
11/19/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
11/19/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
11/17/2023 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 11/13/2023
Activity Closed Date: 11/21/2023 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 11/21/2023
Comment: Finished
Comments:
Comment Date: 11/19/2023 User: KHAN_MR_1
Description: Met onsite with Austin Boleware with 7G Environmental for this inspection. A copy of this inspection report and compliance assistance offer letter will be sent to Scott Janashak (sjanasha@circlek.com), Christopher Bavuso (Christopher.Bavuso@circlek.com) and Mike Sawkiewicz (MSawkiew@cirlcek.com) with Circle K Stores, Inc. TANKS: They have modified their tanks to DW by utilizing Parabeam. 3- Tanks. unknown manufacturer (now DW with Parabeam) . RELEASE DETECTION: veeder root-TLS 350 EQ# 197. OVERFILL PROTECTION: ball check valves. PIPING: DW SMITH FIBER GLASS EQ=252.Also Ameron Dualoy 3000 EQ # 291. DISPENSERS: 4 Dispenser ,Bravo white EQ # 444. STP SUMPS: STP(3) have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631. SPILL CONTAINMENT: 3 DW spill buckets=EMCO EQ-524 Please note that Tank #3 was registered as "Out of Service" December 2014. If Tank #3 is not returned to service by December 1, 2024, the tank must be properly closed.
11/13/2023 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6063
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2
11/13/2023 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6011
Rule: 62-761.420(2)
11/13/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6002
Rule: 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2, 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7)
11/13/2023 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6056
Rule: 62-761.600(1)(d), 62-761.600(1)(e), 62-761.600(1)(g)
11/13/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
08/24/2022 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 09/15/2022
Comment: Sent
Events:
Event Type: Activity has been finished Date: 09/15/2022
Comment: Finished
Attachments:
Attachment Date: 09/15/2022 User: WILSON_ML_1
Description: Return to Compliance Letter
View Attachment
08/23/2022 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: Christopher Bavuso Activity Closed Date: 08/24/2022
Events:
Event Type: Activity has been finished Date: 08/24/2022
Comment: Finished
Comments:
Comment Date: 08/24/2022 User: KHAN_MR_1
Description: 8-23-22 at 4-11 pm ,Christopher Bavuso sent current record on my request,we received: leak detector test done on 4-28-2022 atg test done on 4-28-2022 overfill test done on 4-28-2022 this will clear corresponding violations
06/13/2022 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6002
Rule: 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2, 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7)
06/13/2022 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/14/2022
Comment: Sent
Events:
Event Type: Activity has been finished Date: 06/14/2022
Comment: Finished
Attachments:
Attachment Date: 06/14/2022 User: WILSON_ML_1
Description: Compliance Assistance Offer Letter
View Attachment
06/13/2022 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
06/13/2022 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
06/13/2022 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
06/13/2022 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 6056
Rule: 62-761.600(1)(d), 62-761.600(1)(e), 62-761.600(1)(g)
05/10/2022 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/17/2022
Activity Closed Date: 06/13/2022 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 06/13/2022
Comment: Finished
Comments:
Comment Date: 05/10/2022 User: KHAN_MR_1
Description: TCI WAS SCHEDULED for 5/10/2022 ,BUT CHANGED TO 7-17-2022 TANKS: They have modified their tanks to DW by utilizing Parabeam. 3- Tanks. unknown manufacturer (now DW with Parabeam) . RELEASE DETECTION: veeder root-TLS 350 EQ# 197. OVERFILL PROTECTION: ball check valves. PIPING: DW SMITH FIBER GLASS EQ=252.Also Ameron Dualoy 3000 EQ # 291. DISPENSERS: 4 Dispenser ,Bravo white EQ # 444. STP SUMPS: STP(3) have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631. SPILL CONTAINMENT: 3 DW spill buckets=EMCO EQ-524
05/10/2022 Phone Conversation Activity Khan, Muhammad Rafique
Call Type: Outgoing Activity Status: Closed
Phone Number: (256) 970-8724 Activity Closed Date: 06/09/2022
Subject: (256) 970-8724 tci scheduled with Jonathan from 7g for 5/17/2022,orignally was suppose to be on 5/10,but could not get chris buvaso that day or even day before.
Events:
Event Type: Activity has been finished Date: 06/09/2022
Comment: Finished
09/23/2019 TCAR Activity Wilson, Monica L
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/23/2019
Events:
Event Type: Activity has been finished Date: 09/23/2019
Comment: Finished
08/22/2019 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: sjanasha@circlek.com; crobbins@circlek.com Activity Closed Date: 08/22/2019
Events:
Event Type: Activity has been finished Date: 08/22/2019
Comment: Finished
08/22/2019 Editable Letter Activity Wilson, Monica L
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/22/2019
Comment: Finished
Events:
Event Type: Document has been sent Date: 08/22/2019
Comment: Sent
Attachments:
Attachment Date: 08/22/2019 User: WILSON_ML_1
Description: In Compliance Letter
View Attachment
08/13/2019 Electronic Communication Activity Khan, Muhammad Rafique
Activity Closed Date: 08/13/2019 Activity Status: Closed
Date: 08/13/2019
Recipient: 'Robbins, Cheri'
Sender: Khan, Rafiq
Subject: Circle k two inspections in Panama city
Message: From: Khan, Rafiq Sent: Friday, August 2, 2019 9:39 AM To: 'Robbins, Cheri' Subject: Circle k two inspections in Panama city Cheri Could you please call me,I have two sites to do inspections this month. 8840697 CIRCLE K #2708507 9808435 CIRCLE K #2721426 Have Great day! Muhammad Khan Environmental Health Division Escambia County Health Department 1300 West Gregory Street Pensacola, FL. 32502 Phone 850.258.8546 Fax 850-595-6774
Events:
Event Type: Activity has been finished Date: 08/13/2019
Comment: Finished
08/07/2019 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/07/2019
Activity Closed Date: 08/21/2019 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 08/21/2019
Comment: Finished
Comments:
Comment Date: 08/07/2019 User: KHAN_MR_1
Description: TANKS: They have modified their tanks to DW by utilizing Parabeam. 3- Tanks. unknown manufacturer (now DW with Parabeam) . RELEASE DETECTION: veeder root-TLS 350 EQ# 197. OVERFILL PROTECTION: ball check valves. PIPING: DW SMITH FIBER GLASS EQ=252.Also Ameron Dualoy 3000 EQ # 291. DISPENSERS: 4 Dispenser ,Bravo white EQ # 444. STP SUMPS: STP(3) have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631. SPILL CONTAINMENT: 3 DW spill buckets=EMCO EQ-524
10/22/2018 Site Inspection Activity Closed Wilson, Monica L
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/18/2018
Activity Closed Date: 10/22/2018 Activity Closed By: WILSON_ML_1
Events:
Event Type: Activity has been finished Date: 10/22/2018
Comment: Finished
Comments:
Comment Date: 10/22/2018 User: WILSON_ML_1
Description: Complaint Inspection conducted per direction of FDEP Tank Division SERT Mission FL-027613 as a follow-up to Hurricane Michael. See attachments section for the field Hurricane Michael Facility Impact Questionnaire.
08/16/2018 Document Management Activity Wilson, Monica L
Activity Title: Closure Document Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/16/2018
Comment: Finished
Attachments:
Attachment Date: 08/16/2018 User: WILSON_ML_1
Description: Limited Closure Report Form for USTs
View Attachment
08/16/2018 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: sjanasha@circlek.com; crobbins@circlek.com; mhart@spsservices.com Activity Closed Date: 08/16/2018
Events:
Event Type: Activity has been finished Date: 08/16/2018
Comment: Finished
08/16/2018 Editable Letter Activity Wilson, Monica L
Activity Title: Limited Closure Summary Report (Complete) Activity Status: Closed
Description: 2019-05-30 CAO Letter
Events:
Event Type: Activity has been finished Date: 08/16/2018
Comment: Finished
Attachments:
Attachment Date: 08/16/2018 User: WILSON_ML_1
Description: Limited Closure Report Form for USTs Review Letter
View Attachment
06/20/2018 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/20/2018
Activity Closed Date: 06/21/2018 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 06/21/2018
Comment: Finished
Comments:
Comment Date: 06/20/2018 User: KHAN_MR_1
Description: Company performing work and PCC#: Superior Petroleum Service of Crest view. PCC# 1256834 Project: To install 2 double walled EBW Defender Spill buckets for premium and regular product List of equipment and EQ# 2 double walled EBW Defender Spill buckets(install) for premium and regular product Placard:ok Current insurance: iron shore 12/1/2017 to 12/1/2018 Release Detection: ATG Overfill protection: FLAPPERS HYDRO test results FOR SPILL BUCKETS: Passed 6/20/2018 Vacuum test for spill bucket: passed 6/20/2018 Forms completed (registration):N/A Is FR up-to-date? yes 06/20/2018 Met on site with David Corn from Superior Petroleum Service of Crest view 06/20/2018 6/20/18: Superior Petroleum Service crew was already here for removal of old 2 spill buckets, this morning they installed both new 2 double walled EBW Defender Spill buckets for premium and regular products.(regular spill was installed yesterday 6/19/2018 later in the day). Hydrotest on both buckets was started at 12 noon and as of 2:16, was still holding. Both riser were removed, cleaned and installed back. Vacuum test on both buckets was done in my presence was 5 psi on both spill buckets,was holding on.
06/19/2018 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/19/2018
Activity Closed Date: 06/21/2018 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 06/21/2018
Comment: Finished
Comments:
Comment Date: 06/19/2018 User: KHAN_MR_1
Description: Company performing work and PCC#: Superior Petroleum Service of Crest view. PCC# 1256834 List of equipment and EQ#s (add to page 3):2 double walled EMCO Spill buckets(removal) Placard Current insurance: iron shore 12/1/2017 to 12/1/2018 Release Detection: ATG Overfill protection: FLAPPERS HYDRO test results FOR SPILL BUCKETS: Passed Forms completed (registration):N/A Is FR up-to-date? yes 2018/6/19: Met on site with David Corn from Superior Petroleum Service of Crest view. 6/14/2018:Crew arrived at facility, cleaned both(Premium and Regular) spill bucket, they found both spill buckets were full of water. After extraction of water new water was added in spill buckets for hydro test. The hydro test was conducted for two hours, Hydro test was passed.. 6/19/2018:Crew arrived at site today, saw cut the concrete around both (Premium and Regular) ,after breaking concrete, they are still digging at 2pm,also they will change the risers too. 6/2018:Both spill buckets(Premium and Regular) double walled were removed. Yesterday only regular spill bucket removal was completed.
01/17/2017 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/17/2017
Activity Closed Date: 01/23/2017 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 01/23/2017
Comment: Finished
Comments:
Comment Date: 01/17/2017 User: KHAN_MR_1
Description: TANKS: They have modified their tanks to DW by utilizing Parabeam. 3- Tanks.unknown manufacturer (now DW with Parabeam) . RELEASE DETECTION: veeder root-TLS 350 EQ# 197. OVERFILL PROTECTION: ball check valves. PIPING: DW SMITH FIBER GLASS EQ=252.Also Ameron Dualoy 3000 EQ # 291. DISPENSERS: 4 Dispenser ,Bravo white EQ # 444. STP SUMPS: STP(3) have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631. SPILL CONTAINMENT: 3 DW spill buckets=EMCO EQ-524 NOTE: During the current inspection on 1-17-2017 Premium tank was not inspected, I was told it has been closed, record did not show any tank closure activity. Circle K office was contacted, they had an INF dated 12-12-2014.where they did mention,they are going to temporary close the tank,but it was never changed on registration form. After contacting Circle K office, they did send tank registration form to tank registration for temporary out of service change today on 1-20-2017, So onward there ate two tanks to be inspected.
12/29/2014 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/29/2014
Activity Closed Date: 12/29/2014 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 12/29/2014
Comment: Finished
Comments:
Comment Date: 12/29/2014 User: KHAN_MR_1
Description: 8840697 - CIRCLE K #8507 TCI 12/29/2014 Met on site with, Scott Puzzio 850 251 472 6547,contact for CIRCLE K #8507 Current FR, placard and RDRL are posted. Inspection report was emailed.. TANKS: They have modified their tanks to DW by utilizing Parabeam. 3- Tanks.unknown manufacturer(now DW with Parabeam) . RELEASE DETECTION: veeder root-TLS 350 EQ# 197. OVERFILL PROTECTION: ball check valves. PIPING: DW SMITH FIBER GLASS EQ=252.Also Ameron Dualoy 3000 EQ # 291. DISPENSERS: 4 Dispenser ,Bravo white EQ # 444. STP SUMPS: STP(3) have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631. SPILL CONTAINMENT: 3 DW spill buckets=EMCO EQ-524
12/29/2014 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 12/29/2014
Events:
Event Type: Activity has been finished Date: 12/29/2014
Comment: Finished
12/22/2014 Document Management Activity Khan, Muhammad Rafique
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 12/22/2014
Comment: Finished
Attachments:
Attachment Date: 12/22/2014 User: KHAN_MR_1
Description: 12/12/2014 INF
View Attachment
12/12/2014 Incident Activity Khan, Muhammad Rafique
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 12/22/2014
Events:
Event Type: Activity has been finished Date: 12/22/2014
Comment: Finished
Comments:
Comment Date: 12/22/2014 User: KHAN_MR_1
Description: Cheri Robbins Environmental Compliance Manager Circle K Stores Inc Sent the following INF status response. Circle K Store 8507, Facility ID 8840697 had an interstitial alarm on the premium tank. Rittiner was dispatched to address the alarm and found liquid in the interstice. The liquid was removed and the tank could not be tested right away so the decision to take the tank out of service was made. All product was removed from the tank. There was no product released to the environment. The tank was tested the week of December 15 2014 and passed testing. Circle K has requested additional testing that will be performed the first of the year 2015. Circle K will forward a copy of the test results once received. Since there was no product released to the environment, INF is closed now.
Comments:
Comment Date: 12/12/2014 User: KHAN_MR_1
Description: Received inf form.Premium tank interstice had liquid,triggered alarm,tank is temporarly closed,product has ben removed.
Comments:
Comment Date: 12/19/2014 User: KHAN_MR_1
Description: 12/19/2014: called Cheri about the update,she is waiting for Tank test to do tank test.
12/12/2014 Incident Activity Khan, Muhammad Rafique
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 12/22/2014
Events:
Event Type: Activity has been finished Date: 12/22/2014
Comment: Finished
Comments:
Comment Date: 12/22/2014 User: KHAN_MR_1
Description: Cheri Robbins Environmental Compliance Manager Circle K Stores Inc Sent the following INF status response. Circle K Store 8507, Facility ID 8840697 had an interstitial alarm on the premium tank. Rittiner was dispatched to address the alarm and found liquid in the interstice. The liquid was removed and the tank could not be tested right away so the decision to take the tank out of service was made. All product was removed from the tank. There was no product released to the environment. The tank was tested the week of December 15 2014 and passed testing. Circle K has requested additional testing that will be performed the first of the year 2015. Circle K will forward a copy of the test results once received. Since there was no product released to the environment, INF is closed now.
Comments:
Comment Date: 12/12/2014 User: KHAN_MR_1
Description: Received inf form.Premium tank interstice had liquid,triggered alarm,tank is temporarly closed,product has ben removed.
Comments:
Comment Date: 12/19/2014 User: KHAN_MR_1
Description: 12/19/2014: called Cheri about the update,she is waiting for Tank test to do tank test.
12/12/2014 Incident Activity Khan, Muhammad Rafique
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 12/22/2014
Events:
Event Type: Activity has been finished Date: 12/22/2014
Comment: Finished
Comments:
Comment Date: 12/22/2014 User: KHAN_MR_1
Description: Cheri Robbins Environmental Compliance Manager Circle K Stores Inc Sent the following INF status response. Circle K Store 8507, Facility ID 8840697 had an interstitial alarm on the premium tank. Rittiner was dispatched to address the alarm and found liquid in the interstice. The liquid was removed and the tank could not be tested right away so the decision to take the tank out of service was made. All product was removed from the tank. There was no product released to the environment. The tank was tested the week of December 15 2014 and passed testing. Circle K has requested additional testing that will be performed the first of the year 2015. Circle K will forward a copy of the test results once received. Since there was no product released to the environment, INF is closed now.
Comments:
Comment Date: 12/12/2014 User: KHAN_MR_1
Description: Received inf form.Premium tank interstice had liquid,triggered alarm,tank is temporarly closed,product has ben removed.
Comments:
Comment Date: 12/19/2014 User: KHAN_MR_1
Description: 12/19/2014: called Cheri about the update,she is waiting for Tank test to do tank test.
02/23/2012 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/23/2012
Activity Closed Date: 02/23/2012 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 02/23/2012
Comment: Finished
Comments:
Comment Date: 02/23/2012 User: KHAN_MR_1
Description: 2-23-2012 rk/db did reinspection on facility.violation was closed.valley tank rep arrived at site took out some liquid from stps.
02/13/2012 Editable Letter Activity Purdy, Elena M.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 02/13/2012
Comment: Sent on Mon Feb 13 00:00:00 EST 2012
Events:
Event Type: Activity has been finished Date: 02/13/2012
Comment: Finished
Attachments:
Attachment Date: 02/13/2012 User: PURDY_EM_1
Description: Non-Compliance Letter
View Attachment
02/09/2012 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
02/09/2012 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/09/2012
Events:
Event Type: Activity has been finished Date: 02/09/2012
Comment: Finished
02/09/2012 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/09/2012
Activity Closed Date: 02/09/2012 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 02/09/2012
Comment: Finished
Comments:
Comment Date: 02/09/2012 User: KHAN_MR_1
Description: 8840697 - CIRCLE K #8507 TCI=2-9-2012 Thursday with no body Valley tanks were coming here but never showed up till 3-30,Appointment was for 2.00 pm today. . Sunny 50 in pm, . They have modified their tanks to DW by utilizing Parabeam. 3- Tanks.unknown manufacturer(now DW with Parabeam) . Release detection= veeder root-TLS 350 EQ# 197. Overfill protection = ball check valves. Piping= DW SMITH FIBER GLASS EQ=252.Also Ameron Dualoy 3000 EQ # 291. 4 Dispenser Sump=dry,,Bravo white EQ # 444. STP(3) have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631. 3 DW spill buckets=EMCO EQ-524 ATG PRINT OUTS = WERE SENT ON 1-25-10 by e.mail . ATG OP TEST ANDILLD TEST= OK RDRL=OK VISUAL INS/ CFR=OK . REPAIR # 1-800-542-3969. CATHY. COMMENTS ON WEDNESDAY 2-9-2012 Could not access tank system would need access. ,
04/14/2011 Comment Brazile, David
Description: 2011/04/07 - Installation/Replacement of the three STP Tank Sumps with Franklin Fueling Systems STP Sumps (EQ-612). Contractor - Superior Petroleum Services - PCC#1256834. This is an EDI/PLRIP combined Eligible Site - Active Score = 56 Tank, Line, & Leak Detector Test were done on 4/9/2011. - All Results = Pass NOTE: The Three Tanks were Upgraded with the Secondary Containment System (Para Beam) in April - June 2008. Interstitial Test were done on the three tanks in March 2011. - Results = Pass
04/11/2011 Attachment Brazile, David
04/07/2011 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/07/2011
Activity Closed Date: 04/14/2011 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 04/14/2011
Comment: Finished
Comments:
Comment Date: 04/11/2011 User: BRAZILE_DO_1
Description: 2011/04/07 - Closure Inspection for Three Green (Unknown Name Brand) STP Tank Sumps Only. This is an EDI/PLRIP (Combined) Site, with an Active Score of 56. The Contractor is Superior Petroleum Services - PCC #1256834 App. 15 Ft. of Smith Fiberglass Piping was removed also with the Three Tank sumps.
04/07/2011 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/07/2011
Activity Closed Date: 04/27/2011 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 04/27/2011
Comment: Finished
Comments:
Comment Date: 04/14/2011 User: BRAZILE_DO_1
Description: 2011/04/07 - Installation/Replacement of the three STP Tank Sumps with Franklin Fueling Systems STP Sumps (EQ-612). Contractor - Superior Petroleum Services - PCC#1256834. This is an EDI/PLRIP combined Eligible Site - Active Score = 56 Tank, Line, & Leak Detector Test were done on 4/9/2011. - All Results = Pass NOTE: The Three Tanks were Upgraded with the Secondary Containment System (Para Beam) in April - June 2008. Interstitial Test were done on the three tanks in March 2011. - Results = Pass
03/09/2011 Editable Letter Activity Purdy, Elena M.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Description: Email
Events:
Event Type: Document has been sent Date: 03/09/2011
Comment: Sent on Wed Mar 09 00:00:00 EST 2011
Events:
Event Type: Activity has been finished Date: 03/09/2011
Comment: Finished
Attachments:
Attachment Date: 03/09/2011 User: PURDY_EM_1
Description: Re-Inspection Letter
View Attachment
03/09/2011 Editable Letter Activity Purdy, Elena M.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Description: Compliance Assistance Offer Letter 12.13.2017
Events:
Event Type: Document has been sent Date: 03/09/2011
Comment: Sent on Wed Mar 09 00:00:00 EST 2011
Events:
Event Type: Activity has been finished Date: 03/09/2011
Comment: Finished
Attachments:
Attachment Date: 03/09/2011 User: PURDY_EM_1
Description: 2nd Re-Inspection
View Attachment
03/07/2011 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/06/2011
Activity Closed Date: 03/08/2011 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 03/08/2011
Comment: Finished
Comments:
Comment Date: 03/07/2011 User: KHAN_MR_1
Description: 8840697 - CIRCLE K #8507 rk and db met john bryant for re-inspection. there was water in 3 sumps and was L-4 fuel alarm on ATG,L4 plus tank sump. ------------------------------------------------------------------------------------------- Conclusion:Facility is still in non compliance..
03/03/2011 Comment Brazile, David
Description: 2011/03/11 - Tank Tech did an Interstitial Test on the three 10,000 GL. underground storage tanks. (10 Hg Mercury for 1 Hr.) NOTE: The interstitial space of the three tanks was dry. Test Results for each of the three tanks can be reviewed in the attachment records. A copy of the test results will be provided upon completion. According to the person doing the testing, the interstitial test results = "Pass" at this time. The test were performed due to a failed interstitial test on the Veeder Root gauge in August 2010, for each of the three tanks. Installation upgrade of the three 10,000 GL. USTs with the Phoenix Containment System was done in April 2008.
03/01/2011 Site Inspection Activity Closed Brazile, David
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/01/2011
Activity Closed Date: 03/03/2011 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 03/03/2011
Comment: Finished
Comments:
Comment Date: 03/02/2011 User: BRAZILE_DO_1
Description: 2011/03/11 - Tank Tech did an Interstitial Test on the three 10,000 GL. underground storage tanks. (10 Hg Mercury for 1 Hr.) NOTE: The interstitial space of the three tanks was dry. Test Results for each of the three tanks can be reviewed in the attachment records. A copy of the test results will be provided upon completion. According to the person doing the testing, the interstitial test results = "Pass" at this time. The test were performed due to a failed interstitial test on the Veeder Root gauge in August 2010, for each of the three tanks. Installation upgrade of the three 10,000 GL. USTs with the Phoenix Containment System was done in April 2008.
02/02/2011 Editable Letter Activity Purdy, Elena M.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 02/02/2011
Comment: Sent on Wed Feb 02 00:00:00 EST 2011
Events:
Event Type: Activity has been finished Date: 02/02/2011
Comment: Finished
Attachments:
Attachment Date: 02/02/2011 User: PURDY_EM_1
Description: Non-compliance letter
View Attachment
01/31/2011 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 01/31/2011
Events:
Event Type: Activity has been finished Date: 01/31/2011
Comment: Finished
01/26/2011 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1010
Rule: 62-761.450(2)(a)1., 62-761.450(2)(a)2., 62-761.450(2)(a)3., 62-761.450(2)(a)4., 62-761.450(2)(a)5., 62-761.450(2)(a)6., 62-761.450(2)(a)7.
Comments: Multiple incidents occurring at the same time at the facility may be reported on one form. #1-3 - Evidence of these types of INF situations are generally found during the inspector's paperwork review. Ask the facility representative what action they took in response, and in what time frame. If the situations are resolved within 24 hours, the owner/operator is not required to submit an INF to the local program. However, the actions they took to resolve the issue must be documented. #4-5, and 7 - Evidence of these types of situations are generally found during the outside or physical portion of the inspection. Give the facility owner/operator 24 hours to resolve, provided they document their actions. If they can not resolve the issues then they must submit the INF, at which time the two week investigative window opens. #6 - Evidence of this type of situation may be found during the physical examination of the release detection device (e.g. alarm mode), or during the examination of the records associated with the method. Note: Inspectors may find events that qualify as incidents during their review of the facility's paperwork. Such issues must have been resolved within 24 hours if an INF was not submitted at the time of the event.
01/26/2011 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/26/2011
Activity Closed Date: 01/27/2011 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 01/27/2011
Comment: Finished
Comments:
Comment Date: 01/27/2011 User: KHAN_MR_1
Description: 8840697 - CIRCLE K #8507 TCI=1-26-2011 Wednesday with JOHN BRYANT from PENSACOLA. Sunny 45 in morning, latter would be 50 degrees. They have modified their tanks to DW by utilizing Parabeam. 3- Tanks.unknown manufacturer(now DW with Parabeam) . Release detection= veeder root-TLS 350 EQ# 197. Overfill protection = ball check valves. Piping= DW SMITH FIBER GLASS EQ=252.Also Ameron Dualoy 3000 EQ # 291. 4 Dispenser Sump=dry,,Bravo white EQ # 444. STP(3) have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631. 3 DW spill buckets=EMCO EQ-524 ATG PRINT OUTS = WERE SENT ON 1-25-10 by e.mail . ATG OP TEST ANDILLD TEST= OK RDRL=OK VISUAL INS/ CFR=OK . REPAIR # 1-800-542-3969. CATHY. COMMENTS ON 12-22-09 TCI=1-26-09 WEDNESDAY AM, . JOHN FROM PENSACLOA WAS HERE. WE COULD NOT OPEN INNER TANK SUMP PLASTIC LIDS EVEN TRYING HAMMER AND CRO BARS ETC FOR QUITE A WHILE.FINALLY GOT OPENED, . BOTH DISPENSER LINER LOOKED DRY. THERE WERE SEVERALFUEL ALARM ON THEIR INVENTORY PRINT OUTS INCLUDED WERE FUEL ALARMS FOR TANK INTERSTICE ALSO. SEVERAL MONTHLY ATG PRINTOUT PAGES WERE NON-READABLE. . TODAY ALL THREE TANK SUMP HAD WATER IN IT, SPECIALLY PLUS TANK SUMP HAD IN EXCESS OF 6 INCHES LIQUID IN IT AND ATG SENSOR WAS HUNG HIGH, SO NO ALARM WAS BEING REGISTERED. THEY NEEDED TO BE EMPTY AND RE-INSPECTION WOULD BE DONE TO CHEK SENSOR HEIGHT ALSO. SPILL BUCKETS HAD SOME OF WATER, WATER WAS REMOVED, SECONDARY SPACE WAS CHECKED FOR SPILL BUCKETS, WAS OK. . THEY HAD TANK INTERSTITIAL FUEL ALARM DURING THE LAST ANNUAL TANK INSPECTION ON THEIR ATG PRINT OUT, SAME WAS THE CASE THIS YEAR (2011) THE DATA SENT TO THIS OFFICE SHOWS SEVERAL INTERSTITIAL FUEL ALARMS ON ALL THREE TANKS AGAIN(WITH THE EXCEPTION OF PAGES AFTER AUGUST 2010 WHICH ARE NON READABLE). THE FOLLOWING DATES SHOW THAT THEY HAD FUEL ALARM ON ALL THREE TANK INTERSTICES,SEVERAL SENSOR OUT ALARMS ARE ALSO PRESENT. APR 23-10 MAY 23-10 AUG 3 -10 MOST OF THE TIME L4-L5-L5-L6 INDICATES ALARM ALSO. WE WILL NEED AN INF,THEN INVESTIGATION SHOWING WHY THEIR INTERSTITAL SPACE IS GEETING SO MANT FUEL ALARMS.
01/26/2011 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
04/09/2010 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: Received on 4-7-10 by e.mail from Linda pearece who got it from heather gi Activity Closed Date: 04/09/2010
Events:
Event Type: Activity has been finished Date: 04/09/2010
Comment: Finished
Comments:
Comment Date: 04/09/2010 User: KHAN_MR_1
Description: Received on 4-7-10 by e.mail from Linda pearece who got it from heather gimore dated 4-2-10. Water was removed FROM REGULAR AND PREMIUN TANK SUMPS per Eagle SWS on 1-19-2010 invoice.This clears the violation # 1115
01/08/2010 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: heather gillman Activity Closed Date: 03/31/2010
Events:
Event Type: Activity has been finished Date: 03/31/2010
Comment: Finished
Comments:
Comment Date: 01/08/2010 User: KHAN_MR_1
Description: Received requested inf for fuel alarm on tank sumps, premium tank test is requested by facility to verify tank fuel alarm
01/06/2010 Editable Letter Activity Pierce, Linda L.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 01/06/2010
Comment: Sent on Wed Jan 06 00:00:00 EST 2010
Events:
Event Type: Activity has been finished Date: 01/06/2010
Comment: Finished
Attachments:
Attachment Date: 01/06/2010 User: PIERCE_LL_1
Description: NCL letter
View Attachment
12/29/2009 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 12/29/2009
Events:
Event Type: Activity has been finished Date: 12/29/2009
Comment: Finished
12/23/2009 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 12/23/2009
Events:
Event Type: Activity has been finished Date: 12/23/2009
Comment: Finished
12/22/2009 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1010
Rule: 62-761.450(2)(a)1., 62-761.450(2)(a)2., 62-761.450(2)(a)3., 62-761.450(2)(a)4., 62-761.450(2)(a)5., 62-761.450(2)(a)6., 62-761.450(2)(a)7.
Comments: Multiple incidents occurring at the same time at the facility may be reported on one form. #1-3 - Evidence of these types of INF situations are generally found during the inspector's paperwork review. Ask the facility representative what action they took in response, and in what time frame. If the situations are resolved within 24 hours, the owner/operator is not required to submit an INF to the local program. However, the actions they took to resolve the issue must be documented. #4-5, and 7 - Evidence of these types of situations are generally found during the outside or physical portion of the inspection. Give the facility owner/operator 24 hours to resolve, provided they document their actions. If they can not resolve the issues then they must submit the INF, at which time the two week investigative window opens. #6 - Evidence of this type of situation may be found during the physical examination of the release detection device (e.g. alarm mode), or during the examination of the records associated with the method. Note: Inspectors may find events that qualify as incidents during their review of the facility's paperwork. Such issues must have been resolved within 24 hours if an INF was not submitted at the time of the event.
12/22/2009 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 12/20/2009
Activity Closed Date: 12/30/2009 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 12/30/2009
Comment: Finished
Comments:
Comment Date: 12/22/2009 User: KHAN_MR_1
Description: . TCI=12-22-09 with MARK from PENSACOLA.Sunny 36 in morning, latter would be 60 degrees. They modified their tanks to DW by utilizing Parabeam. 3- Tanks.unknown manufacturer(now DW with Parabeam) . Release detection= veeder root-TLS 350 EQ# 197. Overfill protection = ball check valves. Piping= DW SMITH FIBER GLASS EQ=252.Also Ameron Dualoy 3000 EQ # 291. 4 Dispenser Sump=dry,,Bravo white EQ # 444 STP(3) have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631. 3 DW spill buckets=EMCO EQ-524 -------------------------- ATG PRINT OUTS = WERE SENT ON 12-29-09. ATG OP TEST ANDILLD TEST= OK RDRL=OK VISUAL= WAS SENT ON 12-29-09. INS/ CFR=OK . REPAIR # 1-800-542-3969. CATHY. COMMENTS ON 12-22-09 TCI=12-22-09 TUESDAT AM, . MARK FROM PENSACLOA WAS HERE. WE COULD NOT OPEN INNER TANK SUMP PLASTIC LIDS EVEN TRYING HAMMER AND CRO BARS ETC FOR ONE HOUR.FINALLY GOT OPENED, BUT HAD LOT OF TROUBLE CLOSING THEM. BOTH DISPENSER LINER LOOKED DRY. THERE WERE 42 FUEL ALARM ON THEIR INVENTORY PRINT OUT. NEED INF FOR THOSE INCIDENTS. TODAT THERE WAS ALSO FUEL ALARM ON L5=REGULAR STP SUMP AND L6 =PREMIUM STP SENSOR. IN ADDITION THERE WAS L3=PREMIUM PRODUCT TANK ANNULARSPACE FUEL ALARM WAS SEEN ON ONE PRINTOUT.(IN AUGUST) NO LIQUID STATUS PRINT OUT WERE AVAILABLE FOR INSPECTION.RECEIVED THEM LATTER ON 12-29-09 SPILL BUCKETS HAD PLENTY OF WATER, WATER WAS REMOVED, SECONDARY SPACE WAS CHECKED FOR SPILL BUCKETS, WAS OK. I CALLED CALLED FRAN,SHE SENT ILLD TEST, ATG OP TEST, INS, CFR ETC VIOLATIONS: REGULAR AND PREMIUM STP¿s HAVE LITTLE LESS THAN ONE FOOT OF LIQUID WITH SHEEN IN THEM.THEY NEEDED TO BE EMPTY AND RE-INSPECTION WOULD BE DONE. NEED INF FOR FUEL ALARMS FOR STP¿s AND FOR PREMIUM TANK¿S ANNULAR SPACE FUEL ALARM.WILL NEED INVESTIGATION RESULTS IN TWO WEEKS
12/22/2009 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
Comments:
Comment Date: 04/09/2010 User: KHAN_MR_1
Description: Received on 4-7-10 by e.mail from Linda pearece who got it from heather gimore dated 4-2-10. Water was removed FROM REGULAR AND PREMIUN TANK SUMPS per Eagle SWS on 1-19-2010 invoice.This clears the violation # 1115
06/01/2009 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/01/2009
Activity Closed Date: 06/02/2009 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 06/01/2009 User: KHAN_MR_1
Description: 2009-1-6 RK CALLED CHARLES TO MAKE SURE VIOLATION WAS CORRECTED. TCR WAS DONE,PAINT AND CROSSES WERE COMPLETED.VIOLATION # 1032 CLEARED.
05/14/2009 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1032
Rule: 62-761.500(5)(a)
Comments: Does not apply to aviation fuels, which have a different color scheme (see API Bulletin 1542 which is not a reference standard). Fillbox covers are to be labeled using one of the following methods: a. Painting or placing a decal on top of the cover and on the rim of the fillbox. b. Attaching a tag to the fill pipe adapter. c. Screwing a tag onto the fillbox rim. d. Fitting a plastic or fiberglass insert inside the rim of the fillbox. Refer to the color coded chart included in the API 1637 Reference Standard.
05/14/2009 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
05/13/2009 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 05/13/2009
Activity Closed Date: 05/14/2009 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 05/14/2009 User: KHAN_MR_1
Description: 2009-5-13.REINSPECTION WAS CONDUCTED TO CHECK THE SPILL BUCKET'S SECONDARY CONTAINMENT .FRAN HAS SENT DOCUMENTS ALSO (SCANNED) SPILL BUCKETS HAVE WATER IN THEM, SO I DID NOT OPEN SECONDARY CONTAINMENT BOLT TO AVOID WATER TO FILL THE SECONDARY CONTAINMENT AGAIN. THE LIDS WILL NEED CROSSES ALS0.I AM SENDING E.MAIL TO FRAN ABOUT ITTODAY.(SENT) NOW THEY HAVE A NEW VIOLATION # 1032
04/15/2009 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
04/15/2009 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
04/15/2009 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/15/2009
Activity Closed Date: 04/15/2009 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 04/15/2009 User: KHAN_MR_1
Description: 2009-4-15 TCR WAS OPENED, LES LEVI CAME FROM PENSACOLA TODAY. THE FOLLLOWING TASKS WERE DONE 1.HOSES ON 2 AND 3 DISPENSERS WERE CHANGED,# 1 HOSE WAS CHANGED YESTERDAY. 2.LIQUID FROM PREMIUM AND MID GRADE STP WAS TAKEN OUT. 3.BLUE SPILL BUCKET SECONDARY WAS ACCESSED. ----------------------- 1.ALARM ON #4 STP SENSORS IS STILL PRESENT.EVEN THOUGH WATRE WAS TAKEN OUT.BUT # L6 ALARM WAS CLEARED AS WATER WAS TAKEN OUT.I THINK # L4 SENSOR IS BAD. THEY WILL REPLACE IT AND WE WILL CHECK THE ATG PRINT AFTER THAT. 2.SECONDARY SPACE STILL HAVE WATER IN ALL DW SPILL BUCKETS. ------------------------------------------------------------- NOTE:STEEL LIDS AND INNER LIDS WERE DIFFICULT TO OPEN .ONE NEEDS PROPER TOOLS TO OPEN NUTS AND HAMMER ETC.
04/01/2009 Comment Khan, Muhammad Rafique
Description: IN 4-2008 THEY UPGRADEDTHE TANKS TO DOUBLE WALLED MY INSTALLING PARABEAM
04/01/2009 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 04/01/2009
04/01/2009 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
03/31/2009 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
03/31/2009 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
03/30/2009 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/30/2009
Activity Closed Date: 04/01/2009 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 03/30/2009 User: KHAN_MR_1
Description: TCI=3-31-04 with ted from us tank alliance.cloudy 55 degrees windy(INSPECTION WAS OPENED A DAY EARLY.) last year 0n 4-17-08-they modified their tanks to dw by utilising parabeam. 3- Tanks.unknown manufacturer(now DW with parabeam) Release detection= veeder root-TLS 350 EQ#197 Overfill protection = ball check valves. Piping= SMITH FIBER GLASS EQ=252.also ameron dualoy 3000 eq # 291 4 dispenser sump=dry,,bravo white eq # 444 Stp have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631 3 DW spill buckets=EMCO EQ-524 -------------------------- ATG PRINT OUTS =MAY 2008 TO JAN 2009 ATG OP TEST=10/21/2008 DUE=10/21/2009 ILLD TEST=10/21/2008 DUE=10/21/2009 INS=OK RDRL=OK VISUAL=OK CFR=OK SIR=OK ----------- LINE TEST WAS DONE ON 10/21/2008 BUT NOT REQUIRED DW PIPING. violations: 1.need access to =regular stp,and secondary containment space on plus product spill bucket.(blue) couldnt be opened by us tank alliance inspector Ted. 2.premium stp and plus product stp were full of water.Also secondary space on regular and pemium spill bucket were full. 3.regulr product hoses on # 1,#2 and # 3 dispenser needed to be replaced. note=inner plastic red lid will not be properly put back on premium stp after stuggling long time by ted. ---------------------------------------------------------------------------------------------------------- THERE WERE TWO ALARM ON ATG PRINTSOUTS DATED MAY2,2008 AND OCT 21, 2008.I EMALED FRAN, SHE REPLIED THAT THEY WERE DUE TO TESTS THEY DID. REPAIR # 1-800-542-3969. CATHY. -----------------------
Comments:
Comment Date: 04/01/2009 User: KHAN_MR_1
Description: 2009-4-1.we do not have any information as equipment list they installed on parabeam, i called to find the information from Tim Fish of guardian this morning, he said he is in naples today and cant access the information also they let the people go who installed the system.he will send me information next week.. ---------- this visit was intended to be re-inspection, but since not every violation was completely resolved it was made as a site visit.
Comments:
Comment Date: 04/14/2009 User: KHAN_MR_1
Description: John from Circkle K visited from Pensacola. For a reinspection. Regular stp was accessed, but plus Tankstp was still full of water, it rained last night. Plus spill bucket secondary still couldn¿t be accessed, Jhn is going to change one hose on dispenser # 1 only at this time,other two would be done latter. ----------- john told me the # for les levi=850-777-9901 charles is the manager 850-233-1788
03/30/2009 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/30/2009
Activity Closed Date: 04/01/2009 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 03/30/2009 User: KHAN_MR_1
Description: TCI=3-31-04 with ted from us tank alliance.cloudy 55 degrees windy(INSPECTION WAS OPENED A DAY EARLY.) last year 0n 4-17-08-they modified their tanks to dw by utilising parabeam. 3- Tanks.unknown manufacturer(now DW with parabeam) Release detection= veeder root-TLS 350 EQ#197 Overfill protection = ball check valves. Piping= SMITH FIBER GLASS EQ=252.also ameron dualoy 3000 eq # 291 4 dispenser sump=dry,,bravo white eq # 444 Stp have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631 3 DW spill buckets=EMCO EQ-524 -------------------------- ATG PRINT OUTS =MAY 2008 TO JAN 2009 ATG OP TEST=10/21/2008 DUE=10/21/2009 ILLD TEST=10/21/2008 DUE=10/21/2009 INS=OK RDRL=OK VISUAL=OK CFR=OK SIR=OK ----------- LINE TEST WAS DONE ON 10/21/2008 BUT NOT REQUIRED DW PIPING. violations: 1.need access to =regular stp,and secondary containment space on plus product spill bucket.(blue) couldnt be opened by us tank alliance inspector Ted. 2.premium stp and plus product stp were full of water.Also secondary space on regular and pemium spill bucket were full. 3.regulr product hoses on # 1,#2 and # 3 dispenser needed to be replaced. note=inner plastic red lid will not be properly put back on premium stp after stuggling long time by ted. ---------------------------------------------------------------------------------------------------------- THERE WERE TWO ALARM ON ATG PRINTSOUTS DATED MAY2,2008 AND OCT 21, 2008.I EMALED FRAN, SHE REPLIED THAT THEY WERE DUE TO TESTS THEY DID. REPAIR # 1-800-542-3969. CATHY. -----------------------
Comments:
Comment Date: 04/01/2009 User: KHAN_MR_1
Description: 2009-4-1.we do not have any information as equipment list they installed on parabeam, i called to find the information from Tim Fish of guardian this morning, he said he is in naples today and cant access the information also they let the people go who installed the system.he will send me information next week.. ---------- this visit was intended to be re-inspection, but since not every violation was completely resolved it was made as a site visit.
Comments:
Comment Date: 04/14/2009 User: KHAN_MR_1
Description: John from Circkle K visited from Pensacola. For a reinspection. Regular stp was accessed, but plus Tankstp was still full of water, it rained last night. Plus spill bucket secondary still couldn¿t be accessed, Jhn is going to change one hose on dispenser # 1 only at this time,other two would be done latter. ----------- john told me the # for les levi=850-777-9901 charles is the manager 850-233-1788
03/30/2009 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/30/2009
Activity Closed Date: 04/01/2009 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 03/30/2009 User: KHAN_MR_1
Description: TCI=3-31-04 with ted from us tank alliance.cloudy 55 degrees windy(INSPECTION WAS OPENED A DAY EARLY.) last year 0n 4-17-08-they modified their tanks to dw by utilising parabeam. 3- Tanks.unknown manufacturer(now DW with parabeam) Release detection= veeder root-TLS 350 EQ#197 Overfill protection = ball check valves. Piping= SMITH FIBER GLASS EQ=252.also ameron dualoy 3000 eq # 291 4 dispenser sump=dry,,bravo white eq # 444 Stp have heavy outer steel lids and inner plastic lids.Advanced Containment, L.L.C. eq # 631 3 DW spill buckets=EMCO EQ-524 -------------------------- ATG PRINT OUTS =MAY 2008 TO JAN 2009 ATG OP TEST=10/21/2008 DUE=10/21/2009 ILLD TEST=10/21/2008 DUE=10/21/2009 INS=OK RDRL=OK VISUAL=OK CFR=OK SIR=OK ----------- LINE TEST WAS DONE ON 10/21/2008 BUT NOT REQUIRED DW PIPING. violations: 1.need access to =regular stp,and secondary containment space on plus product spill bucket.(blue) couldnt be opened by us tank alliance inspector Ted. 2.premium stp and plus product stp were full of water.Also secondary space on regular and pemium spill bucket were full. 3.regulr product hoses on # 1,#2 and # 3 dispenser needed to be replaced. note=inner plastic red lid will not be properly put back on premium stp after stuggling long time by ted. ---------------------------------------------------------------------------------------------------------- THERE WERE TWO ALARM ON ATG PRINTSOUTS DATED MAY2,2008 AND OCT 21, 2008.I EMALED FRAN, SHE REPLIED THAT THEY WERE DUE TO TESTS THEY DID. REPAIR # 1-800-542-3969. CATHY. -----------------------
Comments:
Comment Date: 04/01/2009 User: KHAN_MR_1
Description: 2009-4-1.we do not have any information as equipment list they installed on parabeam, i called to find the information from Tim Fish of guardian this morning, he said he is in naples today and cant access the information also they let the people go who installed the system.he will send me information next week.. ---------- this visit was intended to be re-inspection, but since not every violation was completely resolved it was made as a site visit.
Comments:
Comment Date: 04/14/2009 User: KHAN_MR_1
Description: John from Circkle K visited from Pensacola. For a reinspection. Regular stp was accessed, but plus Tankstp was still full of water, it rained last night. Plus spill bucket secondary still couldn¿t be accessed, Jhn is going to change one hose on dispenser # 1 only at this time,other two would be done latter. ----------- john told me the # for les levi=850-777-9901 charles is the manager 850-233-1788
01/06/2009 Record Document Activity Brazile, David
Activity Status: Closed
Contact Name: Fax Activity Closed Date: 01/06/2009
09/30/2008 Record Document Activity Brazile, David
Activity Status: Closed
Contact Name: E-Mail Activity Closed Date: 09/30/2008
09/30/2008 Record Document Activity Brazile, David
Activity Status: Closed
Contact Name: Mail Activity Closed Date: 09/30/2008
05/28/2008 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: fran/by e.mail attachment Activity Closed Date: 03/30/2009
Comments:
Comment Date: 05/28/2008 User: KHAN_MR_1
Description: 5-28-08 they sent water record reading for 2006 violation.this will clear 2006 violation. it was sent by fran via e.mail attachment to rk.
05/27/2008 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: FRANCONI Activity Closed Date: 03/30/2009
Comments:
Comment Date: 05/27/2008 User: KHAN_MR_1
Description: 5-27-08, RECEIVED VISUAL CHECKS FROM JAN 07 TO DEC 2007. WAITING FOR WATER CHECK RECORD TO REMOVE THE VIOLATION.
04/11/2008 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/11/2008
Activity Closed Date: 06/18/2008 Activity Closed By: BRAZILE_DO_1
Comments:
Comment Date: 04/11/2008 User: BRAZILE_DO_1
Description: 2008/04/11 - Begin Installation upgrade of USTs with the Phoenix Containment System
Comments:
Comment Date: 04/29/2008 User: KHAN_MR_1
Description: 2008-4-17 4-17-08-TANKTEC-PARABEAM INSTALLATION. RK VISITED THERE IN AFTERNOON. THE PROCESS.They pumped out the product from the tank,earated it with ventura,cut a hole in the tank.a man was sent down to cleanout the sludge. then a manway was installedof fiberglass.tank was inspected again,integrity was checked,deflection reading was taken for hardness of interior of tank. after sand blast barcol reading was taken.fiberglass resin coating was applied,parabeam was applied,then another coating of f/g was applied. was inspected,sanded,then appoxy coating was applied,work was checked and pressurised to 3 psi for i/s check.
Comments:
Comment Date: 04/29/2008 User: KHAN_MR_1
Description: 2008-4-17 4-23-08 GUARDIAN-JODY. RK VISITED THE SITE TO CHECK PRIMARY PIPING TEST(50 PSI),SECONDARY TEST(5PSI) AND HYDROTEST.ALL THESE TESTS WERE STARTED YESTERDAY. ALL TEST WERE OK.
04/11/2008 Emergency Preparedness Information Activity Brazile, David
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 04/11/2008
04/11/2008 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/11/2008
Activity Closed Date: 06/18/2008 Activity Closed By: BRAZILE_DO_1
Comments:
Comment Date: 04/11/2008 User: BRAZILE_DO_1
Description: 2008/04/11 - Begin Installation upgrade of USTs with the Phoenix Containment System
Comments:
Comment Date: 04/29/2008 User: KHAN_MR_1
Description: 2008-4-17 4-17-08-TANKTEC-PARABEAM INSTALLATION. RK VISITED THERE IN AFTERNOON. THE PROCESS.They pumped out the product from the tank,earated it with ventura,cut a hole in the tank.a man was sent down to cleanout the sludge. then a manway was installedof fiberglass.tank was inspected again,integrity was checked,deflection reading was taken for hardness of interior of tank. after sand blast barcol reading was taken.fiberglass resin coating was applied,parabeam was applied,then another coating of f/g was applied. was inspected,sanded,then appoxy coating was applied,work was checked and pressurised to 3 psi for i/s check.
Comments:
Comment Date: 04/29/2008 User: KHAN_MR_1
Description: 2008-4-17 4-23-08 GUARDIAN-JODY. RK VISITED THE SITE TO CHECK PRIMARY PIPING TEST(50 PSI),SECONDARY TEST(5PSI) AND HYDROTEST.ALL THESE TESTS WERE STARTED YESTERDAY. ALL TEST WERE OK.
04/11/2008 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/11/2008
Activity Closed Date: 06/18/2008 Activity Closed By: BRAZILE_DO_1
Comments:
Comment Date: 04/11/2008 User: BRAZILE_DO_1
Description: 2008/04/11 - Begin Installation upgrade of USTs with the Phoenix Containment System
Comments:
Comment Date: 04/29/2008 User: KHAN_MR_1
Description: 2008-4-17 4-17-08-TANKTEC-PARABEAM INSTALLATION. RK VISITED THERE IN AFTERNOON. THE PROCESS.They pumped out the product from the tank,earated it with ventura,cut a hole in the tank.a man was sent down to cleanout the sludge. then a manway was installedof fiberglass.tank was inspected again,integrity was checked,deflection reading was taken for hardness of interior of tank. after sand blast barcol reading was taken.fiberglass resin coating was applied,parabeam was applied,then another coating of f/g was applied. was inspected,sanded,then appoxy coating was applied,work was checked and pressurised to 3 psi for i/s check.
Comments:
Comment Date: 04/29/2008 User: KHAN_MR_1
Description: 2008-4-17 4-23-08 GUARDIAN-JODY. RK VISITED THE SITE TO CHECK PRIMARY PIPING TEST(50 PSI),SECONDARY TEST(5PSI) AND HYDROTEST.ALL THESE TESTS WERE STARTED YESTERDAY. ALL TEST WERE OK.
03/17/2008 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
03/03/2008 Attachment Khan, Muhammad Rafique
02/05/2008 Attachment Khan, Muhammad Rafique
02/05/2008 Attachment Khan, Muhammad Rafique
02/04/2008 Comment Khan, Muhammad Rafique
Description: jason was rep for copmpany during inspection. 2008/05/02 - Final Install Inspection
02/04/2008 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
02/04/2008 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
02/04/2008 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1058
Rule: 62-761.600(1)(a)1.
Comments: Mark this as out of compliance if the release detection method is not able to register or detect a new release. If you feel that the release detection system has lost its ability to detect a new release, document why in the inspection report. Examples include: a. An automatic tank gauge system already in alarm mode will not be able to detect a new release; b. sumps with water/product may impair detection abilities; c. monitoring wells at contaminated sites may also have impaired ability to detect new releases. See .640(2)(c)2. for further guidance on using contaminated monitoring wells for release detection.
01/29/2008 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/29/2008
Activity Closed Date: 02/05/2008 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 05/27/2008 User: KHAN_MR_1
Description: I SPOKE TO FRAN, SHE SENT ME PAPERWORK, i.e. visual,tank test,bucket test,line testatg test,illd tests etc,were done on5-2-08 i did not take document violation,because she still needs to send water record.
Comments:
Comment Date: 02/04/2008 User: KHAN_MR_1
Description: tci=1-29-08 with jason meredith-614-949-3055 release detection= sir=veeder root-ustman ver 95.2 b eq=458. overfill protection = ball check valves. 3-single walled tanks.unknown piping=unknown f/g single wall.also ameron dualoy 3000 eq #291 4 dispenser sump=dry,bravo white eq # 444 stp have heavy outer steel lids and inner plastic lids.unknown fiberglass brand. 3 spill buckets=holding line test passed for 3 lines on12-4-07 illd test passed on 12-4-07 tank test overdue no weekly water product check record and monthly visual are available for whole year. -------------------------------------- dispenser key=gbco blue (midgrade) product stp and blue product spill bucket were full of water,other two stp's were dry. after jason arrived, since all paperwork was not available, i called fran and left message for her to send paperwork for four facilities.
Comments:
Comment Date: 05/27/2008 User: KHAN_MR_1
Description: morty houser came to office, he gave me tank diagram ang sort of equipment list. i gave him blank contractor for, he will bring it back, also he will give us site diagram.
01/29/2008 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/29/2008
Activity Closed Date: 02/05/2008 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 05/27/2008 User: KHAN_MR_1
Description: I SPOKE TO FRAN, SHE SENT ME PAPERWORK, i.e. visual,tank test,bucket test,line testatg test,illd tests etc,were done on5-2-08 i did not take document violation,because she still needs to send water record.
Comments:
Comment Date: 02/04/2008 User: KHAN_MR_1
Description: tci=1-29-08 with jason meredith-614-949-3055 release detection= sir=veeder root-ustman ver 95.2 b eq=458. overfill protection = ball check valves. 3-single walled tanks.unknown piping=unknown f/g single wall.also ameron dualoy 3000 eq #291 4 dispenser sump=dry,bravo white eq # 444 stp have heavy outer steel lids and inner plastic lids.unknown fiberglass brand. 3 spill buckets=holding line test passed for 3 lines on12-4-07 illd test passed on 12-4-07 tank test overdue no weekly water product check record and monthly visual are available for whole year. -------------------------------------- dispenser key=gbco blue (midgrade) product stp and blue product spill bucket were full of water,other two stp's were dry. after jason arrived, since all paperwork was not available, i called fran and left message for her to send paperwork for four facilities.
Comments:
Comment Date: 05/27/2008 User: KHAN_MR_1
Description: morty houser came to office, he gave me tank diagram ang sort of equipment list. i gave him blank contractor for, he will bring it back, also he will give us site diagram.
01/29/2008 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/29/2008
Activity Closed Date: 02/05/2008 Activity Closed By: KHAN_MR_1
Comments:
Comment Date: 05/27/2008 User: KHAN_MR_1
Description: I SPOKE TO FRAN, SHE SENT ME PAPERWORK, i.e. visual,tank test,bucket test,line testatg test,illd tests etc,were done on5-2-08 i did not take document violation,because she still needs to send water record.
Comments:
Comment Date: 02/04/2008 User: KHAN_MR_1
Description: tci=1-29-08 with jason meredith-614-949-3055 release detection= sir=veeder root-ustman ver 95.2 b eq=458. overfill protection = ball check valves. 3-single walled tanks.unknown piping=unknown f/g single wall.also ameron dualoy 3000 eq #291 4 dispenser sump=dry,bravo white eq # 444 stp have heavy outer steel lids and inner plastic lids.unknown fiberglass brand. 3 spill buckets=holding line test passed for 3 lines on12-4-07 illd test passed on 12-4-07 tank test overdue no weekly water product check record and monthly visual are available for whole year. -------------------------------------- dispenser key=gbco blue (midgrade) product stp and blue product spill bucket were full of water,other two stp's were dry. after jason arrived, since all paperwork was not available, i called fran and left message for her to send paperwork for four facilities.
Comments:
Comment Date: 05/27/2008 User: KHAN_MR_1
Description: morty houser came to office, he gave me tank diagram ang sort of equipment list. i gave him blank contractor for, he will bring it back, also he will give us site diagram.
06/05/2007 Phone Conversation Activity Khan, Muhammad Rafique
Activity Status: Closed
Phone Number: 813-910-6884 Activity Closed Date: 06/05/2007
Subject: RK talked to her about the open violation, she took my e.mail address and will talk to her marketing manager and will contact me
02/28/2007 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/28/2007
Activity Closed Date: 06/15/2010 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 06/15/2010
Comment: Finished
Comments:
Comment Date: 02/28/2007 User: BRAZILE_DO_1
Description: Jim Blankenship -UST Tanks-727-919-6300 Fran Franconi -UST Tanks -1-813-910-6884 Store Manager- Charles Altman -850-233-1788
02/13/2007 Emergency Preparedness Information Activity Khan, Muhammad Rafique
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/13/2007
12/22/2006 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
12/22/2006 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 12/22/2006
Comment: Sent on Fri Dec 22 00:00:00 EST 2006
Attachments:
Attachment Date: 12/22/2006 User: KHAN_MR_1
Description: NCL Report
View Attachment
12/21/2006 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
12/20/2006 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 12/20/2006
Activity Closed Date: 12/22/2006 Activity Closed By: KHAN_MR_1
09/21/2006 Emergency Preparedness Information Activity Brazile, David
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/21/2006
01/24/2006 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
01/23/2006 Violation Closed Unknown, User
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
Comments:
Comment Date: 07/23/2019 User: HERNANDEZ_N
Description: Equipment list: Tank - double-walled, UL2085 Armor Cast, EQ-754) Spill containment - tight fill, single-walled remote spill containment box located next to each tank. Overfill protection - flow shut-off valve, a Morrison Clock gauge (not visible from the fill port), and a Greenleaf Solar Gauge (Model EFG-8000, EQ-713) with audible alarm. Release detection - Continuous electronic monitoring of tank interstice space via Veeder-Root TLS 350 (EQ-596)
12/05/2005 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
11/29/2005 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.700(1)(a)1
Comments:
Comment Date: 02/27/2009 User: MURLEY_A_1
Description: Highland double wall Titan tanks, EQ#674. Ameron Dualoy 3000LCX, EQ#291. OPW fiberglass dispenser liners, EQ-368. OPW Flexworks fiberglass STP sumps, EQ-368. Emco Wheaton A 1004-210 SX, double walled, spill containment buckets, EQ- 594. OPW 61SO overfill prevention valves, EQ-223. Mechanical in line leak detectors Vaporless Model 98 LD-2000, EQ-329.
Comments:
Comment Date: 03/24/2017 User: YOUNG_K_1
Description: Release Detection: - Visual inspection of dispensers/liners, spill containment buckets and STP sumps. - Manual monitoring of tank interstices.
11/29/2005 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
11/29/2005 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.700(1)(c)1
Comments:
Comment Date: 02/23/2012 User: PUCCI_SA_1
Description: Generac double-wall steel belly tank with built-in spill containment (EQ-566)
Comments:
Comment Date: 08/11/2022 User: LEVERETTE_VK_1
Description: Removed Model #6967170800 Serial #2090720
11/29/2005 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.700(1)(c)1
Comments:
Comment Date: 02/23/2012 User: PUCCI_SA_1
Description: Generac double-wall steel belly tank with built-in spill containment (EQ-566)
Comments:
Comment Date: 08/11/2022 User: LEVERETTE_VK_1
Description: Removed Model #6967170800 Serial #2090720
11/29/2005 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.510(1)(b)3
Comments:
Comment Date: 05/13/2011 User: REID_MT_1
Description: EQ-497
11/29/2005 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.700(1)(a)1
Comments:
Comment Date: 02/27/2009 User: MURLEY_A_1
Description: Highland double wall Titan tanks, EQ#674. Ameron Dualoy 3000LCX, EQ#291. OPW fiberglass dispenser liners, EQ-368. OPW Flexworks fiberglass STP sumps, EQ-368. Emco Wheaton A 1004-210 SX, double walled, spill containment buckets, EQ- 594. OPW 61SO overfill prevention valves, EQ-223. Mechanical in line leak detectors Vaporless Model 98 LD-2000, EQ-329.
Comments:
Comment Date: 03/24/2017 User: YOUNG_K_1
Description: Release Detection: - Visual inspection of dispensers/liners, spill containment buckets and STP sumps. - Manual monitoring of tank interstices.
11/28/2005 Violation Closed Unknown, User
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
Comments:
Comment Date: 02/27/2009 User: MURLEY_A_1
Description: Highland double wall Titan tanks, EQ#674. Ameron Dualoy 3000LCX, EQ#291. OPW fiberglass dispenser liners, EQ-368. OPW Flexworks fiberglass STP sumps, EQ-368. Emco Wheaton A 1004-210 SX, double walled, spill containment buckets, EQ- 594. OPW 61SO overfill prevention valves, EQ-223. Mechanical in line leak detectors Vaporless Model 98 LD-2000, EQ-329.
Comments:
Comment Date: 03/24/2017 User: YOUNG_K_1
Description: Release Detection: - Visual inspection of dispensers/liners, spill containment buckets and STP sumps. - Manual monitoring of tank interstices.
11/28/2005 Violation Closed Unknown, User
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
Comments:
Comment Date: 02/27/2009 User: MURLEY_A_1
Description: Highland double wall Titan tanks, EQ#674. Ameron Dualoy 3000LCX, EQ#291. OPW fiberglass dispenser liners, EQ-368. OPW Flexworks fiberglass STP sumps, EQ-368. Emco Wheaton A 1004-210 SX, double walled, spill containment buckets, EQ- 594. OPW 61SO overfill prevention valves, EQ-223. Mechanical in line leak detectors Vaporless Model 98 LD-2000, EQ-329.
Comments:
Comment Date: 03/24/2017 User: YOUNG_K_1
Description: Release Detection: - Visual inspection of dispensers/liners, spill containment buckets and STP sumps. - Manual monitoring of tank interstices.
03/07/2005 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
03/02/2005 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
12/30/2004 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.700(1)(a)1
12/30/2004 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: PIPING: UNKNOWN FIBERGLASS
12/30/2004 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.710(2)
12/30/2004 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 761.700(1)(c)1
08/04/2004 Legacy Activity Pinkovsky, Dennis D.
Activity Name: DISCHARGE SUSPECTED - NO RELEASE FOUND Activity Status: Closed
Completion Notes: MAINTENANCE RECORDS GIVE NO INDICATION OF FREE PRODUCT IN SUMPS.
07/27/2004 Legacy Activity Pinkovsky, Dennis D.
Activity Name: INCIDENT REPORT FORM RECEIVED Activity Status: Closed
Completion Notes: INF FOR PLUS AND PREMIUM TANK SUMPS FAILING A BREACH OF INTEGRITY TEST.
04/27/2004 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: PIPING: UNKNOWN FIBERGLASS
03/31/2004 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 510(1)(b)3
03/31/2004 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: PIPING: UNKNOWN FIBERGLASS
12/30/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 510(1)(b)3
12/30/2003 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: PIPING: FIBERGLASS (REDDISH BROWN IN COLOR)
12/30/2003 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 700(1)(c)1
01/02/2003 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
12/18/2002 Violation Closed Godwin, Christine
Significance: SNC-B Status: Closed
Rule: 400(3)
12/18/2002 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
12/18/2002 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 710(2)
12/12/2001 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/22/2001 Legacy Activity Godwin, Christine
Activity Name: TANK CLOSURE INSPECTION Activity Status: Closed
06/22/2001 Legacy Activity Godwin, Christine
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
02/12/2001 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
12/20/2000 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
12/14/2000 Violation Closed Godwin, Christine
Significance: SNC-B Status: Closed
Rule: 600(1)(d)
12/14/2000 Legacy Activity Godwin, Christine
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
12/14/2000 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 710(2)
12/14/2000 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 640(3)(d)
12/14/2000 Violation Closed Godwin, Christine
Significance: SNC-B Status: Closed
Rule: 610(4)(a)2
12/14/2000 Violation Closed Godwin, Christine
Significance: Minor Status: Closed
Rule: 640(3)(c)3
03/20/2000 Legacy Activity Godwin, Christine
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
01/24/2000 Legacy Activity Godwin, Christine
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
12/23/1999 Violation Closed Pinkovsky, Dennis D.
Significance: SNC-B Status: Closed
Rule: 400(3)
Comments:
Comment Date: 11/03/2014 User: PERRY_JF_2
Description: Store manager is Patrick Lowry, store phone is 386-760-6498
12/23/1999 Violation Closed Pinkovsky, Dennis D.
Significance: Minor Status: Closed
Rule: 510(1)(b)3
12/23/1999 Violation Closed Pinkovsky, Dennis D.
Significance: SNC-B Status: Closed
Rule: 610(4)(a)2
Comments:
Comment Date: 09/12/2006 User: HUTCHERSON_P
Description: REGULAR UNLEADED GAS TANK: Double-walled. Fiberglass (XERXES - EQ-537). SUMP: OPW-PISCES (EQ-368). In-line leak detector attached. Peak Tubes. D-LINERS: OPW-PISCES (EQ-368). Shear valves mounted. FILLS: OPW ( EQ-224)-Removed and Franklin Steel SW Steel (EQ-757) installed. PIPING: Double-walled flex (APT- EQ-569). INTERSTICE: Manual monitoring using clear plastic tubing.
12/23/1999 Violation Closed Pinkovsky, Dennis D.
Significance: Minor Status: Closed
Rule: 640(3)(d)
12/23/1999 Violation Closed Pinkovsky, Dennis D.
Significance: SNC-B Status: Closed
Rule: 600(2)(d)
Comments:
Comment Date: 01/28/2015 User: COLSON_NJ_1
Description: EZ Gauges
Comments:
Comment Date: 09/12/2006 User: HUTCHERSON_P
Description: VEHICULAR DIESEL TANK: Double-walled. Fiberglass (XERXES - EQ-537). SUMP: OPW-PISCES (EQ-368). In-line leak detector attached. Peak Tubes. D-LINERS: OPW-PISCES (EQ-368). Shear valves mounted. FILLS: OPW ( EQ-224)-Removed and Franklin Steel SW Steel (EQ-757) installed. PIPING: Double-walled flex (APT- EQ-569). INTERSTICE: Manual monitoring using clear plastic tubing.
12/23/1999 Violation Closed Pinkovsky, Dennis D.
Significance: SNC-B Status: Closed
Rule: 600(2)(d)
Comments:
Comment Date: 01/28/2015 User: COLSON_NJ_1
Description: EZ Gauges
Comments:
Comment Date: 09/12/2006 User: HUTCHERSON_P
Description: VEHICULAR DIESEL TANK: Double-walled. Fiberglass (XERXES - EQ-537). SUMP: OPW-PISCES (EQ-368). In-line leak detector attached. Peak Tubes. D-LINERS: OPW-PISCES (EQ-368). Shear valves mounted. FILLS: OPW ( EQ-224)-Removed and Franklin Steel SW Steel (EQ-757) installed. PIPING: Double-walled flex (APT- EQ-569). INTERSTICE: Manual monitoring using clear plastic tubing.
12/23/1999 Violation Closed Pinkovsky, Dennis D.
Significance: Minor Status: Closed
Rule: 700(1)(a)1
12/23/1999 Violation Closed Pinkovsky, Dennis D.
Significance: Minor Status: Closed
Rule: 700(1)(c)1
12/23/1999 Legacy Activity Pinkovsky, Dennis D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed