DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/27/2025        Last Data Refresh: 04/26/2025        Report Generated from DOPPLER
 
Facility ID: 8841332
Facility Name: AURORA MARATHON
 
03/19/2024 Violation Open Grantham, Jeffrey W
Significance: Minor Status: Open
Criteria ID: 6003
Rule: 62-761.400(1)(b), 62-761.400(2), 62-761.400(2)(a), 62-761.400(3), 62-761.400(3)(a), 62-761.400(3)(b), 62-761.400(3)(c)
03/19/2024 Editable Letter Activity Grantham, Jeffrey W
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/19/2024
Comment: Finished
Attachments:
Attachment Date: 03/19/2024 User: GRANTHAM_JW_1
Description: 3/19/2024 compliance assistance offer
View Attachment
03/19/2024 Site Inspection Activity Closed Grantham, Jeffrey W
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 03/19/2024
Activity Closed Date: 03/19/2024 Activity Closed By: GRANTHAM_JW_1
Events:
Event Type: Activity has been finished Date: 03/19/2024
Comment: Finished
Comments:
Comment Date: 03/19/2024 User: GRANTHAM_JW_1
Description: No access provided to the tank. Store was closed. I attempted to contact the owner via phone and email with no success. Dispensers have been removed from the site. A copy of the tank inspection report will be emailed to the facility owner/operator upon completion. All the violations remain. Two new violations were added. The facility is currently under enforcement with the FDEP. The tank STP's appear to be cemented over. The tank needs to be registered as out of service or it needs to be removed.
03/19/2024 Violation Open Grantham, Jeffrey W
Significance: Minor Status: Open
Criteria ID: 6001
Rule: 62-761.100(3)
04/12/2023 Electronic Communication Activity Horvath, Kage
Activity Closed Date: 04/12/2023 Activity Status: Closed
Date: 04/12/2023
Recipient: MITCHPATEL1985@YAHOO.COM
Sender: Kage.Horvath@floridadep.gov
Subject: [PART 2] OUTSTANDING VIOLATIONS - AURORA MARATHON - FAC ID #8841332
Message: [OUTLINED LIST OF VIOLATIONS] Thank you kindly for your time and cooperation. I look forward to resolving this matter with you. Kindest Regards, Kage Horvath Environmental Specialist I Florida Department of Environmental Protection Central District - Orlando Kage.Horvath@FloridaDEP.gov Office: 407-897-4334
Events:
Event Type: Activity has been finished Date: 04/12/2023
Comment: Finished
04/12/2023 Electronic Communication Activity Horvath, Kage
Activity Closed Date: 04/12/2023 Activity Status: Closed
Date: 04/12/2023
Recipient: MITCHPATEL1985@YAHOO.COM
Sender: Kage.Horvath@floridadep.gov
Subject: [PART 1] OUTSTANDING VIOLATIONS - AURORA MARATHON - FAC ID #8841332
Message: This message is time-sensitive. Please respond at your earliest convenience. Good morning Mr. Patel, My name is Kage Horvath and I work with the Florida Department of Environmental Protection. I am reaching out regarding 1724 N HARBOR CITY BLVD. MELBOURNE, FL 32935, or Aurora Marathon, as it is listed in our system. There seems to be a long list of open violations regarding your Underground Storage Tank. Please refer to the list at the end of this message for further details. I would like to address the below-referenced violations with you and work to resolve them. Please respond at your earliest convenience to address the matter. Any details you can provide regarding the tank would be helpful. Please respond by Wednesday, April 19, 2023. If no response is received, the Department will pursue formal enforcement and that will result in fines and penalties against the facility. [CONTINUED]
Events:
Event Type: Activity has been finished Date: 04/12/2023
Comment: Finished
08/23/2022 Editable Letter Activity Dalton, Kyle
Activity Title: Warning Letter Activity Status: Closed
Events:
Event Type: Activity/Document has been approved Date: 10/04/2022
Comment: Approved by DANIEL K HALL: approved
Events:
Event Type: Activity has been finished Date: 10/10/2022
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 10/03/2022
Comment: Submitted for approval by: Kyle Dalton
Attachments:
Attachment Date: 10/03/2022 User: DALTON_K
Description: 8841332 Aurora Marathon: Warning Letter
View Attachment
08/10/2022 Electronic Communication Activity Dalton, Kyle
Activity Closed Date: 08/10/2022 Activity Status: Closed
Date: 08/10/2022
Recipient: MITCHPATEL1985@YAHOO.COM
Sender: Dalton, Kyle
Subject: Regulated Storage Tank Facility 8841332 AURORA MARATHON: Outstanding Non-Compliance
Message: See Attachment.
Events:
Event Type: Activity has been finished Date: 08/10/2022
Comment: Finished
06/06/2022 Enforcement Tracking Activity Useche, Viviana
Activity Status: Open
05/04/2022 Electronic Communication Activity Ulrich, Chris A.
Activity Closed Date: 05/04/2022 Activity Status: Closed
Date: 05/04/2022
Recipient: Viviana Useche
Sender: Chris Ulrich
Subject: 1Apr22 referral to Central District FDEP.
Message: Referral has been withdrawn as requested. Will attempt to re-submit.
Events:
Event Type: Activity has been finished Date: 05/04/2022
Comment: Finished
04/01/2022 Enforcement Referral Activity Ulrich, Chris A.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 06/06/2022
Events:
Event Type: Activity has been withdrawn from submission by the requestor Date: 05/05/2022
Comment: Withdrawn by Chris A. Ulrich: Re-attempting to direct enforcement referral to Viviana Useche, FDEP Central District.
Events:
Event Type: Activity has been submitted for approval Date: 05/05/2022
Comment: Submitted for approval by: Chris A. Ulrich: Re-attempting to direct this referral to FDEP Central District
Events:
Event Type: Activity has been submitted for approval Date: 04/01/2022
Comment: Submitted for approval by: Chris A. Ulrich: 1Apr22 facility referral
Events:
Event Type: Activity has been submitted for approval Date: 05/04/2022
Comment: Submitted for approval by: Chris A. Ulrich: Original 1Apr22 referral has been withdrawn as requested. Referral is now re-submitted.
Events:
Event Type: Activity has been withdrawn from submission by the requestor Date: 05/04/2022
Comment: Withdrawn by Chris A. Ulrich: Withdrawn as directed on 4May22. Will re-submit.
Events:
Event Type: Activity has been submitted for approval Date: 06/01/2022
Comment: Submitted for approval by: Chris A. Ulrich: File re-submitted to FDEP Central District for enforcement.
Events:
Event Type: Activity has been withdrawn from submission by the requestor Date: 06/01/2022
Comment: Withdrawn by Chris A. Ulrich: As instructed by FDEP central district.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 06/06/2022
Comment: Acknowledged and Assigned by Viviana Useche
Events:
Event Type: Activity has been finished Date: 06/06/2022
Comment: Finished
Events:
Event Type: Activity has been assigned Date: 06/06/2022
Comment: Assigned to Viviana Useche
Events:
Event Type: Activity/Document was accepted on this date Date: 06/06/2022
Comment: Accepted by Viviana Useche: Accepted
Comments:
Comment Date: 04/01/2022 User: ULRICH_CA_1
Description: On 17Feb22, FDEP Tallahassee sent an email entitled "Brevard Co Fuel Delivery Prohibition List". This facility was on that list. Facility is no longer a gas station, but a liquor store. The canopy and the two dispensers have been removed. During the last routine compliance inspection, it was noted that the tank contained petroleum contact water and the VeederRoot tank monitor was discovered turn off. On 17Mar22, by email, Brevard County Natural Resources was directed to refer this facility for enforcement.
Comments:
Comment Date: 04/01/2022 User: ULRICH_CA_1
Description: 1Apr22 facility referral
Attachments:
Attachment Date: 04/01/2022 User: ULRICH_CA_1
Description: 1Apr22 Memo
View Attachment
04/01/2022 Electronic Communication Activity Ulrich, Chris A.
Activity Closed Date: 04/01/2022 Activity Status: Closed
Date: 04/01/2022
Recipient: Chris Ulrich
Sender: Amanda Dorsett
Subject: 17Mar22 email stating that this facility should be referred to FDEP Central District.
Message: Email is attached. Heavily edited (it listed a few other facilities).
Events:
Event Type: Activity has been finished Date: 04/01/2022
Comment: Finished
04/01/2022 Electronic Communication Activity Ulrich, Chris A.
Activity Closed Date: 04/01/2022 Activity Status: Closed
Date: 04/01/2022
Recipient: Mitch Patel
Sender: Chris Ulrich
Subject: 23Mar22 email
Message: See attachment
Events:
Event Type: Activity has been finished Date: 04/01/2022
Comment: Finished
04/01/2022 Electronic Communication Activity Ulrich, Chris A.
Activity Closed Date: 04/01/2022 Activity Status: Closed
Date: 04/01/2022
Recipient: Mitch Patel
Sender: Chris Ulrich
Subject: email
Message: See attachment
Events:
Event Type: Activity has been finished Date: 04/01/2022
Comment: Finished
04/01/2022 Electronic Communication Activity Ulrich, Chris A.
Activity Closed Date: 04/01/2022 Activity Status: Closed
Date: 04/01/2022
Recipient: Mitch Patel
Sender: Chris Ulrich
Subject: Email
Message: See attachment
Events:
Event Type: Activity has been finished Date: 04/01/2022
Comment: Finished
04/01/2022 Enforcement Referral Activity Ulrich, Chris A.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 06/06/2022
Events:
Event Type: Activity has been withdrawn from submission by the requestor Date: 05/05/2022
Comment: Withdrawn by Chris A. Ulrich: Re-attempting to direct enforcement referral to Viviana Useche, FDEP Central District.
Events:
Event Type: Activity has been submitted for approval Date: 05/05/2022
Comment: Submitted for approval by: Chris A. Ulrich: Re-attempting to direct this referral to FDEP Central District
Events:
Event Type: Activity has been submitted for approval Date: 04/01/2022
Comment: Submitted for approval by: Chris A. Ulrich: 1Apr22 facility referral
Events:
Event Type: Activity has been submitted for approval Date: 05/04/2022
Comment: Submitted for approval by: Chris A. Ulrich: Original 1Apr22 referral has been withdrawn as requested. Referral is now re-submitted.
Events:
Event Type: Activity has been withdrawn from submission by the requestor Date: 05/04/2022
Comment: Withdrawn by Chris A. Ulrich: Withdrawn as directed on 4May22. Will re-submit.
Events:
Event Type: Activity has been submitted for approval Date: 06/01/2022
Comment: Submitted for approval by: Chris A. Ulrich: File re-submitted to FDEP Central District for enforcement.
Events:
Event Type: Activity has been withdrawn from submission by the requestor Date: 06/01/2022
Comment: Withdrawn by Chris A. Ulrich: As instructed by FDEP central district.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 06/06/2022
Comment: Acknowledged and Assigned by Viviana Useche
Events:
Event Type: Activity has been finished Date: 06/06/2022
Comment: Finished
Events:
Event Type: Activity has been assigned Date: 06/06/2022
Comment: Assigned to Viviana Useche
Events:
Event Type: Activity/Document was accepted on this date Date: 06/06/2022
Comment: Accepted by Viviana Useche: Accepted
Comments:
Comment Date: 04/01/2022 User: ULRICH_CA_1
Description: On 17Feb22, FDEP Tallahassee sent an email entitled "Brevard Co Fuel Delivery Prohibition List". This facility was on that list. Facility is no longer a gas station, but a liquor store. The canopy and the two dispensers have been removed. During the last routine compliance inspection, it was noted that the tank contained petroleum contact water and the VeederRoot tank monitor was discovered turn off. On 17Mar22, by email, Brevard County Natural Resources was directed to refer this facility for enforcement.
Comments:
Comment Date: 04/01/2022 User: ULRICH_CA_1
Description: 1Apr22 facility referral
Attachments:
Attachment Date: 04/01/2022 User: ULRICH_CA_1
Description: 1Apr22 Memo
View Attachment
09/03/2021 Violation Open Ulrich, Chris A.
Significance: SNC-B Status: Open
Criteria ID: 6060
Rule: 62-761.600(2), 62-761.600(2)(a), 62-761.600(2)(a)1, 62-761.600(2)(a)2, 62-761.600(2)(a)3, 62-761.600(2)(a)4, 62-761.600(2)(a)5, 62-761.600(2)(a)6, 62-761.600(2)(a)6.a, 62-761.600(2)(a)6.b, 62-761.600(2)(a)7, 62-761.600(2)(a)8
09/03/2021 Editable Letter Activity Ulrich, Chris A.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 10/05/2021
Comment: Finished
Attachments:
Attachment Date: 09/07/2021 User: ULRICH_CA_1
Description: 7 September 2021 Compliance Assistance Offer letter
View Attachment
09/03/2021 Phone Conversation Activity Ulrich, Chris A.
Call Type: Outgoing Activity Status: Closed
Phone Number: (321) 259-5554 Activity Closed Date: 10/05/2021
Subject: Left a voice mail stating I was calling to discuss the tank inspection I conducted last week. Left my name and my land line phone number.
Events:
Event Type: Activity has been finished Date: 10/05/2021
Comment: Finished
09/03/2021 Violation Closed Ulrich, Chris A.
Significance: Minor Status: Closed
Criteria ID: 6005
Rule: 62-761.400(4), 62-761.400(4)(a), 62-761.400(4)(b), 62-761.400(4)(c), 62-761.400(4)(d), 62-761.400(4)(e), 62-761.400(4)(f)
08/25/2021 Site Inspection Activity Closed Ulrich, Chris A.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 08/25/2021
Activity Closed Date: 09/03/2021 Activity Closed By: ULRICH_CA_1
Events:
Event Type: Activity has been finished Date: 09/03/2021
Comment: Finished
Comments:
Comment Date: 08/25/2021 User: ULRICH_CA_1
Description: Current registration placard - did not see current registration placard at the facility. According to FIRST, the registration fees haven't been paid since May, 2019. Upon arrival, the cashier had me speak on the phone with Mich Patel (owner/operator). I introduced myself and told him I was here to inspect the fuel tank. Mr. Patel told me he never received my notification letter (dated 11Aug21), which I add mailed to the store. I an email written in May, 2021 I had suggested that he could register the tank "out of service", but the tank had to be emptied. (email attached). The tank top is in disrepair. The middle sump lid (PUL) has broken and is marked off with two orange traffic and a couple cinder blocks. I looked in all sumps and fills I could access. Stuck both the diesel and premium (PUL) compartments - about four feet of product in the diesel and about two feet in the PUL. These readings are circumspect since neither the facility or I had a tank stick. The use of a tape measure is not very reliable. Irregardless, these compartments need to be emptied ASAP. Went to check the VeederRoot storage tank monitor. After moving several boxes of apple whisky, found the VeederRoot without power. It has been turned off. NO release detection at all. According to the last (2109) inspection: VeederRoot liquid status report lists 1 interstitial and 3 STP sump float sensors; 72 inches of product in the diesel compartment, 26 inches of premium gasoline and 12 inches of regular gasoline. A copy of the tank inspection report will be emailed to the facility owner/operator upon completion. All the 2019 violations remain. Two new violations were added. As designated in the contract between FDEP and Brevard County Natural Resources, this facility will be forwarded to Central District FDEP office for enforcement action.
06/26/2020 Record Document Activity Ulrich, Chris A.
Activity Status: Closed
Contact Name: And Ma Harsiddhi Activity Closed Date: 06/26/2020
Events:
Event Type: Activity has been finished Date: 06/26/2020
Comment: Finished
05/07/2019 Editable Letter Activity Ulrich, Chris A.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 05/07/2019
Comment: Finished
Attachments:
Attachment Date: 05/07/2019 User: ULRICH_CA_1
Description: 7May19 compliance assistance offer letter
View Attachment
05/02/2019 Violation Open Ulrich, Chris A.
Significance: SNC-B Status: Open
Criteria ID: 4059
Rule: 62-761.600(1)(d), 62-761.600(1)(e)
05/02/2019 Violation Open Ulrich, Chris A.
Significance: Minor Status: Open
Criteria ID: 4001
Rule: 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2., 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7)
05/02/2019 Violation Open Ulrich, Chris A.
Significance: Minor Status: Open
Criteria ID: 4067
Rule: 62-761.600(4)
05/02/2019 Violation Open Ulrich, Chris A.
Significance: SNC-B Status: Open
Criteria ID: 4014
Rule: 62-761.420(2)
05/02/2019 Violation Open Ulrich, Chris A.
Significance: Minor Status: Open
Criteria ID: 4078
Rule: 62-761.710(1)
04/02/2019 Site Inspection Activity Closed Ulrich, Chris A.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 04/02/2019
Activity Closed Date: 05/07/2019 Activity Closed By: ULRICH_CA_1
Events:
Event Type: Activity has been finished Date: 05/07/2019
Comment: Finished
Comments:
Comment Date: 04/04/2019 User: ULRICH_CA_1
Description: Current registration placard - did not see current registration placard at the facility. The registration fee payments are up to date however. Upon arrival Mrs. Patel had me speak on the phone with Mitch Patel (owner/operator). He conveyed to me that he was looking into having the tank removed. I suggested that he could register the tank "out of service", but the tank had to be emptied. I subsequently wrote him a email outlining that process (email attached). Checked all sumps, fills and under dispenser liners - All OK. Then is some water in the in the diesel and regular STP sump and in the fill buckets - about an inch in each. The premium STP sump has about 6 inches of petroleum contact water (PCW) in it. Both the dispenser under-liners was full of rainwater (did not detect a sheen on the waters). Alarm history report, obtained from VeederRoot monitoring system, was reviewed & all OK (nothing suspicious to report). Report lists 1 interstitial and 3 STP sump float sensors. Empty the three tank compartments as soon as possible. This immediately removes any potential threat to the environment. The VeederRoot reports 72 inches of product in the diesel compartment, 26 inches of premium gasoline and 12 inches of regular gasoline. A copy of the tank inspection report will be emailed to the facility owner/operator completion.
03/01/2019 Electronic Communication Activity Ulrich, Chris A.
Activity Closed Date: 03/01/2019 Activity Status: Closed
Date: 03/01/2019
Recipient: Mitch Patel
Sender: Chris Ulrich
Subject: tank inspection
Message: notice to inspect
Events:
Event Type: Activity has been finished Date: 03/01/2019
Comment: Finished
02/03/2017 Attachment Ulrich, Chris A.
02/03/2017 Site Inspection Activity Closed Ulrich, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/03/2017
Activity Closed Date: 02/03/2017 Activity Closed By: ULRICH_CA_1
Events:
Event Type: Activity has been finished Date: 02/03/2017
Comment: Finished
Comments:
Comment Date: 02/03/2017 User: ULRICH_CA_1
Description: Current 2016/2017 registration placard is posted on the bulletin board. AB Certificate is also posted. Checked all 3 sumps, 3 fills & 2 under dispenser liners - All OK. The gasoline STP sumps were recently repainted. Well done. A Liquid Status report was obtained from the VeederRoot monitoring system: All functions normal. Report lists 3 STP sump and 1 UST interstitial sensors. Very good inspection. A copy of this report will be emailed to the owner upon completion.
02/03/2017 Attachment Ulrich, Chris A.
12/15/2014 Site Inspection Activity Closed Ulrich, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/15/2014
Activity Closed Date: 12/15/2014 Activity Closed By: ULRICH_CA_1
Events:
Event Type: Activity has been finished Date: 12/15/2014
Comment: Finished
Comments:
Comment Date: 12/15/2014 User: ULRICH_CA_1
Description: Current registration placard - posted. AB Certificate is posted. Checked all sumps, fills & under dispenser liners - All OK. Liquid Status report obtained from VeederRoot monitoring system: All functions normal. Report lists 3 STP sump and 1 UST interstitial sensors.
12/15/2014 Document Management Activity Ulrich, Chris A.
Activity Title: Operator Training Certification Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 12/15/2014
Comment: Finished
Attachments:
Attachment Date: 12/15/2014 User: ULRICH_CA_1
Description: Aqeel Mirza AB
View Attachment
12/15/2014 Electronic Communication Activity Ulrich, Chris A.
Activity Closed Date: 12/15/2014 Activity Status: Closed
Date: 12/15/2014
Recipient: Aqeel Mirza
Sender: Chris Ulrich
Subject: Copy of inspection report
Message: See attachment
Events:
Event Type: Activity has been finished Date: 12/15/2014
Comment: Finished
12/15/2014 Emergency Preparedness Information Activity Ulrich, Chris A.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 12/15/2014
Events:
Event Type: Activity has been finished Date: 12/15/2014
Comment: Finished
09/04/2013 Record Document Activity Stewart, Thomas
Activity Status: Closed
Contact Name: Aqeel Mizra Activity Closed Date: 09/10/2013
Events:
Event Type: Activity has been finished Date: 09/10/2013
Comment: Finished
08/23/2013 Electronic Communication Activity Stewart, Thomas
Activity Closed Date: 08/23/2013 Activity Status: Closed
Date: 08/23/2013
Recipient: Aqeel Mizra
Sender: Tom Stewart
Subject: 2013-2014 A 1 EXPRESS NCL email
Message: See attachment.
Events:
Event Type: Activity has been finished Date: 08/23/2013
Comment: Finished
08/23/2013 Editable Letter Activity Stewart, Thomas
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 08/23/2013
Comment: Sent on Fri Aug 23 00:00:00 EDT 2013
Events:
Event Type: Activity has been finished Date: 08/23/2013
Comment: Finished
Attachments:
Attachment Date: 08/23/2013 User: STEWART_TJ_1
Description: 2013-2014 A 1 EXPRESS NCL
View Attachment
08/23/2013 Document Management Activity Stewart, Thomas
Activity Title: Operator Training Certification Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/23/2013
Comment: Finished
Attachments:
Attachment Date: 08/23/2013 User: STEWART_TJ_1
Description: Training certificates
View Attachment
08/21/2013 Violation Closed Stewart, Thomas
Significance: Minor Status: Closed
Criteria ID: 1020
Rule: 62-761.500(1)(d)5.
Comments: The breach of integrity test is intended for closed interstices only. A closed interstice has no unsecured or unsealed opening to the outside. Double-walled piping without a boot connector, or if the boot has a bleed valve (for tightness testing), is considered an open interstice. The breach of integrity test may be performed by using at least one of the following methods: a. A continuous hydrostatic system b. A continuous vacuum system c. Testing of the interstice for liquid tightness in accordance with manufacturer's installation instructions; or d. Another method in accordance with subsection 62-761.850(2). How the breach of integrity test is performed or to what degree can depend on the depth to groundwater at each facility. When the tank and or piping are fully submerged, the lack of water intrusion into the secondary containment may be considered a verification of its integrity. However, when total submersion is not the case, one of the rule stipulated options must be used. The breach of integrity test should not be confused with a precision tightness test, which tests the primary tank or piping only. The breach of integrity test will test the secondary and primary shells, but is not a precision test.
08/21/2013 Emergency Preparedness Information Activity Stewart, Thomas
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 08/21/2013
Events:
Event Type: Activity has been finished Date: 08/21/2013
Comment: Finished
08/21/2013 Site Inspection Activity Closed Stewart, Thomas
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 08/21/2013
Activity Closed Date: 08/23/2013 Activity Closed By: STEWART_TJ_1
Events:
Event Type: Activity has been finished Date: 08/23/2013
Comment: Finished
Comments:
Comment Date: 08/21/2013 User: STEWART_TJ_1
Description: Water in premium sump below piping penetrations, diesel in diesel sump, leftover from ILLD test. Pump and absorb these liquids out when next you open the sumps. Not severe enough to warrant a violation. Premium spill bucket pumped out at time of inspection. Double-walled system with double-walled buckets, sumps and interstitial sensors to TLS 350. Inspected sumps, pipe, STP and flex, LD, ATG and interstitial sensor risers, spill containment and overfill, vapor recovery, dispensers, shears and udls. Current placard displayed. Inspection sent 8/21 by email.
05/07/2012 Site Inspection Activity Closed Stewart, Thomas
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/07/2012
Activity Closed Date: 05/07/2012 Activity Closed By: STEWART_TJ_1
Events:
Event Type: Activity has been finished Date: 05/07/2012
Comment: Finished
Comments:
Comment Date: 05/07/2012 User: STEWART_TJ_1
Description: Inspected all portions of the system that could be inspected including risers, sumps, spill buckets and interstices, dispensers, UDLs and hoses. Liquid status and alarm history provided for Veeder-Root. Current registration placard displayed. Excellent job of record keeping and maintenance. Monthly visual inspecton and release detection results incorrectrly listed as ending 5/30/2012. Should be 4/30/2012.
05/07/2012 Emergency Preparedness Information Activity Stewart, Thomas
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 05/07/2012
Events:
Event Type: Activity has been finished Date: 05/07/2012
Comment: Finished
06/08/2011 Site Inspection Activity Closed Ulrich, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/08/2011
Activity Closed Date: 06/13/2011 Activity Closed By: ULRICH_CA_1
Events:
Event Type: Activity has been finished Date: 06/13/2011
Comment: Finished
Comments:
Comment Date: 06/08/2011 User: ULRICH_CA_1
Description: To put the facility in full compliance for this 2010/2011 inspection year, I need: Recent in-line leak detector tests ( you have 3) and recent recertification of the VeederRoot monitoring system.
Comments:
Comment Date: 06/08/2011 User: ULRICH_CA_1
Description: Current registration placard - posted. Checked all sumps, fills and under dispenser liners - All OK. Liquid Status report obtained from VeederRoot monitoring system ¿ All functions normal. Report lists 3 STP sump and 1 UST interstitial sensors.
06/08/2011 Emergency Preparedness Information Activity Ulrich, Chris A.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/08/2011
Events:
Event Type: Activity has been finished Date: 06/08/2011
Comment: Finished
06/08/2011 Site Inspection Activity Closed Ulrich, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/08/2011
Activity Closed Date: 06/13/2011 Activity Closed By: ULRICH_CA_1
Events:
Event Type: Activity has been finished Date: 06/13/2011
Comment: Finished
Comments:
Comment Date: 06/08/2011 User: ULRICH_CA_1
Description: To put the facility in full compliance for this 2010/2011 inspection year, I need: Recent in-line leak detector tests ( you have 3) and recent recertification of the VeederRoot monitoring system.
Comments:
Comment Date: 06/08/2011 User: ULRICH_CA_1
Description: Current registration placard - posted. Checked all sumps, fills and under dispenser liners - All OK. Liquid Status report obtained from VeederRoot monitoring system ¿ All functions normal. Report lists 3 STP sump and 1 UST interstitial sensors.
06/16/2010 Comment Stewart, Thomas
Description: aqeelmirza@bellsouth.net
06/16/2010 Site Inspection Activity Closed Stewart, Thomas
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/16/2010
Activity Closed Date: 06/16/2010 Activity Closed By: STEWART_TJ_1
Events:
Event Type: Activity has been finished Date: 06/16/2010
Comment: Finished
Comments:
Comment Date: 06/16/2010 User: STEWART_TJ_1
Description: Inspected all portions of the system that could be inspected including risers, sumps, spill buckets, dispensers, shear valves and clamps, external sensors , ATG sensor UDLs and hoses. Pulled liquid status and alarm historyon Veeder-Root. Current placard displayed. Small quantity of diesel/water mix in diesel STP sump. Not above penetrations. No violation, should be removed at your convenience.
05/12/2010 Issue Document Activity Stewart, Thomas
Activity Status: Closed
Contact Name: Aqeel Mizra Activity Closed Date: 05/12/2010
Events:
Event Type: Activity has been finished Date: 05/12/2010
Comment: Finished
06/23/2009 Comment Ulrich, Chris A.
Description: Facility was invoiced for 4 tanks. The 3 old USTs were removed in Mar09 and 1 new DW installed there after.
06/23/2009 Site Inspection Activity Closed Ulrich, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/23/2009
Activity Closed Date: 06/23/2009 Activity Closed By: ULRICH_CA_1
Comments:
Comment Date: 06/23/2009 User: ULRICH_CA_1
Description: Looked in three STP sumps and three fill buckets- all ok. You do have some corrosion (rust) in the metal fixtures in the premium and regular STP sumps (this is from the ethanol). Keep and eye on this. You may have to wire brush, prime and paint these components. Current (orange) placard is posted. Last leak detector tests and VeederRoot certification was11Jun08 by US Tank Alliance. You are due again. Have these tests conducted immediately so you will be set for next year's inspection. Have 12 liquid status printouts (one each month) for next year's inspection.
Comments:
Comment Date: 06/23/2009 User: ULRICH_CA_1
Description: Note: the annual operability tests refers the the annual recertification of the VeederRoot and it's sensors. The annual line test is no longer required since the facility product piping is double walled.
06/23/2009 Site Inspection Activity Closed Ulrich, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/23/2009
Activity Closed Date: 06/23/2009 Activity Closed By: ULRICH_CA_1
Comments:
Comment Date: 06/23/2009 User: ULRICH_CA_1
Description: Looked in three STP sumps and three fill buckets- all ok. You do have some corrosion (rust) in the metal fixtures in the premium and regular STP sumps (this is from the ethanol). Keep and eye on this. You may have to wire brush, prime and paint these components. Current (orange) placard is posted. Last leak detector tests and VeederRoot certification was11Jun08 by US Tank Alliance. You are due again. Have these tests conducted immediately so you will be set for next year's inspection. Have 12 liquid status printouts (one each month) for next year's inspection.
Comments:
Comment Date: 06/23/2009 User: ULRICH_CA_1
Description: Note: the annual operability tests refers the the annual recertification of the VeederRoot and it's sensors. The annual line test is no longer required since the facility product piping is double walled.
05/30/2008 Site Inspection Activity Closed Stewart, Thomas
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/30/2008
Activity Closed Date: 07/01/2010 Activity Closed By: STEWART_TJ_1
Events:
Event Type: Activity has been finished Date: 07/01/2010
Comment: Finished
Comments:
Comment Date: 05/30/2008 User: STEWART_TJ_1
Description: Petroleum Construction installed 1 22,000 gallon modern Glasteel steel over steel UST. Ul-P 837701. System de-watered to sanitary. Allowed re-use of deadmen from previous installation. Good gravel bottom. Proper BD. 16 inches vacuum. PCC 047153. Smith fiberglass piping 2" inside 3". OPW Flexworks sumps and UDLs. Primary and secondary pressure tested at 56 and 5 PSIG respectively. Passed. UDLs and STP sumps hydrostatically tested and passed. TLS 350 and external sensors certified and tested. Passed. Double-walled buckets pressure tested. Shear valves tested and operational.
05/29/2008 Site Inspection Activity Closed Stewart, Thomas
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/29/2008
Activity Closed Date: 03/13/2009 Activity Closed By: ULRICH_CA_1
02/26/2008 Record Document Activity Stewart, Thomas
Activity Status: Closed
Contact Name: Stephen Phillips Activity Closed Date: 02/26/2008
01/16/2008 Record Document Activity Stewart, Thomas
Activity Status: Closed
Contact Name: Clayton Fields Activity Closed Date: 03/13/2009
12/06/2007 Issue Document Activity Stewart, Thomas
Activity Status: Closed
Contact Name: Fran Franconi Activity Closed Date: 12/06/2007
02/08/2007 Emergency Preparedness Information Activity Ulrich, Chris A.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/08/2007
12/22/2006 Attachment Ulrich, Chris A.
12/20/2006 Attachment Ulrich, Chris A.
12/19/2006 Site Inspection Activity Closed Ulrich, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/19/2006
Activity Closed Date: 12/19/2006 Activity Closed By: ULRICH_CA_1
Comments:
Comment Date: 12/19/2006 User: ULRICH_CA_1
Description: Checked all sumps (3), fills (3) and under dispenser liners (2) - All OK. Monthly visual inspection records and SIRs reports provided by corporate HQ. All SIR results pass, except one inconclusive on the premium UST in September 2006. The inconclusive did not repeat in October 2006. Current registration placard is posted.
09/27/2006 Emergency Preparedness Information Activity Ulrich, Chris A.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/27/2006
01/17/2006 Legacy Activity Stewart, Thomas
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
11/17/2004 Legacy Activity Ulrich, Chris A.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
09/04/2003 Legacy Activity Unknown, User
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
09/29/2002 Legacy Activity Cowan, Donna
Activity Name: TELEPHONE CONVERSATION Activity Status: Closed
09/29/2002 Legacy Activity Cowan, Donna
Activity Name: COMPLIANCE W/O FORMAL ENFORCEMENT ACTION Activity Status: Closed
08/07/2002 Violation Closed Cowan, Donna
Significance: Minor Status: Closed
Rule: 400(2)(a)6
08/07/2002 Legacy Activity Cowan, Donna
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
08/07/2002 Legacy Activity Cowan, Donna
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
08/07/2002 Violation Closed Cowan, Donna
Significance: Minor Status: Closed
Rule: 700(1)(c)1
10/05/2001 Legacy Activity Cowan, Donna
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
10/04/2001 Violation Closed Cowan, Donna
Significance: Minor Status: Closed
Rule: 700(1)(c)1
10/04/2001 Legacy Activity Cowan, Donna
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
09/18/2000 Legacy Activity Cowan, Donna
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
10/01/1999 Legacy Activity Cowan, Donna
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
10/08/1998 Legacy Activity Cowan, Donna
Activity Name: UST ROUTINE COMPLIANCE INSPECTION Activity Status: Closed