Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 04/27/2025 Last Data Refresh: 04/26/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 8841332 | ||||||||||
Facility Name: | AURORA MARATHON | ||||||||||
03/19/2024 | Violation Open | Grantham, Jeffrey W | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 6003 | ||||||||||
Rule: | 62-761.400(1)(b), 62-761.400(2), 62-761.400(2)(a), 62-761.400(3), 62-761.400(3)(a), 62-761.400(3)(b), 62-761.400(3)(c) | ||||||||||
03/19/2024 | Editable Letter Activity | Grantham, Jeffrey W | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/19/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 03/19/2024 | User: | GRANTHAM_JW_1 | ||||||||
Description: | 3/19/2024 compliance assistance offer | ||||||||||
View Attachment | |||||||||||
03/19/2024 | Site Inspection Activity Closed | Grantham, Jeffrey W | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 03/19/2024 | ||||||||||
Activity Closed Date: | 03/19/2024 | Activity Closed By: | GRANTHAM_JW_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/19/2024 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 03/19/2024 | User: | GRANTHAM_JW_1 | ||||||||
Description: | No access provided to the tank. Store was closed. I attempted to contact the owner via phone and email with no success. Dispensers have been removed from the site. A copy of the tank inspection report will be emailed to the facility owner/operator upon completion. All the violations remain. Two new violations were added. The facility is currently under enforcement with the FDEP. The tank STP's appear to be cemented over. The tank needs to be registered as out of service or it needs to be removed. | ||||||||||
03/19/2024 | Violation Open | Grantham, Jeffrey W | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 6001 | ||||||||||
Rule: | 62-761.100(3) | ||||||||||
04/12/2023 | Electronic Communication Activity | Horvath, Kage | |||||||||
Activity Closed Date: | 04/12/2023 | Activity Status: | Closed | ||||||||
Date: | 04/12/2023 | ||||||||||
Recipient: | MITCHPATEL1985@YAHOO.COM | ||||||||||
Sender: | Kage.Horvath@floridadep.gov | ||||||||||
Subject: | [PART 2] OUTSTANDING VIOLATIONS - AURORA MARATHON - FAC ID #8841332 | ||||||||||
Message: | [OUTLINED LIST OF VIOLATIONS] Thank you kindly for your time and cooperation. I look forward to resolving this matter with you. Kindest Regards, Kage Horvath Environmental Specialist I Florida Department of Environmental Protection Central District - Orlando Kage.Horvath@FloridaDEP.gov Office: 407-897-4334 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/12/2023 | ||||||||
Comment: | Finished | ||||||||||
04/12/2023 | Electronic Communication Activity | Horvath, Kage | |||||||||
Activity Closed Date: | 04/12/2023 | Activity Status: | Closed | ||||||||
Date: | 04/12/2023 | ||||||||||
Recipient: | MITCHPATEL1985@YAHOO.COM | ||||||||||
Sender: | Kage.Horvath@floridadep.gov | ||||||||||
Subject: | [PART 1] OUTSTANDING VIOLATIONS - AURORA MARATHON - FAC ID #8841332 | ||||||||||
Message: | This message is time-sensitive. Please respond at your earliest convenience. Good morning Mr. Patel, My name is Kage Horvath and I work with the Florida Department of Environmental Protection. I am reaching out regarding 1724 N HARBOR CITY BLVD. MELBOURNE, FL 32935, or Aurora Marathon, as it is listed in our system. There seems to be a long list of open violations regarding your Underground Storage Tank. Please refer to the list at the end of this message for further details. I would like to address the below-referenced violations with you and work to resolve them. Please respond at your earliest convenience to address the matter. Any details you can provide regarding the tank would be helpful. Please respond by Wednesday, April 19, 2023. If no response is received, the Department will pursue formal enforcement and that will result in fines and penalties against the facility. [CONTINUED] | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/12/2023 | ||||||||
Comment: | Finished | ||||||||||
08/23/2022 | Editable Letter Activity | Dalton, Kyle | |||||||||
Activity Title: | Warning Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity/Document has been approved | Date: | 10/04/2022 | ||||||||
Comment: | Approved by DANIEL K HALL: approved | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/10/2022 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 10/03/2022 | ||||||||
Comment: | Submitted for approval by: Kyle Dalton | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 10/03/2022 | User: | DALTON_K | ||||||||
Description: | 8841332 Aurora Marathon: Warning Letter | ||||||||||
View Attachment | |||||||||||
08/10/2022 | Electronic Communication Activity | Dalton, Kyle | |||||||||
Activity Closed Date: | 08/10/2022 | Activity Status: | Closed | ||||||||
Date: | 08/10/2022 | ||||||||||
Recipient: | MITCHPATEL1985@YAHOO.COM | ||||||||||
Sender: | Dalton, Kyle | ||||||||||
Subject: | Regulated Storage Tank Facility 8841332 AURORA MARATHON: Outstanding Non-Compliance | ||||||||||
Message: | See Attachment. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/10/2022 | ||||||||
Comment: | Finished | ||||||||||
06/06/2022 | Enforcement Tracking Activity | Useche, Viviana | |||||||||
Activity Status: | Open | ||||||||||
05/04/2022 | Electronic Communication Activity | Ulrich, Chris A. | |||||||||
Activity Closed Date: | 05/04/2022 | Activity Status: | Closed | ||||||||
Date: | 05/04/2022 | ||||||||||
Recipient: | Viviana Useche | ||||||||||
Sender: | Chris Ulrich | ||||||||||
Subject: | 1Apr22 referral to Central District FDEP. | ||||||||||
Message: | Referral has been withdrawn as requested. Will attempt to re-submit. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/04/2022 | ||||||||
Comment: | Finished | ||||||||||
04/01/2022 | Enforcement Referral Activity | Ulrich, Chris A. | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 06/06/2022 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been withdrawn from submission by the requestor | Date: | 05/05/2022 | ||||||||
Comment: | Withdrawn by Chris A. Ulrich: Re-attempting to direct enforcement referral to Viviana Useche, FDEP Central District. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 05/05/2022 | ||||||||
Comment: | Submitted for approval by: Chris A. Ulrich: Re-attempting to direct this referral to FDEP Central District | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 04/01/2022 | ||||||||
Comment: | Submitted for approval by: Chris A. Ulrich: 1Apr22 facility referral | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 05/04/2022 | ||||||||
Comment: | Submitted for approval by: Chris A. Ulrich: Original 1Apr22 referral has been withdrawn as requested. Referral is now re-submitted. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been withdrawn from submission by the requestor | Date: | 05/04/2022 | ||||||||
Comment: | Withdrawn by Chris A. Ulrich: Withdrawn as directed on 4May22. Will re-submit. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 06/01/2022 | ||||||||
Comment: | Submitted for approval by: Chris A. Ulrich: File re-submitted to FDEP Central District for enforcement. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been withdrawn from submission by the requestor | Date: | 06/01/2022 | ||||||||
Comment: | Withdrawn by Chris A. Ulrich: As instructed by FDEP central district. | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 06/06/2022 | ||||||||
Comment: | Acknowledged and Assigned by Viviana Useche | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/06/2022 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 06/06/2022 | ||||||||
Comment: | Assigned to Viviana Useche | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 06/06/2022 | ||||||||
Comment: | Accepted by Viviana Useche: Accepted | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/01/2022 | User: | ULRICH_CA_1 | ||||||||
Description: | On 17Feb22, FDEP Tallahassee sent an email entitled "Brevard Co Fuel Delivery Prohibition List". This facility was on that list. Facility is no longer a gas station, but a liquor store. The canopy and the two dispensers have been removed. During the last routine compliance inspection, it was noted that the tank contained petroleum contact water and the VeederRoot tank monitor was discovered turn off. On 17Mar22, by email, Brevard County Natural Resources was directed to refer this facility for enforcement. | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/01/2022 | User: | ULRICH_CA_1 | ||||||||
Description: | 1Apr22 facility referral | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 04/01/2022 | User: | ULRICH_CA_1 | ||||||||
Description: | 1Apr22 Memo | ||||||||||
View Attachment | |||||||||||
04/01/2022 | Electronic Communication Activity | Ulrich, Chris A. | |||||||||
Activity Closed Date: | 04/01/2022 | Activity Status: | Closed | ||||||||
Date: | 04/01/2022 | ||||||||||
Recipient: | Chris Ulrich | ||||||||||
Sender: | Amanda Dorsett | ||||||||||
Subject: | 17Mar22 email stating that this facility should be referred to FDEP Central District. | ||||||||||
Message: | Email is attached. Heavily edited (it listed a few other facilities). | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/01/2022 | ||||||||
Comment: | Finished | ||||||||||
04/01/2022 | Electronic Communication Activity | Ulrich, Chris A. | |||||||||
Activity Closed Date: | 04/01/2022 | Activity Status: | Closed | ||||||||
Date: | 04/01/2022 | ||||||||||
Recipient: | Mitch Patel | ||||||||||
Sender: | Chris Ulrich | ||||||||||
Subject: | 23Mar22 email | ||||||||||
Message: | See attachment | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/01/2022 | ||||||||
Comment: | Finished | ||||||||||
04/01/2022 | Electronic Communication Activity | Ulrich, Chris A. | |||||||||
Activity Closed Date: | 04/01/2022 | Activity Status: | Closed | ||||||||
Date: | 04/01/2022 | ||||||||||
Recipient: | Mitch Patel | ||||||||||
Sender: | Chris Ulrich | ||||||||||
Subject: | |||||||||||
Message: | See attachment | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/01/2022 | ||||||||
Comment: | Finished | ||||||||||
04/01/2022 | Electronic Communication Activity | Ulrich, Chris A. | |||||||||
Activity Closed Date: | 04/01/2022 | Activity Status: | Closed | ||||||||
Date: | 04/01/2022 | ||||||||||
Recipient: | Mitch Patel | ||||||||||
Sender: | Chris Ulrich | ||||||||||
Subject: | |||||||||||
Message: | See attachment | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 04/01/2022 | ||||||||
Comment: | Finished | ||||||||||
04/01/2022 | Enforcement Referral Activity | Ulrich, Chris A. | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 06/06/2022 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been withdrawn from submission by the requestor | Date: | 05/05/2022 | ||||||||
Comment: | Withdrawn by Chris A. Ulrich: Re-attempting to direct enforcement referral to Viviana Useche, FDEP Central District. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 05/05/2022 | ||||||||
Comment: | Submitted for approval by: Chris A. Ulrich: Re-attempting to direct this referral to FDEP Central District | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 04/01/2022 | ||||||||
Comment: | Submitted for approval by: Chris A. Ulrich: 1Apr22 facility referral | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 05/04/2022 | ||||||||
Comment: | Submitted for approval by: Chris A. Ulrich: Original 1Apr22 referral has been withdrawn as requested. Referral is now re-submitted. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been withdrawn from submission by the requestor | Date: | 05/04/2022 | ||||||||
Comment: | Withdrawn by Chris A. Ulrich: Withdrawn as directed on 4May22. Will re-submit. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 06/01/2022 | ||||||||
Comment: | Submitted for approval by: Chris A. Ulrich: File re-submitted to FDEP Central District for enforcement. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been withdrawn from submission by the requestor | Date: | 06/01/2022 | ||||||||
Comment: | Withdrawn by Chris A. Ulrich: As instructed by FDEP central district. | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 06/06/2022 | ||||||||
Comment: | Acknowledged and Assigned by Viviana Useche | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/06/2022 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 06/06/2022 | ||||||||
Comment: | Assigned to Viviana Useche | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 06/06/2022 | ||||||||
Comment: | Accepted by Viviana Useche: Accepted | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/01/2022 | User: | ULRICH_CA_1 | ||||||||
Description: | On 17Feb22, FDEP Tallahassee sent an email entitled "Brevard Co Fuel Delivery Prohibition List". This facility was on that list. Facility is no longer a gas station, but a liquor store. The canopy and the two dispensers have been removed. During the last routine compliance inspection, it was noted that the tank contained petroleum contact water and the VeederRoot tank monitor was discovered turn off. On 17Mar22, by email, Brevard County Natural Resources was directed to refer this facility for enforcement. | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/01/2022 | User: | ULRICH_CA_1 | ||||||||
Description: | 1Apr22 facility referral | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 04/01/2022 | User: | ULRICH_CA_1 | ||||||||
Description: | 1Apr22 Memo | ||||||||||
View Attachment | |||||||||||
09/03/2021 | Violation Open | Ulrich, Chris A. | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 6060 | ||||||||||
Rule: | 62-761.600(2), 62-761.600(2)(a), 62-761.600(2)(a)1, 62-761.600(2)(a)2, 62-761.600(2)(a)3, 62-761.600(2)(a)4, 62-761.600(2)(a)5, 62-761.600(2)(a)6, 62-761.600(2)(a)6.a, 62-761.600(2)(a)6.b, 62-761.600(2)(a)7, 62-761.600(2)(a)8 | ||||||||||
09/03/2021 | Editable Letter Activity | Ulrich, Chris A. | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/05/2021 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 09/07/2021 | User: | ULRICH_CA_1 | ||||||||
Description: | 7 September 2021 Compliance Assistance Offer letter | ||||||||||
View Attachment | |||||||||||
09/03/2021 | Phone Conversation Activity | Ulrich, Chris A. | |||||||||
Call Type: | Outgoing | Activity Status: | Closed | ||||||||
Phone Number: | (321) 259-5554 | Activity Closed Date: | 10/05/2021 | ||||||||
Subject: | Left a voice mail stating I was calling to discuss the tank inspection I conducted last week. Left my name and my land line phone number. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/05/2021 | ||||||||
Comment: | Finished | ||||||||||
09/03/2021 | Violation Closed | Ulrich, Chris A. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 6005 | ||||||||||
Rule: | 62-761.400(4), 62-761.400(4)(a), 62-761.400(4)(b), 62-761.400(4)(c), 62-761.400(4)(d), 62-761.400(4)(e), 62-761.400(4)(f) | ||||||||||
08/25/2021 | Site Inspection Activity Closed | Ulrich, Chris A. | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/25/2021 | ||||||||||
Activity Closed Date: | 09/03/2021 | Activity Closed By: | ULRICH_CA_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/03/2021 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/25/2021 | User: | ULRICH_CA_1 | ||||||||
Description: | Current registration placard - did not see current registration placard at the facility. According to FIRST, the registration fees haven't been paid since May, 2019. Upon arrival, the cashier had me speak on the phone with Mich Patel (owner/operator). I introduced myself and told him I was here to inspect the fuel tank. Mr. Patel told me he never received my notification letter (dated 11Aug21), which I add mailed to the store. I an email written in May, 2021 I had suggested that he could register the tank "out of service", but the tank had to be emptied. (email attached). The tank top is in disrepair. The middle sump lid (PUL) has broken and is marked off with two orange traffic and a couple cinder blocks. I looked in all sumps and fills I could access. Stuck both the diesel and premium (PUL) compartments - about four feet of product in the diesel and about two feet in the PUL. These readings are circumspect since neither the facility or I had a tank stick. The use of a tape measure is not very reliable. Irregardless, these compartments need to be emptied ASAP. Went to check the VeederRoot storage tank monitor. After moving several boxes of apple whisky, found the VeederRoot without power. It has been turned off. NO release detection at all. According to the last (2109) inspection: VeederRoot liquid status report lists 1 interstitial and 3 STP sump float sensors; 72 inches of product in the diesel compartment, 26 inches of premium gasoline and 12 inches of regular gasoline. A copy of the tank inspection report will be emailed to the facility owner/operator upon completion. All the 2019 violations remain. Two new violations were added. As designated in the contract between FDEP and Brevard County Natural Resources, this facility will be forwarded to Central District FDEP office for enforcement action. | ||||||||||
06/26/2020 | Record Document Activity | Ulrich, Chris A. | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | And Ma Harsiddhi | Activity Closed Date: | 06/26/2020 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/26/2020 | ||||||||
Comment: | Finished | ||||||||||
05/07/2019 | Editable Letter Activity | Ulrich, Chris A. | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/07/2019 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 05/07/2019 | User: | ULRICH_CA_1 | ||||||||
Description: | 7May19 compliance assistance offer letter | ||||||||||
View Attachment | |||||||||||
05/02/2019 | Violation Open | Ulrich, Chris A. | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 4059 | ||||||||||
Rule: | 62-761.600(1)(d), 62-761.600(1)(e) | ||||||||||
05/02/2019 | Violation Open | Ulrich, Chris A. | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 4001 | ||||||||||
Rule: | 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2., 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7) | ||||||||||
05/02/2019 | Violation Open | Ulrich, Chris A. | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 4067 | ||||||||||
Rule: | 62-761.600(4) | ||||||||||
05/02/2019 | Violation Open | Ulrich, Chris A. | |||||||||
Significance: | SNC-B | Status: | Open | ||||||||
Criteria ID: | 4014 | ||||||||||
Rule: | 62-761.420(2) | ||||||||||
05/02/2019 | Violation Open | Ulrich, Chris A. | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 4078 | ||||||||||
Rule: | 62-761.710(1) | ||||||||||
04/02/2019 | Site Inspection Activity Closed | Ulrich, Chris A. | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 04/02/2019 | ||||||||||
Activity Closed Date: | 05/07/2019 | Activity Closed By: | ULRICH_CA_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/07/2019 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 04/04/2019 | User: | ULRICH_CA_1 | ||||||||
Description: | Current registration placard - did not see current registration placard at the facility. The registration fee payments are up to date however. Upon arrival Mrs. Patel had me speak on the phone with Mitch Patel (owner/operator). He conveyed to me that he was looking into having the tank removed. I suggested that he could register the tank "out of service", but the tank had to be emptied. I subsequently wrote him a email outlining that process (email attached). Checked all sumps, fills and under dispenser liners - All OK. Then is some water in the in the diesel and regular STP sump and in the fill buckets - about an inch in each. The premium STP sump has about 6 inches of petroleum contact water (PCW) in it. Both the dispenser under-liners was full of rainwater (did not detect a sheen on the waters). Alarm history report, obtained from VeederRoot monitoring system, was reviewed & all OK (nothing suspicious to report). Report lists 1 interstitial and 3 STP sump float sensors. Empty the three tank compartments as soon as possible. This immediately removes any potential threat to the environment. The VeederRoot reports 72 inches of product in the diesel compartment, 26 inches of premium gasoline and 12 inches of regular gasoline. A copy of the tank inspection report will be emailed to the facility owner/operator completion. | ||||||||||
03/01/2019 | Electronic Communication Activity | Ulrich, Chris A. | |||||||||
Activity Closed Date: | 03/01/2019 | Activity Status: | Closed | ||||||||
Date: | 03/01/2019 | ||||||||||
Recipient: | Mitch Patel | ||||||||||
Sender: | Chris Ulrich | ||||||||||
Subject: | tank inspection | ||||||||||
Message: | notice to inspect | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/01/2019 | ||||||||
Comment: | Finished | ||||||||||
02/03/2017 | Attachment | Ulrich, Chris A. | |||||||||
02/03/2017 | Site Inspection Activity Closed | Ulrich, Chris A. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 02/03/2017 | ||||||||||
Activity Closed Date: | 02/03/2017 | Activity Closed By: | ULRICH_CA_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/03/2017 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 02/03/2017 | User: | ULRICH_CA_1 | ||||||||
Description: | Current 2016/2017 registration placard is posted on the bulletin board. AB Certificate is also posted. Checked all 3 sumps, 3 fills & 2 under dispenser liners - All OK. The gasoline STP sumps were recently repainted. Well done. A Liquid Status report was obtained from the VeederRoot monitoring system: All functions normal. Report lists 3 STP sump and 1 UST interstitial sensors. Very good inspection. A copy of this report will be emailed to the owner upon completion. | ||||||||||
02/03/2017 | Attachment | Ulrich, Chris A. | |||||||||
12/15/2014 | Site Inspection Activity Closed | Ulrich, Chris A. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 12/15/2014 | ||||||||||
Activity Closed Date: | 12/15/2014 | Activity Closed By: | ULRICH_CA_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/15/2014 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 12/15/2014 | User: | ULRICH_CA_1 | ||||||||
Description: | Current registration placard - posted. AB Certificate is posted. Checked all sumps, fills & under dispenser liners - All OK. Liquid Status report obtained from VeederRoot monitoring system: All functions normal. Report lists 3 STP sump and 1 UST interstitial sensors. | ||||||||||
12/15/2014 | Document Management Activity | Ulrich, Chris A. | |||||||||
Activity Title: | Operator Training Certification | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/15/2014 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 12/15/2014 | User: | ULRICH_CA_1 | ||||||||
Description: | Aqeel Mirza AB | ||||||||||
View Attachment | |||||||||||
12/15/2014 | Electronic Communication Activity | Ulrich, Chris A. | |||||||||
Activity Closed Date: | 12/15/2014 | Activity Status: | Closed | ||||||||
Date: | 12/15/2014 | ||||||||||
Recipient: | Aqeel Mirza | ||||||||||
Sender: | Chris Ulrich | ||||||||||
Subject: | Copy of inspection report | ||||||||||
Message: | See attachment | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/15/2014 | ||||||||
Comment: | Finished | ||||||||||
12/15/2014 | Emergency Preparedness Information Activity | Ulrich, Chris A. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 12/15/2014 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/15/2014 | ||||||||
Comment: | Finished | ||||||||||
09/04/2013 | Record Document Activity | Stewart, Thomas | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Aqeel Mizra | Activity Closed Date: | 09/10/2013 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 09/10/2013 | ||||||||
Comment: | Finished | ||||||||||
08/23/2013 | Electronic Communication Activity | Stewart, Thomas | |||||||||
Activity Closed Date: | 08/23/2013 | Activity Status: | Closed | ||||||||
Date: | 08/23/2013 | ||||||||||
Recipient: | Aqeel Mizra | ||||||||||
Sender: | Tom Stewart | ||||||||||
Subject: | 2013-2014 A 1 EXPRESS NCL email | ||||||||||
Message: | See attachment. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/23/2013 | ||||||||
Comment: | Finished | ||||||||||
08/23/2013 | Editable Letter Activity | Stewart, Thomas | |||||||||
Activity Title: | 1st Non-Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 08/23/2013 | ||||||||
Comment: | Sent on Fri Aug 23 00:00:00 EDT 2013 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/23/2013 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 08/23/2013 | User: | STEWART_TJ_1 | ||||||||
Description: | 2013-2014 A 1 EXPRESS NCL | ||||||||||
View Attachment | |||||||||||
08/23/2013 | Document Management Activity | Stewart, Thomas | |||||||||
Activity Title: | Operator Training Certification | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/23/2013 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 08/23/2013 | User: | STEWART_TJ_1 | ||||||||
Description: | Training certificates | ||||||||||
View Attachment | |||||||||||
08/21/2013 | Violation Closed | Stewart, Thomas | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Criteria ID: | 1020 | ||||||||||
Rule: | 62-761.500(1)(d)5. | ||||||||||
Comments: | The breach of integrity test is intended for closed interstices only. A closed interstice has no unsecured or unsealed opening to the outside. Double-walled piping without a boot connector, or if the boot has a bleed valve (for tightness testing), is considered an open interstice. The breach of integrity test may be performed by using at least one of the following methods: a. A continuous hydrostatic system b. A continuous vacuum system c. Testing of the interstice for liquid tightness in accordance with manufacturer's installation instructions; or d. Another method in accordance with subsection 62-761.850(2). How the breach of integrity test is performed or to what degree can depend on the depth to groundwater at each facility. When the tank and or piping are fully submerged, the lack of water intrusion into the secondary containment may be considered a verification of its integrity. However, when total submersion is not the case, one of the rule stipulated options must be used. The breach of integrity test should not be confused with a precision tightness test, which tests the primary tank or piping only. The breach of integrity test will test the secondary and primary shells, but is not a precision test. | ||||||||||
08/21/2013 | Emergency Preparedness Information Activity | Stewart, Thomas | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 08/21/2013 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/21/2013 | ||||||||
Comment: | Finished | ||||||||||
08/21/2013 | Site Inspection Activity Closed | Stewart, Thomas | |||||||||
Activity Result: | Minor Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/21/2013 | ||||||||||
Activity Closed Date: | 08/23/2013 | Activity Closed By: | STEWART_TJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/23/2013 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/21/2013 | User: | STEWART_TJ_1 | ||||||||
Description: | Water in premium sump below piping penetrations, diesel in diesel sump, leftover from ILLD test. Pump and absorb these liquids out when next you open the sumps. Not severe enough to warrant a violation. Premium spill bucket pumped out at time of inspection. Double-walled system with double-walled buckets, sumps and interstitial sensors to TLS 350. Inspected sumps, pipe, STP and flex, LD, ATG and interstitial sensor risers, spill containment and overfill, vapor recovery, dispensers, shears and udls. Current placard displayed. Inspection sent 8/21 by email. | ||||||||||
05/07/2012 | Site Inspection Activity Closed | Stewart, Thomas | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 05/07/2012 | ||||||||||
Activity Closed Date: | 05/07/2012 | Activity Closed By: | STEWART_TJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/07/2012 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/07/2012 | User: | STEWART_TJ_1 | ||||||||
Description: | Inspected all portions of the system that could be inspected including risers, sumps, spill buckets and interstices, dispensers, UDLs and hoses. Liquid status and alarm history provided for Veeder-Root. Current registration placard displayed. Excellent job of record keeping and maintenance. Monthly visual inspecton and release detection results incorrectrly listed as ending 5/30/2012. Should be 4/30/2012. | ||||||||||
05/07/2012 | Emergency Preparedness Information Activity | Stewart, Thomas | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 05/07/2012 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/07/2012 | ||||||||
Comment: | Finished | ||||||||||
06/08/2011 | Site Inspection Activity Closed | Ulrich, Chris A. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/08/2011 | ||||||||||
Activity Closed Date: | 06/13/2011 | Activity Closed By: | ULRICH_CA_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/13/2011 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/08/2011 | User: | ULRICH_CA_1 | ||||||||
Description: | To put the facility in full compliance for this 2010/2011 inspection year, I need: Recent in-line leak detector tests ( you have 3) and recent recertification of the VeederRoot monitoring system. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/08/2011 | User: | ULRICH_CA_1 | ||||||||
Description: | Current registration placard - posted. Checked all sumps, fills and under dispenser liners - All OK. Liquid Status report obtained from VeederRoot monitoring system ¿ All functions normal. Report lists 3 STP sump and 1 UST interstitial sensors. | ||||||||||
06/08/2011 | Emergency Preparedness Information Activity | Ulrich, Chris A. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 06/08/2011 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/08/2011 | ||||||||
Comment: | Finished | ||||||||||
06/08/2011 | Site Inspection Activity Closed | Ulrich, Chris A. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/08/2011 | ||||||||||
Activity Closed Date: | 06/13/2011 | Activity Closed By: | ULRICH_CA_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/13/2011 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/08/2011 | User: | ULRICH_CA_1 | ||||||||
Description: | To put the facility in full compliance for this 2010/2011 inspection year, I need: Recent in-line leak detector tests ( you have 3) and recent recertification of the VeederRoot monitoring system. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/08/2011 | User: | ULRICH_CA_1 | ||||||||
Description: | Current registration placard - posted. Checked all sumps, fills and under dispenser liners - All OK. Liquid Status report obtained from VeederRoot monitoring system ¿ All functions normal. Report lists 3 STP sump and 1 UST interstitial sensors. | ||||||||||
06/16/2010 | Comment | Stewart, Thomas | |||||||||
Description: | aqeelmirza@bellsouth.net | ||||||||||
06/16/2010 | Site Inspection Activity Closed | Stewart, Thomas | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/16/2010 | ||||||||||
Activity Closed Date: | 06/16/2010 | Activity Closed By: | STEWART_TJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/16/2010 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/16/2010 | User: | STEWART_TJ_1 | ||||||||
Description: | Inspected all portions of the system that could be inspected including risers, sumps, spill buckets, dispensers, shear valves and clamps, external sensors , ATG sensor UDLs and hoses. Pulled liquid status and alarm historyon Veeder-Root. Current placard displayed. Small quantity of diesel/water mix in diesel STP sump. Not above penetrations. No violation, should be removed at your convenience. | ||||||||||
05/12/2010 | Issue Document Activity | Stewart, Thomas | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Aqeel Mizra | Activity Closed Date: | 05/12/2010 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/12/2010 | ||||||||
Comment: | Finished | ||||||||||
06/23/2009 | Comment | Ulrich, Chris A. | |||||||||
Description: | Facility was invoiced for 4 tanks. The 3 old USTs were removed in Mar09 and 1 new DW installed there after. | ||||||||||
06/23/2009 | Site Inspection Activity Closed | Ulrich, Chris A. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/23/2009 | ||||||||||
Activity Closed Date: | 06/23/2009 | Activity Closed By: | ULRICH_CA_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 06/23/2009 | User: | ULRICH_CA_1 | ||||||||
Description: | Looked in three STP sumps and three fill buckets- all ok. You do have some corrosion (rust) in the metal fixtures in the premium and regular STP sumps (this is from the ethanol). Keep and eye on this. You may have to wire brush, prime and paint these components. Current (orange) placard is posted. Last leak detector tests and VeederRoot certification was11Jun08 by US Tank Alliance. You are due again. Have these tests conducted immediately so you will be set for next year's inspection. Have 12 liquid status printouts (one each month) for next year's inspection. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/23/2009 | User: | ULRICH_CA_1 | ||||||||
Description: | Note: the annual operability tests refers the the annual recertification of the VeederRoot and it's sensors. The annual line test is no longer required since the facility product piping is double walled. | ||||||||||
06/23/2009 | Site Inspection Activity Closed | Ulrich, Chris A. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 06/23/2009 | ||||||||||
Activity Closed Date: | 06/23/2009 | Activity Closed By: | ULRICH_CA_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 06/23/2009 | User: | ULRICH_CA_1 | ||||||||
Description: | Looked in three STP sumps and three fill buckets- all ok. You do have some corrosion (rust) in the metal fixtures in the premium and regular STP sumps (this is from the ethanol). Keep and eye on this. You may have to wire brush, prime and paint these components. Current (orange) placard is posted. Last leak detector tests and VeederRoot certification was11Jun08 by US Tank Alliance. You are due again. Have these tests conducted immediately so you will be set for next year's inspection. Have 12 liquid status printouts (one each month) for next year's inspection. | ||||||||||
Comments: | |||||||||||
Comment Date: | 06/23/2009 | User: | ULRICH_CA_1 | ||||||||
Description: | Note: the annual operability tests refers the the annual recertification of the VeederRoot and it's sensors. The annual line test is no longer required since the facility product piping is double walled. | ||||||||||
05/30/2008 | Site Inspection Activity Closed | Stewart, Thomas | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 05/30/2008 | ||||||||||
Activity Closed Date: | 07/01/2010 | Activity Closed By: | STEWART_TJ_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/01/2010 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/30/2008 | User: | STEWART_TJ_1 | ||||||||
Description: | Petroleum Construction installed 1 22,000 gallon modern Glasteel steel over steel UST. Ul-P 837701. System de-watered to sanitary. Allowed re-use of deadmen from previous installation. Good gravel bottom. Proper BD. 16 inches vacuum. PCC 047153. Smith fiberglass piping 2" inside 3". OPW Flexworks sumps and UDLs. Primary and secondary pressure tested at 56 and 5 PSIG respectively. Passed. UDLs and STP sumps hydrostatically tested and passed. TLS 350 and external sensors certified and tested. Passed. Double-walled buckets pressure tested. Shear valves tested and operational. | ||||||||||
05/29/2008 | Site Inspection Activity Closed | Stewart, Thomas | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 05/29/2008 | ||||||||||
Activity Closed Date: | 03/13/2009 | Activity Closed By: | ULRICH_CA_1 | ||||||||
02/26/2008 | Record Document Activity | Stewart, Thomas | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Stephen Phillips | Activity Closed Date: | 02/26/2008 | ||||||||
01/16/2008 | Record Document Activity | Stewart, Thomas | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Clayton Fields | Activity Closed Date: | 03/13/2009 | ||||||||
12/06/2007 | Issue Document Activity | Stewart, Thomas | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Fran Franconi | Activity Closed Date: | 12/06/2007 | ||||||||
02/08/2007 | Emergency Preparedness Information Activity | Ulrich, Chris A. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 02/08/2007 | ||||||||||
12/22/2006 | Attachment | Ulrich, Chris A. | |||||||||
12/20/2006 | Attachment | Ulrich, Chris A. | |||||||||
12/19/2006 | Site Inspection Activity Closed | Ulrich, Chris A. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 12/19/2006 | ||||||||||
Activity Closed Date: | 12/19/2006 | Activity Closed By: | ULRICH_CA_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 12/19/2006 | User: | ULRICH_CA_1 | ||||||||
Description: | Checked all sumps (3), fills (3) and under dispenser liners (2) - All OK. Monthly visual inspection records and SIRs reports provided by corporate HQ. All SIR results pass, except one inconclusive on the premium UST in September 2006. The inconclusive did not repeat in October 2006. Current registration placard is posted. | ||||||||||
09/27/2006 | Emergency Preparedness Information Activity | Ulrich, Chris A. | |||||||||
Activity Result: | Satisfied | Activity Status: | Closed | ||||||||
Activity Closed Date: | 09/27/2006 | ||||||||||
01/17/2006 | Legacy Activity | Stewart, Thomas | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
11/17/2004 | Legacy Activity | Ulrich, Chris A. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
09/04/2003 | Legacy Activity | Unknown, User | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
09/29/2002 | Legacy Activity | Cowan, Donna | |||||||||
Activity Name: | TELEPHONE CONVERSATION | Activity Status: | Closed | ||||||||
09/29/2002 | Legacy Activity | Cowan, Donna | |||||||||
Activity Name: | COMPLIANCE W/O FORMAL ENFORCEMENT ACTION | Activity Status: | Closed | ||||||||
08/07/2002 | Violation Closed | Cowan, Donna | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 400(2)(a)6 | ||||||||||
08/07/2002 | Legacy Activity | Cowan, Donna | |||||||||
Activity Name: | NON-COMPLIANCE LETTER ISSUED | Activity Status: | Closed | ||||||||
08/07/2002 | Legacy Activity | Cowan, Donna | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
08/07/2002 | Violation Closed | Cowan, Donna | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 700(1)(c)1 | ||||||||||
10/05/2001 | Legacy Activity | Cowan, Donna | |||||||||
Activity Name: | NON-COMPLIANCE LETTER ISSUED | Activity Status: | Closed | ||||||||
10/04/2001 | Violation Closed | Cowan, Donna | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 700(1)(c)1 | ||||||||||
10/04/2001 | Legacy Activity | Cowan, Donna | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
09/18/2000 | Legacy Activity | Cowan, Donna | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
10/01/1999 | Legacy Activity | Cowan, Donna | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
10/08/1998 | Legacy Activity | Cowan, Donna | |||||||||
Activity Name: | UST ROUTINE COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||