DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/30/2025        Last Data Refresh: 04/29/2025        Report Generated from DOPPLER
 
Facility ID: 8842061
Facility Name: TWO SISTERS CNTRY STORE
 
04/10/2025 Editable Letter Activity Paul, Jennifer
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 04/10/2025
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 04/10/2025
Comment: Submitted for approval by: Jennifer Paul
Events:
Event Type: Activity/Document has been approved Date: 04/10/2025
Comment: Approved by Shane Tierney: Return to compliance approved 4/10/25
Attachments:
Attachment Date: 04/10/2025 User: PAUL_JK
Description: Return to Compliance Letter
View Attachment
03/30/2025 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Bob Wood Activity Closed Date: 03/30/2025
Events:
Event Type: Activity has been finished Date: 03/30/2025
Comment: Finished
03/30/2025 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Bob Wood Activity Closed Date: 03/30/2025
Events:
Event Type: Activity has been finished Date: 03/30/2025
Comment: Finished
03/30/2025 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 03/30/2025 Activity Status: Closed
Date: 03/30/2025
Recipient: Bob Wood
Sender: M Keim
Subject: TCI
Message: E-mail correspondence with Bob Wood regarding TCI scheduling and records needed.
Events:
Event Type: Activity has been finished Date: 03/30/2025
Comment: Finished
03/30/2025 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 03/30/2025 Activity Status: Closed
Date: 03/30/2025
Recipient: Tonmoy Rahim, Bob Wood
Sender: M Keim
Subject: TCI report
Message: Storage tank inspection report and compliance letter sent via e-mail to Tonmoy Rahim, tonmoy.rahim@yahoo.com and Bob Wood, bobwoodspci@icloud.com
Events:
Event Type: Activity has been finished Date: 03/30/2025
Comment: Finished
03/21/2025 Site Inspection Activity Closed Keim, Michael J
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/23/2025
Activity Closed Date: 03/30/2025 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 03/30/2025
Comment: Finished
Comments:
Comment Date: 03/30/2025 User: KEIM_MJ_1
Description: Storage tank inspection report and compliance letter sent via e-mail to Tonmoy Rahim, tonmoy.rahim@yahoo.com and Bob Wood, bobwoodspci@icloud.com Compliance assist with Anthony Gomez of SPCI
03/11/2024 Enforcement Tracking Activity Dallas, Richard D
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 04/10/2025
Events:
Event Type: Activity has been finished Date: 04/10/2025
Comment: Finished
05/31/2023 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 6001
Rule: 62-761.100(3)
05/31/2023 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 05/31/2023
Comment: Sent
Events:
Event Type: Activity has been finished Date: 05/31/2023
Comment: Finished
Attachments:
Attachment Date: 05/31/2023 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
05/31/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 05/31/2023 Activity Status: Closed
Date: 05/31/2023
Recipient: Tomoy
Sender: M Keim
Subject: TCI scheduling
Message: Text correspondence with Tomoy regarding TCI scheduling and records needed.
Events:
Event Type: Activity has been finished Date: 05/31/2023
Comment: Finished
05/31/2023 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 05/31/2023 Activity Status: Closed
Date: 05/31/2023
Recipient: Mohamed Rahim
Sender: M Keim
Subject: TCI report
Message: Storage tank inspection and compliance letter sent via e-mail to Mohamed Rahim, mrahim1978@yahoo.com
Events:
Event Type: Activity has been finished Date: 05/31/2023
Comment: Finished
05/25/2023 Site Inspection Activity Closed Keim, Michael J
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/12/2023
Activity Closed Date: 05/31/2023 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 05/31/2023
Comment: Finished
Comments:
Comment Date: 05/31/2023 User: KEIM_MJ_1
Description: Storage tank inspection and compliance letter sent via e-mail to Mohamed Rahim, mrahim1978@yahoo.com
10/17/2022 Meeting Activity Keim, Michael J
Activity Closed Date: 10/17/2022 Activity Status: Closed
Location: Dixie One Stop facility
Subject: Met with Mohamed Rahim during the routine inspection at Dixie One Stop facility and discussed inspecting Two Sisters Country Store but was unable to confirm a date.
Events:
Event Type: Activity has been finished Date: 10/17/2022
Comment: Finished
10/17/2022 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 10/17/2022 Activity Status: Closed
Date: 10/17/2022
Recipient: Mohamed Rahim
Sender: M Keim
Subject: Request for information regarding outstanding violations and Two Sisters Country Store.
Message: Outstanding violations at Two Sisters store Michael Keim Mr. Rahim, Please contact me as soon as possible to discuss outstanding violations at the Two Sisters Store in Old Town. This store has existing violations that I would like to clear before the end of the week. For your records I have attached the last report to view the violations. This facility will be referred to enforcement this week Sincerely,
Events:
Event Type: Activity has been finished Date: 10/17/2022
Comment: Finished
10/17/2022 Enforcement Referral Activity Keim, Michael J
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/11/2024
Events:
Event Type: Activity has been submitted for approval Date: 10/17/2022
Comment: Submitted for approval by: Michael J Keim: Please accept this referral for enforcement as several attempts were made to schedule a routine inspection and resolve existing violations at this facility (please see memo in attachments.)
Events:
Event Type: Activity has been finished Date: 03/11/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 03/11/2024
Comment: Accepted by Richard D Dallas: Accepted
Events:
Event Type: Activity has been assigned Date: 02/29/2024
Comment: Assigned to Richard D Dallas
Events:
Event Type: Activity/Document was acknowledged on this date Date: 02/29/2024
Comment: Acknowledged and Assigned by Brierra Mack
Comments:
Comment Date: 10/17/2022 User: KEIM_MJ_1
Description: Please accept this referral for enforcement as several attempts were made to schedule a routine inspection and resolve existing violations at this facility (please see memo in attachments.)
Comments:
Comment Date: 10/17/2022 User: KEIM_MJ_1
Description: Please accept this referral for enforcement as several attempts were made to schedule a routine inspection and resolve existing violations at this facility (please see memo in attachments.)
10/17/2022 Enforcement Referral Activity Keim, Michael J
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/11/2024
Events:
Event Type: Activity has been submitted for approval Date: 10/17/2022
Comment: Submitted for approval by: Michael J Keim: Please accept this referral for enforcement as several attempts were made to schedule a routine inspection and resolve existing violations at this facility (please see memo in attachments.)
Events:
Event Type: Activity has been finished Date: 03/11/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 03/11/2024
Comment: Accepted by Richard D Dallas: Accepted
Events:
Event Type: Activity has been assigned Date: 02/29/2024
Comment: Assigned to Richard D Dallas
Events:
Event Type: Activity/Document was acknowledged on this date Date: 02/29/2024
Comment: Acknowledged and Assigned by Brierra Mack
Comments:
Comment Date: 10/17/2022 User: KEIM_MJ_1
Description: Please accept this referral for enforcement as several attempts were made to schedule a routine inspection and resolve existing violations at this facility (please see memo in attachments.)
Comments:
Comment Date: 10/17/2022 User: KEIM_MJ_1
Description: Please accept this referral for enforcement as several attempts were made to schedule a routine inspection and resolve existing violations at this facility (please see memo in attachments.)
10/17/2022 Phone Conversation Activity Keim, Michael J
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 356-7046 Activity Closed Date: 10/17/2022
Subject: Left phone message for Mohamed Rahim regarding outstanding violations at Two Sisters Country Store.
Events:
Event Type: Activity has been finished Date: 10/17/2022
Comment: Finished
06/14/2021 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4007
Rule: 62-761.400(4), 62-761.400(4)(a), 62-761.400(4)(b), 62-761.400(4)(c), 62-761.400(4)(d), 62-761.400(4)(e), 62-761.400(4)(f)
06/14/2021 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 06/14/2021 Activity Status: Closed
Date: 06/14/2021
Recipient: Mohamed Rahim
Sender: M Keim
Subject: TCI report
Message: Storage tank inspection report and compliance letter sent via e-mail to Mohamed Rahim, mrahim1978@yahoo.com
Events:
Event Type: Activity has been finished Date: 06/14/2021
Comment: Finished
06/14/2021 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/14/2021
Comment: Finished
Events:
Event Type: Document has been sent Date: 06/14/2021
Comment: Sent
Attachments:
Attachment Date: 06/14/2021 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
06/14/2021 Meeting Activity Keim, Michael J
Activity Closed Date: 06/14/2021 Activity Status: Closed
Location: Two Sisters facility
Subject: Met with Fayfal (store clerk) to schedule TCI and inform of records needed. Clerk stated that the owner was out of the country and would not return until June 2021.
Events:
Event Type: Activity has been finished Date: 06/14/2021
Comment: Finished
06/14/2021 Violation Closed Keim, Michael J
Significance: SNC-B Status: Closed
Criteria ID: 4014
Rule: 62-761.420(2)
06/14/2021 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4067
Rule: 62-761.600(4)
06/14/2021 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4074
Rule: 62-761.700(2)(c)
06/14/2021 Violation Closed Keim, Michael J
Significance: SNC-B Status: Closed
Criteria ID: 4059
Rule: 62-761.600(1)(d), 62-761.600(1)(e)
06/14/2021 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4077
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1., 62-761.700(3)(b)2.
05/07/2021 Site Inspection Activity Closed Keim, Michael J
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/07/2021
Activity Closed Date: 06/14/2021 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 06/14/2021
Comment: Finished
Comments:
Comment Date: 06/14/2021 User: KEIM_MJ_1
Description: Storage tank inspection report and compliance letter sent via e-mail to Mohamed Rahim, mrahim1978@yahoo.com Compliance assist with Charlotte Mauldin Please address the noted violations as soon as possible and forward all documents to the inspector to address them.
05/20/2018 Comment Keim, Michael J
Description: Facility contact information: Mohamed Rahim, mrahim1978@yahoo.com phone: 352-356-7046
05/20/2018 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 05/20/2018 Activity Status: Closed
Date: 05/20/2018
Recipient: Mohamed Rahim
Sender: M Keim
Subject: TCI report
Message: Sent TCI report, CAO letter, guidance and INF form to Mohamed Rahim, mrahim1978@yahoo.com
Events:
Event Type: Activity has been finished Date: 05/20/2018
Comment: Finished
05/20/2018 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Description: In Compliance Letter
Events:
Event Type: Activity has been finished Date: 05/20/2018
Comment: Finished
Events:
Event Type: Document has been sent Date: 05/20/2018
Comment: Sent
Attachments:
Attachment Date: 05/20/2018 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
05/20/2018 Phone Conversation Activity Keim, Michael J
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 356-7046 Activity Closed Date: 05/20/2018
Subject: Spoke with Mohamed Rahim regarding TCI scheduling and records needed.
Events:
Event Type: Activity has been finished Date: 05/20/2018
Comment: Finished
05/20/2018 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4067
Rule: 62-761.600(4)
05/20/2018 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4057
Rule: 62-761.500(7)(e)
05/20/2018 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4079
Rule: 62-761.710(2), 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d)
05/20/2018 Violation Closed Keim, Michael J
Significance: Minor Status: Closed
Criteria ID: 4068
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1., 62-761.700(1)(a)2.
05/20/2018 Attachment Keim, Michael J
05/17/2018 Site Inspection Activity Closed Keim, Michael J
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 05/17/2018
Activity Closed Date: 05/20/2018 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 05/20/2018
Comment: Finished
Comments:
Comment Date: 05/20/2018 User: KEIM_MJ_1
Description: Tank Compliance Inspection Report and Compliance Assistance Letter sent via e-mail to Mohamed Rahim, mrahim1978@yahoo.com Compliance assistance with Mohamed Rahim Note: (3) violations were cited 1 and 2) Annual testing (operability, line leak detectors and overfill prevention) have not been conducted as of this inspection report. 3) Damaged piping entry fittings in the (STP) sumps and dispenser liners. This violation will require an incident notification form to be completed and submitted. (form attached to e-mail). Also due to insufficient records provided during facility inspection and visual observations a closure assessment (sampling) will be required. Also included: An incident notification form and incident guidance explaining steps to follow regarding the damaged piping entry fittings.
11/19/2015 Editable Letter Activity Graham, David L.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 11/19/2015
Comment: Finished
Events:
Event Type: Document has been sent Date: 11/19/2015
Comment: Sent on Thu Nov 19 00:00:00 EST 2015
Attachments:
Attachment Date: 11/19/2015 User: GRAHAM_DL_1
Description: 2nd NCL 11-19-15
View Attachment
11/19/2015 Record Document Activity Graham, David L.
Activity Status: Closed
Contact Name: Faxed Activity Closed Date: 11/19/2015
Events:
Event Type: Activity has been finished Date: 11/19/2015
Comment: Finished
09/30/2015 Editable Letter Activity Graham, David L.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 09/30/2015
Comment: Sent on Wed Sep 30 00:00:00 EDT 2015
Events:
Event Type: Activity has been finished Date: 09/30/2015
Comment: Finished
Attachments:
Attachment Date: 09/30/2015 User: GRAHAM_DL_1
Description: NCL 09-30-15
View Attachment
09/17/2015 Violation Closed Graham, David L.
Significance: SNC-B Status: Closed
Criteria ID: 1004
Rule: 62-761.400(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2).
09/17/2015 Violation Closed Graham, David L.
Significance: Minor Status: Closed
Criteria ID: 1063
Rule: 62-761.600(1)(e)
Comments: The electronic monitoring unit is a system consisting of a sensor, wiring, and a panel. The sensor and the component that it monitors are exempt from the visual inspection process. However, the proper operation of the remainder of the electronic system must be verified on a monthly basis. One way to test is to activate the panel alarm switch. Depending on the system in place this test may check the alarm light, alarm horn, or the circuit continuity between the panel and the remote sensor. This test procedure must be documented by the facility, as required in rule 62-761.710(2). The remote verification feature meets this requirement, such as the Veeder-Root Simplicity system.
09/17/2015 Violation Closed Graham, David L.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
09/16/2015 Site Inspection Activity Closed Graham, David L.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 09/17/2015
Activity Closed Date: 09/30/2015 Activity Closed By: GRAHAM_DL_1
Events:
Event Type: Activity has been finished Date: 09/30/2015
Comment: Finished
Comments:
Comment Date: 09/16/2015 User: GRAHAM_DL_1
Description: FILE REVIEW: 01. Prior phone call to facility to schedule a compliance inspection, inspection scheduled for 09/17/2015. RELEASE DETECTION: 01. Monthly visual inspections including spill containment buckets and dispenser liners. 02. Continuous electronic monitoring of sumps and tank interstice. 03. Mechanical in-line leak detectors.
09/10/2015 Phone Conversation Activity Graham, David L.
Call Type: Incoming Activity Status: Closed
Phone Number: (352) 542-8761 Activity Closed Date: 09/10/2015
Subject: Inspector phoned the facility, which is the listed contact number for the owner. Inspector requested the owner or a phone number to reach the owner. The clerk advised he could schedule the inspection. Inspection scheduled for 09/17/2015. Appt letter to be mailed with a link to the FDEP website.
Events:
Event Type: Activity has been finished Date: 09/10/2015
Comment: Finished
01/08/2014 Issue Document Activity Graham, David L.
Activity Status: Closed
Contact Name: Mohammed Rahim Activity Closed Date: 01/08/2014
Events:
Event Type: Activity has been finished Date: 01/08/2014
Comment: Finished
12/16/2013 Site Inspection Activity Closed Graham, David L.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/16/2013
Activity Closed Date: 01/08/2014 Activity Closed By: GRAHAM_DL_1
Events:
Event Type: Activity has been finished Date: 01/08/2014
Comment: Finished
Comments:
Comment Date: 12/16/2013 User: GRAHAM_DL_1
Description: FILE REVIEW: 01. Appointment letter mailed to facility/storage tank owner, inspection scheduled for 01/03/2014. RELEASE DETECTION: 01. Monthly visual inspections including spill containment buckets and dispenser liners. 02. Continuous electronic monitoring of sumps and tank interstice. 03. Mechanical in-line leak detectors.
04/19/2013 Meeting Activity Lubinski, David R.
Activity Closed Date: 04/19/2013 Activity Status: Closed
Location: at facility: 10252 NE HWY 349 OLD TOWN
Subject: Met with both owners, and completed a Compliance Assistance visit. See comments for details.
Events:
Event Type: Activity has been finished Date: 04/19/2013
Comment: Finished
Comments:
Comment Date: 04/19/2013 User: LUBINSKI_D
Description: Rahim Mohammed, owner, responded by phone to the April 10, 2013, Compliance Assistance Offer letter, which was sent after the facility was brought back into compliance. Met both owners in person at the site: Rahim Mohammed, and Kabir Homayoun, at 10252 NE Hwy 349 Old Town, Fl 32680. The non-compliance issues from January 2013 involved failure to test release detection devices annually, and failure to maintain certain required records, such as a pollution liability insurance policy and leak sensor status reports. In person, Rahim was cordial and receptive to talking about the rules. We specifically covered the procedure for printing the sensor status reports every month, about annual device testing, and about presenting the correct records for the compliance inspection. We also opened up the sumps and lids to the storage tank system, where I showed the exact locations of the piping sump sensors, the tank interstitial sensor, the Automatic Tank Gauge sensor, and the piping leak detectors. Rahim takes pride in keeping his system very clean every month, and in basic maintenance such as changing his own fuel filters since contractors aren¿t always careful, and carefully monitoring the fill process since he feels the drivers don¿t always follow all procedures. The sumps are indeed very clean, free of debris and dry. I handed out the Compliance Assistance Tool for Storage Tank Facilities, and we covered it by circling the items pertinent to Rahim¿s system.
04/12/2013 Phone Conversation Activity Lubinski, David R.
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 542-8761 Activity Closed Date: 04/12/2013
Subject: Mr. Rahim was suspicious, but responded to 4/8/2013 CA offer letter, and then accepted offer - See comments for details.
Events:
Event Type: Activity has been finished Date: 04/12/2013
Comment: Finished
Comments:
Comment Date: 04/12/2013 User: LUBINSKI_D
Description: Received CA offer letter, doesn't understand, please call back. Returned call, Mr. Rahim was a little suspicious - mentioned his compliance issues were resolved (they are) and are there further issues (there are not). I explained about the compliance assistance visit, that its not an inspection, its informal, and I will offer advice to comply with 761 rules and pass the next compliance inspection. Mr. Rahim said ¿Really? no cost, its free?¿ (yes its free). Mr. Rahim was interested, and we set an appointment for Wednesday April 17 at 10:30 am.
04/08/2013 Issue Document Activity Lubinski, David R.
Activity Status: Closed
Contact Name: to: Ehsan, Inc. Activity Closed Date: 04/08/2013
Events:
Event Type: Activity has been finished Date: 04/08/2013
Comment: Finished
03/12/2013 Attachment Graham, David L.
03/12/2013 Record Document Activity Graham, David L.
Activity Status: Closed
Contact Name: Paticia Collins Activity Closed Date: 03/12/2013
Events:
Event Type: Activity has been finished Date: 03/12/2013
Comment: Finished
03/12/2013 Record Document Activity Graham, David L.
Activity Status: Closed
Contact Name: Mohammed Rahim Activity Closed Date: 03/12/2013
Events:
Event Type: Activity has been finished Date: 03/12/2013
Comment: Finished
01/15/2013 Phone Conversation Activity Graham, David L.
Call Type: Incoming Activity Status: Closed
Activity Closed Date: 01/15/2013
Subject: Inspector contacted by Mohammed with Two Sisters Country Store. He reported he believed he had all items needed to return the facility to compliance. He reported signing the updated registration form. He indicated starting the monthly visual inspections. Mohammed advised he would fax the information he had and the testing results which were being completed by Petrolwum Compliance SW Inc would be provided by the company performing the work.
Events:
Event Type: Activity has been finished Date: 01/15/2013
Comment: Finished
01/04/2013 Editable Letter Activity Graham, David L.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/04/2013
Comment: Finished
Events:
Event Type: Document has been sent Date: 01/04/2013
Comment: Sent on Fri Jan 04 00:00:00 EST 2013
Attachments:
Attachment Date: 01/04/2013 User: GRAHAM_DL_1
Description: NCL 01-04-13
View Attachment
01/04/2013 Emergency Preparedness Information Activity Graham, David L.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 01/04/2013
Events:
Event Type: Activity has been finished Date: 01/04/2013
Comment: Finished
12/21/2012 Violation Closed Graham, David L.
Significance: SNC-B Status: Closed
Criteria ID: 1004
Rule: 62-761.400(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2).
12/21/2012 Violation Closed Graham, David L.
Significance: Minor Status: Closed
Criteria ID: 1063
Rule: 62-761.600(1)(e)
Comments: The electronic monitoring unit is a system consisting of a sensor, wiring, and a panel. The sensor and the component that it monitors are exempt from the visual inspection process. However, the proper operation of the remainder of the electronic system must be verified on a monthly basis. One way to test is to activate the panel alarm switch. Depending on the system in place this test may check the alarm light, alarm horn, or the circuit continuity between the panel and the remote sensor. This test procedure must be documented by the facility, as required in rule 62-761.710(2). The remote verification feature meets this requirement, such as the Veeder-Root Simplicity system.
12/21/2012 Violation Closed Graham, David L.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
12/12/2012 Site Inspection Activity Closed Graham, David L.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 12/21/2012
Activity Closed Date: 01/04/2013 Activity Closed By: GRAHAM_DL_1
Events:
Event Type: Activity has been finished Date: 01/04/2013
Comment: Finished
Comments:
Comment Date: 12/12/2012 User: GRAHAM_DL_1
Description: FILE REVIEW: 01. Appointment letter mailed to facility/storage tank owner, inspection scheduled for 12/21/2012. RELEASE DETECTION: 01. Monthly visual inspections including spill containment buckets and dispenser liners. 02. Continuous electronic monitoring of sumps and tank interstice. 03. Mechanical in-line leak detectors.
01/04/2012 Violation Closed Graham, David L.
Significance: Minor Status: Closed
Criteria ID: 1020
Rule: 62-761.500(1)(d)5.
Comments: The breach of integrity test is intended for closed interstices only. A closed interstice has no unsecured or unsealed opening to the outside. Double-walled piping without a boot connector, or if the boot has a bleed valve (for tightness testing), is considered an open interstice. The breach of integrity test may be performed by using at least one of the following methods: a. A continuous hydrostatic system b. A continuous vacuum system c. Testing of the interstice for liquid tightness in accordance with manufacturer's installation instructions; or d. Another method in accordance with subsection 62-761.850(2). How the breach of integrity test is performed or to what degree can depend on the depth to groundwater at each facility. When the tank and or piping are fully submerged, the lack of water intrusion into the secondary containment may be considered a verification of its integrity. However, when total submersion is not the case, one of the rule stipulated options must be used. The breach of integrity test should not be confused with a precision tightness test, which tests the primary tank or piping only. The breach of integrity test will test the secondary and primary shells, but is not a precision test.
06/09/2011 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/08/2011
Activity Closed Date: 06/09/2011 Activity Closed By: SNIPES_SR_1
Events:
Event Type: Activity has been finished Date: 06/09/2011
Comment: Finished
06/09/2011 Issue Document Activity Snipes, Stephen R.
Activity Status: Closed
Contact Name: Mohammed Rahim Activity Closed Date: 06/09/2011
Events:
Event Type: Activity has been finished Date: 06/09/2011
Comment: Finished
Comments:
Comment Date: 06/09/2011 User: SNIPES_SR_1
Description: Madison County Health Department generated re-inspection cover letter mailed to storage tank owner/manager on 6/9/2011.
04/05/2011 Phone Conversation Activity Snipes, Stephen R.
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 542-8761 Activity Closed Date: 04/05/2011
Subject: Phone call to Mr. Kabir (Facility/Storage Tank Owner) concerning required annual testing that had not been completed. Mr. Kabir stated that the testing had been completed. No test results have been recieved at the Madison County Health Department. Mr. Kabir was told that two Non-compliance letters had been sent to him and no response has been recieved. The next step for me would be to refer this file to the Northeast District DEP Department in Jacksonville.
Events:
Event Type: Activity has been finished Date: 04/05/2011
Comment: Finished
03/02/2011 Editable Letter Activity Snipes, Stephen R.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/02/2011
Comment: Finished
Events:
Event Type: Document has been sent Date: 03/02/2011
Comment: Sent on Wed Mar 02 00:00:00 EST 2011
Attachments:
Attachment Date: 03/02/2011 User: SNIPES_SR_1
Description: 2nd Non-Compliance Letter Mailed 3/2/2011
View Attachment
01/28/2011 Attachment Snipes, Stephen R.
01/28/2011 Emergency Preparedness Information Activity Snipes, Stephen R.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 01/28/2011
Events:
Event Type: Activity has been finished Date: 01/28/2011
Comment: Finished
01/28/2011 Attachment Snipes, Stephen R.
01/28/2011 Attachment Snipes, Stephen R.
01/26/2011 Editable Letter Activity Snipes, Stephen R.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/26/2011
Comment: Finished
Events:
Event Type: Document has been sent Date: 01/26/2011
Comment: Sent on Wed Jan 26 00:00:00 EST 2011
Attachments:
Attachment Date: 01/26/2011 User: SNIPES_SR_1
Description: 1ST Non-Compliance Letter Mailed 1-26-2011
View Attachment
01/18/2011 Violation Closed Snipes, Stephen R.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
01/18/2011 Violation Closed Snipes, Stephen R.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
01/10/2011 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/18/2011
Activity Closed Date: 01/26/2011 Activity Closed By: SNIPES_SR_1
Events:
Event Type: Activity has been finished Date: 01/26/2011
Comment: Finished
Comments:
Comment Date: 01/10/2011 User: SNIPES_SR_1
Description: Phone conversation with facility/storage tank owner to schedule annual compliance inspection. Inspection scheduled for 1/18/2011. Appointment letter mailed to facility/storage tank owner on 1/10/2011.
01/10/2011 Issue Document Activity Snipes, Stephen R.
Activity Status: Closed
Contact Name: Homayoun Kabir Activity Closed Date: 01/10/2011
Events:
Event Type: Activity has been finished Date: 01/10/2011
Comment: Finished
Comments:
Comment Date: 01/10/2011 User: SNIPES_SR_1
Description: Madison County Health Department generated appointment letter for upcoming annual compliance inspection mailed to facility/storage tank owner.
04/30/2010 Issue Document Activity Snipes, Stephen R.
Activity Status: Closed
Contact Name: Homayoun Kabir Activity Closed Date: 04/30/2010
Events:
Event Type: Activity has been finished Date: 04/30/2010
Comment: Finished
Comments:
Comment Date: 04/30/2010 User: SNIPES_SR_1
Description: Madison County Health Department generated inspection cover letter mailed to facility owner.
04/30/2010 Emergency Preparedness Information Activity Snipes, Stephen R.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 04/30/2010
Events:
Event Type: Activity has been finished Date: 04/30/2010
Comment: Finished
04/15/2010 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/21/2010
Activity Closed Date: 04/30/2010 Activity Closed By: SNIPES_SR_1
Events:
Event Type: Activity has been finished Date: 04/30/2010
Comment: Finished
Comments:
Comment Date: 04/15/2010 User: SNIPES_SR_1
Description: Phone conversation with facility owner to confirm annual compliance inspection. Inspection scheduled for 4/21/2010.
04/15/2010 Issue Document Activity Snipes, Stephen R.
Activity Status: Closed
Contact Name: Mohammed Rahim Activity Closed Date: 04/15/2010
Events:
Event Type: Activity has been finished Date: 04/15/2010
Comment: Finished
Comments:
Comment Date: 04/15/2010 User: SNIPES_SR_1
Description: Appointment letter for annual compliance inspection scheduled for 4/21/2010 mailed to facility owner.
08/11/2009 Issue Document Activity Snipes, Stephen R.
Activity Status: Closed
Contact Name: Mohammed Rahim Activity Closed Date: 08/11/2009
Comments:
Comment Date: 08/11/2009 User: SNIPES_SR_1
Description: Madison County Health Department generated Compliance Letter mailed to facility owner.
07/31/2009 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/31/2009
Activity Closed Date: 08/11/2009 Activity Closed By: SNIPES_SR_1
Comments:
Comment Date: 07/31/2009 User: SNIPES_SR_1
Description: RE-INSPECTION ON 7-30-2009 01. Inspection of discrepancies noted during the Annual Compliance Inspection completed on 6/22/2009. Discrepancies have been corrected. A. Diesel leak over shear valve was repaired on 7/28/2009 by Bryco Fueling Solutions. B. Insurance documentation page was reviewed: Zurich-American Insurance Company- Policy Number: USC 9418586 03 1M/1M Coverage 5/15/2009-5/15/2010. C. Annual operability test completed on Automatic Tank Gauge/sensors on 7/22/2009 by Petroleum Compliance Solutions Inc. Tests passed. D. Annual test for the mechanical in-line leak detectors completed on 7/22/2009 by Petroleum Compliance Solutions Inc. Tests passed. NOTE: FIRST COMPUTER SHOWING INCORRECT DATES. RE-INSPECTION COMPLETED ON 7-30-2009. No discrepancies noted during the Re-inspection. Inspection report completed in office. Report mailed to facility owner.
06/22/2009 Violation Closed Snipes, Stephen R.
Significance: SNC-B Status: Closed
Criteria ID: 1004
Rule: 62-761.400(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2).
06/22/2009 Emergency Preparedness Information Activity Snipes, Stephen R.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/22/2009
Comments:
Comment Date: 06/22/2009 User: SNIPES_SR_1
Description: Facility has Two (2) dispensers on site.
06/22/2009 Editable Letter Activity Snipes, Stephen R.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Comments:
Comment Date: 06/22/2009 User: SNIPES_SR_1
Description: Madison County Health Department generated Non-Compliance Letter mailed to facility owner on 6-22-2009.
06/22/2009 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 06/22/2009
Activity Closed Date: 06/22/2009 Activity Closed By: SNIPES_SR_1
Comments:
Comment Date: 06/22/2009 User: SNIPES_SR_1
Description: Phone conversation with facility manager to confirm annual compliance inspection for 6/22/2009.
06/22/2009 Violation Closed Snipes, Stephen R.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
06/22/2009 Violation Closed Snipes, Stephen R.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
06/22/2009 Violation Closed Snipes, Stephen R.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
06/20/2008 Emergency Preparedness Information Activity Snipes, Stephen R.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/20/2008
Comments:
Comment Date: 06/20/2008 User: SNIPES_SR_1
Description: Facility has two (2) dispensers on site.
06/10/2008 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/10/2008
Activity Closed Date: 06/18/2008 Activity Closed By: SNIPES_SR_1
04/03/2008 Emergency Preparedness Information Activity Snipes, Stephen R.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 04/03/2008
Comments:
Comment Date: 04/03/2008 User: SNIPES_SR_1
Description: Facility was upgraded in February 2008 with new double-walled underground storage tank and Two (2) new dispensers.
03/19/2008 TCAR Activity Snipes, Stephen R.
Activity Result: Complete Activity Status: Closed
Activity Closed Date: 03/19/2008
03/19/2008 Editable Letter Activity Snipes, Stephen R.
Activity Title: Closure Review Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 03/19/2008
Comment: Sent on Wed Mar 19 16:29:57 EST 2008
Comments:
Comment Date: 03/19/2008 User: SNIPES_SR_1
Description: Sent Madison County generated review letter to facility owner.
01/04/2008 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/04/2008
Activity Closed Date: 02/19/2008 Activity Closed By: SNIPES_SR_1
Comments:
Comment Date: 01/16/2008 User: SNIPES_SR_1
Description: SITE INSPECTION Completed soap test on primary fiberglass piping AO Smith double-walled fiberglass piping. 50 lbs pressure No leaks observed.
Comments:
Comment Date: 01/18/2008 User: SNIPES_SR_1
Description: SITE INSPECTION: Soap test completed on secondary piping. 5 lbs pressure. No leaks observed. Hydro static test completed on sumps, spill containment buckets and dispenser liners.All Passed.
Comments:
Comment Date: 02/07/2008 User: SNIPES_SR_1
Description: FINAL INSPECTION: 01. ATG: Alarm tested: All functions normal. Liquid sensors tested: All functions normal. Completed printout. 02. Financial Responsibility reviewed. Updated new tank information has been added. 03. Shear valves mounted and tight. 04. Inspection report reviewed with owner. 05. Talked to owner about required information needed at this facility to maintain compliance with Chapter 62-761. F.A.C. TEST RESULTS REVIEWED: 01. Tank and line tightness test completed by Bryco on 1/31/2008. Passed. Due 1/31/2018. 02. Annual in-line leak detector test completed by Bryco on 1/31/2008. Passed. Due 1/31/2009. 03. Annual operability test on ATG completed by Bryco on 1/31/2008. Passed. Due 1/31/2009. RELEASE DETECTION: 01. Mechanical in-line leak detectors. 02. Continuous electronic monitoring of sumps/interstice. 03. Monthly visual inspections of sumps, spill containment buckets and dispenser liners. System is in compliance with Chapter 62-761,F.A.C.
Comments:
Comment Date: 01/04/2008 User: SNIPES_SR_1
Description: SITE INSPECTION: INSTALLATION OF ONE 22,000 GALLON DOUBLE-WALLED STEEL COMPARTMENTED HIGHLAND UST. TANK: Double-walled Highland UST-EQ#506 SUMPS: OPW Pisces fiberglass-EQ#368. FILLS:EMCO Wheaton spill containment bucket-EQ#524 PIPING:A O Smith Red Thread II2 Double-walled Fiberglass-EQ#252. DISPENSER LINERS: OPW Pisces Fiberglass-EQ#368. ATG: Veedor-Root TLS 300-EQ#614. 01. UST onsite 02. Contractor installing tank- Bryco Fueling Systems-PSCC 051722. 03. 14 inches of vacuum on tank interstice .
Comments:
Comment Date: 01/08/2008 User: SNIPES_SR_1
Description: SITE VISIT: CONTRACTOR INSTALLING SUMPS.
01/04/2008 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/04/2008
Activity Closed Date: 02/19/2008 Activity Closed By: SNIPES_SR_1
Comments:
Comment Date: 01/16/2008 User: SNIPES_SR_1
Description: SITE INSPECTION Completed soap test on primary fiberglass piping AO Smith double-walled fiberglass piping. 50 lbs pressure No leaks observed.
Comments:
Comment Date: 01/18/2008 User: SNIPES_SR_1
Description: SITE INSPECTION: Soap test completed on secondary piping. 5 lbs pressure. No leaks observed. Hydro static test completed on sumps, spill containment buckets and dispenser liners.All Passed.
Comments:
Comment Date: 02/07/2008 User: SNIPES_SR_1
Description: FINAL INSPECTION: 01. ATG: Alarm tested: All functions normal. Liquid sensors tested: All functions normal. Completed printout. 02. Financial Responsibility reviewed. Updated new tank information has been added. 03. Shear valves mounted and tight. 04. Inspection report reviewed with owner. 05. Talked to owner about required information needed at this facility to maintain compliance with Chapter 62-761. F.A.C. TEST RESULTS REVIEWED: 01. Tank and line tightness test completed by Bryco on 1/31/2008. Passed. Due 1/31/2018. 02. Annual in-line leak detector test completed by Bryco on 1/31/2008. Passed. Due 1/31/2009. 03. Annual operability test on ATG completed by Bryco on 1/31/2008. Passed. Due 1/31/2009. RELEASE DETECTION: 01. Mechanical in-line leak detectors. 02. Continuous electronic monitoring of sumps/interstice. 03. Monthly visual inspections of sumps, spill containment buckets and dispenser liners. System is in compliance with Chapter 62-761,F.A.C.
Comments:
Comment Date: 01/04/2008 User: SNIPES_SR_1
Description: SITE INSPECTION: INSTALLATION OF ONE 22,000 GALLON DOUBLE-WALLED STEEL COMPARTMENTED HIGHLAND UST. TANK: Double-walled Highland UST-EQ#506 SUMPS: OPW Pisces fiberglass-EQ#368. FILLS:EMCO Wheaton spill containment bucket-EQ#524 PIPING:A O Smith Red Thread II2 Double-walled Fiberglass-EQ#252. DISPENSER LINERS: OPW Pisces Fiberglass-EQ#368. ATG: Veedor-Root TLS 300-EQ#614. 01. UST onsite 02. Contractor installing tank- Bryco Fueling Systems-PSCC 051722. 03. 14 inches of vacuum on tank interstice .
Comments:
Comment Date: 01/08/2008 User: SNIPES_SR_1
Description: SITE VISIT: CONTRACTOR INSTALLING SUMPS.
01/04/2008 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/04/2008
Activity Closed Date: 02/19/2008 Activity Closed By: SNIPES_SR_1
Comments:
Comment Date: 01/16/2008 User: SNIPES_SR_1
Description: SITE INSPECTION Completed soap test on primary fiberglass piping AO Smith double-walled fiberglass piping. 50 lbs pressure No leaks observed.
Comments:
Comment Date: 01/18/2008 User: SNIPES_SR_1
Description: SITE INSPECTION: Soap test completed on secondary piping. 5 lbs pressure. No leaks observed. Hydro static test completed on sumps, spill containment buckets and dispenser liners.All Passed.
Comments:
Comment Date: 02/07/2008 User: SNIPES_SR_1
Description: FINAL INSPECTION: 01. ATG: Alarm tested: All functions normal. Liquid sensors tested: All functions normal. Completed printout. 02. Financial Responsibility reviewed. Updated new tank information has been added. 03. Shear valves mounted and tight. 04. Inspection report reviewed with owner. 05. Talked to owner about required information needed at this facility to maintain compliance with Chapter 62-761. F.A.C. TEST RESULTS REVIEWED: 01. Tank and line tightness test completed by Bryco on 1/31/2008. Passed. Due 1/31/2018. 02. Annual in-line leak detector test completed by Bryco on 1/31/2008. Passed. Due 1/31/2009. 03. Annual operability test on ATG completed by Bryco on 1/31/2008. Passed. Due 1/31/2009. RELEASE DETECTION: 01. Mechanical in-line leak detectors. 02. Continuous electronic monitoring of sumps/interstice. 03. Monthly visual inspections of sumps, spill containment buckets and dispenser liners. System is in compliance with Chapter 62-761,F.A.C.
Comments:
Comment Date: 01/04/2008 User: SNIPES_SR_1
Description: SITE INSPECTION: INSTALLATION OF ONE 22,000 GALLON DOUBLE-WALLED STEEL COMPARTMENTED HIGHLAND UST. TANK: Double-walled Highland UST-EQ#506 SUMPS: OPW Pisces fiberglass-EQ#368. FILLS:EMCO Wheaton spill containment bucket-EQ#524 PIPING:A O Smith Red Thread II2 Double-walled Fiberglass-EQ#252. DISPENSER LINERS: OPW Pisces Fiberglass-EQ#368. ATG: Veedor-Root TLS 300-EQ#614. 01. UST onsite 02. Contractor installing tank- Bryco Fueling Systems-PSCC 051722. 03. 14 inches of vacuum on tank interstice .
Comments:
Comment Date: 01/08/2008 User: SNIPES_SR_1
Description: SITE VISIT: CONTRACTOR INSTALLING SUMPS.
01/04/2008 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/04/2008
Activity Closed Date: 02/19/2008 Activity Closed By: SNIPES_SR_1
Comments:
Comment Date: 01/16/2008 User: SNIPES_SR_1
Description: SITE INSPECTION Completed soap test on primary fiberglass piping AO Smith double-walled fiberglass piping. 50 lbs pressure No leaks observed.
Comments:
Comment Date: 01/18/2008 User: SNIPES_SR_1
Description: SITE INSPECTION: Soap test completed on secondary piping. 5 lbs pressure. No leaks observed. Hydro static test completed on sumps, spill containment buckets and dispenser liners.All Passed.
Comments:
Comment Date: 02/07/2008 User: SNIPES_SR_1
Description: FINAL INSPECTION: 01. ATG: Alarm tested: All functions normal. Liquid sensors tested: All functions normal. Completed printout. 02. Financial Responsibility reviewed. Updated new tank information has been added. 03. Shear valves mounted and tight. 04. Inspection report reviewed with owner. 05. Talked to owner about required information needed at this facility to maintain compliance with Chapter 62-761. F.A.C. TEST RESULTS REVIEWED: 01. Tank and line tightness test completed by Bryco on 1/31/2008. Passed. Due 1/31/2018. 02. Annual in-line leak detector test completed by Bryco on 1/31/2008. Passed. Due 1/31/2009. 03. Annual operability test on ATG completed by Bryco on 1/31/2008. Passed. Due 1/31/2009. RELEASE DETECTION: 01. Mechanical in-line leak detectors. 02. Continuous electronic monitoring of sumps/interstice. 03. Monthly visual inspections of sumps, spill containment buckets and dispenser liners. System is in compliance with Chapter 62-761,F.A.C.
Comments:
Comment Date: 01/04/2008 User: SNIPES_SR_1
Description: SITE INSPECTION: INSTALLATION OF ONE 22,000 GALLON DOUBLE-WALLED STEEL COMPARTMENTED HIGHLAND UST. TANK: Double-walled Highland UST-EQ#506 SUMPS: OPW Pisces fiberglass-EQ#368. FILLS:EMCO Wheaton spill containment bucket-EQ#524 PIPING:A O Smith Red Thread II2 Double-walled Fiberglass-EQ#252. DISPENSER LINERS: OPW Pisces Fiberglass-EQ#368. ATG: Veedor-Root TLS 300-EQ#614. 01. UST onsite 02. Contractor installing tank- Bryco Fueling Systems-PSCC 051722. 03. 14 inches of vacuum on tank interstice .
Comments:
Comment Date: 01/08/2008 User: SNIPES_SR_1
Description: SITE VISIT: CONTRACTOR INSTALLING SUMPS.
01/04/2008 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/04/2008
Activity Closed Date: 02/19/2008 Activity Closed By: SNIPES_SR_1
Comments:
Comment Date: 01/16/2008 User: SNIPES_SR_1
Description: SITE INSPECTION Completed soap test on primary fiberglass piping AO Smith double-walled fiberglass piping. 50 lbs pressure No leaks observed.
Comments:
Comment Date: 01/18/2008 User: SNIPES_SR_1
Description: SITE INSPECTION: Soap test completed on secondary piping. 5 lbs pressure. No leaks observed. Hydro static test completed on sumps, spill containment buckets and dispenser liners.All Passed.
Comments:
Comment Date: 02/07/2008 User: SNIPES_SR_1
Description: FINAL INSPECTION: 01. ATG: Alarm tested: All functions normal. Liquid sensors tested: All functions normal. Completed printout. 02. Financial Responsibility reviewed. Updated new tank information has been added. 03. Shear valves mounted and tight. 04. Inspection report reviewed with owner. 05. Talked to owner about required information needed at this facility to maintain compliance with Chapter 62-761. F.A.C. TEST RESULTS REVIEWED: 01. Tank and line tightness test completed by Bryco on 1/31/2008. Passed. Due 1/31/2018. 02. Annual in-line leak detector test completed by Bryco on 1/31/2008. Passed. Due 1/31/2009. 03. Annual operability test on ATG completed by Bryco on 1/31/2008. Passed. Due 1/31/2009. RELEASE DETECTION: 01. Mechanical in-line leak detectors. 02. Continuous electronic monitoring of sumps/interstice. 03. Monthly visual inspections of sumps, spill containment buckets and dispenser liners. System is in compliance with Chapter 62-761,F.A.C.
Comments:
Comment Date: 01/04/2008 User: SNIPES_SR_1
Description: SITE INSPECTION: INSTALLATION OF ONE 22,000 GALLON DOUBLE-WALLED STEEL COMPARTMENTED HIGHLAND UST. TANK: Double-walled Highland UST-EQ#506 SUMPS: OPW Pisces fiberglass-EQ#368. FILLS:EMCO Wheaton spill containment bucket-EQ#524 PIPING:A O Smith Red Thread II2 Double-walled Fiberglass-EQ#252. DISPENSER LINERS: OPW Pisces Fiberglass-EQ#368. ATG: Veedor-Root TLS 300-EQ#614. 01. UST onsite 02. Contractor installing tank- Bryco Fueling Systems-PSCC 051722. 03. 14 inches of vacuum on tank interstice .
Comments:
Comment Date: 01/08/2008 User: SNIPES_SR_1
Description: SITE VISIT: CONTRACTOR INSTALLING SUMPS.
01/02/2008 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/02/2008
Activity Closed Date: 01/31/2008 Activity Closed By: SNIPES_SR_1
Comments:
Comment Date: 01/03/2008 User: SNIPES_SR_1
Description: SITE INSPECTION; REMOVAL OF THREE (3) 4,000 GALLON SINGLE WALLED FIBERGLASS CLAD STEEL USTS AND ASSOCIATED PIPING. 01. Closure conducted by Bryco Fueling Solutions- PSSC-051722 02. Environmental Consultant- Handex Consulting & Remediation,LLC.Southeast. 03. Testing completed with FID Soil Analyzer. 04. No evidence of releases noted during closure activities. 05. Tanks were inerted before removal. 06. Tanks appeared to be in good condition. No holes or pits. 07. Tanks constructed as registered. 08. Tanks to be taken to local salvage yard. 09. Old piping (double-walled Pisces) and dispensers were removed. 10. No facility records or tests reviewed during closure inspection. 11. Facility Registration form to be completed by contractor. Blank form given to contractor. 12. New compartmented UST is scheduled to be installed on 1/4/2008. 13. Discrepancy noted during previous inspection completed on June 13, 2007 has been corrected. Old single walled steel underground storage tanks have been removed. 14. Tank Closure Assessment Report is due by March 3, 2008 at the Madison County Health Department.
Comments:
Comment Date: 01/02/2008 User: SNIPES_SR_1
Description: Recieved Notification of tank removal from Bryco Fueling Solutions. Removal scheduled to begin January 3, 2008.
01/02/2008 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/02/2008
Activity Closed Date: 01/31/2008 Activity Closed By: SNIPES_SR_1
Comments:
Comment Date: 01/03/2008 User: SNIPES_SR_1
Description: SITE INSPECTION; REMOVAL OF THREE (3) 4,000 GALLON SINGLE WALLED FIBERGLASS CLAD STEEL USTS AND ASSOCIATED PIPING. 01. Closure conducted by Bryco Fueling Solutions- PSSC-051722 02. Environmental Consultant- Handex Consulting & Remediation,LLC.Southeast. 03. Testing completed with FID Soil Analyzer. 04. No evidence of releases noted during closure activities. 05. Tanks were inerted before removal. 06. Tanks appeared to be in good condition. No holes or pits. 07. Tanks constructed as registered. 08. Tanks to be taken to local salvage yard. 09. Old piping (double-walled Pisces) and dispensers were removed. 10. No facility records or tests reviewed during closure inspection. 11. Facility Registration form to be completed by contractor. Blank form given to contractor. 12. New compartmented UST is scheduled to be installed on 1/4/2008. 13. Discrepancy noted during previous inspection completed on June 13, 2007 has been corrected. Old single walled steel underground storage tanks have been removed. 14. Tank Closure Assessment Report is due by March 3, 2008 at the Madison County Health Department.
Comments:
Comment Date: 01/02/2008 User: SNIPES_SR_1
Description: Recieved Notification of tank removal from Bryco Fueling Solutions. Removal scheduled to begin January 3, 2008.
12/11/2007 Enforcement Referral Activity Snipes, Stephen R.
Activity Result: Rejected Activity Status: Closed
Activity Closed Date: 05/09/2008
Events:
Event Type: Activity/Document was rejected on this date Date: 05/09/2008
Comment: Refrerred violation closed by local program 3 weeks after referral. Enforcement action will not be taken. Case Closed.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 12/12/2007
Comment: district received enforcement referral from county.
Events:
Event Type: Activity has been submitted for approval Date: 12/11/2007
Comment: Referred to District on 12-11-2007.
Comments:
Comment Date: 12/11/2007 User: SNIPES_SR_1
Description: Referred to District on 12-11-07.
Comments:
Comment Date: 05/09/2008 User: LUBINSKI_D
Description: Refrerred violation closed by local program 3 weeks after referral. Enforcement action will not be taken. Case Closed.
Comments:
Comment Date: 12/12/2007 User: DOHANEY_T
Description: district received enforcement referral from county.
Comments:
Comment Date: 12/11/2007 User: SNIPES_SR_1
Description: Referred to District on 12-11-2007.
12/11/2007 Enforcement Referral Activity Snipes, Stephen R.
Activity Result: Rejected Activity Status: Closed
Activity Closed Date: 05/09/2008
Events:
Event Type: Activity/Document was rejected on this date Date: 05/09/2008
Comment: Refrerred violation closed by local program 3 weeks after referral. Enforcement action will not be taken. Case Closed.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 12/12/2007
Comment: district received enforcement referral from county.
Events:
Event Type: Activity has been submitted for approval Date: 12/11/2007
Comment: Referred to District on 12-11-2007.
Comments:
Comment Date: 12/11/2007 User: SNIPES_SR_1
Description: Referred to District on 12-11-07.
Comments:
Comment Date: 05/09/2008 User: LUBINSKI_D
Description: Refrerred violation closed by local program 3 weeks after referral. Enforcement action will not be taken. Case Closed.
Comments:
Comment Date: 12/12/2007 User: DOHANEY_T
Description: district received enforcement referral from county.
Comments:
Comment Date: 12/11/2007 User: SNIPES_SR_1
Description: Referred to District on 12-11-2007.
12/11/2007 Enforcement Referral Activity Snipes, Stephen R.
Activity Result: Rejected Activity Status: Closed
Activity Closed Date: 05/09/2008
Events:
Event Type: Activity/Document was rejected on this date Date: 05/09/2008
Comment: Refrerred violation closed by local program 3 weeks after referral. Enforcement action will not be taken. Case Closed.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 12/12/2007
Comment: district received enforcement referral from county.
Events:
Event Type: Activity has been submitted for approval Date: 12/11/2007
Comment: Referred to District on 12-11-2007.
Comments:
Comment Date: 12/11/2007 User: SNIPES_SR_1
Description: Referred to District on 12-11-07.
Comments:
Comment Date: 05/09/2008 User: LUBINSKI_D
Description: Refrerred violation closed by local program 3 weeks after referral. Enforcement action will not be taken. Case Closed.
Comments:
Comment Date: 12/12/2007 User: DOHANEY_T
Description: district received enforcement referral from county.
Comments:
Comment Date: 12/11/2007 User: SNIPES_SR_1
Description: Referred to District on 12-11-2007.
12/11/2007 Enforcement Referral Activity Snipes, Stephen R.
Activity Result: Rejected Activity Status: Closed
Activity Closed Date: 05/09/2008
Events:
Event Type: Activity/Document was rejected on this date Date: 05/09/2008
Comment: Refrerred violation closed by local program 3 weeks after referral. Enforcement action will not be taken. Case Closed.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 12/12/2007
Comment: district received enforcement referral from county.
Events:
Event Type: Activity has been submitted for approval Date: 12/11/2007
Comment: Referred to District on 12-11-2007.
Comments:
Comment Date: 12/11/2007 User: SNIPES_SR_1
Description: Referred to District on 12-11-07.
Comments:
Comment Date: 05/09/2008 User: LUBINSKI_D
Description: Refrerred violation closed by local program 3 weeks after referral. Enforcement action will not be taken. Case Closed.
Comments:
Comment Date: 12/12/2007 User: DOHANEY_T
Description: district received enforcement referral from county.
Comments:
Comment Date: 12/11/2007 User: SNIPES_SR_1
Description: Referred to District on 12-11-2007.
10/25/2007 Phone Conversation Activity Snipes, Stephen R.
Activity Status: Closed
Phone Number: (352) 542-8761 Activity Closed Date: 10/25/2007
Subject: Phone conversation with Mr. Kabir. Mr Kabir told me that the tanks are tentatively scheduled to be removed and replaced with new double-wall tanks and piping in January 2008.
07/26/2007 Editable Letter Activity Snipes, Stephen R.
Activity Title: Warning Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 07/26/2007
Comment: Sent on Thu Jul 26 15:26:50 EST 2007
Comments:
Comment Date: 07/26/2007 User: SNIPES_SR_1
Description: 7-26-2007 Mailed Warning Letter to facility owner.
Attachments:
Attachment Date: 07/26/2007 User: SNIPES_SR_1
Description: Warning Letter Report
View Attachment
06/19/2007 Violation Closed Snipes, Stephen R.
Significance: Minor Status: Closed
Criteria ID: 1102
Rule: 62-761.640(3)(f)1., 62-761.640(3)(f)2., 62-761.640(3)(f)3., 62-761.640(3)(f)4.
Comments: a. Tightness test method meets 0.1 gph performance standard. What is the pass/fail threshold? Look up the test method in the DEP Master Equipment book. Compare the threshold to the actual test data. b. The various test effects are compensated for by the test developer. Request a copy of the operation manual from the RQ tester or the test developer. While not specifically mentioned, the amount of water present in the tank at the start of the test is required to be recorded. c. Test methods generally test the: wetted portion of the tank (product), and the ullage (air space above the product). d. Define which test method is used: volumetric or non volumetric. e. The tester, especially with single-walled tanks, must know the depth to groundwater especially relative to the tank and the product level. The rule compensates for this by setting two minimum product volume values. 30% if depth actually known, 65% if unknown. f. Do overfill and spill containment devices interfere with the test method? This is something the RQ tester must determine, and they may remove these pieces of equipment.
06/19/2007 Editable Letter Activity Snipes, Stephen R.
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/19/2007
Comment: Sent on Tue Jun 19 00:00:00 EST 2007
Attachments:
Attachment Date: 06/19/2007 User: SNIPES_SR_1
Description: NCL Report
View Attachment
06/13/2007 Site Inspection Activity Closed Snipes, Stephen R.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 06/13/2007
Activity Closed Date: 06/19/2007 Activity Closed By: SNIPES_SR_1
Comments:
Comment Date: 06/13/2007 User: SNIPES_SR_1
Description: Records Reviewed: 01. Registration Placard-2006-2007 (2007-2008 Placard) Posted on site. 02. Certification of Financial Responsibility Declaration Page- Commerce and Industry 5/15/2007-5/15/2008. 03. Certification of Financial Responsibility Form was reviewed. OK. 04. Monthly visual inspections were reviewed from 3/10/2006-5/15/2007.All OK. All completed within 35 day range. 05. SIR Reports (Simmons 5.7 Version) reviewed from 5/1/2006-4/30/2007. All OK. 06. Written Release Detection Response Level (RDRL) was reviewed and appears to be accurate. Release Detection: 01. Monthly visual inspections of sumps and liners. 02. SIRS with 3 year tank tightness test. Site Inspection: 01. Inspection conducted with Mr. Hamayoun Kabir (Facility Operator). 02. Inspection of three single-wall fiberglass clad steel USTs. 03. Spill containment buckets were clean, dry,in good condition and properly coded. 04. Dispenser liners were clean, dry, and in good condition. 05. Check valves were anchored in place. 06. Double- wall suction piping. 07. Flapper valves for overfill protection. No spills or discharges observed during inspection. Discrepancies noted during inspection: 01. Storage tank tightness test has not been completed in past three years. The last tank tightness test available during this inspection was completed on 4/2/2003 by Clemens. Passed. Due 4/2/2006 (PAST DUE). UPGRADE SYSTEM FOR SECONDARY CONTAINMENT BEFORE 12/31/2009 Inspection report completed in office. Mailed to owner.
02/15/2007 Emergency Preparedness Information Activity Snipes, Stephen R.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/15/2007
09/26/2006 Emergency Preparedness Information Activity Snipes, Stephen R.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/26/2006
09/01/2005 Legacy Activity Dohaney, Tim
Activity Name: PROGRAM DISCRETION/NO ENFORCEMENT INITIATED Activity Status: Closed
08/25/2005 Legacy Activity Maroney, Emily K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: FILL LIDS NEED TO BE REPAINTED. MISSING HOSE BREAKAWAYS ON #1 & #3.
02/22/2005 Violation Closed Dohaney, Tim
Significance: Minor Status: Closed
Rule: 761.510(1)(b)3
Comments:
Comment Date: 05/24/2017 User: ALEXANDER_A_1
Description: Spill containment: OPW Pomeco double walled spill bucket EQ 224. Overfill protection: flow shut off valves present in fills - EQ Unknown. Tank: Containment Solutions double walled fiberglass UST - EQ 191 Piping: OPW Flexworks double walled flexible piping - EQ 709. Sumps: Environ - EQ 540. Dispenser liners: OPW Flexworks - EQ 368. Release Detection: Visual inspections of dispenser liners and spill buckets. Electronic monitoring of tank interstices and STP sumps using a Veeder Root TLS 350 (EQ 197). Mechanical leak detectors (EQ Unknown).
Comments:
Comment Date: 02/01/2012 User: MCDANIEL_ML_1
Description: Veeder Root TLS 350 panel (EQ # 197) monitors electronic sensors in the UST interstices (2) 15,000-gallon, Containment Solutions, double-walled, fiberglass USTs. OPW (formerly Environ) Geoflex, double walled, flexible piping (DPE EQ # 511). OPW(formerly Environ STP Sumps EQ#540) and OPW(formerly Environ dispenser-EQ# 439).
02/22/2005 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: TANK TEST DUE 4-2-06
02/22/2005 Violation Closed Dohaney, Tim
Significance: Minor Status: Closed
Rule: 761.510(1)(b)3
Comments:
Comment Date: 05/24/2017 User: ALEXANDER_A_1
Description: Spill containment: OPW Pomeco double walled spill bucket EQ 224. Overfill protection: flow shut off valves present in fills - EQ Unknown. Tank: Containment Solutions double walled fiberglass UST - EQ 191 Piping: OPW Flexworks double walled flexible piping - EQ 709. Sumps: Environ - EQ 540. Dispenser liners: OPW Flexworks - EQ 368. Release Detection: Visual inspections of dispenser liners and spill buckets. Electronic monitoring of tank interstices and STP sumps using a Veeder Root TLS 350 (EQ 197). Mechanical leak detectors (EQ Unknown).
Comments:
Comment Date: 02/01/2012 User: MCDANIEL_ML_1
Description: Veeder Root TLS 350 panel (EQ # 197) monitors electronic sensors in the UST interstices (2) 15,000-gallon, Containment Solutions, double-walled, fiberglass USTs. OPW (formerly Environ) Geoflex, double walled, flexible piping (DPE EQ # 511). OPW(formerly Environ STP Sumps EQ#540) and OPW(formerly Environ dispenser-EQ# 439).
02/29/2004 Legacy Activity Sheffield, Cynthia K.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: REC'D FAX THAT WATER HAD BEEN REMOVED FROM THE SPILL BUCKETS
01/30/2004 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 700(1)(c)1
01/30/2004 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/21/2003 Legacy Activity Sheffield, Cynthia K.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: REC'D COPY OF TIGHTNESS TEST.
02/05/2003 Legacy Activity Sheffield, Cynthia K.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: REC'D COPY OF SIR REPORTS
02/04/2003 Legacy Activity Sheffield, Cynthia K.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
01/27/2003 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 640(3)(c)3
01/27/2003 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: BLUE OPW PISCES D/W FLEX PIPE
01/27/2003 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 710(1)
01/27/2003 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 640(3)(c)4
03/14/2002 Legacy Activity Sheffield, Cynthia K.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: FOUND FAX DATED 2-22-02 THAT HAD SIR REPORTS FOR FEB 2001 THRU JAN 2002
02/21/2002 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 640(3)(c)3
02/21/2002 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/21/2002 Violation Closed Sheffield, Cynthia K.
Significance: SNC-B Status: Closed
Rule: 600(1)(d)
04/16/2001 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/05/2001 Legacy Activity Sheffield, Cynthia K.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: FACILITY FAXED OCT AND NOV SIR REPORTS. ALL PASSED.
10/25/2000 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
10/25/2000 Legacy Activity Sheffield, Cynthia K.
Activity Name: PROGRAM DISCRETION/NO ENFORCEMENT INITIATED Activity Status: Closed
09/22/2000 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 450(2)(a)
09/22/2000 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
09/22/2000 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 600(1)(k)
07/24/2000 Legacy Activity Sheffield, Cynthia K.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
06/15/2000 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 510(1)(b)3
Comments:
Comment Date: 08/08/2014 User: COLSON_NJ_1
Description: VR TLS-350 & (4) sensors
06/15/2000 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/15/2000 Violation Closed Sheffield, Cynthia K.
Significance: SNC-B Status: Closed
Rule: 600(1)(d)
06/15/2000 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 600(1)(k)
Comments:
Comment Date: 08/08/2014 User: COLSON_NJ_1
Description: VR TLS-350 & (4) sensors
05/05/1999 Legacy Activity Unknown, User
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed