DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/30/2025        Last Data Refresh: 04/29/2025        Report Generated from DOPPLER
 
Facility ID: 9046976
Facility Name: GRAINGER FARMS INC
 
04/09/2025 Editable Letter Activity Wimberly, Evan
Activity Title: Return to Compliance Letter Activity Status: Open
04/09/2025 Document Management Activity Wimberly, Evan
Activity Title: Closure Document Activity Status: Closed
Events:
Event Type: Activity/Document has been approved Date: 04/09/2025
Comment: Approved by Jayme Brock: Approved
Events:
Event Type: Activity has been finished Date: 04/09/2025
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 04/09/2025
Comment: Submitted for approval by: Evan Wimberly
Attachments:
Attachment Date: 04/09/2025 User: WIMBERLY_E
Description: Memo to file
View Attachment
01/17/2023 Enforcement Tracking Activity Sides, Alexandra
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 04/09/2025
Events:
Event Type: Activity has been finished Date: 04/09/2025
Comment: Finished
11/18/2022 Electronic Communication Activity Trethewey, Mark B.
Activity Closed Date: 11/18/2022 Activity Status: Closed
Date: 11/18/2022
Recipient: Jim Grainger
Sender: Mark Trethewey
Subject: Inspections
Message: Good afternoon Jim, Here are copies of the inspections performed today. Most of the issues can be addressed with the removal/closure of the tanks. Is there a new contact for the sale? Thanks, Mark Trethewey
Events:
Event Type: Activity has been finished Date: 11/18/2022
Comment: Finished
11/18/2022 Electronic Communication Activity Trethewey, Mark B.
Activity Closed Date: 11/18/2022 Activity Status: Closed
Date: 11/18/2022
Recipient: Mark Trethewey
Sender: Jim Grainger
Subject: Re-inspections
Message: YOU HAVE ANY TIME IN THE NEXT WEEK OR SO I CAN MEET WITH YOU? WANT TO MAKE SURE I GET THIS RIGHT TO BE IN COMPLIANCE. SO WE CAN MOVE FORWARD. THANKS JIM
Events:
Event Type: Activity has been finished Date: 11/18/2022
Comment: Finished
11/18/2022 Electronic Communication Activity Trethewey, Mark B.
Activity Closed Date: 11/18/2022 Activity Status: Closed
Date: 11/18/2022
Recipient: Jim Grainger
Sender: Mark Trethewey
Subject: Scheduled inspections
Message: Good morning Jim, I wasn’t able to reach you at either phone number I have. I’ll still need to perform an inspection for those tanks. If there is any paperwork you can send, I can review it first. When the tanks are removed, I’ll need to perform a Closure Inspection. I can help you with that when the time comes. I’ll be in the field again this morning, back this afternoon. Thanks, Mark Trethewey
Events:
Event Type: Activity has been finished Date: 11/18/2022
Comment: Finished
11/18/2022 Enforcement Referral Activity Trethewey, Mark B.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 01/17/2023
Events:
Event Type: Activity has been assigned Date: 01/13/2023
Comment: Assigned to Alexandra Sides
Events:
Event Type: Activity/Document was acknowledged on this date Date: 01/13/2023
Comment: Acknowledged and Assigned by Jayme Brock
Events:
Event Type: Activity has been finished Date: 01/17/2023
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 01/17/2023
Comment: Accepted by Alexandra Sides: Okay.
Events:
Event Type: Activity has been submitted for approval Date: 11/18/2022
Comment: Submitted for approval by: Mark B. Trethewey: Referred for Enforcement
Comments:
Comment Date: 11/18/2022 User: TRETHEWEY_MB_1
Description: Referred for Enforcement
Attachments:
Attachment Date: 11/18/2022 User: TRETHEWEY_MB_1
Description: Prop. Appr. info
View Attachment
Attachments:
Attachment Date: 11/18/2022 User: TRETHEWEY_MB_1
Description: Corp. Info
View Attachment
Attachments:
Attachment Date: 11/18/2022 User: TRETHEWEY_MB_1
Description: Enforcement Referral Form SWD - 11-18-2022
View Attachment
11/18/2022 Electronic Communication Activity Trethewey, Mark B.
Activity Closed Date: 11/18/2022 Activity Status: Closed
Date: 11/18/2022
Recipient: Jim Grainger
Sender: Mark Trethewey
Subject: Re-inspections
Message: Hi Jim, So far, I’m open 8/4 and 8/8. Mark Trethewey
Events:
Event Type: Activity has been finished Date: 11/18/2022
Comment: Finished
07/28/2022 Attachment Trethewey, Mark B.
07/28/2022 Editable Letter Activity Trethewey, Mark B.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Description: 116 UST Overfill test
Events:
Event Type: Document has been sent Date: 07/28/2022
Comment: Sent
Events:
Event Type: Activity has been finished Date: 07/28/2022
Comment: Finished
Attachments:
Attachment Date: 07/28/2022 User: TRETHEWEY_MB_1
Description: CAO 2022-2023.011
View Attachment
07/28/2022 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 07/28/2022
Activity Closed Date: 07/28/2022 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 07/28/2022
Comment: Finished
Comments:
Comment Date: 07/28/2022 User: TRETHEWEY_MB_1
Description: RECORDS: #9046976, 7/28/2022 Placard: #618765; issued 8/4/2021, 4 tanks listed. This is last year’s placard. Submit fees to FDEP. Financial Responsibility: Last provided, Commerce & Industry, 8/18/2019 - 8/18/2020. Coverage for 8/18/2020 to 8/18/2021 and 8/18/2021 to 8/18/2022 not provided. Immediately provide Manatee County NRD with copies of the required documents. CoFR: Not provided. Release Detection: a. This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. The monthly visual inspection records from 12/1/2019 to present were not provided. Immediately provide Manatee County NRD with copies of the required documents. PHYSICAL: Tank and piping: Inspected Tank #s 1, 2 & 3. Tank #4 was not accessible. Tank #1 (Block 7 & 8) has been disconnected. There is no pump. Tank #2 (Block 25) has been disconnected. There is no pump. Tank #3 (Block 26) has been disconnected. There is no pump. Tank #4 (Block 23) was not observed. Tank Reference: DEP ID Facility ID 1 Block 7&8 2 Block 25 3 Block 26 4 Block 23 NOTE: Facility may be sold. Provide required documents. Ensure that notification is received prior to removal activities.
07/28/2022 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 7003
Rule: 62-762.401(4), 62-762.401(4)(a), 62-762.401(4)(a)1, 62-762.401(4)(a)2, 62-762.401(4)(b), 62-762.401(4)(c), 62-762.401(4)(d), 62-762.401(4)(e), 62-762.401(4)(f), 62-762.401(4)(g), 62-762.401(4)(h), 62-762.401(4)(i)
07/28/2022 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 7094
Rule: 62-762.711(1)
07/19/2022 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: James Grainger Activity Closed Date: 07/28/2022
Events:
Event Type: Activity has been finished Date: 07/28/2022
Comment: Finished
Attachments:
Attachment Date: 07/28/2022 User: TRETHEWEY_MB_1
Description: 7/19/2022 Notification Letter
View Attachment
12/03/2019 Meeting Activity Trethewey, Mark B.
Activity Closed Date: 12/03/2019 Activity Status: Closed
Location: Grainger Farms
Subject: Met with Jim Grainger, reviewed records with Roy.
Events:
Event Type: Activity has been finished Date: 12/03/2019
Comment: Finished
12/03/2019 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Jim Grainger Activity Closed Date: 12/03/2019
Events:
Event Type: Activity has been finished Date: 12/03/2019
Comment: Finished
Attachments:
Attachment Date: 12/03/2019 User: TRETHEWEY_MB_1
Description: 12/3/2019 Return to Compliance letter
View Attachment
11/08/2019 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 5143
Rule: 62-762.711(1)
11/08/2019 Editable Letter Activity Trethewey, Mark B.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 11/08/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 11/08/2019
Comment: Finished
Attachments:
Attachment Date: 11/08/2019 User: TRETHEWEY_MB_1
Description: CAO 2019-2020.035
View Attachment
11/08/2019 Phone Conversation Activity Trethewey, Mark B.
Call Type: Incoming Activity Status: Closed
Phone Number: (941) 737-2532 Activity Closed Date: 11/08/2019
Subject: Agreed to reschedule for 11/5/2019
Events:
Event Type: Activity has been finished Date: 11/08/2019
Comment: Finished
11/05/2019 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 11/05/2019
Activity Closed Date: 11/08/2019 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 11/08/2019
Comment: Finished
Comments:
Comment Date: 11/08/2019 User: TRETHEWEY_MB_1
Description: RECORDS: #9046976, 11/5/2019 Placard: #558006; issued 6/14/2019, 4 tanks listed. Financial Responsibility: Last provided, C & I, 8/18/2017 - 8/18/2018. Coverage for 8/18/2018 to 8/18/2019 and 8/18/2019 to 8/18/2020 not provided. Immediately provide Manatee County PNRD with copies of the required documents. CoFR: Not provided. Release Detection: a. This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. The monthly visual inspection records from 12/5/2017 to present were not provided. Immediately provide Manatee County PNRD with copies of the required documents. PHYSICAL: NOTE: All tanks product IDs need to be re-marked (“Diesel”) at fill. Tank and piping: Inspected Tank #s 1, 2, 3 & 4. All systems are roofed. Tank #1 (Block 7 & 8) is in good condition. There is minor staining on the tank, unknown source. Recommend continued monitoring of tank. Tank #2 (Block 25) is in good condition. Tank #3 (Block 26) is in good condition. Tank #4 (Block 23) is in good condition. Containment: All containment systems are in good condition. The drain valves are closed. Tank Reference: DEP ID Facility ID 1 Block 7&8 2 Block 25 3 Block 26 4 Block 23 NOTE: Inspection results discussed with Jim 11/6/2019
10/02/2019 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: James Grainger Activity Closed Date: 11/08/2019
Events:
Event Type: Activity has been finished Date: 11/08/2019
Comment: Finished
Attachments:
Attachment Date: 11/08/2019 User: TRETHEWEY_MB_1
Description: 10/2/2019 Notification Letter
View Attachment
12/28/2017 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/28/2017
Activity Closed Date: 12/28/2017 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 12/28/2017
Comment: Finished
Comments:
Comment Date: 12/28/2017 User: TRETHEWEY_MB_1
Description: RECORDS: #9046976, 12/28/2017 Placard: #511078; issued 6/14/2017, 4 tanks listed. Financial Responsibility: Commerce & Industry, 08/18/2016 - 08/18/2018. Violations Cited at Compliance Inspection 9/26/2017: 1. Type: Violation Significance: Minor Rule: 62-762.711(1) Violation Text: Required records not available within 5 working days notice. Explanation: Proof of Financial Responsibility from 8/18/2016 to 8/16/2018 was not provided. release detection records from 10/2/2015 to present were not provided. Corrective Action: Immediately provide Manatee County PNRD with copies of all required documents. Corrective Action Taken: Yes. Review at re-inspection confirms available records. FR is C & I, coverage from 8/18/2016 to 8/18/2018 provided. Release detection from 10/2/2015 to 12/5/2017 provided. 2. Type: Violation Significance: SNC-B Rule: 62-762.501(3)(d), 62-762.501(3)(d)1., 62-762.501(3)(d)2., 62-762.501(3)(d)3. Violation Text: Valves not installed as required for small diameter integral piping. Explanation: The ASV on Tank #1(Block 7&8) has been removed. Corrective Action: Immediately replace ASV. Ensure all ASVs are in place. Corrective Action Taken: Yes. Re-inspection confirms that valves have been re-installed.
12/28/2017 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Chuck Hautot Activity Closed Date: 12/28/2017
Events:
Event Type: Activity has been finished Date: 12/28/2017
Comment: Finished
Attachments:
Attachment Date: 12/28/2017 User: TRETHEWEY_MB_1
Description: 12-28-2017 Return to Compliance Letter
View Attachment
12/07/2017 Electronic Communication Activity Trethewey, Mark B.
Activity Closed Date: 12/07/2017 Activity Status: Closed
Date: 12/07/2017
Recipient: Mark Trethewey
Sender: Debe G.
Subject: FR
Message: Received current Proof of Financial Responsibility. C & I 8/18/2017 to 8/18/2018.
Events:
Event Type: Activity has been finished Date: 12/07/2017
Comment: Finished
09/29/2017 Violation Closed Trethewey, Mark B.
Significance: SNC-B Status: Closed
Criteria ID: 5060
Rule: 62-762.501(3)(d), 62-762.501(3)(d)1., 62-762.501(3)(d)2., 62-762.501(3)(d)3.
09/29/2017 Editable Letter Activity Trethewey, Mark B.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 09/29/2017
Comment: Finished
Events:
Event Type: Document has been sent Date: 09/29/2017
Comment: Sent
Attachments:
Attachment Date: 09/29/2017 User: TRETHEWEY_MB_1
Description: CAO 2017-2018.014
View Attachment
09/29/2017 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 5143
Rule: 62-762.711(1)
09/26/2017 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 09/26/2017
Activity Closed Date: 09/29/2017 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 09/29/2017
Comment: Finished
Comments:
Comment Date: 09/29/2017 User: TRETHEWEY_MB_1
Description: RECORDS: #9046976, 9/26/2017 Placard: #511078; issued 6/14/2017, 4 tanks listed. Financial Responsibility: Last provided, AIG, 08/18/2015 - 08/18/2016. Coverage for 8/18/2016 to 8/18/2017 and 8/18/2017 to 8/18/2018 not provided. Immediately provide Manatee County PNRD with copies of the required documents. CoFR: Not provided. Release Detection: a. This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. The monthly visual inspection records from 10/2/2015 to present were not provided. Immediately provide Manatee County PNRD with copies of the required documents. PHYSICAL: NOTE: All tanks product IDs need to be re-marked (“Diesel”) at fill. Tank and piping: Inspected Tank #s 1, 2, 3 & 4. All systems are roofed. Tank #1 (Block 7 & 8) is in good condition. The ASV is missing, immediately replace ASV or raise lines above gravity head. Tank #2 (Block 25) is in good condition. Tank #3 (Block 26) is in good condition. Tank #4 (Block 23) is in good condition. Containment: All containment systems are in good condition. The drain valves are closed. There is minor water in the containment of Tank #1, ensure that water is removed within 72 hours. Tank Reference: DEP ID Facility ID 1 Block 7&8 2 Block 25 3 Block 26 4 Block 23
09/13/2017 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: James Grainger Activity Closed Date: 09/29/2017
Events:
Event Type: Activity has been finished Date: 09/29/2017
Comment: Finished
Attachments:
Attachment Date: 09/29/2017 User: TRETHEWEY_MB_1
Description: 9-13-2017 Notification Letter
View Attachment
10/05/2015 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Chuck Hautot Activity Closed Date: 10/05/2015
Events:
Event Type: Activity has been finished Date: 10/05/2015
Comment: Finished
10/02/2015 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/02/2015
Activity Closed Date: 10/05/2015 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 10/05/2015
Comment: Finished
Comments:
Comment Date: 10/05/2015 User: TRETHEWEY_MB_1
Description: RECORDS: #9046976, 10/2/2015 Placard: #458195; issued 6/4/2015, 4 tanks listed. Financial Responsibility: AIG, 08/18/2015 - 08/18/2016. CoFR: Available with FR. RDRL: With release detection records. Release Detection: a. This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. Reviewed the monthly visual inspection records from 5/2/2013 to 10/2/2015. Inspections include the condition of the tank, piping, equipment and containment. Release detection was performed at least once a month not exceeding 35 days apart. PHYSICAL: Tank and piping: Inspected Tank #s 1, 2, 3 & 4. All systems are roofed. Recommend replacement of signage. Tank #1 (Block 7 & 8) is in satisfactory condition. Tank #2 (Block 25) is in satisfactory condition. Tank #3 (Block 26) is in satisfactory condition. Tank #4 (Block 23) is in satisfactory condition. Containment: All containment systems are in good condition. The drain valves are closed. Tank Reference: DEP ID Facility ID 1 Block 7&8 2 Block 25 3 Block 26 4 Block 23
09/14/2015 Document Management Activity Trethewey, Mark B.
Activity Title: Compliance Assistance Visit Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 09/14/2015
Comment: Finished
Attachments:
Attachment Date: 09/14/2015 User: TRETHEWEY_MB_1
Description: CAV 9/10/2015
View Attachment
04/24/2013 Issue Document Activity Trethewey, Mark B.
Activity Status: Closed
Contact Name: Chuck Hautot Activity Closed Date: 04/24/2013
Events:
Event Type: Activity has been finished Date: 04/24/2013
Comment: Finished
04/22/2013 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/22/2013
Activity Closed Date: 04/24/2013 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 04/24/2013
Comment: Finished
Comments:
Comment Date: 04/24/2013 User: TRETHEWEY_MB_1
Description: RECORDS: #9046976, 4/22/2013 Placard: #390471; issued 6/19/2012, 4 tanks listed. Financial Responsibility: Commerce & Industry, 08/18/2011 - 08/18/2012. Current FR not provided. CoFR: Current CFR not provided. RDRL: Current RDRL not provided. Release Detection: a. This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. The monthly visual inspection records from 3/7/2012 to present were not provided. Immediately provided Manatee County NRD with copies of all required documents. PHYSICAL: Tank and piping: Inspected Tank #s 1, 2, 3 & 4. All systems are roofed. Recommend replacement of signage. Tank #1 (Block 7 & 8) is in satisfactory condition. Tank #2 (Block 25) is in satisfactory condition. Tank #3 (Block 26) is in satisfactory condition. Tank #4 (Block 23) is in satisfactory condition. Containment: All containment systems are in good condition. The drain valves are closed. Tank Reference: DEP ID Facility ID 1 Block 7&8 2 Block 25 3 Block 26 4 Block 23
03/13/2012 Site Inspection Activity Closed Mason, Steve
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/14/2012
Activity Closed Date: 03/16/2012 Activity Closed By: MASON_RS_1
Events:
Event Type: Activity has been finished Date: 03/16/2012
Comment: Finished
Comments:
Comment Date: 03/16/2012 User: MASON_RS_1
Description: RECORDS: #9046976, 03/13/2012 Placard: #368224; issued 06/16/2011, 4 tanks listed Financial Responsibility: Commerce & Industry, 08/18/2011 - 08/18/2012 CoFR: Available, complete, and accurate RDRL: With Release Detection Records Release Detection: a. This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period of 02/04/2011 to 03/07/2012. Visual inspections include inspections of the tanks, equipment, and piping along with the condition of the tank containment areas. Inspections were performed once per month and did not exceed 35 days apart. PHYSICAL: Tank and piping: Inspected Tank #s 1, 2, 3 & 4. All systems are roofed. Tank #1 (Block 7 & 8) has minor corrosion which is addressed as a part of regular maintenance. The tank also has older repairs (plugs and patches). Recommend replacement of this tank. Tank #2 (Block 25) is in satisfactory condition. Tank #3 (Block 26) is in satisfactory condition. Tank #4 (Block 23) is in satisfactory condition. Containment: All containment systems are in good condition. The drain valves are closed. Tank Reference: DEP ID Facility ID 1 Block 7&8 2 Block 25 3 Block 26 4 Block 23
02/10/2011 Site Inspection Activity Closed Mason, Steve
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/10/2011
Activity Closed Date: 02/15/2011 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 02/15/2011
Comment: Finished
Comments:
Comment Date: 02/10/2011 User: MASON_RS_1
Description: RECORDS: # 9046976, 2/10/2010 Placard: #339710; issued 6/1/2010, 4 tanks listed. Financial Responsibility: Commerce & Industry. 8/18/2010 to 8/18/2011. CoFR: Available and accurate. RDRL: With Release Detection Records. Release Detection: a.This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period of 2/4/2010 through 2/4/2011. Visual inspections include inspections of the tanks, equipment, and piping along with the condition of the tank containment areas. Inspections were performed once a month within 35 days. PHYSICAL: Tank and piping: Inspected Tank #s 1, 2, 3 & 4. All systems are roofed. Tank #1 (Block 7 & 8) has minor corrosion addressed as regular maintenance. Tank also has older repairs (plugs and patches), recommend replacement of tank. Tank #2 (Block 25) is in satisfactory condition. Tank #3 (Block 26) is in satisfactory condition. Tank #4 (Block 23) is in satisfactory condition. Stained soil noted on last inspection has been addressed. Containment: All containment systems are in good condition, valves are closed. Tank Reference: DEP ID Facility ID 1 Block 7&8 2 Block 25 3 Block 26 4 Block 23
03/02/2010 Editable Letter Activity Trethewey, Mark B.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/29/2010
Comment: Finished
Attachments:
Attachment Date: 03/02/2010 User: TRETHEWEY_MB_1
Description: NCL 2009-2010.047
View Attachment
02/26/2010 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 2163
Rule: 62-762.821(2)(e)
Comments: Refer to 62-770.300(2) source removal. If possible, document the disposal of the contaminated soil. Per 770.300(2)(a)5, stockpiled soils can not remain on site for more than 60 days.
02/26/2010 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/23/2010
Activity Closed Date: 03/02/2010 Activity Closed By: TRETHEWEY_MB_1
Events:
Event Type: Activity has been finished Date: 03/02/2010
Comment: Finished
Comments:
Comment Date: 03/02/2010 User: TRETHEWEY_MB_1
Description: RECORDS: # 9046976, 2/23/2010 Placard: #319729; issued 5/20/2009, 4 tanks listed. Financial Responsibility: Commerce & Industry. 8/18/2009 to 8/18/2010. CoFR: Available and accurate. RDRL: With Release Detection Records. Release Detection: a. This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period 3/6/2009 through 2/4/2010. Visual inspections include visual inspection of tank, equipment, piping and the condition of the tank interstice. Inspections were performed once a month within 35 days. February 2009 inspection was not available PHYSICAL: Tank and piping: Inspected Tank #s 1, 2, 3 & 4. All systems are roofed. Tank #1 (Block 7 & 8) has minor corrosion addressed as regular maintenance. Tank also has older repairs (plugs and patches), recommend replacement of tank. Tank #2 (Block 25) is in satisfactory condition. Tank #3 (Block 26) is in satisfactory condition. Tank #4 (Block 23) is in satisfactory condition. There is soil staining outside the Containment, source is unknown. Ensure that containment valves are closed at all times other than manned removal of water. Immediately remove and properly dispose of all stained soil. Containment: All containment systems are in good condition, valves are closed.
01/28/2009 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/28/2009
Activity Closed Date: 01/28/2009 Activity Closed By: TRETHEWEY_MB_1
Comments:
Comment Date: 01/28/2009 User: TRETHEWEY_MB_1
Description: RECORDS: # 9046976, 1-28-2009 Placard: # 294222; issued 5/23/2008, 4 tanks listed. Financial Responsibility: Commerce & Industry. 8/18/2008 to 8/18/2009. CoFR: Available and accurate. RDRL: With Release Detection Records. Release Detection: a. This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period 1/10/2008 through 1/8/2009. Visual inspections include visual inspection of tank, equipment, piping and the condition of the tank interstice. Inspections were performed once a month within 35 days. PHYSICAL: Tank and piping: Inspected Tank #s 1, 2, 3 & 4. All systems are roofed. Tank #1 (Block 7 & 8) has minor corrosion addressed as regular maintenance. Tank also has older repairs (plugs and patches), recommend replacement of tank. Tank #2 (Block 25) is in satisfactory condition. Tank #3 (Block 26) Corrosion spots noted at last inspection have been addressed. Tank #4 (Block 23) is in satisfactory condition. Containment: All containment systems are in good condition.
03/21/2008 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/21/2008
Activity Closed Date: 03/21/2008 Activity Closed By: TRETHEWEY_MB_1
Comments:
Comment Date: 03/21/2008 User: TRETHEWEY_MB_1
Description: RECORDS: # 8624312, 3/21/2008 Placard: #280002; issued 6/7/2007, 5 tanks listed. Financial Responsibility: Commerce & Industry, 8/18/2007 ¿ 8/18/2008. Violations Cited at Compliance Inspection of 1/28/2008: 1. Rule Number(s): 62-762.501(1)(b) Violation Text: AST system exterior coating does not meet standards. Explanation: Tank #s 1 (Block 7 & 8) and 3 (Block 26) are showing signs of corrosion. Corrective Action: Immediately repair spots of corrosion and recoat affected areas. Significance: Minor Corrective Action Taken: Yes Re-inspection confirms that actions have been taken to repair corrosion and recoat tank exteriors. Two photos were taken to verify repairs. Note: Facility indicates that Tank #1 (Block 7 & 8) is scheduled for replacement and a new tank has been ordered. Ensure that Manatee County EMD is notified at least 10 days prior to removal activities and 30 days prior to installation activities.
01/28/2008 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 2014
Rule: 62-762.501(1)(b)
Comments: Examine exterior surfaces for damage during shipping and installation. Has the on site applied exterior coating been applied according to the manufacturer's specifications? Light colored paints show fuel discoloration. Refer to item #2110 for Cat A, B system tank condition.
01/28/2008 Editable Letter Activity Trethewey, Mark B.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
01/28/2008 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/28/2008
Activity Closed Date: 01/28/2008 Activity Closed By: TRETHEWEY_MB_1
Comments:
Comment Date: 01/28/2008 User: TRETHEWEY_MB_1
Description: RECORDS: # 9046976, 1-28-2008 Placard: # 280002; issued 6/7/2007, 4 tanks listed. Financial Responsibility: Commerce & Industry. 8/18/2007 to 8/18/2008. CoFR: Available and accurate. RDRL: With Release Detection Records. Release Detection: a. This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. Reviewed the monthly visual inspection records for the time period 1/11/2007 through 1/10/2008. Visual inspections include visual inspection of tank, equipment, piping and the condition of the tank interstice. Inspections were performed once a month within 35 days. PHYSICAL: Tank and piping: Inspected Tank #s 1, 2, 3 & 4. All systems are roofed. Tank #1 (Block 7 & 8) has corrosion, immediately repair corrosion spots and recoat affected areas. Tank also has older repairs (plugs and patches) Tank #2 (Block 25) is in satisfactory condition. Tank #3 (Block 26) has corrosion, immediately repair corrosion spots and recoat affected areas. Tank #4 (Block 23) is in satisfactory condition. Containment: All containment systems are in good condition. Tank Reference: DEP ID Facility ID 1 Block 7&8 2 Block 25 3 Block 26 4 Block 23
02/27/2007 Attachment Trethewey, Mark B.
02/27/2007 Editable Letter Activity Trethewey, Mark B.
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 02/27/2007
Comment: Sent on Tue Feb 27 00:00:00 EST 2007
Attachments:
Attachment Date: 02/27/2007 User: TRETHEWEY_MB_1
Description: NCL Report
View Attachment
02/27/2007 Site Inspection Activity Closed Trethewey, Mark B.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/27/2007
Activity Closed Date: 02/27/2007 Activity Closed By: TRETHEWEY_MB_1
Comments:
Comment Date: 02/27/2007 User: TRETHEWEY_MB_1
Description: RECORDS: # 9046976, 2-27-2007 Placard: # 250864, issued 5/26/2006, 4 tanks listed. Financial Responsibility: Not provided. CoFR: Not provided RDRL: Not provided. Release Detection: a. This Facility has the following release detection methods: 1. Visual inspection of tank, equipment & containment areas. b. Facility monthly release detection results: 1. Not provided. PHYSICAL: Tank and piping: Inspected Tank #s 1, 2, 3 & 4. All systems are roofed. Tank #1 (Block 7 & 8) is in fair condition. Tank has older repairs (plugs and patches) Tank #2 (Block 25) is in satisfactory condition. Tank #3 (Block 26) is in satisfactory condition. Tank #4 (Block 23) is in satisfactory condition. Containment: All containment systems are in good condition. Tank Reference DEP ID 1 2 3 4 Facility ID Block 7&8 Block 25 Block 26 Block 23
02/27/2007 Violation Closed Trethewey, Mark B.
Significance: Minor Status: Closed
Criteria ID: 1122
Rule: 62-761.710(1)
Comments: Was reasonable access to the facility granted? If not, document the circumstances. Were the records available within the specified time frame? If five day pre-inspection notice was not given by the inspector, this item can not be marked as a discrepancy. Make note of the missing documents, and arrange a review period.
02/27/2007 Attachment Trethewey, Mark B.
02/27/2007 Attachment Trethewey, Mark B.
02/27/2007 Attachment Trethewey, Mark B.
02/27/2007 Attachment Trethewey, Mark B.
03/02/2006 Legacy Activity Trethewey, Mark B.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
02/28/2006 Violation Closed Trethewey, Mark B.
Significance: SNC-B Status: Closed
Rule: 762.611(2)(b)
Comments:
Comment Date: 04/01/2014 User: COLSON_NJ_1
Description: Reportedly a Com-Fab tank - EQ#386. Morrison Bros. 518 spill bucket - EQ#345. OPW 144TA overfill alarm system - EQ#610. Krueger Level Gauge - EQ#730. Madison M7700 liquid sensor in the rupture basin - EQ# 682. (Monitored by the generator alarm panel & a remote Kohler alarm panel.) Krueger Leakk Gauge - EQ#675.
02/28/2006 Legacy Activity Trethewey, Mark B.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/14/2005 Legacy Activity Trethewey, Mark B.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: IN COMPLIANCE
10/31/2003 Legacy Activity Sego, John R.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
05/29/2003 Violation Closed Sego, John R.
Significance: Minor Status: Closed
Rule: 500(4)(c)2
05/29/2003 Legacy Activity Panik, Paul J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/03/2002 Legacy Activity Panik, Paul J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
05/02/2001 Legacy Activity Panik, Paul J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
05/08/2000 Legacy Activity Panik, Paul J.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
05/08/2000 Legacy Activity Panik, Paul J.
Activity Name: COMPLIANCE W/O FORMAL ENFORCEMENT ACTION Activity Status: Closed
03/23/2000 Legacy Activity Panik, Paul J.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
03/03/2000 Violation Closed Panik, Paul J.
Significance: Minor Status: Closed
Rule: 450(1)(a)1
03/03/2000 Legacy Activity Panik, Paul J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/03/2000 Violation Closed Panik, Paul J.
Significance: Minor Status: Closed
Rule: 500(3)(c)3b
02/26/1999 Legacy Activity Panik, Paul J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed