DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/27/2025        Last Data Refresh: 04/26/2025        Report Generated from DOPPLER
 
Facility ID: 9101062
Facility Name: EZ FOOD MART
 
12/10/2024 Editable Letter Activity Jackson, Sydney M
Activity Title: Warning Letter Activity Status: Closed
Description: 8515922_INF for diesel STP sump
Events:
Event Type: Activity has been finished Date: 12/10/2024
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 12/10/2024
Comment: Submitted for approval by: Sydney M Jackson
Events:
Event Type: Activity/Document has been approved Date: 12/10/2024
Comment: Approved by Jennifer Paul: WL24-260 12/10/24
Attachments:
Attachment Date: 12/10/2024 User: JACKSON_SM
Description: Warning Letter
View Attachment
06/10/2024 Enforcement Tracking Activity Jackson, Sydney M
Activity Status: Open
06/07/2024 Enforcement Referral Activity Harrington, Richard D.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 06/10/2024
Events:
Event Type: Activity has been submitted for approval Date: 06/07/2024
Comment: Submitted for approval by: Richard D. Harrington: See 2024 Routine Inspection report and CA>Electronic Communications. This facility referral is being re-submitted due to it was rejected in error.
Events:
Event Type: Activity/Document was accepted on this date Date: 06/10/2024
Comment: Accepted by Sydney M Jackson: accepted
Events:
Event Type: Activity/Document was acknowledged on this date Date: 06/10/2024
Comment: Acknowledged and Assigned by Jennifer Paul
Events:
Event Type: Activity has been assigned Date: 06/10/2024
Comment: Assigned to Sydney M Jackson
Events:
Event Type: Activity has been finished Date: 06/10/2024
Comment: Finished
Comments:
Comment Date: 06/07/2024 User: HARRINGTON_RD_1
Description: See 2024 Routine Inspection report and CA>Electronic Communications. This facility referral is being re-submitted due to it was rejected in error.
05/07/2024 Electronic Communication Activity Harrington, Richard D.
Activity Closed Date: 05/07/2024 Activity Status: Closed
Date: 05/07/2024
Recipient: Wenda Lewis
Sender: RH
Subject: Sent email follow up to 2024 TCI violations. Attached.
Message: Attached.
Events:
Event Type: Activity has been finished Date: 05/07/2024
Comment: Finished
05/07/2024 Enforcement Referral Activity Harrington, Richard D.
Activity Result: Rejected Activity Status: Closed
Activity Closed Date: 06/03/2024
Events:
Event Type: Activity has been assigned Date: 05/07/2024
Comment: Assigned to Sydney M Jackson
Events:
Event Type: Activity/Document was acknowledged on this date Date: 05/07/2024
Comment: Acknowledged and Assigned by Jennifer Paul
Events:
Event Type: Activity has been submitted for approval Date: 05/07/2024
Comment: Submitted for approval by: Richard D. Harrington: See 2024 TCI report.
Events:
Event Type: Activity has been finished Date: 06/03/2024
Comment: Finished
Events:
Event Type: Activity/Document was rejected on this date Date: 06/03/2024
Comment: Rejected by Sydney M Jackson: accepted
Comments:
Comment Date: 05/07/2024 User: HARRINGTON_RD_1
Description: See 2024 TCI report.
02/11/2024 Record Document Activity Harrington, Richard D.
Activity Status: Closed
Contact Name: Sally Leonard- ARC Dynamics- sleonard@arcdynamicsllc.com Activity Closed Date: 02/11/2024
Events:
Event Type: Activity has been finished Date: 02/11/2024
Comment: Finished
02/02/2024 Electronic Communication Activity Harrington, Richard D.
Activity Closed Date: 02/02/2024 Activity Status: Closed
Date: 02/02/2024
Recipient: Wenda Lewis
Sender: RH
Subject: Sent TCI 2024 and CAO.
Message: -
Events:
Event Type: Activity has been finished Date: 02/02/2024
Comment: Finished
01/28/2024 Violation Open Harrington, Richard D.
Significance: Minor Status: Open
Criteria ID: 6074
Rule: 62-761.710(1), 62-761.710(2), 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(3), 62-761.710(3)(a), 62-761.710(3)(b), 62-761.710(3)(c), 62-761.710(3)(d), 62-761.710(3)(e), 62-761.710(3)(f), 62-761.710(3)(g), 62-761.710(3)(h), 62-761.710(3)(i)
01/28/2024 Editable Letter Activity Harrington, Richard D.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 01/28/2024
Comment: Sent
Events:
Event Type: Activity has been finished Date: 01/28/2024
Comment: Finished
Comments:
Comment Date: 01/28/2024 User: HARRINGTON_RD_1
Description: CAO to be sent 1/29/2024 with TCI report.
Attachments:
Attachment Date: 01/28/2024 User: HARRINGTON_RD_1
Description: Compliance Assistance Offer Letter 2024
View Attachment
01/28/2024 Site Inspection Activity Closed Harrington, Richard D.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/18/2024
Activity Closed Date: 01/28/2024 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 01/28/2024
Comment: Finished
Comments:
Comment Date: 01/28/2024 User: HARRINGTON_RD_1
Description: Report to be emailed to Wenda Lewis and ARC Dynamics.
01/28/2024 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
01/28/2024 Violation Open Harrington, Richard D.
Significance: Minor Status: Open
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
01/28/2024 Violation Open Harrington, Richard D.
Significance: Minor Status: Open
Criteria ID: 6066
Rule: 62-761.700(1)(c), 62-761.700(1)(c)1, 62-761.700(1)(c)2
11/06/2023 Attachment Harrington, Richard D.
09/27/2021 Editable Letter Activity Keim, Michael J
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 09/27/2021
Comment: Finished
Events:
Event Type: Document has been sent Date: 09/27/2021
Comment: Sent
Attachments:
Attachment Date: 09/27/2021 User: KEIM_MJ_1
Description: RTC Letter
View Attachment
09/27/2021 Record Document Activity Keim, Michael J
Activity Status: Closed
Contact Name: Wenda Lewis Activity Closed Date: 09/27/2021
Events:
Event Type: Activity has been finished Date: 09/27/2021
Comment: Finished
08/29/2021 Violation Closed Keim, Michael J
Significance: SNC-B Status: Closed
Criteria ID: 6011
Rule: 62-761.420(2)
08/29/2021 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 08/29/2021 Activity Status: Closed
Date: 08/29/2021
Recipient: Wenda Lewis
Sender: M Keim
Subject: TCI report
Message: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com
Events:
Event Type: Activity has been finished Date: 08/29/2021
Comment: Finished
08/29/2021 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/29/2021
Comment: Finished
Events:
Event Type: Document has been sent Date: 08/29/2021
Comment: Sent
Attachments:
Attachment Date: 08/29/2021 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
08/29/2021 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 08/29/2021 Activity Status: Closed
Date: 08/29/2021
Recipient: Joe Long
Sender: M Keim
Subject: TCI
Message: E-mail correspondence regarding TCI scheduling and records needed.
Events:
Event Type: Activity has been finished Date: 08/29/2021
Comment: Finished
08/13/2021 Site Inspection Activity Closed Keim, Michael J
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 08/13/2021
Activity Closed Date: 08/29/2021 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 08/29/2021
Comment: Finished
Comments:
Comment Date: 08/29/2021 User: KEIM_MJ_1
Description: Storage tank inspection report and compliance letter sent via e-mail to Wenda Lewis, wlewis@lewisoilco.com Compliance assist with Jesse Wilkinson
03/12/2020 Site Inspection Activity Closed Ramsey, Timothy H
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/12/2020
Activity Closed Date: 03/12/2020 Activity Closed By: RAMSEY_TH_1
Events:
Event Type: Activity has been finished Date: 03/12/2020
Comment: Finished
Comments:
Comment Date: 03/12/2020 User: RAMSEY_TH_1
Description: Routine Compliance Inspection > Jesse Wilkinson with Petroleum Aids assisted with the inspection > Inspection of 2 Double Wall underground tanks. > Release detection methods for the facility's UST systems are: electronic monitoring for the interstice of the double-wall USTs and STP sumps, and visual inspections of the STP & dispenser sumps, and single-wall spill buckets. > Current tank registration placard is displayed in store. > Financial responsibility records for the UST systems are satisfactory. > Monthly electronic and visual release detection records for the UST systems are satisfactory. > Test records indicate annual operability tests for the Line leak detectors and ATG system were performed. Single wall spill buckets were hydro tested. > Note that some annual testing was completed more than 12 months apart. Please ensure that "Annual" testing is completed at least once every 12 months. > Dispenser sumps, and STP piping sumps were hydro tested and all passed. > Overfill devices (Ball valves) were tested. > All STP sumps, spill buckets, and dispenser sumps were dry > UST vent risers and vent caps are satisfactory. > All fuel nozzles, fuel hoses, and break-away fittings are in good condition. > A copy of the inspection report and In Compliance Letter were emailed to Wenda Lewis (WLewis@lewisoilco.com)
03/12/2020 Editable Letter Activity Ramsey, Timothy H
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/12/2020
Comment: Finished
Events:
Event Type: Document has been sent Date: 03/12/2020
Comment: Sent
Attachments:
Attachment Date: 03/12/2020 User: RAMSEY_TH_1
Description: In Compliance Letter
View Attachment
03/12/2020 Electronic Communication Activity Ramsey, Timothy H
Activity Closed Date: 03/12/2020 Activity Status: Closed
Date: 03/12/2020
Recipient: Wenda Lewis
Sender: Tim Ramsey
Subject: Copy of Inspection and In Compliance Letter
Message: Emailed Copy of Inspection and In Compliance Letter
Events:
Event Type: Activity has been finished Date: 03/12/2020
Comment: Finished
02/24/2020 Electronic Communication Activity Ramsey, Timothy H
Activity Closed Date: 02/24/2020 Activity Status: Closed
Date: 02/24/2020
Recipient: Wenda Lewis
Sender: Tim Ramsey
Subject: Outreach Email to schedule compliance inspection
Message: Sent Outreach Email to schedule compliance inspection
Events:
Event Type: Activity has been finished Date: 02/24/2020
Comment: Finished
08/09/2017 Site Inspection Activity Closed Ramsey, Timothy H
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/09/2017
Activity Closed Date: 08/09/2017 Activity Closed By: RAMSEY_TH_1
Events:
Event Type: Activity has been finished Date: 08/09/2017
Comment: Finished
Comments:
Comment Date: 08/09/2017 User: RAMSEY_TH_1
Description: Routine Compliance Inspection > Agustin Andres, Lewis Oil Inspector, assisted with the UST inspection. > Release detection methods for the facility's UST systems are: electronic monitoring for the interstices of the double-wall USTs and STP sumps; visual monitoring of the dispenser sumps. > 2017-2018 tank registration placard was reviewed. > Financial responsibility records and CFR for the UST systems are satisfactory. > Monthly visual and electronic release detection records for the UST systems from March 2015 to date are satisfactory. > Veeder Root system printer is not operable, so monthly status is recorded manually along with visual inspections. > Test records indicate annual operability tests of the Veeder-Root monitoring system were conducted on 12/30/2015 and on 12/8/2016 by Lewis Oil Co. > Testing of the MLLDs were conducted on 12/3/2015 and 12/29/2016 by Petroleum Aids. > All STP sumps, spill buckets, and dispenser sumps are satisfactory. Some water/PCW present in the spill buckets was pumped out for disposal during the inspection. > Secondary piping test fittings in the STP sumps are open; secondary piping test fittings in the dispenser sumps are capped. > All drop tubes and Vapor extractor dry-break adaptors are satisfactory. > UST vent risers and vent caps are satisfactory. > All fuel nozzles, fuel hoses, and break-away fittings are adequate. > All indicator lights and audible alarm on the Veeder-Root tank monitor are operational. > A copy of the inspection report was provided to Wenda Lewis by email.
08/09/2017 Issue Document Activity Ramsey, Timothy H
Activity Status: Closed
Contact Name: Wenda Lewis Activity Closed Date: 08/09/2017
Events:
Event Type: Activity has been finished Date: 08/09/2017
Comment: Finished
Attachments:
Attachment Date: 08/09/2017 User: RAMSEY_TH_1
Description: In Compliance Letter
View Attachment
08/09/2017 Electronic Communication Activity Ramsey, Timothy H
Activity Closed Date: 08/09/2017 Activity Status: Closed
Date: 08/09/2017
Recipient: Wenda Lewis
Sender: Tim Ramsey
Subject: Copy of inspection report and In Compliance Letter
Message: Emailed copy of inspection and In compliance letter to facility contact
Events:
Event Type: Activity has been finished Date: 08/09/2017
Comment: Finished
07/10/2017 Phone Conversation Activity Ramsey, Timothy H
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 339-4839 Activity Closed Date: 07/10/2017
Subject: Called facility inspector to schedule Routine Tank inspection and discuss required records for inspection
Events:
Event Type: Activity has been finished Date: 07/10/2017
Comment: Finished
05/26/2015 Record Document Activity Harrington, Richard D.
Activity Status: Closed
Contact Name: wenda lewis Activity Closed Date: 05/26/2015
Events:
Event Type: Activity has been finished Date: 05/26/2015
Comment: Finished
03/10/2015 Violation Closed Harrington, Richard D.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
03/10/2015 Emergency Preparedness Information Activity Harrington, Richard D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 03/10/2015
Events:
Event Type: Activity has been finished Date: 03/10/2015
Comment: Finished
03/10/2015 Editable Letter Activity Harrington, Richard D.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/10/2015
Comment: Finished
Attachments:
Attachment Date: 03/10/2015 User: HARRINGTON_RD_1
Description: ncl
View Attachment
03/10/2015 Site Inspection Activity Closed Harrington, Richard D.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/05/2015
Activity Closed Date: 03/10/2015 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 03/10/2015
Comment: Finished
Comments:
Comment Date: 03/10/2015 User: HARRINGTON_RD_1
Description: E-mailed report and ncl to Wenda Lewis 3/10/2015.
12/19/2012 Site Inspection Activity Closed Harrington, Richard D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/19/2012
Activity Closed Date: 12/19/2012 Activity Closed By: HARRINGTON_RD_1
Events:
Event Type: Activity has been finished Date: 12/19/2012
Comment: Finished
12/19/2012 Emergency Preparedness Information Activity Harrington, Richard D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 12/19/2012
Events:
Event Type: Activity has been finished Date: 12/19/2012
Comment: Finished
12/19/2012 Electronic Communication Activity Harrington, Richard D.
Activity Closed Date: 12/19/2012 Activity Status: Closed
Date: 12/19/2012
Recipient: w lewis
Sender: rh
Subject: sent report
Message: -
Events:
Event Type: Activity has been finished Date: 12/19/2012
Comment: Finished
06/09/2011 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/09/2011
Activity Closed Date: 06/09/2011 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 06/09/2011
Comment: Finished
06/09/2011 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/09/2011
Events:
Event Type: Activity has been finished Date: 06/09/2011
Comment: Finished
06/21/2010 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/21/2010
Activity Closed Date: 06/22/2010 Activity Closed By: OWENS_JS_1
Events:
Event Type: Activity has been finished Date: 06/22/2010
Comment: Finished
06/21/2010 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/21/2010
Events:
Event Type: Activity has been finished Date: 06/21/2010
Comment: Finished
06/01/2009 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/01/2009
Activity Closed Date: 06/02/2009 Activity Closed By: OWENS_JS_1
05/28/2008 Attachment Owens, Joe S.
05/14/2008 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/14/2008
Activity Closed Date: 05/14/2008 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 05/14/2008 User: OWENS_JS_1
Description: REVIEWED DOCUMENTS FOR FAC #: 9101062 Placard current & displayed: OK CFR form complete - FR records are updated - OK RDRL - present and applicable for facility: TANKS; Count. elect. monitoring of tank interstice / PIPING; Count. electric monitoring of piping interstice within STP sumps. MLLD. All disp. liners, spill buckets visual inspection. Site Diagram for accuracy, attached to ATTACHMENT Facility information. No changes frm. last inspection. Facility registration information including tank system attributes appear to be accurate. Monthly release detection records - Accepted. Date range for Inspection records: 6/2007 to present No Monthly ATG alarm status documented on insp. form - all systems normal w/ printout to verify - OK. A review of the Alarm Report for the ATG confirms the Operability test for the facility was performed. FUTURE DUE DATES OF FOLLOWING: Tank Insurance Renewal Due: 1/2009 MLLD testing due: 9/2008 Leak Sensor operability test due - 5/2009 Placard Registration renewal due- 6/2008 Visual inspection revealed: (3) STP sumps are dry and clean, no issues observed within the sumps. Spill buckets appear maintained, visual inspection did not reveal any apparent problems with integrity. Dispenser liners (2) are dry with no trace of any release, no issues addressed during monthly visual inspections. Monthly inspections should document any maint. which is performed or recommended as needed to prevent any release. The entry boots within the sumps appear sound and sealed ¿ no cracks observed and no leakage from any groundwater. Facility has no documented release and is currently not scored for funded clean-up work status. The compliance inspection folder is complete and concise - RDRL is posted above ATG and is applicable for facility - Facility inspection records well maintained. Operability Test performed w/ contact and (5) leak sensors functioned properly when inverted to simulate a leak - all reset (3 sumps & 2 interstice). Vapor recovery poppets are functional and marked correctly.
05/14/2008 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 05/14/2008
05/31/2007 Attachment Owens, Joe S.
05/29/2007 Attachment Owens, Joe S.
05/29/2007 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/29/2007
Activity Closed Date: 05/29/2007 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 05/29/2007 User: OWENS_JS_1
Description: REVIEWED DOCUMENTS FOR FAC #: 9101062 Placard current & displayed: OK CFR form complete - FR records are updated - OK RDRL - present and applicable for facility: TANKS; Monthly check of count. elect. monitoring of tank interstice / PIPING; count. electric monitoring of piping interstice within STP sumps. MLLD. All disp. liners, spill buckets visual inspection. Straight drop tubes w/ ball check for overfill prevention. Site Diagram for accuracy, attached to ATTACHMENT Facility information. Facility registration information including tank system attributes appear to be accurate. Monthly elect. release detection records - Accepted. Date range for Inspection records: 5/2006 to present No Monthly ATG alarm status documented on insp. form - all systems normal w/ printout to verify - OK. A review of the Alarm Report for the ATG confirms the Operability test for the facility was performed. FUTURE DUE DATES OF FOLLOWING: Tank Insurance Renewal Due: 1/31/08 MLLD - 9/2007 Leak Sensor operability test due - 5/2008 Placard Registration renewal due: 6/2007 Visual inspection revealed: STP sumps are dry and clean, Spill buckets contain a slight trace of fuel but appear maintained. Dispenser liners (2) are dry with no trace of any release, no issues addressed during monthly visual inspections. Monthly inspections should document any maint. which is performed or recommended as needed to prevent any release. No Diesel present for this facility. The entry boots within the sumps appear sound and sealed ¿ no cracks observed and no leakage from any groundwater. Facility has a documented release and is currently scored a 5 - below current clean-up work status. The compliance inspection folder is complete and concise - RDRL is posted above ATG and is applicable for facility - Facility inspection records well maintained. Operability Test performed w/ contact and (5) leak sensors functioned properly when inverted to simulate a leak - all reset (3 sumps & 2 interstice). The facility has TCI tanks w/ TCI sumps and no indication of any water intrusion evident. All components appear dry and no staining present to indicate any release. Buckets are steel and have a slight amount of liquid but records indicate that contact maintains a active removal log of any residual product following deliveries.
02/08/2007 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/08/2007
09/21/2006 Emergency Preparedness Information Activity Owens, Joe S.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/21/2006
07/26/2006 Site Inspection Activity Closed Owens, Joe S.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/26/2006
Activity Closed Date: 07/26/2006 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 07/26/2006 User: OWENS_JS_1
Description: The Reg. sump has a installed coupling for the electrical power, in the side of the sump which was installed during fabrication. The appearance of the entry is that a boot was not in-place and could possibly was leaking. Due to the depth of the sump, the inspector could not inspect closely the component. A hydrostatic integrity test was requested / performed on the sump and after 48 hrs. the level of the water was un-changed. Hydro-static test of Reg. sump entry fittings - passed.
05/01/2006 Editable Letter Activity Ramsey, Timothy H
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 05/01/2006
Comment: Sent on Mon May 01 12:00:00 EST 2006
Attachments:
Attachment Date: 05/01/2006 User: RAMSEY_TH_1
Description: NCL Report
View Attachment
04/26/2006 Violation Closed Owens, Joe S.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
04/26/2006 Site Inspection Activity Closed Owens, Joe S.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/26/2006
Activity Closed Date: 04/26/2006 Activity Closed By: OWENS_JS_1
Comments:
Comment Date: 04/26/2006 User: OWENS_JS_1
Description: Reviewed RDRL, CFR, Monthly inspection records, MLLD Test, monthly ATG status printouts, Maint reports - ALL OK. Visual inspection of (3) sumps ((see note)), Spill bucket/fills w/ straight drop tubes for overfill protection, (2) vapor recovery ports and (2) disp. liners - all except Reg. sump appear sound. Records of inspections indicate timely inspections performed on time w/ sufficient maint. performed to prevent any release from occuring. CFR & RDRL posted near ATG and copies from contact in inspection packet. Tests perfromed: Operability today of (5) leaqk sensors - (3) sump & (2) interstice - function tested properly. MLLD was s few days late - please maintain the testing within 365 days of the previous year in the future. NOTE FOR REG. SUMP: the entry boot on the power conduit appears to have a problem - not all of the boot is visible; please repair - Photo taken and included in inspection.
05/24/2005 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: MLLD TEST 8/18/04, ANNUAL OPERABILITY TEST 5/24/05
03/11/2004 Legacy Activity Dohaney, Tim
Activity Name: TANK COMPLIANCE - DISTRICT QA INSPECTION Activity Status: Closed
Completion Notes: QA CONDUCTED PRIOR TO ANNUAL PROGRAM REVIEW.
01/28/2004 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: LLD 9/11/03, ANNUAL OPERABILITY TEST 1/28/04
04/23/2003 Legacy Activity Ramsey, Timothy H
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: ANNUAL OPERABILITY TEST 4/23/03
02/20/2003 Violation Closed Ramsey, Timothy H
Significance: Minor Status: Closed
Rule: 600(1)(a)2
02/20/2003 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: LLD TEST 8/20/02
02/15/2002 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE INSPECTION, ANNUAL OPERATIONS TEST 2/15/02, PLD TESTED 8/31/01
02/15/2001 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE INSPECTION
05/03/2000 Legacy Activity Ramsey, Timothy H
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: COMPLIANCE INSPECTION
03/01/2000 Legacy Activity Ramsey, Timothy H
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
Completion Notes: INSTALLATION INSPECTION
09/07/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 600(1)(d)
09/07/1999 Legacy Activity Buono, Mike
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
09/07/1999 Violation Closed Buono, Mike
Significance: Minor Status: Closed
Rule: 700(1)(a)1
06/03/1999 Legacy Activity Buono, Mike
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/11/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/23/2023 User: MCARTOR_H_1
Description: Jason Cason email: Jack.Cason@cologix.com
Comments:
Comment Date: 10/19/2023 User: MCARTOR_H_1
Description: Twann Davis
Comments:
Comment Date: 06/28/2007 User: TISSINGTON_AB_1
Description: Alabama DW stip3 steel tank eq # 277 Ameron fiberglass DW pipe eq # 378 Sumps are Total Containment eq # 122 Liners are Formex eq # 001 Veederoot TLS 350 eq # 033 Red Jacket FXIV MLLD eq # 373 Visual inspection of sumps and liners ATG monitors tank interstice for release detection
02/11/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/23/2023 User: MCARTOR_H_1
Description: Jason Cason email: Jack.Cason@cologix.com
Comments:
Comment Date: 10/19/2023 User: MCARTOR_H_1
Description: Twann Davis
Comments:
Comment Date: 06/28/2007 User: TISSINGTON_AB_1
Description: Alabama DW stip3 steel tank eq # 277 Ameron fiberglass DW pipe eq # 378 Sumps are Total Containment eq # 122 Liners are Formex eq # 001 Veederoot TLS 350 eq # 033 Red Jacket FXIV MLLD eq # 373 Visual inspection of sumps and liners ATG monitors tank interstice for release detection
02/11/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/23/2023 User: MCARTOR_H_1
Description: Jason Cason email: Jack.Cason@cologix.com
Comments:
Comment Date: 10/19/2023 User: MCARTOR_H_1
Description: Twann Davis
Comments:
Comment Date: 06/28/2007 User: TISSINGTON_AB_1
Description: Alabama DW stip3 steel tank eq # 277 Ameron fiberglass DW pipe eq # 378 Sumps are Total Containment eq # 122 Liners are Formex eq # 001 Veederoot TLS 350 eq # 033 Red Jacket FXIV MLLD eq # 373 Visual inspection of sumps and liners ATG monitors tank interstice for release detection
02/11/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/28/2007 User: TISSINGTON_AB_1
Description: Alabama DW stip3 steel tank eq # 277 Ameron fiberglass DW pipe eq # 378 Sumps are Total Containment eq # 122 Liners are Formex eq # 001 Veederoot TLS 350 eq # 033 Red Jacket FXIV MLLD eq # 373 Visual inspection of sumps and liners ATG monitors tank interstice for release detection
Comments:
Comment Date: 01/31/2006 User: UNKNOWN
Description: COMMUNICATION: TO: NONE, SITE MANAGER Email: None - Default to:...compliancenotification@dep.state.fl.us Email Date: 01/31/2006 ACTIVITY ID: 11684857 - TANK ANNUAL COMPLIANCE INSPECTION WAS PERFORMED AT FACILITY ID: 9801063 ON 01/31/2006 BY MILTON LARA. EVALUATION RESULT = IN-COMPLIANCE. ACTIVITY RECORDED ON 01/31/2006 USER: MILTON LARA OF ST JOHNS COUNTY HEALTH DEPARTMENT
02/11/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 06/28/2007 User: TISSINGTON_AB_1
Description: Alabama DW stip3 steel tank eq # 277 Ameron fiberglass DW pipe eq # 378 Sumps are Total Containment eq # 122 Liners are Formex eq # 001 Veederoot TLS 350 eq # 033 Red Jacket FXIV MLLD eq # 373 Visual inspection of sumps and liners ATG monitors tank interstice for release detection
Comments:
Comment Date: 01/31/2006 User: UNKNOWN
Description: COMMUNICATION: TO: NONE, SITE MANAGER Email: None - Default to:...compliancenotification@dep.state.fl.us Email Date: 01/31/2006 ACTIVITY ID: 11684857 - TANK ANNUAL COMPLIANCE INSPECTION WAS PERFORMED AT FACILITY ID: 9801063 ON 01/31/2006 BY MILTON LARA. EVALUATION RESULT = IN-COMPLIANCE. ACTIVITY RECORDED ON 01/31/2006 USER: MILTON LARA OF ST JOHNS COUNTY HEALTH DEPARTMENT
02/11/1998 Legacy Activity Carawan, Lorraine S.
Activity Name: UST ROUTINE COMPLIANCE INSPECTION Activity Status: Closed