DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/27/2025        Last Data Refresh: 04/26/2025        Report Generated from DOPPLER
 
Facility ID: 9103007
Facility Name: REBEL #838
 
08/27/2024 Editable Letter Activity Wimberly, Evan
Activity Title: Warning Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/27/2024
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 08/27/2024
Comment: Submitted for approval by: Evan Wimberly
Events:
Event Type: Activity/Document has been approved Date: 08/27/2024
Comment: Approved by Jayme Brock: Approved
Attachments:
Attachment Date: 08/27/2024 User: WIMBERLY_E
Description: WL24-147TK52SWD
View Attachment
07/26/2024 Enforcement Tracking Activity Wimberly, Evan
Activity Status: Open
06/28/2024 Electronic Communication Activity TUCKER, SHARYN
Activity Closed Date: 06/28/2024 Activity Status: Closed
Date: 06/28/2024
Recipient: Licensing Info
Sender: Sharyn Tucker- FDOH
Subject: reminder of 2 violations left
Message: 2 violation left: 1) Liquid in RUL and MUL (E0) spill buckets occurred after integrity test was conducted on 5/3/2023. Provide investigation results and confirm that the RUL and E0 spill buckets are tight. 2) Periodic integrity testing of the STP sumps and UDCs is overdue as of 4/15/2023. Sharyn Tucker Environmental Specialist II Florida Department of Health Pinellas County Petroleum Storage Tank Compliance Tarpon Springs Center 301 S Disston Ave Tarpon Springs FL 34689 Office 727-485-1834 Fax 727-538-7293 sharyn.tucker@flhealth.gov We value your feedback as a customer. We are committed to continuously assessing and improving the level and quality of services provided to you. To comment on the quality of service you received, simply click on this link to our Customer Survey. Thank you in advance for completing the survey. Please consider our environment before printing this e-mail. FDOH Mission: To protect, promote & improve the health of all people in Florida through integrated state, county, & community efforts. Please note: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. This e-mail communication may therefore be subject to public disclosure. From: Tucker, Sharyn Sent: Friday, March 29, 2024 7:16 AM To: Licensing Info Subject: Re: FEF 838 - FL Pinellas County UST - Inspection Report and Compliance Asst. Letter - 9103007 Good morning 2 violation left: Liquid in RUL and MUL (E0) spill buckets occurred after integrity test was conducted on 5/3/2023. Periodic integrity testing of the STP sumps and UDCs is overdue as of 4/15/2023. Sharyn Tucker Environmental Specialist II Florida Department of Health Pinellas County Petroleum Storage Tank Compliance Tarpon Springs Center 301 S Disston Ave Tarpon Springs FL 34689 Office 727-485-1834 Fax 727-538-7293 sharyn.tucker@flhealth.gov We value your feedback as a customer. We are committed to continuously assessing and improving the level and quality of services provided to you. To comment on the quality of service you received, simply click on this link to our Customer Survey. Thank you in advance for completing the survey. Please consider our environment before printing this e-mail. FDOH Mission: To protect, promote & improve the health of all people in Florida through integrated state, county, & community efforts. Please note: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. This e-mail communication may therefore be subject to public disclosure. ________________________________________ From: Licensing Info Sent: Thursday, March 28, 2024 6:20 PM To: Tucker, Sharyn Subject: Read: FEF 838 - FL Pinellas County UST - Inspection Report and Compliance Asst. Letter - 9103007 EXTERNAL EMAIL: DO NOT CLICK links or open attachments unless you recognize the sender and know the content is safe.
Events:
Event Type: Activity has been finished Date: 06/28/2024
Comment: Finished
06/28/2024 Electronic Communication Activity TUCKER, SHARYN
Activity Closed Date: 06/28/2024 Activity Status: Closed
Date: 06/28/2024
Recipient: darwinpelphrey@guardianfueltech.com
Sender: Sharyn Tucker- FDOH
Subject: email to compliance company for 2 outstanding violations
Message: Hi Lee, Pleasure to meet you in person today. Below is the only 2 outstanding violations I have for store #838. I believe someone else is currently getting me the info for store #836. If you want I can let you know. Violation: Liquid in RUL and MUL (E0) spill buckets occurred after integrity test was conducted on 5/3/2023. Corrective Action: Provide investigation results and confirm that the RUL and E0 spill buckets are tight. Violation: Periodic integrity testing of the STP sumps and UDCs is overdue as of 4/15/2023. Corrective Action: Provide integrity test results for the STP sumps and UDCs. Sharyn Tucker Environmental Specialist II Florida Department of Health Pinellas County Petroleum Storage Tank Compliance Tarpon Springs Center 301 S Disston Ave Tarpon Springs FL 34689 Office 727-485-1834 Fax 727-538-7293 sharyn.tucker@flhealth.gov We value your feedback as a customer. We are committed to continuously assessing and improving the level and quality of services provided to you. To comment on the quality of service you received, simply click on this link to our Customer Survey. Thank you in advance for completing the survey. Please consider our environment before printing this e-mail. FDOH Mission: To protect, promote & improve the health of all people in Florida through integrated state, county, & community efforts. Please note: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. This e-mail communication may therefore be subject to public disclosure.
Events:
Event Type: Activity has been finished Date: 06/28/2024
Comment: Finished
06/27/2024 Record Document Activity TUCKER, SHARYN
Activity Status: Closed
Contact Name: Compliance Activity Closed Date: 06/28/2024
Events:
Event Type: Activity has been finished Date: 06/28/2024
Comment: Finished
05/16/2024 Electronic Communication Activity Juaristic, George K.
Activity Closed Date: 05/16/2024 Activity Status: Closed
Date: 05/16/2024
Recipient: George Juaristic
Sender: Compliance
Subject: see attached CA response
Message: see attached CA response
Events:
Event Type: Activity has been finished Date: 05/16/2024
Comment: Finished
05/16/2024 Electronic Communication Activity Juaristic, George K.
Activity Closed Date: 05/16/2024 Activity Status: Closed
Date: 05/16/2024
Recipient: Compliance
Sender: Sharyn Tucker [Sharyn.Tucker@FLHealth.gov]
Subject: see attached Compliance Assistance Emails and responses from 3/28-4/3/2024
Message: see attached Compliance Assistance Emails and responses from 3/28-4/3/2024
Events:
Event Type: Activity has been finished Date: 05/16/2024
Comment: Finished
05/16/2024 Electronic Communication Activity Juaristic, George K.
Activity Closed Date: 05/16/2024 Activity Status: Closed
Date: 05/16/2024
Recipient: Compliance
Sender: George Juaristic
Subject: RE: FEF 838 - FL Pinellas County UST - Inspection Report and Compliance Asst. Letter - 9103007
Message: Good morning, We are quickly approaching 90-days on the outstanding violation: 9103007 REBEL #838 Minor 02/01/2024 Periodic integrity testing of the STP sumps and UDCs is overdue as of 4/15/2023. Please provide the integrity test results for the STP sumps and UDCs immediately, to prevent enforcement activities. Thanks, George K Juaristic Environmental Supervisor I Florida Department of Health Pinellas County Petroleum Storage Tank Compliance Tarpon Springs Center 301 S Disston Ave Tarpon Springs FL 34689 Office 727-485-1817 Fax 727-538-7293 george.juaristic@flhealth.gov
Events:
Event Type: Activity has been finished Date: 05/16/2024
Comment: Finished
05/16/2024 Electronic Communication Activity Juaristic, George K.
Activity Closed Date: 05/16/2024 Activity Status: Closed
Date: 05/16/2024
Recipient: Compliance
Sender: Sharyn Tucker [Sharyn.Tucker@FLHealth.gov]
Subject: FW: FEF 838 - FL Pinellas County UST - Inspection Report and Compliance Asst. Letter - 9103007
Message: Good afternoon, Please advise the status of the outstanding violations cited in the routine report. Violation Liquid in RUL and MUL (E0) spill buckets occurred after integrity test was conducted on 5/3 /2023. Corrective Action: Provide investigation results and confirm that the RUL and E0 spill buckets are tight. Violation: Periodic integrity testing of the STP sumps and UDCs is overdue as of 4/15/2023. Corrective Action: Provide integrity test results for the STP sumps and UDCs. Violation: Observed a strong vapor odor emanating from the RUL STP sump and repair. Causing corrosion in the RUL STP sump. Corrective Action: Investigate the source of the strong vapor odor emanating from the RUL STP sump and repair. Sharyn Tucker Environmental Specialist II Florida Department of Health Pinellas County Petroleum Storage Tank Compliance Tarpon Springs Center 301 S Disston Ave Tarpon Springs FL 34689 Office 727-485-1834 Fax 727-538-7293 sharyn.tucker@flhealth.gov
Events:
Event Type: Activity has been finished Date: 05/16/2024
Comment: Finished
05/07/2024 Enforcement Referral Activity Juaristic, George K.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 07/26/2024
Events:
Event Type: Activity/Document was accepted on this date Date: 07/26/2024
Comment: Accepted by Evan Wimberly: Assigned to Evan Wimberly
Events:
Event Type: Activity has been finished Date: 07/26/2024
Comment: Finished
Events:
Event Type: Activity has been assigned Date: 07/18/2024
Comment: Assigned to Evan Wimberly
Events:
Event Type: Activity has been submitted for approval Date: 05/16/2024
Comment: Submitted for approval by: George K. Juaristic: Routine compliance inspection conducted on 1/22/2024. CAO Letter sent 2/2/2024. Violations cited for the following: 1. Corrosion in STP sump (resolved with 3/28/2024 WO). 2. Liquid in RUL and MUL (E0) spill buckets occurred after integrity test was conducted on 5/3/2023. 3. Periodic integrity testing of the STP sumps and UDCs is overdue as of 4/15/2023. Compliance Assistance Emails sent on 2/26/2024, 3/28/2024 (response received 3/29), 4/1 (response received 4/1 and 4/3), and 4/24/2024 (response received same day). Facility stated that they are waiting on a quote from JF Petroleum for repairs. Corporate filing sheet and property appraiser sheet attached.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 07/18/2024
Comment: Acknowledged and Assigned by Jayme Brock
Comments:
Comment Date: 05/16/2024 User: JUARISTIC_GK_1
Description: Routine compliance inspection conducted on 1/22/2024. CAO Letter sent 2/2/2024. Violations cited for the following: 1. Corrosion in STP sump (resolved with 3/28/2024 WO). 2. Liquid in RUL and MUL (E0) spill buckets occurred after integrity test was conducted on 5/3/2023. 3. Periodic integrity testing of the STP sumps and UDCs is overdue as of 4/15/2023. Compliance Assistance Emails sent on 2/26/2024, 3/28/2024 (response received 3/29), 4/1 (response received 4/1 and 4/3), and 4/24/2024 (response received same day). Facility stated that they are waiting on a quote from JF Petroleum for repairs. Corporate filing sheet and property appraiser sheet attached.
04/03/2024 Electronic Communication Activity TUCKER, SHARYN
Activity Closed Date: 04/03/2024 Activity Status: Closed
Date: 04/03/2024
Recipient: Compliance
Sender: Sharyn Tucker- FDOH
Subject: RE: FEF 838 - FL Pinellas County UST - Inspection Report and Compliance Asst. Letter - 9103007
Message: Hi David, I looked back at the emails and documentation Erin sent in. On March 28th they only addressed the corrosion. I assumed that she sent in all the corrections which is why I originally stated I would try to close out the report. If you could either find the email with the documentation for the integrity test dues 4/15/23 for the STP sumps and documentation or invoice for liquid in the spill bucket secondaries, I can close these right away. Here are the 2 violation left: 1) Liquid in RUL and MUL (E0) spill buckets occurred after integrity test was conducted on 5/3/2023. Provide investigation results and confirm that the RUL and E0 spill buckets are tight. 2) Periodic integrity testing of the STP sumps and UDCs is overdue as of 4/15/2023. Thank you for your swift response. Also to note if you need to update the emails for this facility, you will have to go on DEP website to do so. Your information is prepopulated from DEP so I cannot change it on my end. Hope this helps 2 violation left: 1) Liquid in RUL and MUL (E0) spill buckets occurred after integrity test was conducted on 5/3/2023. Provide investigation results and confirm that the RUL and E0 spill buckets are tight. 2) Periodic integrity testing of the STP sumps and UDCs is overdue as of 4/15/2023.
Events:
Event Type: Activity has been finished Date: 04/03/2024
Comment: Finished
03/28/2024 Record Document Activity TUCKER, SHARYN
Activity Status: Closed
Contact Name: Erin Acosta Activity Closed Date: 04/02/2024
Events:
Event Type: Activity has been finished Date: 04/02/2024
Comment: Finished
02/01/2024 Violation Open Juaristic, George K.
Significance: Minor Status: Open
Criteria ID: 6009
Rule: 62-761.405(3)
02/01/2024 Editable Letter Activity Juaristic, George K.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 02/02/2024
Comment: Submitted for approval by: SHARYN TUCKER
Events:
Event Type: Document has been sent Date: 02/02/2024
Comment: Sent
Events:
Event Type: Activity has been finished Date: 02/23/2024
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 02/23/2024
Comment: Approved by George K. Juaristic: Good
Attachments:
Attachment Date: 02/02/2024 User: TUCKER_SX_1
Description: CAO letter
View Attachment
02/01/2024 Violation Open Juaristic, George K.
Significance: Minor Status: Open
Criteria ID: 6024
Rule: 62-761.500(1)(b)4, 62-761.500(1)(b)5, 62-761.500(1)(b)6, 62-761.500(1)(b)7
01/22/2024 Violation Closed Juaristic, George K.
Significance: SNC-B Status: Closed
Criteria ID: 6063
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2
01/22/2024 Site Inspection Activity Closed TUCKER, SHARYN
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 01/22/2024
Activity Closed Date: 02/01/2024 Activity Closed By: JUARISTIC_GK_1
Events:
Event Type: Activity has been finished Date: 02/01/2024
Comment: Finished
Comments:
Comment Date: 02/01/2024 User: JUARISTIC_GK_1
Description: Records Review: Financial Responsibility: Ironshore Specialty Insurance Co. Part D and P Financial Responsibility forms. UST Training Certificates: A/B for Romina Palmer, and Class C training certificates provided. *Tanknology reports E0 as MUL in visual inspection reports and testing. Release Detection: Monthly visual inspections of the "Spill Containment Buckets, STP Containment Sumps, and Dispensers". 5/31-6/27/2023 reported RUL and MUL spill bucket secondaries contained liquid. *(2) Liquid in RUL and MUL (E0) spill buckets occurred after integrity test was conducted on 5/3/2023. Provide investigation results and confirm that the RUL and E0 spill buckets are tight. Electronic monitoring of the tank interstices and STP sumps. 2/15/2022-4/21/2023 documented Release Detection "Electronic Interstitial Monitoring not in alarm" instead of pulling liquid and smart sensor status reports. 5/31/2023 to 1/8/2024 liquid status tapes monitoring the tank interstices (3) and UDCs (3), and smart sensor status. Following positive response of a release detection level reported: 5/31/2023: L4 RUL STP and L6 PUL STP Fuel Alarms, reported as 12" of liquid; 9/3/2023, 10/5/2023, 11/3/2023, 12/6/2023, and 1/8/2024: L4 RUL STP Fuel Alarms, reported as 5" of liquid in sump; 12/6/2023: L3 PUL Interstitial Low Liquid Alarm Tests: See System Tests section. *(3) Periodic integrity testing of the STP sumps and UDCs is overdue as of 4/15/2023. Provide integrity test results for the STP sumps and UDCs. *(4) The RUL and E0 spill bucket gauges failed the 5/3/2023 annual operability test results. Provide passing test results for the RUL and E0 spill bucket gauges. Report will be emailed to LICENSING@CARENTERPRISES.NET
01/09/2024 Electronic Communication Activity Juaristic, George K.
Activity Closed Date: 01/09/2024 Activity Status: Closed
Date: 01/09/2024
Recipient: LICENSING@CARENTERPRISES.NET
Sender: George Juaristic
Subject: see attached NOI
Message: see attached NOI
Events:
Event Type: Activity has been finished Date: 01/09/2024
Comment: Finished
06/27/2023 Site Inspection Activity Closed Colson, Nathan J
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/05/2023
Activity Closed Date: 06/27/2023 Activity Closed By: COLSON_NJ_1
Events:
Event Type: Activity has been finished Date: 06/27/2023
Comment: Finished
06/27/2023 Editable Letter Activity Colson, Nathan J
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/27/2023
Comment: Finished
Events:
Event Type: Document has been sent Date: 06/27/2023
Comment: Sent
Attachments:
Attachment Date: 06/27/2023 User: COLSON_NJ_1
Description: 06/27/2023 In Compliance Letter
View Attachment
06/27/2023 Editable Letter Activity Colson, Nathan J
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/27/2023
Comment: Sent
Events:
Event Type: Activity has been finished Date: 06/27/2023
Comment: Finished
Attachments:
Attachment Date: 06/27/2023 User: COLSON_NJ_1
Description: 06/27/2023 In Compliance Letter
View Attachment
06/26/2023 Site Inspection Activity Closed Colson, Nathan J
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/05/2023
Activity Closed Date: 06/27/2023 Activity Closed By: COLSON_NJ_1
Events:
Event Type: Activity has been finished Date: 06/27/2023
Comment: Finished
Comments:
Comment Date: 06/27/2023 User: COLSON_NJ_1
Description: A Closure Assessment Report was submitted on 05/26/2023 & appears to comply with FDEP requirements.
05/30/2023 Document Management Activity Lashbrook, Scott John
Activity Title: Closure Document Activity Status: Submitted
Events:
Event Type: Activity has been submitted for approval Date: 05/30/2023
Comment: Submitted for approval by: Scott John Lashbrook
Attachments:
Attachment Date: 05/30/2023 User: LASHBROOK_SJ_1
Description: Closure Assessment Report
View Attachment
05/30/2023 TCAR Activity Lashbrook, Scott John
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 06/27/2023
Events:
Event Type: Activity has been finished Date: 06/27/2023
Comment: Finished
Attachments:
Attachment Date: 06/27/2023 User: COLSON_NJ_1
Description: 05/26/2023 SB Closure Assessment Report
View Attachment
04/11/2023 Attachment Colson, Nathan J
09/19/2022 Editable Letter Activity Shock, Eric
Activity Title: Return to Compliance Letter Activity Status: Closed
Description: Inspection/ECAO email
Events:
Event Type: Activity has been finished Date: 09/20/2022
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 09/20/2022
Comment: Approved by Scott John Lashbrook: Approve 9/19/2022 RTC Letter
Events:
Event Type: Document has been sent Date: 09/19/2022
Comment: Sent
Events:
Event Type: Activity has been submitted for approval Date: 09/19/2022
Comment: Submitted for approval by: Eric Shock
Attachments:
Attachment Date: 09/19/2022 User: SHOCK_E_1
Description: Return to compliance letter Rebel 838
View Attachment
09/19/2022 Record Document Activity Shock, Eric
Activity Status: Closed
Contact Name: Kristina Daines Activity Closed Date: 09/19/2022
Events:
Event Type: Activity has been finished Date: 09/19/2022
Comment: Finished
Attachments:
Attachment Date: 09/19/2022 User: SHOCK_E_1
Description: RUL SB repairs & integrity test results
View Attachment
07/21/2022 Record Document Activity Shock, Eric
Activity Status: Closed
Contact Name: Damon Bastin Activity Closed Date: 07/21/2022
Events:
Event Type: Activity has been finished Date: 07/21/2022
Comment: Finished
Comments:
Comment Date: 07/21/2022 User: SHOCK_E_1
Description: Facility provided multiple MUSTIs, multiple liquid status tapes, annual testing results for 2020, 2021 and 2022, and integrity testing for 2020.
Attachments:
Attachment Date: 07/21/2022 User: SHOCK_E_1
Description: Integrity retest 3 2020
View Attachment
Attachments:
Attachment Date: 07/21/2022 User: SHOCK_E_1
Description: Annual operability testing for 2022
View Attachment
Attachments:
Attachment Date: 07/21/2022 User: SHOCK_E_1
Description: Integrity testing for 2020
View Attachment
Attachments:
Attachment Date: 07/21/2022 User: SHOCK_E_1
Description: Integrity retest 1 2020
View Attachment
Attachments:
Attachment Date: 07/21/2022 User: SHOCK_E_1
Description: Liquid status tapes 3/16/22
View Attachment
Attachments:
Attachment Date: 07/21/2022 User: SHOCK_E_1
Description: MUSTI from 6/15/22
View Attachment
Attachments:
Attachment Date: 07/21/2022 User: SHOCK_E_1
Description: MUSTI from 4/21/22
View Attachment
Attachments:
Attachment Date: 07/21/2022 User: SHOCK_E_1
Description: Liquid status tapes 5/19/22
View Attachment
Attachments:
Attachment Date: 07/21/2022 User: SHOCK_E_1
Description: MUSTI from 5/19/22
View Attachment
06/02/2022 Record Document Activity Shock, Eric
Activity Status: Closed
Contact Name: Christina Devellerez Activity Closed Date: 06/02/2022
Events:
Event Type: Activity has been finished Date: 06/02/2022
Comment: Finished
Attachments:
Attachment Date: 06/02/2022 User: SHOCK_E_1
Description: Tank registration placard 2021-2022
View Attachment
05/18/2022 Record Document Activity Shock, Eric
Activity Status: Closed
Contact Name: Romina Palmer Activity Closed Date: 05/18/2022
Events:
Event Type: Activity has been finished Date: 05/18/2022
Comment: Finished
Comments:
Comment Date: 05/18/2022 User: SHOCK_E_1
Description: The facility also provided 6 other UST Class C operator certs that were not uploaded
Attachments:
Attachment Date: 05/18/2022 User: SHOCK_E_1
Description: Romina Palmer UST Class A-B-C cert
View Attachment
Attachments:
Attachment Date: 05/18/2022 User: SHOCK_E_1
Description: Example UST Class C cert
View Attachment
05/04/2022 Editable Letter Activity Lashbrook, Scott John
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 05/05/2022
Comment: Sent
Events:
Event Type: Activity has been submitted for approval Date: 05/05/2022
Comment: Submitted for approval by: Eric Shock
Events:
Event Type: Activity/Document has been approved Date: 05/06/2022
Comment: Approved by Scott John Lashbrook: Approve 5/5/2022 CAO Letter
Events:
Event Type: Activity has been finished Date: 05/06/2022
Comment: Finished
Attachments:
Attachment Date: 05/05/2022 User: SHOCK_E_1
Description: Compliance Assistance Offer Letter Rebel #838
View Attachment
05/03/2022 Violation Closed Lashbrook, Scott John
Significance: Minor Status: Closed
Criteria ID: 6066
Rule: 62-761.700(1)(c), 62-761.700(1)(c)1, 62-761.700(1)(c)2
05/03/2022 Violation Closed Lashbrook, Scott John
Significance: Minor Status: Closed
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
05/02/2022 Violation Closed Lashbrook, Scott John
Significance: Minor Status: Closed
Criteria ID: 6074
Rule: 62-761.710(1), 62-761.710(2), 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(3), 62-761.710(3)(a), 62-761.710(3)(b), 62-761.710(3)(c), 62-761.710(3)(d), 62-761.710(3)(e), 62-761.710(3)(f), 62-761.710(3)(g), 62-761.710(3)(h), 62-761.710(3)(i)
05/02/2022 Site Inspection Activity Closed Shock, Eric
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 04/19/2022
Activity Closed Date: 05/04/2022 Activity Closed By: LASHBROOK_SJ_1
Events:
Event Type: Activity/Document has been approved Date: 05/04/2022
Comment: Approved by Scott John Lashbrook: Approve 4/19/2022 inspection report
Events:
Event Type: Activity has been finished Date: 05/04/2022
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 05/03/2022
Comment: Submitted for approval by: Eric Shock
05/02/2022 Violation Closed Lashbrook, Scott John
Significance: Minor Status: Closed
Criteria ID: 6002
Rule: 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2, 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7)
05/02/2022 Violation Closed Lashbrook, Scott John
Significance: Minor Status: Closed
Criteria ID: 6006
Rule: 62-761.400(5)
05/02/2022 Violation Closed Lashbrook, Scott John
Significance: Minor Status: Closed
Criteria ID: 6072
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1, 62-761.700(3)(a)1.a, 62-761.700(3)(a)1.b, 62-761.700(3)(a)1.c, 62-761.700(3)(a)1.d, 62-761.700(3)(a)1.e, 62-761.700(3)(a)1.f, 62-761.700(3)(a)1.g, 62-761.700(3)(a)2
05/02/2022 Violation Closed Lashbrook, Scott John
Significance: Minor Status: Closed
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
05/02/2022 Violation Closed Lashbrook, Scott John
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
05/02/2022 Violation Closed Lashbrook, Scott John
Significance: SNC-B Status: Closed
Criteria ID: 6056
Rule: 62-761.600(1)(d), 62-761.600(1)(e), 62-761.600(1)(g)
05/02/2022 Violation Closed Lashbrook, Scott John
Significance: Minor Status: Closed
Criteria ID: 6075
Rule: 62-761.710(4)
01/20/2022 Electronic Communication Activity Shock, Eric
Activity Closed Date: 01/20/2022 Activity Status: Closed
Date: 01/20/2022
Recipient: Romina Palmer, Jason Alvarado and LICENSING@CARENTERPRISES.NET
Sender: Eric Shock
Subject: 9103007 REBEL at 5798 Roosevelt Blvd N, Clearwater, FL
Message: Good morning All, We also need to conduct a compliance inspection, at the above subject facility (sorry that this one was left off the previous list of north Pinellas inspection locations). I believe this location might be in Jason’s service area, if he can reach out to me, we can take care of it on his next planned visit to the location. You can view the Preparing for a Storage Tank Inspection Information Video¿on the FDEP website : http://www.dep.state.fl.us/waste/categories/tanks/default.htm for information on the inspection process. Please review the previous inspection to help prepare and ensure that this facility remains in compliance. If you don’t have copies of the previous inspections, you can find them at Florida Department of Environmental Protection Electronic Document Management System (OCULUS) https://depedms.dep.state.fl.us/Oculus/servlet/login?loginState=loginInvalidPassword. Click on “Public Oculus Login”, select “Storage Tanks” under the category tab, then select “Property” under the Search by tab, then select “Facility-Site ID” under the Property tab. You can then enter the facility ID# to search all the documents for the facility. Thanks you, Eric Shock Environmental Specialist II Storage Tank Compliance Environmental Health Division Florida Department of Health in Pinellas County 8751 Ulmerton Road, Suite 2000 - Largo, FL 33771 Eric.Shock@flhealth.gov Phone: 727 538-7277 Cell: 727 732-9501 Fax: 727 538-7293
Events:
Event Type: Activity has been finished Date: 01/20/2022
Comment: Finished
Attachments:
Attachment Date: 01/20/2022 User: SHOCK_E_1
Description: NOI
View Attachment
10/04/2019 Record Document Activity Strauss, Randall
Activity Status: Closed
Contact Name: Zach Davis Activity Closed Date: 10/04/2019
Events:
Event Type: Activity has been finished Date: 10/04/2019
Comment: Finished
Attachments:
Attachment Date: 10/04/2019 User: STRAUSS_RH_1
Description: RRBD 10.4.19
View Attachment
Attachments:
Attachment Date: 10/04/2019 User: STRAUSS_RH_1
Description: Recvd 10.4.19 - PCW removed PUL sump
View Attachment
10/04/2019 Editable Letter Activity Strauss, Randall
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 10/04/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 10/04/2019
Comment: Finished
Attachments:
Attachment Date: 10/04/2019 User: STRAUSS_RH_1
Description: RTC letter 10.4.19
View Attachment
09/26/2019 Violation Closed Strauss, Randall
Significance: Minor Status: Closed
Criteria ID: 4077
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1., 62-761.700(3)(b)2.
09/26/2019 Editable Letter Activity Strauss, Randall
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Description: 2019-11-04 HPG Family Ltd Parnership LLP-DelCAO Letter.
Events:
Event Type: Document has been sent Date: 09/26/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 09/26/2019
Comment: Finished
Attachments:
Attachment Date: 09/26/2019 User: STRAUSS_RH_1
Description: CAO letter 9.26.19
View Attachment
09/24/2019 Site Inspection Activity Closed Strauss, Randall
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 09/24/2019
Activity Closed Date: 09/26/2019 Activity Closed By: STRAUSS_RH_1
Events:
Event Type: Activity has been finished Date: 09/26/2019
Comment: Finished
Attachments:
Attachment Date: 09/26/2019 User: STRAUSS_RH_1
Description: Veeder-Root tapes 9.24.19
View Attachment
09/13/2019 Electronic Communication Activity Strauss, Randall
Activity Closed Date: 09/13/2019 Activity Status: Closed
Date: 09/13/2019
Recipient: Zach Davis
Sender: Randall Strauss
Subject: Inspection notification
Message: See attached
Events:
Event Type: Activity has been finished Date: 09/13/2019
Comment: Finished
Attachments:
Attachment Date: 09/13/2019 User: STRAUSS_RH_1
Description: Inspection notification 9.13.19
View Attachment
07/11/2017 Site Inspection Activity Closed Strauss, Randall
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/11/2017
Activity Closed Date: 07/11/2017 Activity Closed By: STRAUSS_RH_1
Events:
Event Type: Activity has been finished Date: 07/11/2017
Comment: Finished
07/11/2017 Issue Document Activity Strauss, Randall
Activity Status: Closed
Contact Name: Charles Chiara Activity Closed Date: 07/11/2017
Events:
Event Type: Activity has been finished Date: 07/11/2017
Comment: Finished
Attachments:
Attachment Date: 07/11/2017 User: STRAUSS_RH_1
Description: In compliance ltr 7.11.17
View Attachment
06/20/2017 Record Document Activity Strauss, Randall
Activity Status: Closed
Contact Name: Charles Chiara Activity Closed Date: 06/20/2017
Events:
Event Type: Activity has been finished Date: 06/20/2017
Comment: Finished
Attachments:
Attachment Date: 06/20/2017 User: STRAUSS_RH_1
Description: RRBD 6.20.17
View Attachment
05/08/2017 Violation Closed Strauss, Randall
Significance: Minor Status: Closed
Criteria ID: 4068
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1., 62-761.700(1)(a)2.
05/08/2017 Editable Letter Activity Strauss, Randall
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 05/08/2017
Comment: Finished
Attachments:
Attachment Date: 05/08/2017 User: STRAUSS_RH_1
Description: NCL 5.8.17
View Attachment
05/08/2017 Violation Closed Strauss, Randall
Significance: Minor Status: Closed
Criteria ID: 4079
Rule: 62-761.710(2), 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d)
05/08/2017 Violation Closed Strauss, Randall
Significance: Minor Status: Closed
Criteria ID: 4078
Rule: 62-761.710(1)
05/08/2017 Violation Closed Strauss, Randall
Significance: Minor Status: Closed
Criteria ID: 4077
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1., 62-761.700(3)(b)2.
05/08/2017 Violation Closed Strauss, Randall
Significance: SNC-B Status: Closed
Criteria ID: 4059
Rule: 62-761.600(1)(d), 62-761.600(1)(e)
05/04/2017 Site Inspection Activity Closed Strauss, Randall
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/04/2017
Activity Closed Date: 05/08/2017 Activity Closed By: STRAUSS_RH_1
Events:
Event Type: Activity has been finished Date: 05/08/2017
Comment: Finished
05/01/2017 Electronic Communication Activity Strauss, Randall
Activity Closed Date: 05/01/2017 Activity Status: Closed
Date: 05/01/2017
Recipient: USTcompliance@speedway.com
Sender: Randall Strauss
Subject: Inspection notification
Message: See attached
Events:
Event Type: Activity has been finished Date: 05/01/2017
Comment: Finished
02/20/2015 Issue Document Activity Strauss, Randall
Activity Status: Closed
Contact Name: Speedway compliance Activity Closed Date: 02/20/2015
Events:
Event Type: Activity has been finished Date: 02/20/2015
Comment: Finished
02/19/2015 Site Inspection Activity Closed Strauss, Randall
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/19/2015
Activity Closed Date: 02/20/2015 Activity Closed By: STRAUSS_RH_1
Events:
Event Type: Activity has been finished Date: 02/20/2015
Comment: Finished
12/09/2014 Editable Letter Activity Strauss, Randall
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: Return to Compliance Letter
Events:
Event Type: Document has been sent Date: 12/09/2014
Comment: Sent on Tue Dec 09 00:00:00 EST 2014
Events:
Event Type: Activity has been finished Date: 12/09/2014
Comment: Finished
Attachments:
Attachment Date: 12/09/2014 User: STRAUSS_RH_1
Description: NCL 12.9.14
View Attachment
12/04/2014 Violation Closed Strauss, Randall
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
12/04/2014 Emergency Preparedness Information Activity Strauss, Randall
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 12/09/2014
Events:
Event Type: Activity has been finished Date: 12/09/2014
Comment: Finished
12/04/2014 Site Inspection Activity Closed Strauss, Randall
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 12/04/2014
Activity Closed Date: 12/09/2014 Activity Closed By: STRAUSS_RH_1
Events:
Event Type: Activity has been finished Date: 12/09/2014
Comment: Finished
11/26/2013 Issue Document Activity Roggelin, Ernest M.
Activity Status: Closed
Contact Name: Jim Howard Activity Closed Date: 11/26/2013
Events:
Event Type: Activity has been finished Date: 11/26/2013
Comment: Finished
02/25/2013 Electronic Communication Activity Sowers, Joseph A.
Activity Closed Date: 02/25/2013 Activity Status: Closed
Date: 02/25/2013
Recipient: Joseph Sowers
Sender: Laurel Culbreth
Subject: AP-1091 for ELLD's
Message: AP-1091 approval for Hess facilities with ELLDs; Hess provides their demonstration of equivalent protection a portion of which is as follows. "Every Hess facility in Florida has piping sumps with sump sensors that provide immediate notification of an incident within the piping sump to the ATG within the facility. Instead of printing an ATG tape for ELLD's demonstrating a passing 0.2 gph test each month, the Hess Corporation proposes to keep weekly records of sump sensor reports instead of monthly reports."
Events:
Event Type: Activity has been finished Date: 02/25/2013
Comment: Finished
10/03/2012 Editable Letter Activity Strauss, Randall
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 10/03/2012
Comment: Finished
Attachments:
Attachment Date: 10/03/2012 User: STRAUSS_RH_1
Description: NCL 10.3.12
View Attachment
10/03/2012 Editable Letter Activity Strauss, Randall
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 10/03/2012
Comment: Sent on Wed Oct 03 00:00:00 EDT 2012
Events:
Event Type: Activity has been finished Date: 10/03/2012
Comment: Finished
Attachments:
Attachment Date: 10/03/2012 User: STRAUSS_RH_1
Description: NCL 10.3.12
View Attachment
10/02/2012 Site Inspection Activity Closed Strauss, Randall
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 10/01/2012
Activity Closed Date: 10/03/2012 Activity Closed By: STRAUSS_RH_1
Events:
Event Type: Activity has been finished Date: 10/03/2012
Comment: Finished
Comments:
Comment Date: 10/02/2012 User: STRAUSS_RH_1
Description: DEP database lists one discharge for the facility dated March 15, 2005, with status of "Remedial Action Ongoing" The site score is 10.
Comments:
Comment Date: 10/02/2012 User: STRAUSS_RH_1
Description: The owner or operator must submit a closure report to this office within 60 days of completing the work. The report must be prepared per the Florida Department of Environmental Protection's (DEP) "Storage Tank System Closure Assessment Requirements" (April 1998).
10/02/2012 Site Inspection Activity Closed Strauss, Randall
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 10/01/2012
Activity Closed Date: 10/03/2012 Activity Closed By: STRAUSS_RH_1
Events:
Event Type: Activity has been finished Date: 10/03/2012
Comment: Finished
10/02/2012 Site Inspection Activity Closed Strauss, Randall
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 10/01/2012
Activity Closed Date: 10/03/2012 Activity Closed By: STRAUSS_RH_1
Events:
Event Type: Activity has been finished Date: 10/03/2012
Comment: Finished
Comments:
Comment Date: 10/02/2012 User: STRAUSS_RH_1
Description: DEP database lists one discharge for the facility dated March 15, 2005, with status of "Remedial Action Ongoing" The site score is 10.
Comments:
Comment Date: 10/02/2012 User: STRAUSS_RH_1
Description: The owner or operator must submit a closure report to this office within 60 days of completing the work. The report must be prepared per the Florida Department of Environmental Protection's (DEP) "Storage Tank System Closure Assessment Requirements" (April 1998).
08/13/2012 Record Document Activity Longen, Julie L.
Activity Status: Closed
Contact Name: matri Activity Closed Date: 08/13/2012
Events:
Event Type: Activity has been finished Date: 08/13/2012
Comment: Finished
07/10/2012 Editable Letter Activity Longen, Julie L.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 07/10/2012
Comment: Sent on Tue Jul 10 00:00:00 EDT 2012
Events:
Event Type: Activity has been finished Date: 07/10/2012
Comment: Finished
Attachments:
Attachment Date: 07/10/2012 User: LONGEN_JL_1
Description: 2012Jul10.JLL.cover letter
View Attachment
06/29/2012 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
06/29/2012 Site Inspection Activity Closed Longen, Julie L.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 06/29/2012
Activity Closed Date: 07/10/2012 Activity Closed By: LONGEN_JL_1
Events:
Event Type: Activity has been finished Date: 07/10/2012
Comment: Finished
Comments:
Comment Date: 07/10/2012 User: LONGEN_JL_1
Description: Placard posted, ok. RDRL lists sensors in the dispenser liners. There are no sensors, the dispenser liner is a visual inspection. RDRL needs to be updated or sensors need to be installed in the dispenser liners. Financial responsibility ok. CFO letter dated 4-20-12. Visual inspection records reviewed from 6-6-11 to 6-27-12, ok. Liquid status results reviewed from 6-6-11 to 6-27-12. 3 Interstitial, 3 STP sumps Veeder Root electronic line leak detector is not enabled to detect a 0.2 gph leak. Test Results: Veeder Root electronic line leak detectors annual operability test results are not available. NOTE: Electronic line leak detector annual operability testing after 3-1-12 is required to be conducted at both the 3.0 gph and the 0.2 gph leak rates. Veeder Root sensors annual operability test on 6-4-12, passed. At inspection on 7-5-12 with Steve from Crompco per Joe Sowers: Fills: Drop tubes with flappers, all marked, all ok. Spill buckets: Double wall large capacity OPW units with primary containment ok. All of the units have what appears to be pieces of rubber in the liners. Integrity testing needed to verify that the penetration boots remain intact. STPs: Double wall Ameron FRP with secondary open, Veeder Root electronic leak detectors, sensors positioned ok. NOTE: Metal componenets in the RUL & PUL sumps appear to be corroded. this needs to be monitored and addressed as needed. Dispensers: Shears securely anchored, hoses ok, liners clean and dry.
06/29/2012 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
06/29/2012 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1122
Rule: 62-761.710(1)
Comments: Was reasonable access to the facility granted? If not, document the circumstances. Were the records available within the specified time frame? If five day pre-inspection notice was not given by the inspector, this item can not be marked as a discrepancy. Make note of the missing documents, and arrange a review period.
06/29/2012 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
06/29/2012 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1103
Rule: 62-761.640(4)(a)1., 62-761.640(4)(a)2., 62-761.640(4)(a)3., 62-761.640(4)(a)4.
Comments: Installation - verify that the line leak detector has been installed during the final installation inspection. Compliance - check to see that the unit is present. Examine the annual function test data - a pass alone is not sufficient. The tester must demonstrate 3.0 gph discharge detection for the mechanical (flow restrictor). Note that the electronic (auto shut off) line leak detector does not need an annual test, but must still be able to detect a 0.2 gph leak after it has been tripped at 150% line operating pressure. Replacements - unit must be tested out of the box - function must be proven. 3.0 gph = 185.4 ml/min (To convert milliliters/minute to gallons/hour, multiple the milliliters by 0.0162162; or, 1 gph equals 61.8 ml/min). Values greater than 186 ml/min fail. Values less than 185 ml/min mean that the line leak detector will activate at a more restrictive rate.
Comments:
Comment Date: 10/02/2012 User: STRAUSS_RH_1
Description: As of 10/1/2012 inspection, 3.0 gal/hr PLLD function tests available; however, PLLDs have not been enabled to perform 0.2 gal/hr line testing
06/29/2012 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1082
Rule: 62-761.600(1)(b), 62-761.640(1)(c)
Comments: Mark this as out of compliance if the RDRL hasn't been written, or if the RDRL presented doesn't match the release detection methods used. Is reality different from their plan? Note that an SPCC or groundwater monitoring plan will suffice as an RDRL. See following sample form. RELEASE DETECTION RESPONSE LEVELS FACILITY NAME: ________________________________________ FACILITY #: ______________ In accordance with 62-761.600(1)(b), Florida Administrative Code (F.A.C.) the following Release Detection Response Level (RDRL) has been established for the checked method(s) of Release Detection: RELEASE DETECTION METHOD: Statistical Inventory Reconciliation (SIR) with a tank tightness test every three years RDRL: One failed SIR report or two consecutive inconclusive SIR reports. A failed tank tightness test. RELEASE DETECTION METHOD: Continuous Automatic Tank Gauge System RDRL: A failed 0.2 gph leak test report/printout. RELEASE DETECTION METHOD: Automatic Tank Gauge System with a tank tightness test every three years RDRL: A failed 0.2 gph leak test report/printout. A failed tank tightness test. RELEASE DETECTION METHOD: Vacuum Monitoring RDRL: A sudden loss of vacuum or a 20% loss of the original vacuum. RELEASE DETECTION METHOD: Electronic Monitoring of tank interstice RDRL: Alarm conditions, audible or visible. RELEASE DETECTION METHOD: Visual Monitoring of tank interstice RDRL: Presence of free product or water. RELEASE DETECTION METHOD: Annual Tank and Line Tightness Tests used with daily inventory reconciliation (available until 10 yrs. after last tank upgrade) RDRL: Failed tank and/or line tightness test, unexplained water fluctuations exceeding one inch; significant loss or gain. RELEASE DETECTION METHOD: Groundwater Monitoring Wells RDRL: Presence of free product or sheen. Discharge Report Form must be submitted within 24 hours. RELEASE DETECTION METHOD: Vapor Monitoring Wells RDRL: Vapor concentrations >= 500 ppm for gasoline, Vapor concentrations >= 50 ppm for diesel RELEASE DETECTION METHOD: Manual Tank Gauging (Only valid for tanks up to 2000 gals) RDRL: Readings exceeding the standards described in 62-761.640 Table MTG, F.A.C.. RELEASE DETECTION METHOD: Electronic Monitoring of sumps and/or dispenser liners RDRL: Alarm conditions, audible or visible. RELEASE DETECTION METHOD: Visual Monitoring of sumps and/or dispenser liners RDRL: Water above the entrance of double-wall piping or presence of free product. RELEASE DETECTION METHOD: Line Leak Detector RDRL: Tripping/Activation of leak detector. RELEASE DETECTION METHOD: Annual Line Tightness Test RDRL: Failed tightness test As required by 62-761.200(71), F.A.C., if the RDRL is measured or observed, we will initiate activities to determine if an incident, release, or discharge has occurred. If within 24 hours we can not determine if a discharge occurred, an Incident Notification Form will be submitted
04/09/2012 Electronic Communication Activity Strauss, Randall
Activity Closed Date: 04/09/2012 Activity Status: Closed
Date: 04/09/2012
Recipient: Randall Strauss
Sender: Laurel Culbreth
Subject: ELLD monthly records
Message: Close citations for missing monthly ELLD records - per DEP not required
Events:
Event Type: Activity has been finished Date: 04/09/2012
Comment: Finished
12/28/2011 Document Management Activity Longen, Julie L.
Activity Title: Closure Document Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 12/28/2011
Comment: Finished
Attachments:
Attachment Date: 12/28/2011 User: LONGEN_JL_1
Description: 2011Dec28.JLL. IAW letter
View Attachment
12/15/2011 TCAR Activity Longen, Julie L.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 12/28/2011
Events:
Event Type: Activity has been finished Date: 12/28/2011
Comment: Finished
09/26/2011 Editable Letter Activity Roggelin, Ernest M.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Description: 1/18/2018 electronic CAO
Events:
Event Type: Document has been sent Date: 09/26/2011
Comment: Sent on Mon Sep 26 00:00:00 EDT 2011
Events:
Event Type: Activity has been finished Date: 09/26/2011
Comment: Finished
Attachments:
Attachment Date: 09/26/2011 User: ROGGELIN_EM_1
Description: 26sep2011.emr_NCL for TIN.
View Attachment
09/21/2011 Site Inspection Activity Closed Roggelin, Ernest M.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 09/21/2011
Activity Closed Date: 09/26/2011 Activity Closed By: ROGGELIN_EM_1
Events:
Event Type: Activity has been finished Date: 09/26/2011
Comment: Finished
09/20/2011 Site Inspection Activity Closed Roggelin, Ernest M.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 09/20/2011
Activity Closed Date: 09/20/2011 Activity Closed By: ROGGELIN_EM_1
Events:
Event Type: Activity has been finished Date: 09/20/2011
Comment: Finished
09/20/2011 Editable Letter Activity Roggelin, Ernest M.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 09/20/2011
Comment: Sent on Tue Sep 20 00:00:00 EDT 2011
Events:
Event Type: Activity has been finished Date: 09/20/2011
Comment: Finished
Attachments:
Attachment Date: 09/20/2011 User: ROGGELIN_EM_1
Description: 20sep2011.emr_TXI NCL.
View Attachment
09/15/2011 Record Document Activity Longen, Julie L.
Activity Status: Closed
Contact Name: Michael Matri Activity Closed Date: 09/15/2011
Events:
Event Type: Activity has been finished Date: 09/15/2011
Comment: Finished
08/09/2011 Incident Activity Longen, Julie L.
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 12/15/2011
Events:
Event Type: Activity has been finished Date: 12/15/2011
Comment: Finished
Comments:
Comment Date: 12/15/2011 User: LONGEN_JL_1
Description: closure report submitted 2011Nov10
05/09/2011 Editable Letter Activity Longen, Julie L.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 05/09/2011
Comment: Sent on Mon May 09 00:00:00 EDT 2011
Events:
Event Type: Activity has been finished Date: 05/09/2011
Comment: Finished
Attachments:
Attachment Date: 05/09/2011 User: LONGEN_JL_1
Description: 2011May9.JLL.cover letter
View Attachment
05/03/2011 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
05/03/2011 Site Inspection Activity Closed Longen, Julie L.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/03/2011
Activity Closed Date: 05/09/2011 Activity Closed By: LONGEN_JL_1
Events:
Event Type: Activity has been finished Date: 05/09/2011
Comment: Finished
Comments:
Comment Date: 05/09/2011 User: LONGEN_JL_1
Description: Records review 4-29-11: Placard posted. RDRL posted. Financial Responsibility ok. CFO letter 4-30-11 to 4-29-12. Visual inspection records reviewed from 6-6-10 to 4-18-11. Missing spill bucket secondary containment inspection log sheet from 01-11 to current. Liquid status results reviewed from 6-14-10 to 4-18-11. Liquid status: 3 tank interstice, 3 STP sumps. Electronic line leak detectors results not available from 06-10 to current. Test Results as listed on page 2 of inspection report.
05/03/2011 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
Attachments:
Attachment Date: 07/14/2021 User: MATHERLY_H
Description: 2021 Destin Central Office overfill protection results
View Attachment
05/03/2011 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1122
Rule: 62-761.710(1)
Comments: Was reasonable access to the facility granted? If not, document the circumstances. Were the records available within the specified time frame? If five day pre-inspection notice was not given by the inspector, this item can not be marked as a discrepancy. Make note of the missing documents, and arrange a review period.
Attachments:
Attachment Date: 07/14/2021 User: MATHERLY_H
Description: 2021 Destin Central Office release detection results
View Attachment
05/03/2011 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1063
Rule: 62-761.600(1)(e)
Comments: The electronic monitoring unit is a system consisting of a sensor, wiring, and a panel. The sensor and the component that it monitors are exempt from the visual inspection process. However, the proper operation of the remainder of the electronic system must be verified on a monthly basis. One way to test is to activate the panel alarm switch. Depending on the system in place this test may check the alarm light, alarm horn, or the circuit continuity between the panel and the remote sensor. This test procedure must be documented by the facility, as required in rule 62-761.710(2). The remote verification feature meets this requirement, such as the Veeder-Root Simplicity system.
05/03/2011 Violation Closed Longen, Julie L.
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
Comments:
Comment Date: 09/06/2011 User: CULBRETH_L
Description: Time extension until 10/31/2011 for Pinellas County to work with the facility to resolve the violation.
Comments:
Comment Date: 09/15/2011 User: LONGEN_JL_1
Description: Provided SB 2' checks 1-11 to 8-11. Missing PLLD results 6-10 to current
Comments:
Comment Date: 12/07/2011 User: CULBRETH_L
Description: Time extension until 1/31/2012 for Pinellas County to work with the facility to resolve the violation.
Comments:
Comment Date: 02/10/2012 User: CULBRETH_L
Description: Time extension until 3/31/2012 for Pinellas County to work with the facility to resolve the violation. Awaiting final guidance from BPSS before resolving.
05/03/2011 Violation Closed Longen, Julie L.
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
Comments:
Comment Date: 09/06/2011 User: CULBRETH_L
Description: Time extension until 10/31/2011 for Pinellas County to work with the facility to resolve the violation.
Comments:
Comment Date: 09/15/2011 User: LONGEN_JL_1
Description: Provided SB 2' checks 1-11 to 8-11. Missing PLLD results 6-10 to current
Comments:
Comment Date: 12/07/2011 User: CULBRETH_L
Description: Time extension until 1/31/2012 for Pinellas County to work with the facility to resolve the violation.
Comments:
Comment Date: 02/10/2012 User: CULBRETH_L
Description: Time extension until 3/31/2012 for Pinellas County to work with the facility to resolve the violation. Awaiting final guidance from BPSS before resolving.
05/03/2011 Violation Closed Longen, Julie L.
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
Comments:
Comment Date: 09/06/2011 User: CULBRETH_L
Description: Time extension until 10/31/2011 for Pinellas County to work with the facility to resolve the violation.
Comments:
Comment Date: 09/15/2011 User: LONGEN_JL_1
Description: Provided SB 2' checks 1-11 to 8-11. Missing PLLD results 6-10 to current
Comments:
Comment Date: 12/07/2011 User: CULBRETH_L
Description: Time extension until 1/31/2012 for Pinellas County to work with the facility to resolve the violation.
Comments:
Comment Date: 02/10/2012 User: CULBRETH_L
Description: Time extension until 3/31/2012 for Pinellas County to work with the facility to resolve the violation. Awaiting final guidance from BPSS before resolving.
05/03/2011 Violation Closed Longen, Julie L.
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
Comments:
Comment Date: 09/06/2011 User: CULBRETH_L
Description: Time extension until 10/31/2011 for Pinellas County to work with the facility to resolve the violation.
Comments:
Comment Date: 09/15/2011 User: LONGEN_JL_1
Description: Provided SB 2' checks 1-11 to 8-11. Missing PLLD results 6-10 to current
Comments:
Comment Date: 12/07/2011 User: CULBRETH_L
Description: Time extension until 1/31/2012 for Pinellas County to work with the facility to resolve the violation.
Comments:
Comment Date: 02/10/2012 User: CULBRETH_L
Description: Time extension until 3/31/2012 for Pinellas County to work with the facility to resolve the violation. Awaiting final guidance from BPSS before resolving.
05/03/2011 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
05/03/2011 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
06/07/2010 Record Document Activity Sowers, Joseph A.
Activity Status: Closed
Contact Name: Michael Matri Activity Closed Date: 06/07/2010
Events:
Event Type: Activity has been finished Date: 06/07/2010
Comment: Finished
05/17/2010 Violation Closed Sowers, Joseph A.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
05/17/2010 Editable Letter Activity Sowers, Joseph A.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 05/17/2010
Comment: Sent on Mon May 17 00:00:00 EDT 2010
Events:
Event Type: Activity has been finished Date: 05/17/2010
Comment: Finished
Attachments:
Attachment Date: 05/17/2010 User: SOWERS_JA_1
Description: Cover Letter
View Attachment
05/06/2010 Site Inspection Activity Closed Sowers, Joseph A.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 05/06/2010
Activity Closed Date: 05/17/2010 Activity Closed By: SOWERS_JA_1
Events:
Event Type: Activity has been finished Date: 05/17/2010
Comment: Finished
04/28/2009 Site Inspection Activity Closed Longen, Julie L.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/28/2009
Activity Closed Date: 04/29/2009 Activity Closed By: LONGEN_JL_1
Comments:
Comment Date: 04/28/2009 User: LONGEN_JL_1
Description: Placard ok. RDRL ok. FR & CoFR ok. CFO letter dated 4-30-08. Monthly visual inspection records reviewed from 3-5-08 to 4-8-09. Visual inspection includes check of double walled spill buckets. Liquid status results reviewed from 3-7-08 to 4-15-09. Liquid status for interstice and STP sumps Test Results: As recorded on page 2 of inspection report. At inspection on 4-28-09 with Steve (Crompco): Fills: Drop tubes with flappers,marked, ok. Spill buckets: OPW DW spill buckets-primary and secondary clean and dry. STP sumps: DW Ameron FRP, VR PLLD, sensors positioned ok. Dispeners: Shears, hoses and liners ok.
04/23/2008 Record Document Activity Sowers, Joseph A.
Activity Status: Closed
Contact Name: Susan Hairston Activity Closed Date: 04/23/2008
02/21/2008 Violation Closed Sowers, Joseph A.
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
02/21/2008 Editable Letter Activity Sowers, Joseph A.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Comments:
Comment Date: 02/21/2008 User: SOWERS_JA_1
Description: 2008Feb21_JAS: system letter not sent; issued cover letter attached to this activity
02/21/2008 Violation Closed Sowers, Joseph A.
Significance: Minor Status: Closed
Criteria ID: 1138
Rule: 62-761.820(1)(a), 62-761.820(1)(b), 62-761.820(1)(c)
Comments: Mark this as out of compliance if an incident was not investigated, or not investigated properly. See rule 62-761.450(2) for incident reporting requirements.
02/06/2008 Attachment Sowers, Joseph A.
02/06/2008 Attachment Sowers, Joseph A.
02/05/2008 Attachment Sowers, Joseph A.
02/05/2008 Emergency Preparedness Information Activity Sowers, Joseph A.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/05/2008
02/05/2008 Site Inspection Activity Closed Sowers, Joseph A.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/05/2008
Activity Closed Date: 02/21/2008 Activity Closed By: SOWERS_JA_1
02/05/2008 Violation Closed Sowers, Joseph A.
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
02/06/2007 Emergency Preparedness Information Activity Strauss, Randall
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/06/2007
09/26/2006 Emergency Preparedness Information Activity Barnett, James
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/26/2006
Comments:
Comment Date: 04/25/2007 User: BARNETT_JX
Description: Annual Line Leak Detector Function Test. Petroleum Compliance Solutiions 8/23/06
Comments:
Comment Date: 01/10/2008 User: BARNETT_JX
Description: Ace American 4/22/07-4/22/08
09/26/2006 Emergency Preparedness Information Activity Barnett, James
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/26/2006
Comments:
Comment Date: 04/25/2007 User: BARNETT_JX
Description: Annual Line Leak Detector Function Test. Petroleum Compliance Solutiions 8/23/06
Comments:
Comment Date: 01/10/2008 User: BARNETT_JX
Description: Ace American 4/22/07-4/22/08
08/03/2006 Editable Letter Activity Longen, Julie L.
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 08/09/2006
Comment: Sent on Wed Aug 09 00:00:00 EST 2006
Attachments:
Attachment Date: 08/09/2006 User: LONGEN_JL_1
Description: NCL Report
View Attachment
08/01/2006 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1010
Rule: 62-761.450(2)(a)1., 62-761.450(2)(a)2., 62-761.450(2)(a)3., 62-761.450(2)(a)4., 62-761.450(2)(a)5., 62-761.450(2)(a)6., 62-761.450(2)(a)7.
Comments: Multiple incidents occurring at the same time at the facility may be reported on one form. #1-3 - Evidence of these types of INF situations are generally found during the inspector's paperwork review. Ask the facility representative what action they took in response, and in what time frame. If the situations are resolved within 24 hours, the owner/operator is not required to submit an INF to the local program. However, the actions they took to resolve the issue must be documented. #4-5, and 7 - Evidence of these types of situations are generally found during the outside or physical portion of the inspection. Give the facility owner/operator 24 hours to resolve, provided they document their actions. If they can not resolve the issues then they must submit the INF, at which time the two week investigative window opens. #6 - Evidence of this type of situation may be found during the physical examination of the release detection device (e.g. alarm mode), or during the examination of the records associated with the method. Note: Inspectors may find events that qualify as incidents during their review of the facility's paperwork. Such issues must have been resolved within 24 hours if an INF was not submitted at the time of the event.
08/01/2006 Site Inspection Activity Closed Longen, Julie L.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 08/01/2006
Activity Closed Date: 08/03/2006 Activity Closed By: LONGEN_JL_1
Comments:
Comment Date: 08/02/2006 User: LONGEN_JL_1
Description: fills with flappers ok. dispensers, hoses and shears ok. RDRL ok. Placard ok. DW Ameron 3"/2" piping. Veeder Root TLS 350. Monthly visuals and liquid status from 1/4/06 to 7/31/06. Annual operability test performed by Crompco on 8/2/05 for ATG and LLD. Note: Crompco onsite at time of inspection to perform annual function testing and remove accumulated liquid from STP sump.
Comments:
Comment Date: 10/28/2008 User: BARNETT_JX
Description: Monthly Visual Inspections. Tank Exterior, Annunciator, Spill Containment. 10/07-10/08.-ok
08/01/2006 Site Inspection Activity Closed Longen, Julie L.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 08/01/2006
Activity Closed Date: 08/03/2006 Activity Closed By: LONGEN_JL_1
Comments:
Comment Date: 08/02/2006 User: LONGEN_JL_1
Description: fills with flappers ok. dispensers, hoses and shears ok. RDRL ok. Placard ok. DW Ameron 3"/2" piping. Veeder Root TLS 350. Monthly visuals and liquid status from 1/4/06 to 7/31/06. Annual operability test performed by Crompco on 8/2/05 for ATG and LLD. Note: Crompco onsite at time of inspection to perform annual function testing and remove accumulated liquid from STP sump.
Comments:
Comment Date: 10/28/2008 User: BARNETT_JX
Description: Monthly Visual Inspections. Tank Exterior, Annunciator, Spill Containment. 10/07-10/08.-ok
08/01/2006 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1001
Rule: 62-761.400(1)(a), 62-761.400(1)(b)
Comments: Does STCM accurately reflect the tanks at the facility? This question concerns the registration process and payment of fees only - it is not about accurate registration. Check the number of tanks listed on the registration placard. Can the facility owner/operator produce a registration form to document submittal to DEP? At the time of tank closure, a registration form should be submitted showing the change in tank codes.
08/01/2006 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
Comments:
Comment Date: 09/23/2008 User: BARNETT_JX
Description: Monthly Visual Inspection Reocrds: Tank exterior, spill containment, piping, Pneumercator. 10/07-9/08
08/01/2006 Violation Closed Longen, Julie L.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
Comments:
Comment Date: 09/23/2008 User: BARNETT_JX
Description: Commerce & Industry 7/1/08-7/1/09
03/29/2006 Legacy Activity Barnett, James
Activity Name: LETTER Activity Status: Closed
03/23/2006 Legacy Activity Barnett, James
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/27/2005 Legacy Activity Roggelin, Ernest M.
Activity Name: CLEANUP NOTIFICATION LETTER ISSUED Activity Status: Closed
Completion Notes: DRF BASED ON SPILL CONTAINMENT UNIT CLOSURE
06/07/2005 Legacy Activity Sowers, Joseph A.
Activity Name: LETTER Activity Status: Closed
Completion Notes: LETTER ISSUED SAYING INCIDENT INVESTIGATION COMPLETED BY SUBMITTAL OF CLOSURE REPORT
06/07/2005 Legacy Activity Sowers, Joseph A.
Activity Name: DISCHARGE CONFIRMED - 770 CU REQUIRED Activity Status: Closed
06/07/2005 Legacy Activity Sowers, Joseph A.
Activity Name: CLEANUP NOTIFICATION LETTER ISSUED Activity Status: Closed
Completion Notes: SAR LETTER ISSUED BASED ON SUBMITTED CLOSURE DOCUMENTS
05/10/2005 Legacy Activity Sowers, Joseph A.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: CLOSURE REPORT DOCUMENTS SUBMITTED
04/19/2005 Legacy Activity Roggelin, Ernest M.
Activity Name: LETTER Activity Status: Closed
03/09/2005 Legacy Activity Strauss, Randall
Activity Name: LETTER Activity Status: Closed
03/09/2005 Legacy Activity Strauss, Randall
Activity Name: LETTER Activity Status: Closed
03/08/2005 Legacy Activity Strauss, Randall
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
Completion Notes: INSTALL OF 3 SPILL CONTAINMENT UNITS
03/07/2005 Legacy Activity Strauss, Randall
Activity Name: TANK CLOSURE INSPECTION Activity Status: Closed
Completion Notes: REMOVAL OF 3 SPILL CONTAINMENT UNITS
12/27/2004 Legacy Activity Roggelin, Ernest M.
Activity Name: LETTER Activity Status: Closed
11/24/2004 Legacy Activity Roggelin, Ernest M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
07/16/2004 Legacy Activity Reeder, Jon H.
Activity Name: CASE CLOSED BY DISTRICT Activity Status: Closed
06/22/2004 Legacy Activity Reeder, Jon H.
Activity Name: SHORT FORM CONSENT ORDER EXECUTED Activity Status: Closed
05/17/2004 Legacy Activity Roggelin, Ernest M.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: HESS RESPONSE - NO CORRECTION
04/13/2004 Legacy Activity Strauss, Randall
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
04/12/2004 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
04/12/2004 Legacy Activity Strauss, Randall
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: AMERON DW FRP PIPE
03/30/2004 Legacy Activity Reeder, Jon H.
Activity Name: ENFORCEMENT PROJECT INITIATED Activity Status: Closed
09/05/2003 Legacy Activity Sowers, Joseph A.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: SUBMITTAL OF ELECTRONIC LLD TEST RESULTS AND ATG CERTIFICATION - ALL TESTED AND PASSED 8/12/03
07/31/2003 Legacy Activity Roggelin, Ernest M.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: PHOTOS EMAILED OF PAINTED LIDS
07/24/2003 Legacy Activity Roggelin, Ernest M.
Activity Name: LETTER Activity Status: Closed
07/23/2003 Legacy Activity Roggelin, Ernest M.
Activity Name: SITE VISIT Activity Status: Closed
Completion Notes: W/ J PINK. PHOTO TAKEN. FILL LIDS HAVE NOT BEEN REPAINTED.
07/21/2003 Legacy Activity Roggelin, Ernest M.
Activity Name: LETTER Activity Status: Closed
07/14/2003 Legacy Activity Roggelin, Ernest M.
Activity Name: SITE VISIT Activity Status: Closed
Completion Notes: W/ J PINK
06/06/2003 Legacy Activity Roggelin, Ernest M.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
05/28/2003 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 510(1)(b)3
05/28/2003 Legacy Activity Roggelin, Ernest M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: AMERON DW PIPE
05/28/2003 Violation Closed Strauss, Randall
Significance: SNC-B Status: Closed
Rule: 600(1)(d)
12/31/2002 Legacy Activity Roggelin, Ernest M.
Activity Name: LETTER Activity Status: Closed
12/18/2002 Legacy Activity Roggelin, Ernest M.
Activity Name: LETTER Activity Status: Closed
10/01/2001 Legacy Activity Roggelin, Ernest M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/18/2001 Legacy Activity Roggelin, Ernest M.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
04/02/2001 Violation Closed Roggelin, Ernest M.
Significance: SNC-B Status: Closed
Rule: 600(1)(d)
04/02/2001 Legacy Activity Roggelin, Ernest M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/02/2001 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 820(1)(a),(b),(c)
04/02/2001 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 450(2)(a)
04/02/2001 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 710(2)
04/02/2001 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 640(3)(c)2
04/02/2001 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
04/02/2001 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 640(3)(d)
04/02/2001 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 600(1)(a)2
06/08/2000 Legacy Activity Roggelin, Ernest M.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
04/20/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 450(2)(a)
04/20/2000 Legacy Activity Roggelin, Ernest M.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
04/20/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 820(1)(a),(b),(c)
Comments:
Comment Date: 10/28/2022 User: WHITAKER_AJ_1
Description: Added site diagram and photos
Comments:
Comment Date: 01/10/2025 User: WHITAKER_AJ_1
Description: Reviewed site diagram and photos- added new photo.
04/20/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 820(1)(a),(b),(c)
Comments:
Comment Date: 10/28/2022 User: WHITAKER_AJ_1
Description: Added site diagram and photos
Comments:
Comment Date: 01/10/2025 User: WHITAKER_AJ_1
Description: Reviewed site diagram and photos- added new photo.
04/20/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 710(2)
04/20/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 710(1)
Attachments:
Attachment Date: 12/02/2020 User: BOYLES_S
Description: Tank site side view
View Attachment
Attachments:
Attachment Date: 12/02/2020 User: BOYLES_S
Description: Tank site front view
View Attachment
04/20/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
Attachments:
Attachment Date: 12/22/2020 User: GLENNON_BM_1
Description: 2020-12-17 Tank Photo
View Attachment
Attachments:
Attachment Date: 12/22/2020 User: GLENNON_BM_1
Description: 2020-12-17 Site Map
View Attachment
Attachments:
Attachment Date: 12/22/2020 User: GLENNON_BM_1
Description: 2020-12-17 Site Photo
View Attachment
04/20/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 600(1)(a)2
01/24/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 710(1)
01/24/2000 Legacy Activity Roggelin, Ernest M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/24/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 710(2)
01/24/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 820(1)(a),(b),(c)
Comments:
Comment Date: 08/17/2016 User: PERRY_JF_2
Description: On site lead operator is Terry Kelsey email at tkelsey@deltonafl.gov
01/24/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 450(2)(a)
01/24/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 600(1)(a)1
01/24/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 600(1)(a)2
01/24/2000 Violation Closed Roggelin, Ernest M.
Significance: SNC-B Status: Closed
Rule: 600(1)(h)
01/24/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 640(3)(a)1
Comments:
Comment Date: 04/29/2016 User: HECKMAN_DA_1
Description: EQ List: Xerxes double walled, fiberglass tanks: EQ# 200 OPW flex piping: EQ# 649 Veeder Root TLS-450 monitoring system with model 208 sensors: EQ# 724 Spill buckets, double walled: Fiberglass sumps: OPW flexworks Polyethylene dispenser liners: EQ# 318 OPW 61/71 flow shutoff valves: EQ# 697 or 815
01/24/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 700(1)(c)1
01/24/2000 Violation Closed Roggelin, Ernest M.
Significance: Minor Status: Closed
Rule: 700(1)(c)3
Comments:
Comment Date: 09/01/2015 User: FOXWORTH_S_1
Description: POC is Alan Campbell, Facility and Security Manager, acampbell@eglinfcu.org or phone 850-862-0111 Ext. 1001.
06/28/1999 Legacy Activity Roggelin, Ernest M.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
06/23/1998 Violation Closed Unknown, User
Significance: SNC-A Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 04/13/2007 User: STEVENSON_JS
Description: UST #3 is a SW bare steel tank with impressed current cathodic protection. Piping is DW 2-inch Ameron rigid FRP Dualoy 3000/L, (EQ-378.) Submersible Turbine Pump Sumps are Xerxes FRP (EQ-397,) and Dispenser sumps are steel Bravo Boxes, (EQ-045.) Release Detection is Ustman SIR Ver. 95.2B, (EQ-377) with tank tightness tests every three years. Piping is equipped with Mechanical Line Leak Detectors (Two VMI LD-2000, EQ-329, and one Red Jacket FX-1V (EQ-373.) All Sumps are visually inspected.
06/23/1998 Violation Closed Unknown, User
Significance: SNC-A Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 10/25/2017 User: BRAGG_SD_2
Description: Franklin Fueling Double-Wall(DW) defender series spill containment.
Comments:
Comment Date: 05/07/2019 User: BRAGG_SD_2
Description: New sumps installed are Petroleum Containment Inc, Fiberglass (EQ-203). Fiberglass systems red thread entry fittings (EQ-252) were used.
Comments:
Comment Date: 05/25/2007 User: STEVENSON_JS
Description: UST #1 is a DW tank with a steel secondary and a FRP primary, the result of installing the "Primary Containment System" (EQ-503,) using a "Parabeam" FRP lining. The original steel tank is protected from corrosion with an impressed-current system. Rectifier is a Tanknology Universal Model GCA1. Integral piping is DW 2-inch rigid FRP Ameron Dualoy 3000/L (EQ-378,) pressurized. Submersible Turbine Pump Sumps are Xerxes FRP; Dispenser Sumps are steel Bravo Boxes (EQ-200.) Release Detection is a Veeder-Root TLS-350 Automatic Tank Gauge (EQ-033,) monitoring Tank Interstice liquid sensors. All sumps are visually inspected. Each STP is equipped with a mechanical Line Leak Detector, a Red Jacket FX-1V (EQ-373) in Regular U/L, and a VMI LD-2000 (EQ-) in Premium.
Comments:
Comment Date: 10/06/2017 User: KEIM_MJ_1
Description: New contact: Mr. Aaron Wells 352-577-4176
06/23/1998 Violation Closed Unknown, User
Significance: SNC-A Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 10/25/2017 User: BRAGG_SD_2
Description: Franklin Fueling Double-Wall(DW) defender series spill containment.
Comments:
Comment Date: 05/07/2019 User: BRAGG_SD_2
Description: New sumps installed are Petroleum Containment Inc, Fiberglass (EQ-203). Fiberglass systems red thread entry fittings (EQ-252) were used.
Comments:
Comment Date: 05/25/2007 User: STEVENSON_JS
Description: UST #1 is a DW tank with a steel secondary and a FRP primary, the result of installing the "Primary Containment System" (EQ-503,) using a "Parabeam" FRP lining. The original steel tank is protected from corrosion with an impressed-current system. Rectifier is a Tanknology Universal Model GCA1. Integral piping is DW 2-inch rigid FRP Ameron Dualoy 3000/L (EQ-378,) pressurized. Submersible Turbine Pump Sumps are Xerxes FRP; Dispenser Sumps are steel Bravo Boxes (EQ-200.) Release Detection is a Veeder-Root TLS-350 Automatic Tank Gauge (EQ-033,) monitoring Tank Interstice liquid sensors. All sumps are visually inspected. Each STP is equipped with a mechanical Line Leak Detector, a Red Jacket FX-1V (EQ-373) in Regular U/L, and a VMI LD-2000 (EQ-) in Premium.
Comments:
Comment Date: 10/06/2017 User: KEIM_MJ_1
Description: New contact: Mr. Aaron Wells 352-577-4176
06/23/1998 Violation Closed Unknown, User
Significance: SNC-A Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 10/25/2017 User: BRAGG_SD_2
Description: Franklin Fueling Double-Wall(DW) defender series spill containment.
Comments:
Comment Date: 05/07/2019 User: BRAGG_SD_2
Description: New sumps installed are Petroleum Containment Inc, Fiberglass (EQ-203). Fiberglass systems red thread entry fittings (EQ-252) were used.
Comments:
Comment Date: 05/25/2007 User: STEVENSON_JS
Description: UST #1 is a DW tank with a steel secondary and a FRP primary, the result of installing the "Primary Containment System" (EQ-503,) using a "Parabeam" FRP lining. The original steel tank is protected from corrosion with an impressed-current system. Rectifier is a Tanknology Universal Model GCA1. Integral piping is DW 2-inch rigid FRP Ameron Dualoy 3000/L (EQ-378,) pressurized. Submersible Turbine Pump Sumps are Xerxes FRP; Dispenser Sumps are steel Bravo Boxes (EQ-200.) Release Detection is a Veeder-Root TLS-350 Automatic Tank Gauge (EQ-033,) monitoring Tank Interstice liquid sensors. All sumps are visually inspected. Each STP is equipped with a mechanical Line Leak Detector, a Red Jacket FX-1V (EQ-373) in Regular U/L, and a VMI LD-2000 (EQ-) in Premium.
Comments:
Comment Date: 10/06/2017 User: KEIM_MJ_1
Description: New contact: Mr. Aaron Wells 352-577-4176
06/23/1998 Violation Closed Unknown, User
Significance: SNC-A Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 10/25/2017 User: BRAGG_SD_2
Description: Franklin Fueling Double-Wall(DW) defender series spill containment.
Comments:
Comment Date: 05/07/2019 User: BRAGG_SD_2
Description: New sumps installed are Petroleum Containment Inc, Fiberglass (EQ-203). Fiberglass systems red thread entry fittings (EQ-252) were used.
Comments:
Comment Date: 05/25/2007 User: STEVENSON_JS
Description: UST #1 is a DW tank with a steel secondary and a FRP primary, the result of installing the "Primary Containment System" (EQ-503,) using a "Parabeam" FRP lining. The original steel tank is protected from corrosion with an impressed-current system. Rectifier is a Tanknology Universal Model GCA1. Integral piping is DW 2-inch rigid FRP Ameron Dualoy 3000/L (EQ-378,) pressurized. Submersible Turbine Pump Sumps are Xerxes FRP; Dispenser Sumps are steel Bravo Boxes (EQ-200.) Release Detection is a Veeder-Root TLS-350 Automatic Tank Gauge (EQ-033,) monitoring Tank Interstice liquid sensors. All sumps are visually inspected. Each STP is equipped with a mechanical Line Leak Detector, a Red Jacket FX-1V (EQ-373) in Regular U/L, and a VMI LD-2000 (EQ-) in Premium.
Comments:
Comment Date: 10/06/2017 User: KEIM_MJ_1
Description: New contact: Mr. Aaron Wells 352-577-4176
06/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 05/25/2007 User: STEVENSON_JS
Description: UST #2 is a DW tank with a steel secondary and a FRP primary, the result of installing the "Primary Containment System" (EQ-503,) using a "Parabeam" FRP lining. The original steel tank is protected from corrosion with an impressed-current system. Rectifier is a Tanknology Universal Model GCA1. Integral piping is DW 2-inch rigid FRP Ameron Dualoy 3000/L (EQ-378,) pressurized. Submersible Turbine Pump Sumps are Xerxes FRP; Dispenser Sumps are steel Bravo Boxes (EQ-200.) Release Detection is a Veeder-Root TLS-350 Automatic Tank Gauge (EQ-033,) monitoring Tank Interstice liquid sensors. All sumps are visually inspected. Each STP is equipped with a mechanical Line Leak Detector, a Red Jacket FX-1V (EQ-373) in Regular U/L, and a VMI LD-2000 (EQ-) in Premium.
06/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 05/07/2019 User: BRAGG_SD_2
Description: New sumps installed are Petroleum Containment Inc, Fiberglass (EQ-203). Fiberglass systems red thread entry fittings (EQ-252) were used.
Comments:
Comment Date: 10/25/2017 User: BRAGG_SD_2
Description: Franklin Fueling Double-Wall(DW) defender series spill containment.
Comments:
Comment Date: 05/25/2007 User: STEVENSON_JS
Description: UST #3 is a DW tank with a steel secondary and a FRP primary, the result of installing the "Primary Containment System" (EQ-503,) using a "Parabeam" FRP lining. The original steel tank is protected from corrosion with an impressed-current system. Rectifier is a Tanknology Universal Model GCA1. Integral piping is DW 2-inch rigid FRP Ameron Dualoy 3000/L (EQ-378,) pressurized. Submersible Turbine Pump Sumps are Xerxes FRP; Dispenser Sumps are steel Bravo Boxes (EQ-200.) Release Detection is a Veeder-Root TLS-350 Automatic Tank Gauge (EQ-033,) monitoring Tank Interstice liquid sensors. All sumps are visually inspected. Each STP is equipped with a mechanical Line Leak Detector, a Red Jacket FX-1V (EQ-373) in Regular U/L, and a VMI LD-2000 (EQ-) in Premium.
Attachments:
Attachment Date: 06/06/2018 User: RICHARDS_JE_1
Description: 8507278_Property Record for Warranty Deed_06-06-2018
View Attachment
06/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 05/07/2019 User: BRAGG_SD_2
Description: New sumps installed are Petroleum Containment Inc, Fiberglass (EQ-203). Fiberglass systems red thread entry fittings (EQ-252) were used.
Comments:
Comment Date: 10/25/2017 User: BRAGG_SD_2
Description: Franklin Fueling Double-Wall(DW) defender series spill containment.
Comments:
Comment Date: 05/25/2007 User: STEVENSON_JS
Description: UST #3 is a DW tank with a steel secondary and a FRP primary, the result of installing the "Primary Containment System" (EQ-503,) using a "Parabeam" FRP lining. The original steel tank is protected from corrosion with an impressed-current system. Rectifier is a Tanknology Universal Model GCA1. Integral piping is DW 2-inch rigid FRP Ameron Dualoy 3000/L (EQ-378,) pressurized. Submersible Turbine Pump Sumps are Xerxes FRP; Dispenser Sumps are steel Bravo Boxes (EQ-200.) Release Detection is a Veeder-Root TLS-350 Automatic Tank Gauge (EQ-033,) monitoring Tank Interstice liquid sensors. All sumps are visually inspected. Each STP is equipped with a mechanical Line Leak Detector, a Red Jacket FX-1V (EQ-373) in Regular U/L, and a VMI LD-2000 (EQ-) in Premium.
Attachments:
Attachment Date: 06/06/2018 User: RICHARDS_JE_1
Description: 8507278_Property Record for Warranty Deed_06-06-2018
View Attachment
06/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 05/07/2019 User: BRAGG_SD_2
Description: New sumps installed are Petroleum Containment Inc, Fiberglass (EQ-203). Fiberglass systems red thread entry fittings (EQ-252) were used.
Comments:
Comment Date: 10/25/2017 User: BRAGG_SD_2
Description: Franklin Fueling Double-Wall(DW) defender series spill containment.
Comments:
Comment Date: 05/25/2007 User: STEVENSON_JS
Description: UST #3 is a DW tank with a steel secondary and a FRP primary, the result of installing the "Primary Containment System" (EQ-503,) using a "Parabeam" FRP lining. The original steel tank is protected from corrosion with an impressed-current system. Rectifier is a Tanknology Universal Model GCA1. Integral piping is DW 2-inch rigid FRP Ameron Dualoy 3000/L (EQ-378,) pressurized. Submersible Turbine Pump Sumps are Xerxes FRP; Dispenser Sumps are steel Bravo Boxes (EQ-200.) Release Detection is a Veeder-Root TLS-350 Automatic Tank Gauge (EQ-033,) monitoring Tank Interstice liquid sensors. All sumps are visually inspected. Each STP is equipped with a mechanical Line Leak Detector, a Red Jacket FX-1V (EQ-373) in Regular U/L, and a VMI LD-2000 (EQ-) in Premium.
Attachments:
Attachment Date: 06/06/2018 User: RICHARDS_JE_1
Description: 8507278_Property Record for Warranty Deed_06-06-2018
View Attachment
06/23/1998 Legacy Activity Vargas-Prada, Pedro X.
Activity Name: UST ROUTINE COMPLIANCE INSPECTION Activity Status: Closed