DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/27/2025        Last Data Refresh: 04/26/2025        Report Generated from DOPPLER
 
Facility ID: 9200588
Facility Name: MARTINS COUNTRY STORE
 
01/16/2024 Editable Letter Activity Mills, MaryAnne
Activity Title: Warning Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 01/16/2024
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 01/16/2024
Comment: Approved by Jennifer Paul: WL23-240 1/16/2024
Events:
Event Type: Activity has been submitted for approval Date: 01/16/2024
Comment: Submitted for approval by: MaryAnne Mills
Attachments:
Attachment Date: 01/16/2024 User: MILLS_MM
Description: Warning Letter WL23-240
View Attachment
08/25/2023 Enforcement Tracking Activity Mills, MaryAnne
Activity Status: Open
07/25/2022 Enforcement Referral Activity Harrington, Richard D.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 08/25/2023
Events:
Event Type: Activity has been submitted for approval Date: 07/25/2022
Comment: Submitted for approval by: Richard D. Harrington: See 2018 and 2021 TCI inspections.
Events:
Event Type: Activity has been finished Date: 08/25/2023
Comment: Finished
Events:
Event Type: Activity has been assigned Date: 08/17/2023
Comment: Assigned to MaryAnne Mills
Events:
Event Type: Activity/Document was accepted on this date Date: 08/25/2023
Comment: Accepted by MaryAnne Mills: Accepted
Events:
Event Type: Activity/Document was acknowledged on this date Date: 08/17/2023
Comment: Acknowledged and Assigned by Brierra Mack
Comments:
Comment Date: 07/25/2022 User: HARRINGTON_RD_1
Description: See 2018 and 2021 TCI inspections.
03/31/2021 Phone Conversation Activity Keim, Michael J
Call Type: Outgoing Activity Status: Closed
Phone Number: (352) 262-1735 Activity Closed Date: 03/31/2021
Subject: Spoke with Betty Martin regarding TCI inspection and records needed
Events:
Event Type: Activity has been finished Date: 03/31/2021
Comment: Finished
03/24/2021 Site Inspection Activity Closed Keim, Michael J
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 03/24/2021
Activity Closed Date: 03/31/2021 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 03/31/2021
Comment: Finished
Comments:
Comment Date: 03/30/2021 User: KEIM_MJ_1
Description: *Note* It is required to maintain monthly visual inspections and annual testing for an In Service registered facility, these items have not been performed. Recommendations: With the facility not operational, the owner should have the tank cleaned, flush the underground piping, disconnect from the tank and cap off the lines, then register the tank as closed in place until the facility is sold. Once the facility has a new owner or if the current owner decides to re-open, the tank and components can be reconnected then integrity tested by a licensed contractor before being placed back in service. Tank Compliance inspection report mailed to Betty Martin P.O.Box 156 Otter Creek, Fl.32683
06/12/2018 Violation Open Keim, Michael J
Significance: SNC-B Status: Open
Criteria ID: 5094
Rule: 62-762.601(1)(d), 62-762.601(1)(e)
06/12/2018 Electronic Communication Activity Keim, Michael J
Activity Closed Date: 06/12/2018 Activity Status: Closed
Date: 06/12/2018
Recipient: Betty Martin
Sender: M Keim
Subject: TCI report with Compliance assist letter
Message: Sent Tank Compliance report with Compliance assist letter via e-mail to Betty Martin, bettymartin1940@gmail.com
Events:
Event Type: Activity has been finished Date: 06/12/2018
Comment: Finished
06/12/2018 Editable Letter Activity Keim, Michael J
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/12/2018
Comment: Sent
Events:
Event Type: Activity has been finished Date: 06/12/2018
Comment: Finished
Attachments:
Attachment Date: 06/12/2018 User: KEIM_MJ_1
Description: CAO Letter
View Attachment
06/12/2018 Violation Open Keim, Michael J
Significance: Minor Status: Open
Criteria ID: 5144
Rule: 62-762.711(2), 62-762.711(2)(a), 62-762.711(2)(b), 62-762.711(2)(c), 62-762.711(2)(d)
05/31/2018 Site Inspection Activity Closed Keim, Michael J
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/31/2018
Activity Closed Date: 06/12/2018 Activity Closed By: KEIM_MJ_1
Events:
Event Type: Activity has been finished Date: 06/12/2018
Comment: Finished
Comments:
Comment Date: 06/12/2018 User: KEIM_MJ_1
Description: Recommended this facility should close, clean out and disconnect the tank in place until facility is sold. Tank Compliance inspection report and compliance letter delivered to facility owner. Also sent via e-mail to bettymartin1940@gmail.com and mailed to: Betty Martin P.O.Box 156 Otter Creek, Fl.32683 Note: All underground sumps and dispenser liners must be initially integrity tested by 10/13/2018 UST operator training A,B or C certificates will be required by 10/13/2018
03/04/2015 Meeting Activity Shulaw, Benjamin J.
Activity Closed Date: 03/04/2015 Activity Status: Closed
Location: office
Subject: Violations cleared by CHD discretion
Events:
Event Type: Activity has been finished Date: 03/04/2015
Comment: Finished
10/29/2014 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 10/29/2014
Comment: Finished
Attachments:
Attachment Date: 10/29/2014 User: SHULAW_BJ_1
Description: 29Oct14 NCL
View Attachment
10/27/2014 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 10/24/2014
Activity Closed Date: 10/29/2014 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 10/29/2014
Comment: Finished
Comments:
Comment Date: 10/28/2014 User: SHULAW_BJ_1
Description: New Violations The system is not being inspected monthly. Inspect the system monthly and record the inspections on the form provided. The dispenser could not be opened. Get the dispenser to open properly and call for a re-inspection. Comments: The owner/ operator should consider taking the system out of service as discussed or close the system. The system has not been functioning and the store is closed. One DW steel 2 compartmented AST with remote fill and 1 remote dispenser. Steel above ground pipe transitions to underground Ameron Dualoy. Pressurized system with STPs, LLDs and anti-siphon valves. Visual monitoring of AST, pipe, liner and stick IM. Has a clock gauge for product level in each compartment. Remote fill has lined concrete secondary with a drain valve. There was no Certificate of Financial Responsibility on site. Keep the insurance and Certificate of Financial Responsibility updated at the facility for inspections. An RDRL was completed. Discharge Information: PLRIP inactive score 10 A facility representative signed the attached inspection notes. This report will be mailed via USPS. A non compliance letter citing the violations accompanies this inspection report; please find it attached. Please provide our office with documentation confirming the resolution of the cited violations within thirty days of receipt of this inspection report and attached non compliance letter. For more inspection details and information or if you have any questions please contact me at 386-758-2185, 386-697-7329 cell, fax 386-758-2187, or email Benjamin.Shulaw@flhealth.gov.
10/24/2014 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 2120
Rule: 62-762.701(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
10/24/2014 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 2133
Rule: 62-762.711(2)(a), 62-762.711(2)(b), 62-762.711(2)(c), 62-762.711(2)(d), 62-762.711(2)(e), 62-762.711(2)(f), 62-762.711(2)(g), 62-762.711(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-762.641(3)(b)1-2, 62-762.641(3)(b)3 and 62-762.701(1)(c)6 b. Repair, operation, and maintenance - rules 62-762.701(1)(a)1, 62-762.701(1)(a)4, 62-762.701(1)(a)6 and 62-762.701(1)(c)3 c. Release detection - rules 62-762.601(1)(e), 62-762.601(2)(g), 62-762.611(2)(b), 62-762.611(3)(b), 62-762.611(3)(d)2, 62-762.641(2)(c) and 62-762.641(2)(e) d. Release detection response level descriptions - rules 62-762.601(1)(b) and 62-762.641(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-762.611(3)(a)1 and 62-762.641(1)(a) f. Financial responsibility - rule 62-762.401(3) g. Repairs and replacements - rule 62-762.701(1)(a)6 The following are not issues for this rule: Rules 62-762.451(1)(a)2, 62-762.451(1)(a)3 and 62-762.451(1)(a)4 are verbal notices of activities that may also be written Rule 62-762.451(1)(b) is a registration issue Rules 62-762.451(2)(a), 62-762.451(3)(a) and 62-762.451(3)(b) are INF/DRF reporting issues Rules 62-762.601(1)(a)3 and 62-762.601(1)(f) are covered by 62-762.711(3) Anything with cathodic protection is covered by 62-762.711(3)
08/09/2012 Site Inspection Activity Closed Oymayan, Avo J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/01/2012
Activity Closed Date: 08/09/2012 Activity Closed By: OYMAYAN_AJ_1
Events:
Event Type: Activity has been finished Date: 08/09/2012
Comment: Finished
Comments:
Comment Date: 08/09/2012 User: OYMAYAN_AJ_1
Description: Violations Summary: There were no violations cited at the time of the inspection. Additional Notes: There are no additional notes, or observations, to document at this time. Discharge Information: There is no new information or obvious evidence of recent release or discharge, within the last year. For more detailed discharge information, please consult the Petroleum Clean Up Section at the F D E P H.Q. in Tallahassee; or the F D E P Northeast District Office in Jacksonville; or the official compliance facility file at the Columbia C H D, Environmental Health Section, in Lake City. Other Comments: For more inspection details and information; please see the copy of the inspection field notes, site schematic and system description that is electronically, as well as physically, attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058.
01/11/2012 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/11/2012
Activity Closed Date: 01/12/2012 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 01/12/2012
Comment: Finished
12/06/2010 Meeting Activity Shulaw, Benjamin J.
Activity Closed Date: 12/06/2010 Activity Status: Closed
Location: facility
Subject: The drain was closed, sp buck dry, the secondary pipe in the dispensers had been opened, monthly inspections were bing logged.
Events:
Event Type: Activity has been finished Date: 12/06/2010
Comment: Finished
10/26/2010 Attachment Perea, Aurelio O.
10/08/2010 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 10/08/2010
Comment: Finished
Attachments:
Attachment Date: 10/08/2010 User: SHULAW_BJ_1
Description: 8Oct10 NCL
View Attachment
10/07/2010 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 2065
Rule: 62-762.601(1)(a)1.
Comments: Mark this as out of compliance if the release detection method is not able to register or detect a new release. If you feel that the release detection system has lost its ability to detect a new release, document why in the inspection report. Examples include: a. An automatic tank gauge system already in alarm mode will not be able to detect a new release; b. sumps with water/product may impair detection abilities; c. monitoring wells at contaminated sites may also have impaired ability to detect new releases. See .641(2)(c)2. for further guidance on using contaminated monitoring wells for release detection.
10/07/2010 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 10/07/2010
Activity Closed Date: 10/08/2010 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 10/08/2010
Comment: Finished
Comments:
Comment Date: 10/08/2010 User: SHULAW_BJ_1
Description: Violations: The secondary pipes in the dispenser liner are closed. Open the secondary pipe by loosening hose clamps and backing away boots. Monthly inspections have not been performed. Perform and record inspections on form provided. Drain valve was open. Keep drain valve closed when not in use. Discharge Information: PLRIP active score 11 A non compliance letter citing the violations accompanies this inspection report; please find it attached. Please provide our office with documentation confirming the resolution of the cited violations within thirty days of receipt of this inspection report and attached non compliance letter. For more inspection details and information, please see the copy of the inspection field notes. If you have any questions please contact me at 386-623-0831 cell, fax 386-758-2187, or office 386-758-2140 or email Benjamin_Shulaw@doh.state.fl.us
10/07/2010 Violation Closed Shulaw, Benjamin J.
Significance: SNC-B Status: Closed
Criteria ID: 2069
Rule: 62-762.601(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells, buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. If there is a record keeping problem, see rule 62-762.711(2).
10/07/2010 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 2126
Rule: 62-762.701(2)(c)
Comments: This applies to secondary containment areas, although spill containment boxes for ASTs may also be equipped with a drain valve.
07/31/2009 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/31/2009
Activity Closed Date: 08/03/2009 Activity Closed By: SHULAW_BJ_1
Comments:
Comment Date: 08/03/2009 User: SHULAW_BJ_1
Description: Anti-siphon valves have been installed. This facility is in compliance without enforcement; if you have any questions please call me at 386-623-0831 or email Benjamin_Shulaw @doh.state.fl.us .
07/22/2009 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
03/31/2009 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 2059
Rule: 62-762.511(1)(d)
Comments: Mark this as out of compliance if small diameter piping with gravity head does not have a properly installed isolation valve at the point the piping meets the tank. The purpose of this Rule cite is to prevent drainage of the tank in case of piping failure. For ASTs, NFPA 30 Section 2-3.8.1 requires each connection through which liquid can normally flow to be equipped with an isolation valve located either inside or outside the tank, but as close as practical to the shell. NFPA 30A Section 2-1.7 requires systems with a gravity head to have a separate device, similar to a solenoid valve, installed downstream of, but as close as practical to, the isolation valve required by NFPA 30 Section 2-3.8.1 (i.e., as close to the tank as possible). Whether there is a suction pump present or not, a gravity head is created when the height of the piping drops below the fuel level in the tank. With most elevated tanks and/or tanks with bottom connections, the weight of the fuel is enough to cause drainage in the event of piping failure. With suction systems, whether the tank drains completely in the event of piping failure will depend on several factors including the height of the failure relative to the fuel level, and whether a vacuum was present on the piping at the time of the failure. NFPA 30A Section 2-4.6, Piping and Ancillary Equipment, has information about requirements for specific systems types (e.g., pressurized, suction, etc.). NFPA is fairly consistent with valve requirements throughout the different publications. NFPA 30 regulates all systems storing flammable and combustibles. NFPA 30A applies only to service stations. NFPA 395 regulates agriculture tanks, and tanks at isolated sites, when the tank volume is less than 1,100 gallons. NFPA 395 Section 2-3 specifies that systems fueling from the top be equipped with anti siphon valves. The device installed on elevated systems must be heat actuated and capable of manual control to prevent d
03/31/2009 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
03/23/2009 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/23/2009
Activity Closed Date: 03/31/2009 Activity Closed By: SHULAW_BJ_1
Comments:
Comment Date: 03/31/2009 User: SHULAW_BJ_1
Description: The store has not been selling fuel since June 2008, but is fully functional. The compartmented tank is near empty. The clock gauges should be checked for accuracy. Properly install anti-siphon or solenoid valves. A non compliance letter citing the violations accompanies this inspection report; please find it attached. Please provide our office with documentation confirming the resolution of the cited violations, within thirty days of receipt of this inspection report and attached non compliance letter. If you have any questions or concerns, please feel free to contact me at (386) 758-2140.
02/26/2008 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/26/2008
01/11/2008 Attachment Kassees, Ramsey D.
01/03/2008 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/03/2008
Activity Closed Date: 01/11/2008 Activity Closed By: KASSEES_RP_1
Comments:
Comment Date: 01/03/2008 User: KASSEES_RP_1
Description: Violations Summary: There were no violations cited at the time of the inspection. Additional Notes: There are no additional notes, or observations, to document at this time. Discharge Information: There is no new information or obvious evidence of recent release or discharge, within the last year. For more detailed discharge information, please consult the Petroleum Clean Up Section at the F D E P H.Q. in Tallahassee; or the F D E P Northeast District Office in Jacksonville; or the official compliance facility file at the Columbia C H D, Environmental Health Section, in Lake City. Other Comments: For more inspection details and information; please see the copy of the inspection field notes, site schematic and system description that is electronically, as well as physically, attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058.
02/15/2007 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/15/2007
02/12/2007 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/12/2007
Activity Closed Date: 02/24/2007 Activity Closed By: KASSEES_RP_1
Comments:
Comment Date: 02/24/2007 User: KASSEES_RP_1
Description: A reinspection (T C R) at this facility, on 02/12/2007, confirms that the following violation has been resolved: 1). The remote A S T fillports are now properly color coded. White for Regular Unleaded; Red for Premium Unleaded. This facility is in compliance without enforcement.
12/11/2006 Editable Letter Activity Kassees, Ramsey D.
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 12/11/2006
Comment: Sent on Mon Dec 11 16:09:35 EST 2006
11/18/2006 Attachment Kassees, Ramsey D.
11/18/2006 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Criteria ID: 2042
Rule: 62-762.501(2)(d)3.
Comments: Fillbox covers should be clearly identified by means of a marking system. At least one fixed component of the fillbox itself should be labeled to avoid accidents that might result from mismatching of fillboxes and their covers. Fillbox covers are to be labeled using one of the following methods: a. Painting or placing a decal on top of the cover and on the rim of the fillbox. b. Attaching a tag to the fill pipe adapter. c. Screwing a tag onto the fillbox rim. d. Fitting a plastic or fiberglass insert inside the rim of the fillbox. Refer to the color-coded chart included in the API 1637 Reference Standard.
11/18/2006 Attachment Kassees, Ramsey D.
11/18/2006 Attachment Kassees, Ramsey D.
11/03/2006 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 11/03/2006
Activity Closed Date: 12/11/2006 Activity Closed By: KASSEES_RP_1
Comments:
Comment Date: 11/18/2006 User: KASSEES_RP_1
Description: Violations Summary: There was one violation observed during the inspection. It is summarized as follows: 1). The remote A S T fill pipes/ports are not adequately marked/color coded. Please properly mark the fill ports with the proper color coding markings. White for Regular Unleaded and Red for Premium/Super Unleaded. A non compliance letter accompanies this inspection report. Please find it attached. Please provide our office with documentation confirming the resolution of the cited violation, within thirty days of receipt of this inspection report and attached non compliance letter. Additional Notes: There was one other infraction observed, but not cited as a violation. It is summarized as follows: 1). The remote A S T fill ports' spill containment unit was excessively trashy. However, it was cleaned out in my presence. Discharge Information: There is no new information or obvious evidence of recent release, spill or discharge. However, the facility appears to have a history of past contamination, as it appears to have a record of ongoing site/contamination assessment work. Other Comments: There is a better way of performing monthly A S T interstitial monitoring, other than climbing upon the A S T to manually/physicall stick the I.M. tube. Install, or have installed, a sight level fuel gauge. A Krueger Gauge, is acceptable for now. For more inspection details and information; please see the copy of the inspection field notes, site schematic and system description that is electronically, as well as physically, attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058.
09/29/2006 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/29/2006
11/09/2004 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
09/30/2003 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
06/20/2003 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: NEW PLACARD (2003-2004) ON DISPLAY
09/19/2002 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 400(2)(a)6
09/19/2002 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/02/2002 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
Completion Notes: CHECKED MONTHLY RELEASE DETECTION/VISUAL INSPECTIONS
10/10/2001 Violation Closed Sheffield, Cynthia K.
Significance: SNC-B Status: Closed
Rule: 600(1)(d)
10/10/2001 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
10/31/2000 Comment MIGRATION
Description: COMPLIANCE: CONTAMINATION
10/27/2000 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/11/2000 Legacy Activity Sheffield, Cynthia K.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
10/12/1999 Legacy Activity Sheffield, Cynthia K.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
08/31/1999 Legacy Activity Sheffield, Cynthia K.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
08/18/1999 Violation Closed Sheffield, Cynthia K.
Significance: SNC-B Status: Closed
Rule: 400(3)
Comments:
Comment Date: 06/06/2016 User: MOLDENHAUER_HL_2
Description: NEED NEW SITE SKETCH AND PHOTO. NEW LAT AND LONG REQUIRED FOR DATABASE
Comments:
Comment Date: 07/28/2015 User: MOLDENHAUER_HL_1
Description: From Clewiston-835 through 4 90s, proceed south approx. 2 mi then watch for double gates on L. .9 mi to farm lane on R
Comments:
Comment Date: 11/13/2012 User: MOLDENHAUER_HL_1
Description: BWhidden@jjagproducts.com Preferrs a summer inspection as people are available to assist at that time.
08/18/1999 Legacy Activity Sheffield, Cynthia K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
08/18/1999 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 640(3)(a)1
Comments:
Comment Date: 02/02/2021 User: MCCOY_DL_2
Description: Luke Davis at Southern Gardens is Grove Manager for Prudential.
Comments:
Comment Date: 08/25/2015 User: MOLDENHAUER_HL_1
Description: Grove contact: Jesus Luna cell number: 673-6620, P.O Box 369; Clewiston, FL 33440 Daniel Skousen Regional contact: Office (813) 331-3942 / cell:(407) 908-0108. Main Office - (407) 892-3672 JLuna@deseretranches.com - Grove Manager DSkousen@deseretranches.com - Regional Manager CLYoung@deseretranches.com - Office Manager
Comments:
Comment Date: 02/22/2018 User: MCCOY_DL_1
Description: New email contact Jmchenry@agreserves.com ....office contact.Gary Walker gwalker@agreserves.com.
08/18/1999 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 640(3)(a)1
Comments:
Comment Date: 02/02/2021 User: MCCOY_DL_2
Description: Luke Davis at Southern Gardens is Grove Manager for Prudential.
Comments:
Comment Date: 08/25/2015 User: MOLDENHAUER_HL_1
Description: Grove contact: Jesus Luna cell number: 673-6620, P.O Box 369; Clewiston, FL 33440 Daniel Skousen Regional contact: Office (813) 331-3942 / cell:(407) 908-0108. Main Office - (407) 892-3672 JLuna@deseretranches.com - Grove Manager DSkousen@deseretranches.com - Regional Manager CLYoung@deseretranches.com - Office Manager
Comments:
Comment Date: 02/22/2018 User: MCCOY_DL_1
Description: New email contact Jmchenry@agreserves.com ....office contact.Gary Walker gwalker@agreserves.com.
08/18/1999 Violation Closed Sheffield, Cynthia K.
Significance: Minor Status: Closed
Rule: 640(3)(a)1
Comments:
Comment Date: 02/02/2021 User: MCCOY_DL_2
Description: Luke Davis at Southern Gardens is Grove Manager for Prudential.
Comments:
Comment Date: 08/25/2015 User: MOLDENHAUER_HL_1
Description: Grove contact: Jesus Luna cell number: 673-6620, P.O Box 369; Clewiston, FL 33440 Daniel Skousen Regional contact: Office (813) 331-3942 / cell:(407) 908-0108. Main Office - (407) 892-3672 JLuna@deseretranches.com - Grove Manager DSkousen@deseretranches.com - Regional Manager CLYoung@deseretranches.com - Office Manager
Comments:
Comment Date: 02/22/2018 User: MCCOY_DL_1
Description: New email contact Jmchenry@agreserves.com ....office contact.Gary Walker gwalker@agreserves.com.
08/18/1999 Violation Closed Sheffield, Cynthia K.
Significance: SNC-B Status: Closed
Rule: 400(3)
Comments:
Comment Date: 06/06/2016 User: MOLDENHAUER_HL_2
Description: NEED NEW SITE SKETCH AND PHOTO. NEW LAT AND LONG REQUIRED FOR DATABASE
Comments:
Comment Date: 07/28/2015 User: MOLDENHAUER_HL_1
Description: From Clewiston-835 through 4 90s, proceed south approx. 2 mi then watch for double gates on L. .9 mi to farm lane on R
Comments:
Comment Date: 11/13/2012 User: MOLDENHAUER_HL_1
Description: BWhidden@jjagproducts.com Preferrs a summer inspection as people are available to assist at that time.
08/18/1999 Violation Closed Sheffield, Cynthia K.
Significance: SNC-B Status: Closed
Rule: 400(3)
Comments:
Comment Date: 06/06/2016 User: MOLDENHAUER_HL_2
Description: NEED NEW SITE SKETCH AND PHOTO. NEW LAT AND LONG REQUIRED FOR DATABASE
Comments:
Comment Date: 07/28/2015 User: MOLDENHAUER_HL_1
Description: From Clewiston-835 through 4 90s, proceed south approx. 2 mi then watch for double gates on L. .9 mi to farm lane on R
Comments:
Comment Date: 11/13/2012 User: MOLDENHAUER_HL_1
Description: BWhidden@jjagproducts.com Preferrs a summer inspection as people are available to assist at that time.
06/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 04/23/2019 User: HARRINGTON_RD_1
Description: Kristi Krebes Publix Super Markets, Inc. ESP - Environmental Specialist (863)688-1188 ext. 43341
Comments:
Comment Date: 10/26/2012 User: HARRINGTON_RD_1
Description: Tank #1: EQ= 497 JRS under generator tank. EQ= 345 Morrison spill bucket. EQ= 682 Madison interstice and fuel level sensors. RD= electronic monitoring of interstice, monthly visuals.
Comments:
Comment Date: 09/25/2017 User: HARRINGTON_RD_1
Description: Jessica.Massanelli@publix.com
Attachments:
Attachment Date: 06/25/2008 User: BARNETT_PC_1
Description: tank #1 (2008)
View Attachment
Attachments:
Attachment Date: 09/24/2008 User: BARNETT_PC_1
Description: Tank 1: schematic
View Attachment
06/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 04/23/2019 User: HARRINGTON_RD_1
Description: Kristi Krebes Publix Super Markets, Inc. ESP - Environmental Specialist (863)688-1188 ext. 43341
Comments:
Comment Date: 10/26/2012 User: HARRINGTON_RD_1
Description: Tank #1: EQ= 497 JRS under generator tank. EQ= 345 Morrison spill bucket. EQ= 682 Madison interstice and fuel level sensors. RD= electronic monitoring of interstice, monthly visuals.
Comments:
Comment Date: 09/25/2017 User: HARRINGTON_RD_1
Description: Jessica.Massanelli@publix.com
Attachments:
Attachment Date: 06/25/2008 User: BARNETT_PC_1
Description: tank #1 (2008)
View Attachment
Attachments:
Attachment Date: 09/24/2008 User: BARNETT_PC_1
Description: Tank 1: schematic
View Attachment
06/23/1998 Violation Closed Unknown, User
Significance: Minor Status: Closed
Rule: 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762, 62-761/762
Comments:
Comment Date: 04/23/2019 User: HARRINGTON_RD_1
Description: Kristi Krebes Publix Super Markets, Inc. ESP - Environmental Specialist (863)688-1188 ext. 43341
Comments:
Comment Date: 10/26/2012 User: HARRINGTON_RD_1
Description: Tank #1: EQ= 497 JRS under generator tank. EQ= 345 Morrison spill bucket. EQ= 682 Madison interstice and fuel level sensors. RD= electronic monitoring of interstice, monthly visuals.
Comments:
Comment Date: 09/25/2017 User: HARRINGTON_RD_1
Description: Jessica.Massanelli@publix.com
Attachments:
Attachment Date: 06/25/2008 User: BARNETT_PC_1
Description: tank #1 (2008)
View Attachment
Attachments:
Attachment Date: 09/24/2008 User: BARNETT_PC_1
Description: Tank 1: schematic
View Attachment
06/23/1998 Legacy Activity Sheffield, Cynthia K.
Activity Name: AST ROUTINE COMPLIANCE INSPECTION Activity Status: Closed