04/16/2025 Editable Letter Activity Jackson, Sydney M
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 04/22/2025
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 04/22/2025
Comment: Approved by Jennifer Paul: RTC 4/16/2025
Events:
Event Type: Activity has been submitted for approval Date: 04/18/2025
Comment: Submitted for approval by: Sydney M Jackson
Attachments:
Attachment Date: 04/16/2025 User: JACKSON_SM
Description: Return To Compliance
View Attachment
03/25/2025 Comment Jackson, Sydney M
Description: Patti McCord - pmccord@aetllc.com
03/24/2025 Enforcement Tracking Activity Jackson, Sydney M
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 04/22/2025
Events:
Event Type: Activity has been finished Date: 04/22/2025
Comment: Finished
Comments:
Comment Date: 04/16/2025 User: JACKSON_SM
Description: JTB Properties were under enforcement for failing to meet their 90-day compliance period. However, without the issuance of a Warning Letter, the facility quickly submitted documentation to resolve their violation and will be receiving a Return to Compliance letter.
03/18/2025 Enforcement Referral Activity Zimmerman, Robert A
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/24/2025
Events:
Event Type: Activity has been finished Date: 03/24/2025
Comment: Finished
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/24/2025
Comment: Acknowledged and Assigned by Jennifer Paul
Events:
Event Type: Activity has been assigned Date: 03/24/2025
Comment: Assigned to Sydney M Jackson
Events:
Event Type: Activity/Document was accepted on this date Date: 03/24/2025
Comment: Accepted by Sydney M Jackson: accepted
Events:
Event Type: Activity has been submitted for approval Date: 03/18/2025
Comment: Submitted for approval by: Robert A Zimmerman: Received directive to refer this facility for enforcement action.
Comments:
Comment Date: 03/18/2025 User: ZIMMERMAN_RA_2
Description: Received directive to refer this facility for enforcement action.
Comments:
Comment Date: 03/18/2025 User: ZIMMERMAN_RA_2
Description: Received directive to refer this facility for enforcement action.
03/18/2025 Enforcement Referral Activity Zimmerman, Robert A
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 03/24/2025
Events:
Event Type: Activity has been finished Date: 03/24/2025
Comment: Finished
Events:
Event Type: Activity/Document was acknowledged on this date Date: 03/24/2025
Comment: Acknowledged and Assigned by Jennifer Paul
Events:
Event Type: Activity has been assigned Date: 03/24/2025
Comment: Assigned to Sydney M Jackson
Events:
Event Type: Activity/Document was accepted on this date Date: 03/24/2025
Comment: Accepted by Sydney M Jackson: accepted
Events:
Event Type: Activity has been submitted for approval Date: 03/18/2025
Comment: Submitted for approval by: Robert A Zimmerman: Received directive to refer this facility for enforcement action.
Comments:
Comment Date: 03/18/2025 User: ZIMMERMAN_RA_2
Description: Received directive to refer this facility for enforcement action.
Comments:
Comment Date: 03/18/2025 User: ZIMMERMAN_RA_2
Description: Received directive to refer this facility for enforcement action.
11/06/2024 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
11/06/2024 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 11/06/2024 Activity Status: Closed
Date: 11/06/2024
Recipient: Patti McCord
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and associated compliance letter email attachments to facility representative; "Patti McCord" pmccord@aetllc.com
Events:
Event Type: Activity has been finished Date: 11/06/2024
Comment: Finished
11/06/2024 Editable Letter Activity Zimmerman, Robert A
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 11/06/2024
Comment: Finished
Events:
Event Type: Document has been sent Date: 11/06/2024
Comment: Sent
Attachments:
Attachment Date: 11/06/2024 User: ZIMMERMAN_RA_2
Description: CAO 9201052 , JTP PROPERTIES LLC-PIT STOP 33 2024.
View Attachment
10/29/2024 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 10/29/2024
Activity Closed Date: 11/06/2024 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 11/06/2024
Comment: Finished
Comments:
Comment Date: 11/05/2024 User: ZIMMERMAN_RA_2
Description: Sent TCI report and associated compliance letter email attachments to facility representative; "Patti McCord" pmccord@aetllc.com
10/11/2024 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 10/11/2024 Activity Status: Closed
Date: 10/11/2024
Recipient: Angela Kelly
Sender: Robert Zimmerman
Subject: Compliance outreach TCI notification-scheduling
Message: Contacted facility representative “Angela Kelly” akelly@aetllc.com for notification and schedule upcoming TCI and to give a reminder that the three-year record file review requirement is: Registration Placards, Proof of Financial Responsibility, STFM, monthly visual inspections, A/B/C level UST operator certifications, annual release detection system operability testing, line leak detector testing, containment integrity evaluation testing and overfill protection device testing certifications.
Events:
Event Type: Activity has been finished Date: 10/11/2024
Comment: Finished
04/18/2023 Record Document Activity Harrington, Richard D.
Activity Status: Closed
Contact Name: patti McCord (AET) Activity Closed Date: 04/18/2023
Events:
Event Type: Activity has been finished Date: 04/18/2023
Comment: Finished
04/18/2023 Editable Letter Activity Harrington, Richard D.
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 04/18/2023
Comment: Finished
Events:
Event Type: Document has been sent Date: 04/18/2023
Comment: Sent
Attachments:
Attachment Date: 04/18/2023 User: HARRINGTON_RD_1
Description: RTC 2023
View Attachment
02/10/2023 Violation Closed Zimmerman, Robert A
Significance: SNC-B Status: Closed
Criteria ID: 6063
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2
02/10/2023 Editable Letter Activity Zimmerman, Robert A
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Description: Compliance Assistance Offer Letter
Events:
Event Type: Document has been sent Date: 02/10/2023
Comment: Sent
Events:
Event Type: Activity has been finished Date: 02/10/2023
Comment: Finished
Attachments:
Attachment Date: 02/10/2023 User: ZIMMERMAN_RA_2
Description: CAO 9201052, JTP PROPERTIES LLC-PIT STOP 33 2023.
View Attachment
02/10/2023 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 02/10/2023 Activity Status: Closed
Date: 02/10/2023
Recipient: Patti McCord
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and associated compliance letter email attachment to facility representative; "Patti McCord" pmccord@aetllc.com
Events:
Event Type: Activity has been finished Date: 02/10/2023
Comment: Finished
02/10/2023 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
02/10/2023 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
02/10/2023 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
02/10/2023 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 6073
Rule: 62-761.700(3)(b), 62-761.700(3)(b)1, 62-761.700(3)(b)2
01/30/2023 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 01/30/2023
Activity Closed Date: 02/10/2023 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 02/10/2023
Comment: Finished
Comments:
Comment Date: 02/09/2023 User: ZIMMERMAN_RA_2
Description: Sent TCI report and associated compliance letter email attachment to facility representative; "Patti McCord" pmccord@aetllc.com
12/02/2022 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 12/02/2022 Activity Status: Closed
Date: 12/02/2022
Recipient: Angela Kelly
Sender: Robert Zimmerman
Subject: Compliance assistance outreach TCI notification-scheduling
Message: Contacted facility representative “Angela Kelly” akelly@aetllc.com for compliance assistance outreach notification scheduling of upcoming TCI and to give a reminder that the three-year record review requirement is: Registration placard, proof of financial responsibility and storage tanks mechanism forms, monthly visual inspections, monthly electronic release detection monitoring records, A/B/C level UST operator certifications, containment integrity evaluation testing, annual overfill protection device, line leak detector and release detection system operability test certifications.
Events:
Event Type: Activity has been finished Date: 12/02/2022
Comment: Finished
08/29/2022 Editable Letter Activity Ramsey, Timothy H
Activity Title: Closure Assessment Report (Complete) Activity Status: Closed
Events:
Event Type: Document has been sent Date: 08/29/2022
Comment: Sent
Events:
Event Type: Activity has been finished Date: 08/29/2022
Comment: Finished
Attachments:
Attachment Date: 08/29/2022 User: RAMSEY_TH_1
Description: Closure Review Letter
View Attachment
08/29/2022 TCAR Activity Ramsey, Timothy H
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 08/29/2022
Events:
Event Type: Activity has been finished Date: 08/29/2022
Comment: Finished
08/29/2022 Electronic Communication Activity Ramsey, Timothy H
Activity Closed Date: 08/29/2022 Activity Status: Closed
Date: 08/29/2022
Recipient: Jack Smith
Sender: Tim Ramsey
Subject: Closure Review Letter
Message: Emailed Closure Review Letter
Events:
Event Type: Activity has been finished Date: 08/29/2022
Comment: Finished
08/14/2022 Editable Letter Activity Ramsey, Timothy H
Activity Title: Site Assessment Request Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/14/2022
Comment: Finished
Events:
Event Type: Document has been sent Date: 08/14/2022
Comment: Sent
Attachments:
Attachment Date: 08/14/2022 User: RAMSEY_TH_1
Description: Site Assessment Request
View Attachment
08/14/2022 Electronic Communication Activity Ramsey, Timothy H
Activity Closed Date: 08/14/2022 Activity Status: Closed
Date: 08/14/2022
Recipient: Jack Smith
Sender: Tim Ramsey
Subject: Site Assessment Request Letter
Message: Emailed Site Assessment Request Letter
Events:
Event Type: Activity has been finished Date: 08/14/2022
Comment: Finished
08/14/2022 Discharge Reporting Activity Ramsey, Timothy H
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 08/14/2022
Events:
Event Type: Activity has been finished Date: 08/14/2022
Comment: Finished
08/14/2022 Document Management Activity Ramsey, Timothy H
Activity Title: Discharge Report Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/14/2022
Comment: Finished
Attachments:
Attachment Date: 08/14/2022 User: RAMSEY_TH_1
Description: Discharge Report Form
View Attachment
09/23/2021 Record Document Activity Zimmerman, Robert A
Activity Status: Closed
Contact Name: Patti McCord Activity Closed Date: 09/23/2021
Events:
Event Type: Activity has been finished Date: 09/23/2021
Comment: Finished
Comments:
Comment Date: 09/23/2021 User: ZIMMERMAN_RA_2
Description: Received proof of violation resolution documents - A/B/C level UST operator certifications and double wall spill bucket CIE testing; entered documents into FIRST.
09/23/2021 Editable Letter Activity Zimmerman, Robert A
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 09/23/2021
Comment: Sent
Events:
Event Type: Activity has been finished Date: 09/23/2021
Comment: Finished
Attachments:
Attachment Date: 09/23/2021 User: ZIMMERMAN_RA_2
Description: RCL 9201052, JTP PROPERTIES LLC-PIT STOP 33 2021.
View Attachment
09/23/2021 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 09/23/2021 Activity Status: Closed
Date: 09/23/2021
Recipient: Patti McCord
Sender: Robert Zimmerman
Subject: Issued RCL
Message: Sent RCL email attachment to facility representative; "Patti McCord" pmccord@aetllc.com
Events:
Event Type: Activity has been finished Date: 09/23/2021
Comment: Finished
11/03/2020 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4001
Rule: 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2., 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7)
11/03/2020 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 11/03/2020 Activity Status: Closed
Date: 11/03/2020
Recipient: Patti McCord
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and associated compliance letter email attachments to facility representative; "Patti McCord" pmccord@aetllc.com
Events:
Event Type: Activity has been finished Date: 11/03/2020
Comment: Finished
11/03/2020 Editable Letter Activity Zimmerman, Robert A
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 11/03/2020
Comment: Finished
Events:
Event Type: Document has been sent Date: 11/03/2020
Comment: Sent
Attachments:
Attachment Date: 11/03/2020 User: ZIMMERMAN_RA_2
Description: CAO 9201052, JTP PROPERTIES LLC-PIT STOP 33.
View Attachment
11/03/2020 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
10/23/2020 Comment Zimmerman, Robert A
Description: interstitial monitoring vacuum gauges
10/23/2020 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 10/23/2020
Activity Closed Date: 11/03/2020 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 11/03/2020
Comment: Finished
Comments:
Comment Date: 11/03/2020 User: ZIMMERMAN_RA_2
Description: Sent TCI report and associated compliance letter email attachments to facility representative; "Patti McCord" pmccord@aetllc.com
07/26/2018 Editable Letter Activity Zimmerman, Robert A
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 07/26/2018
Comment: Finished
Attachments:
Attachment Date: 07/26/2018 User: ZIMMERMAN_RA_2
Description: ICL 9201052, JOHNSON & JOHNSON #33.
View Attachment
07/26/2018 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 07/26/2018 Activity Status: Closed
Date: 07/26/2018
Recipient: Patti McCord
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and ICL email attachments to facility representative.
Events:
Event Type: Activity has been finished Date: 07/26/2018
Comment: Finished
07/19/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/19/2018
Activity Closed Date: 07/26/2018 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 07/26/2018
Comment: Finished
07/03/2018 Phone Conversation Activity Zimmerman, Robert A
Call Type: Outgoing Activity Status: Closed
Phone Number: (850) 933-2269 Activity Closed Date: 07/03/2018
Subject: Compliance assistance outreach contact with facility representative for notification and to schedule upcoming TCI and to give a reminder that the two year record review requirement is: Registration Placard, Proof of Financial Responsibility, CFR, Monthly visual inspections and Electronic release detection records, containment integrity (if required), annual overfill protection, Line leak detector, Operability test and A/B/C UST operator certifications.
Events:
Event Type: Activity has been finished Date: 07/03/2018
Comment: Finished
06/30/2017 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/30/2017
Activity Closed Date: 07/10/2017 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 07/10/2017
Comment: Finished
11/23/2016 Editable Letter Activity Zimmerman, Robert A
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 11/23/2016
Comment: Finished
Attachments:
Attachment Date: 11/23/2016 User: ZIMMERMAN_RA_2
Description: NCL 9201052 JOHNSON & JOHNSON #33
View Attachment
11/17/2016 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
11/17/2016 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 11/17/2016
Activity Closed Date: 11/23/2016 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 11/23/2016
Comment: Finished
Comments:
Comment Date: 11/23/2016 User: ZIMMERMAN_RA_2
Description: Tanks registration is incorrect and needs to be changed. Registration does not show diesel is stored at facility.
11/17/2016 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
03/06/2015 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/10/2015
Activity Closed Date: 03/11/2015 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 03/11/2015
Comment: Finished
Comments:
Comment Date: 03/11/2015 User: SHULAW_BJ_1
Description: The mounting brackets have been secured. The insurance policy has expired[ send the renewed policy. Annual tests due this month.
10/02/2014 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 10/02/2014
Comment: Finished
Attachments:
Attachment Date: 10/02/2014 User: SHULAW_BJ_1
Description: 2Oct14 NCL
View Attachment
10/02/2014 Emergency Preparedness Information Activity Shulaw, Benjamin J.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 10/02/2014
Events:
Event Type: Activity has been finished Date: 10/02/2014
Comment: Finished
09/30/2014 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
09/25/2014 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 09/30/2014
Activity Closed Date: 10/02/2014 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 10/02/2014
Comment: Finished
Comments:
Comment Date: 10/02/2014 User: SHULAW_BJ_1
Description: New Violations: In each of the dispensers 9 and 1 there is a shear valve mounting bracket not properly secured. Properly secure the mounting brackets and call for a re-inspection. Comments: Two USTs, 1-2 compartmented with 5 dispensers. Visual monitoring of 3 sumps, 2 interstices and 5 dispensers. Product levels are monitored by an ATG. The interstice riser on each UST is equipped with a vacuum gauge. The gauges for the regular and super/diesel USTs read 15 and 24¿ Hg respectively. Overfill prevention is by flapper valves. The Total Containment sumps and OPW spill buckets appeared tight. Sumps, spill buckets and dispenser liners were dry, hoses and nozzles are good. The area is clean. The registration placard was displayed. A Certificate of Financial Responsibility and insurance documentation was at the facility for inspection. The RDRL was in the log. Class A, B, and C certificates were obtained by the inspector. Discharge Information: No discharges After consultation, a facility representative signed the attached notes for this report. This report will be mailed via USPS. A non compliance letter citing the violations accompanies this inspection report; please find it attached. Please provide our office with documentation confirming the resolution of the cited violations within thirty days of receipt of this inspection report and attached non compliance letter. For more inspection details and information or if you have any questions please contact me at 386-758-2185, 386-697-7329 cell, fax 386-758-2187, or email Benjamin.Shulaw@flhealth.gov.
09/13/2012 Document Management Activity Perea, Aurelio O.
Activity Title: Operator Training Certification Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 09/13/2012
Comment: Submitted for approval by Aurelio O. Perea
Events:
Event Type: Activity has been finished Date: 09/25/2012
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 09/20/2012
Comment: Approved by Ramsey D. Kassees: Facility compliance inspection report approved.
Attachments:
Attachment Date: 09/13/2012 User: PEREA_AO_1
Description: A/B Certification
View Attachment
09/11/2012 Site Inspection Activity Closed Perea, Aurelio O.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 09/11/2012
Activity Closed Date: 09/20/2012 Activity Closed By: KASSEES_RP_1
Events:
Event Type: Activity has been finished Date: 09/20/2012
Comment: Finished
Comments:
Comment Date: 09/11/2012 User: PEREA_AO_1
Description: Violations Summary: There were no violations cited at the time of the inspection. Additional Notes: The hose at dispenser no. 4 is gouged of its outermost layer. Please replace as soon as possible. The dispenser liners are in need of cleaning. Please clean them as soon as possible to allow for better monitoring of their integrity. One of the Monthly Visual Inspection records was more than thirty-five days after the preceding record. Please make sure all of these inspections are performed within thirty-five days, or less, of one another. Discharge Information: There is no new information or obvious evidence of recent release or discharge, within the last year. For more detailed discharge information, please consult the Petroleum Clean Up Section at the F D E P H.Q. in Tallahassee; or the F D E P Northeast District Office in Jacksonville; or the official compliance facility file at the Columbia C H D, Environmental Health Section, in Lake City. Other Comments: For more inspection details and information; please see the copy of the inspection field notes, site schematic and system description that is electronically, as well as physically, attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058.
09/11/2012 Emergency Preparedness Information Activity Perea, Aurelio O.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/20/2012
Events:
Event Type: Activity has been finished Date: 09/20/2012
Comment: Finished
05/26/2011 Meeting Activity Shulaw, Benjamin J.
Activity Closed Date: 05/26/2011 Activity Status: Closed
Location: facility
Subject: shear valve disp 5 properly secured.
Events:
Event Type: Activity has been finished Date: 05/26/2011
Comment: Finished
02/18/2011 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/18/2011
Comment: Finished
Attachments:
Attachment Date: 02/18/2011 User: SHULAW_BJ_1
Description: 15Feb11 NCL
View Attachment
02/17/2011 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
02/17/2011 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/09/2011
Activity Closed Date: 02/18/2011 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 02/18/2011
Comment: Finished
Comments:
Comment Date: 02/18/2011 User: SHULAW_BJ_1
Description: Violations: Dispenser 5 shear valve secured by 1 bolt only. Secure with another bolt. Comments: No comments Discharge Information: No discharges A non compliance letter citing the violations accompanies this inspection report; please find it attached. Please provide our office with documentation confirming the resolution of the cited violations within thirty days of receipt of this inspection report and attached non compliance letter. For more inspection details and information, please see the copy of the inspection field notes. If you have any questions please contact me at 386-623-0831 cell, fax 386-758-2187, or office 386-758-2140 or email Benjamin_Shulaw@doh.state.fl.us
02/15/2011 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
12/11/2009 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/04/2009
Activity Closed Date: 12/11/2009 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 12/11/2009
Comment: Finished
Comments:
Comment Date: 12/11/2009 User: SHULAW_BJ_1
Description: I visited the site and found that the vacuum gauges had been replaced and a vacuum reinstated.
10/22/2009 Editable Letter Activity Kassees, Ramsey D.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
06/08/2009 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
06/08/2009 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
06/03/2009 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 06/03/2009
Activity Closed Date: 06/08/2009 Activity Closed By: SHULAW_BJ_1
Comments:
Comment Date: 06/08/2009 User: SHULAW_BJ_1
Description: Test the vacuum gauges. A non compliance letter citing the violations accompanies this inspection report; please find it attached. Please provide our office with documentation confirming the resolution of the cited violations within thirty days of receipt of this inspection report and attached non compliance letter. If you have any questions or concerns, please feel free to contact me at (386) 758-2140.
02/27/2008 Attachment Oymayan, Avo J.
02/27/2008 Emergency Preparedness Information Activity Oymayan, Avo J.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/27/2008
02/27/2008 Attachment Oymayan, Avo J.
02/27/2008 Attachment Oymayan, Avo J.
02/27/2008 Attachment Oymayan, Avo J.
02/27/2008 Attachment Oymayan, Avo J.
02/27/2008 Attachment Oymayan, Avo J.
02/27/2008 Attachment Oymayan, Avo J.
02/26/2008 Site Inspection Activity Closed Oymayan, Avo J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/26/2008
Activity Closed Date: 02/27/2008 Activity Closed By: OYMAYAN_AJ_1
Comments:
Comment Date: 02/27/2008 User: OYMAYAN_AJ_1
Description: Violation Summary: None at this time. Additional Comments: There was one issue that needs to be addressed, but was not cited as a violation. It was as follows: 1). This facility uses vaccuum gauge as part of its UST I.M. release detection equipment, already approved by FDEP. In FDEP's approval letter of 7-28-2006, there are conditions that have to be met. These conditions state that any drop of more than 10% on the vaccum readings from the previous month reading or a cummulative loss of 20% during the year will be investigated as an incident. Therefore, please take this conditions into consideration when checking and recording your vacuum gauge readings each month. Also, please make sure to write any maintenance and calibration of your vacuum gauges on your monthly visual inspection forms. Discharge Information: There is no new inforamtion or obvious evidence of a release or discharge. However, the facility appears to have a history of past contamination, as there appears to be a record of active clean up activity - score 54. Other Comments: For more inspection details and information, please see the copy of the inspection fieldnotes, site schematic and system description, that is electronically as well as physicallly attached to this inspection report. If you have any questions or concerns, please contact me at (386) 758-2140 or (386) 758-1058.
05/23/2007 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 05/23/2007
02/14/2007 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/14/2007
09/22/2006 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/22/2006
08/14/2006 Record Document Activity Dohaney, Tim
Activity Status: Closed
Contact Name: PCS Activity Closed Date: 08/14/2006
Comments:
Comment Date: 08/14/2006 User: DOHANEY_T
Description: RECEIVED UPDATED PCS REVIEW COMMENTS CONCERNING POSSIBLE DISCHARGE FOUND AT THIS SITE WHILE ADDRESSING STATE SITE ACROSS THE STREET. PCS RECOMMENDS THAT ENFORCEMENT ACTION AND A REQUEST FOR A DRF BE DROPPED AT THIS TIME. DISTRICT DROPS ITS CASE BASED ON PCS RECOMMENDATION.
07/12/2006 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/12/2006
Activity Closed Date: 07/12/2006 Activity Closed By: KASSEES_RP_1
Comments:
Comment Date: 07/12/2006 User: KASSEES_RP_1
Description: The department is in receipt of adequate response that corrects and resolves the following violations: 1). An Alternate Procedure Request has been tendered to FDEP Tallahassee, requesting continued use of Vacuum Gauge Interstitial Monitoring, on 05/17/2006. The facility owner/operator is awaiting approval/disapproval response from FDEP Tallahassee. 2). The diesel UST spill containment bucket has been emptied and cleaned. The product has been properly disposed. 3). Monthly visual inspections are now being performed and recorded no more than thirty five days apart. This facility is in Compliance Without Enforcement (CWOE). If you have any questions or concerns, please feel free to contact me at (386) 7582140 or (386) 758-1058.
07/12/2006 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/12/2006
Activity Closed Date: 04/17/2007 Activity Closed By: OYMAYAN_AJ_1
Comments:
Comment Date: 04/17/2007 User: OYMAYAN_AJ_1
Description: Violations Summary: There were no violations cited at the time of the inspection. Additional Notes: Please repair the breakaway area on the diesel pump hose. It appears to be slightly leaky. Please repair / replace the U S T I .M. vacuum gauge on the diesel / premium underground tank, to ensure a more proper and easier readings. Discharge Information: There is no new information or obvious evidence of a recent release or discharge. However, the facility appears to have a history of past contamination, as there appears to be a record of active cleanup activity - score 54. Other Comments: For more information and inspection details, please see the copy of the inspection fieldnotes, site schematics and system description, that is electronically as well as physically attached d to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058.
05/02/2006 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Criteria ID: 1060
Rule: 62-761.600(1)(a)3.
Comments: Mark this as out of compliance if the release detection method used doesn't meet these performance standards. Some methods may have stricter criteria, which is usually incorporated in the equipment approval. Also note this as a record keeping violation, rule 62-761.710(3), if the written performance claims are not retained.
05/02/2006 Editable Letter Activity Kassees, Ramsey D.
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 05/02/2006
Comment: Sent on Tue May 02 12:00:00 EST 2006
Attachments:
Attachment Date: 05/02/2006 User: KASSEES_RP_1
Description: NCL Report
View Attachment
05/02/2006 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/02/2006
Activity Closed Date: 05/02/2006 Activity Closed By: KASSEES_RP_1
Comments:
Comment Date: 05/02/2006 User: KASSEES_RP_1
Description: There were several months when the spill containment buckets were were not marked as being checked/inspected. Please inspect all components of the UST system and record the status of each. Also, there were several months of inspection records that were more than thirty five days apart. Please make sure all inspections are performed and recorded no more than thirty five days apart.
05/02/2006 Violation Closed Kassees, Ramsey D.
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
05/02/2006 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
08/03/2005 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
04/29/2005 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 761.700(1)(c)1
04/29/2005 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
11/19/2004 Comment MIGRATION
Description: IMMINENT THREAT: REASON FOR ITS APPROVAL: > 1/2 MCL IN POTABLE WELL
11/19/2004 Comment MIGRATION
Description: IMMINENT THREAT: REASON FOR ITS APPROVAL: > 1/2 MCL IN POTABLE WELL
11/19/2004 Comment MIGRATION
Description: IMMINENT THREAT: ITS APPROVAL DATE: 11/19/04
06/02/2004 Legacy Activity Kassees, Ramsey D.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
06/02/2004 Legacy Activity Kassees, Ramsey D.
Activity Name: COMPLIANCE W/O FORMAL ENFORCEMENT ACTION Activity Status: Closed
03/16/2004 Violation Closed Kassees, Ramsey D.
Significance: SNC-B Status: Closed
Rule: 600(1)(d)
03/16/2004 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/16/2004 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 450(2)(a)
08/28/2003 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
03/05/2003 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 610(4)(c)
Comments:
Comment Date: 03/31/2021 User: ROJAS_Y_1
Description: Release Detection: Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) Red jacket STPs, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Tank: Phoenix Parabeam double walled system (EQ# 403) with Smith Red Thread IIA double walled piping (EQ# 252) and STP OPW Pisces TSDF 4536 sumps (EQ# 318) - Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) - Overfill Protection: Flow shut off valves (unknown make/model/EQ #) OPW Pisces DS1242 dispenser liners, EQ# 318
Comments:
Comment Date: 09/21/2010 User: DIAZ_HZ_1
Description: Phoenix Parabeam double walled system (EQ# 403) Smith Red Thread IIA double walled piping (EQ# 252) Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) STP OPW Pisces TSDF 4536 sumps (EQ# 318) Red jacket STP¿s, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) OPW Pisces DS1242 dispenser liners, EQ# 318 Existing overfill protection (Ball floats)
Comments:
Comment Date: 06/11/2007 User: JARRETT_SE
Description: 06/07/2007 Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252).
Comments:
Comment Date: 04/24/2008 User: JARRETT_SE
Description: 04/10/2008 Release Detection: - Tanks: Veeder Root TLS 350 Continuous Statistical Leak Detection (CSLD) (DEP EQ # 033) with continuous automatic tank gauging - Piping: Electronic (PLLD) line leak detectors (DEP EQ # 271) with monthly PLLD 0.2 gallons per hour (gph) line leak test and annual 3 gph leak tests; - Visual inspections of STP manways, dispensers/liners and spill containment buckets; - Veeder Root TLS-350 panel checked - monitors the CSLD & PLLD 0.2 gph tests; Tanks/STP Manways/Piping: (3) Single-walled, fiberglass USTs {(12,000-gallon (Regular), 10,000-gallon (Premium) and 6,000-gallon (Plus)}. Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252). Tanks are equipped with: - (3) STP manways;
03/05/2003 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/05/2003 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 640(3)(a)3
Comments:
Comment Date: 03/31/2021 User: ROJAS_Y_1
Description: Release Detection: Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) Red jacket STPs, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Tank: Phoenix Parabeam double walled system (EQ# 403) with Smith Red Thread IIA double walled piping (EQ# 252) and STP OPW Pisces TSDF 4536 sumps (EQ# 318) - Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) - Overfill Protection: Flow shut off valves (unknown make/model/EQ #) OPW Pisces DS1242 dispenser liners, EQ# 318
Comments:
Comment Date: 09/21/2010 User: DIAZ_HZ_1
Description: Phoenix Parabeam double walled system (EQ# 403) Smith Red Thread IIA double walled piping (EQ# 252) Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) STP OPW Pisces TSDF 4536 sumps (EQ# 318) Red jacket STP¿s, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) OPW Pisces DS1242 dispenser liners, EQ# 318 Existing overfill protection (Ball floats)
Comments:
Comment Date: 06/11/2007 User: JARRETT_SE
Description: 06/07/2007 Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252).
Comments:
Comment Date: 04/24/2008 User: JARRETT_SE
Description: 04/10/2008 Release Detection: - Tanks: Veeder Root TLS 350 Continuous Statistical Leak Detection (CSLD) (DEP EQ # 033) with continuous automatic tank gauging - Piping: Electronic (PLLD) line leak detectors (DEP EQ # 271) with monthly PLLD 0.2 gallons per hour (gph) line leak test and annual 3 gph leak tests; - Visual inspections of STP manways, dispensers/liners and spill containment buckets; - Veeder Root TLS-350 panel checked - monitors the CSLD & PLLD 0.2 gph tests; Tanks/STP Manways/Piping: (3) Single-walled, fiberglass USTs {(12,000-gallon (Regular), 10,000-gallon (Premium) and 6,000-gallon (Plus)}. Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252). Tanks are equipped with: - (3) STP manways;
03/05/2003 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 640(3)(a)3
Comments:
Comment Date: 03/31/2021 User: ROJAS_Y_1
Description: Release Detection: Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) Red jacket STPs, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Tank: Phoenix Parabeam double walled system (EQ# 403) with Smith Red Thread IIA double walled piping (EQ# 252) and STP OPW Pisces TSDF 4536 sumps (EQ# 318) - Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) - Overfill Protection: Flow shut off valves (unknown make/model/EQ #) OPW Pisces DS1242 dispenser liners, EQ# 318
Comments:
Comment Date: 09/21/2010 User: DIAZ_HZ_1
Description: Phoenix Parabeam double walled system (EQ# 403) Smith Red Thread IIA double walled piping (EQ# 252) Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) STP OPW Pisces TSDF 4536 sumps (EQ# 318) Red jacket STP¿s, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) OPW Pisces DS1242 dispenser liners, EQ# 318 Existing overfill protection (Ball floats)
Comments:
Comment Date: 06/11/2007 User: JARRETT_SE
Description: 06/07/2007 Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252).
Comments:
Comment Date: 04/24/2008 User: JARRETT_SE
Description: 04/10/2008 Release Detection: - Tanks: Veeder Root TLS 350 Continuous Statistical Leak Detection (CSLD) (DEP EQ # 033) with continuous automatic tank gauging - Piping: Electronic (PLLD) line leak detectors (DEP EQ # 271) with monthly PLLD 0.2 gallons per hour (gph) line leak test and annual 3 gph leak tests; - Visual inspections of STP manways, dispensers/liners and spill containment buckets; - Veeder Root TLS-350 panel checked - monitors the CSLD & PLLD 0.2 gph tests; Tanks/STP Manways/Piping: (3) Single-walled, fiberglass USTs {(12,000-gallon (Regular), 10,000-gallon (Premium) and 6,000-gallon (Plus)}. Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252). Tanks are equipped with: - (3) STP manways;
03/05/2003 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 640(3)(a)3
Comments:
Comment Date: 03/31/2021 User: ROJAS_Y_1
Description: Release Detection: Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) Red jacket STPs, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Tank: Phoenix Parabeam double walled system (EQ# 403) with Smith Red Thread IIA double walled piping (EQ# 252) and STP OPW Pisces TSDF 4536 sumps (EQ# 318) - Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) - Overfill Protection: Flow shut off valves (unknown make/model/EQ #) OPW Pisces DS1242 dispenser liners, EQ# 318
Comments:
Comment Date: 09/21/2010 User: DIAZ_HZ_1
Description: Phoenix Parabeam double walled system (EQ# 403) Smith Red Thread IIA double walled piping (EQ# 252) Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) STP OPW Pisces TSDF 4536 sumps (EQ# 318) Red jacket STP¿s, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) OPW Pisces DS1242 dispenser liners, EQ# 318 Existing overfill protection (Ball floats)
Comments:
Comment Date: 06/11/2007 User: JARRETT_SE
Description: 06/07/2007 Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252).
Comments:
Comment Date: 04/24/2008 User: JARRETT_SE
Description: 04/10/2008 Release Detection: - Tanks: Veeder Root TLS 350 Continuous Statistical Leak Detection (CSLD) (DEP EQ # 033) with continuous automatic tank gauging - Piping: Electronic (PLLD) line leak detectors (DEP EQ # 271) with monthly PLLD 0.2 gallons per hour (gph) line leak test and annual 3 gph leak tests; - Visual inspections of STP manways, dispensers/liners and spill containment buckets; - Veeder Root TLS-350 panel checked - monitors the CSLD & PLLD 0.2 gph tests; Tanks/STP Manways/Piping: (3) Single-walled, fiberglass USTs {(12,000-gallon (Regular), 10,000-gallon (Premium) and 6,000-gallon (Plus)}. Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252). Tanks are equipped with: - (3) STP manways;
03/05/2003 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 640(3)(a)3
Comments:
Comment Date: 03/31/2021 User: ROJAS_Y_1
Description: Release Detection: Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) Red jacket STPs, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Tank: Phoenix Parabeam double walled system (EQ# 403) with Smith Red Thread IIA double walled piping (EQ# 252) and STP OPW Pisces TSDF 4536 sumps (EQ# 318) - Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) - Overfill Protection: Flow shut off valves (unknown make/model/EQ #) OPW Pisces DS1242 dispenser liners, EQ# 318
Comments:
Comment Date: 09/21/2010 User: DIAZ_HZ_1
Description: Phoenix Parabeam double walled system (EQ# 403) Smith Red Thread IIA double walled piping (EQ# 252) Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) STP OPW Pisces TSDF 4536 sumps (EQ# 318) Red jacket STP¿s, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) OPW Pisces DS1242 dispenser liners, EQ# 318 Existing overfill protection (Ball floats)
Comments:
Comment Date: 06/11/2007 User: JARRETT_SE
Description: 06/07/2007 Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252).
Comments:
Comment Date: 04/24/2008 User: JARRETT_SE
Description: 04/10/2008 Release Detection: - Tanks: Veeder Root TLS 350 Continuous Statistical Leak Detection (CSLD) (DEP EQ # 033) with continuous automatic tank gauging - Piping: Electronic (PLLD) line leak detectors (DEP EQ # 271) with monthly PLLD 0.2 gallons per hour (gph) line leak test and annual 3 gph leak tests; - Visual inspections of STP manways, dispensers/liners and spill containment buckets; - Veeder Root TLS-350 panel checked - monitors the CSLD & PLLD 0.2 gph tests; Tanks/STP Manways/Piping: (3) Single-walled, fiberglass USTs {(12,000-gallon (Regular), 10,000-gallon (Premium) and 6,000-gallon (Plus)}. Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252). Tanks are equipped with: - (3) STP manways;
03/05/2003 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 610(4)(c)
Comments:
Comment Date: 03/31/2021 User: ROJAS_Y_1
Description: Release Detection: Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) Red jacket STPs, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Tank: Phoenix Parabeam double walled system (EQ# 403) with Smith Red Thread IIA double walled piping (EQ# 252) and STP OPW Pisces TSDF 4536 sumps (EQ# 318) - Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) - Overfill Protection: Flow shut off valves (unknown make/model/EQ #) OPW Pisces DS1242 dispenser liners, EQ# 318
Comments:
Comment Date: 09/21/2010 User: DIAZ_HZ_1
Description: Phoenix Parabeam double walled system (EQ# 403) Smith Red Thread IIA double walled piping (EQ# 252) Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) STP OPW Pisces TSDF 4536 sumps (EQ# 318) Red jacket STP¿s, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) OPW Pisces DS1242 dispenser liners, EQ# 318 Existing overfill protection (Ball floats)
Comments:
Comment Date: 06/11/2007 User: JARRETT_SE
Description: 06/07/2007 Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252).
Comments:
Comment Date: 04/24/2008 User: JARRETT_SE
Description: 04/10/2008 Release Detection: - Tanks: Veeder Root TLS 350 Continuous Statistical Leak Detection (CSLD) (DEP EQ # 033) with continuous automatic tank gauging - Piping: Electronic (PLLD) line leak detectors (DEP EQ # 271) with monthly PLLD 0.2 gallons per hour (gph) line leak test and annual 3 gph leak tests; - Visual inspections of STP manways, dispensers/liners and spill containment buckets; - Veeder Root TLS-350 panel checked - monitors the CSLD & PLLD 0.2 gph tests; Tanks/STP Manways/Piping: (3) Single-walled, fiberglass USTs {(12,000-gallon (Regular), 10,000-gallon (Premium) and 6,000-gallon (Plus)}. Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252). Tanks are equipped with: - (3) STP manways;
03/05/2003 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 610(4)(c)
Comments:
Comment Date: 03/31/2021 User: ROJAS_Y_1
Description: Release Detection: Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) Red jacket STPs, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Tank: Phoenix Parabeam double walled system (EQ# 403) with Smith Red Thread IIA double walled piping (EQ# 252) and STP OPW Pisces TSDF 4536 sumps (EQ# 318) - Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) - Overfill Protection: Flow shut off valves (unknown make/model/EQ #) OPW Pisces DS1242 dispenser liners, EQ# 318
Comments:
Comment Date: 09/21/2010 User: DIAZ_HZ_1
Description: Phoenix Parabeam double walled system (EQ# 403) Smith Red Thread IIA double walled piping (EQ# 252) Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) STP OPW Pisces TSDF 4536 sumps (EQ# 318) Red jacket STP¿s, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) OPW Pisces DS1242 dispenser liners, EQ# 318 Existing overfill protection (Ball floats)
Comments:
Comment Date: 06/11/2007 User: JARRETT_SE
Description: 06/07/2007 Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252).
Comments:
Comment Date: 04/24/2008 User: JARRETT_SE
Description: 04/10/2008 Release Detection: - Tanks: Veeder Root TLS 350 Continuous Statistical Leak Detection (CSLD) (DEP EQ # 033) with continuous automatic tank gauging - Piping: Electronic (PLLD) line leak detectors (DEP EQ # 271) with monthly PLLD 0.2 gallons per hour (gph) line leak test and annual 3 gph leak tests; - Visual inspections of STP manways, dispensers/liners and spill containment buckets; - Veeder Root TLS-350 panel checked - monitors the CSLD & PLLD 0.2 gph tests; Tanks/STP Manways/Piping: (3) Single-walled, fiberglass USTs {(12,000-gallon (Regular), 10,000-gallon (Premium) and 6,000-gallon (Plus)}. Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252). Tanks are equipped with: - (3) STP manways;
03/05/2003 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 610(4)(c)
Comments:
Comment Date: 03/31/2021 User: ROJAS_Y_1
Description: Release Detection: Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) Red jacket STPs, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Tank: Phoenix Parabeam double walled system (EQ# 403) with Smith Red Thread IIA double walled piping (EQ# 252) and STP OPW Pisces TSDF 4536 sumps (EQ# 318) - Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) - Overfill Protection: Flow shut off valves (unknown make/model/EQ #) OPW Pisces DS1242 dispenser liners, EQ# 318
Comments:
Comment Date: 09/21/2010 User: DIAZ_HZ_1
Description: Phoenix Parabeam double walled system (EQ# 403) Smith Red Thread IIA double walled piping (EQ# 252) Veeder Root TLS 350 Simplicity (EQ # 197) with Veeder Root sensors (EQ# 614) STP OPW Pisces TSDF 4536 sumps (EQ# 318) Red jacket STP¿s, FK1V (Gas) and FX1DV (Diesel) mechanical leak detectors (EQ# 373) Emco Wheaton A1004 double spill containment buckets (DEP EQ# 594) OPW Pisces DS1242 dispenser liners, EQ# 318 Existing overfill protection (Ball floats)
Comments:
Comment Date: 06/11/2007 User: JARRETT_SE
Description: 06/07/2007 Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252).
Comments:
Comment Date: 04/24/2008 User: JARRETT_SE
Description: 04/10/2008 Release Detection: - Tanks: Veeder Root TLS 350 Continuous Statistical Leak Detection (CSLD) (DEP EQ # 033) with continuous automatic tank gauging - Piping: Electronic (PLLD) line leak detectors (DEP EQ # 271) with monthly PLLD 0.2 gallons per hour (gph) line leak test and annual 3 gph leak tests; - Visual inspections of STP manways, dispensers/liners and spill containment buckets; - Veeder Root TLS-350 panel checked - monitors the CSLD & PLLD 0.2 gph tests; Tanks/STP Manways/Piping: (3) Single-walled, fiberglass USTs {(12,000-gallon (Regular), 10,000-gallon (Premium) and 6,000-gallon (Plus)}. Underground piping is A.O. Smith, single-walled, fiberglass piping (DEP EQ # 252). Tanks are equipped with: - (3) STP manways;
05/28/2002 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 450(1)b
05/28/2002 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
05/28/2002 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 820(1)(a),(b),(c)
05/28/2002 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 640(3)(c)4
10/17/2001 Legacy Activity Lubinski, David R.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
05/10/2001 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 450(1)b
05/10/2001 Violation Closed Kassees, Ramsey D.
Significance: SNC-B Status: Closed
Rule: 500(2)(d)2
05/10/2001 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Rule: 640(3)(d)
05/10/2001 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
08/09/1999 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed