Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 04/30/2025 Last Data Refresh: 04/29/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 9300330 | ||||||||||
Facility Name: | LONG GROVE | ||||||||||
11/06/2024 | Enforcement Tracking Activity | Cerquera, Lina | |||||||||
Activity Status: | Open | ||||||||||
08/17/2022 | Electronic Communication Activity | Parks, Jeff S | |||||||||
Activity Closed Date: | 08/17/2022 | Activity Status: | Closed | ||||||||
Date: | 08/17/2022 | ||||||||||
Recipient: | Jeff Parks | ||||||||||
Sender: | Kathy Walker | ||||||||||
Subject: | 9300330 and 9602364 | ||||||||||
Message: |
K. Walker sent the insurance document showing that two sites have been added to the policy. |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/17/2022 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 08/17/2022 | User: | PARKS_J_4 | ||||||||
Description: | Policy addendum | ||||||||||
View Attachment | |||||||||||
08/15/2022 | Violation Open | Parks, Jeff S | |||||||||
Significance: | SNC-A | Status: | Open | ||||||||
Criteria ID: | 7010 | ||||||||||
Rule: | 62-762.421(2), 62-762.421(3)(c) | ||||||||||
08/15/2022 | Electronic Communication Activity | Parks, Jeff S | |||||||||
Activity Closed Date: | 08/15/2022 | Activity Status: | Closed | ||||||||
Date: | 08/15/2022 | ||||||||||
Recipient: | Jeff Parks | ||||||||||
Sender: | Kathy Walker | ||||||||||
Subject: | Tank Compliance | ||||||||||
Message: | See attached email. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/15/2022 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 08/15/2022 | User: | PARKS_J_4 | ||||||||
Description: | |||||||||||
View Attachment | |||||||||||
08/15/2022 | Electronic Communication Activity | Parks, Jeff S | |||||||||
Activity Closed Date: | 08/15/2022 | Activity Status: | Closed | ||||||||
Date: | 08/15/2022 | ||||||||||
Recipient: | Jeff Parks | ||||||||||
Sender: | Eugene Turner | ||||||||||
Subject: | Email Chain regarding inspection scheduling. | ||||||||||
Message: | Email chain attached. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/15/2022 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 08/15/2022 | User: | PARKS_J_4 | ||||||||
Description: | Scheduling email chain | ||||||||||
View Attachment | |||||||||||
08/15/2022 | Enforcement Referral Activity | Parks, Jeff S | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 11/06/2024 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 08/15/2022 | ||||||||
Comment: | Submitted for approval by: Jeff S Parks: This facility is referred for enforcement per division guidance for no CFR greater than 180 days. | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 01/24/2023 | ||||||||
Comment: | Acknowledged and Assigned by Ryan B Snyder | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 01/24/2023 | ||||||||
Comment: | Assigned to Lina Cerquera | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 11/06/2024 | ||||||||
Comment: | Accepted by Lina Cerquera: Colin, please assess referral. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 11/06/2024 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/15/2022 | User: | PARKS_J_4 | ||||||||
Description: | This facility is referred for enforcement per division guidance for no CFR greater than 180 days. | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 08/15/2022 | User: | PARKS_J_4 | ||||||||
Description: | Compliance G | ||||||||||
View Attachment | |||||||||||
08/10/2022 | Site Inspection Activity Closed | Parks, Jeff S | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/10/2022 | ||||||||||
Activity Closed Date: | 08/15/2022 | Activity Closed By: | PARKS_J_4 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/15/2022 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/15/2022 | User: | PARKS_J_4 | ||||||||
Description: | Jeff Parks from Lee County met with your facility representative to conduct the Compliance Inspection of a non-retail fuel tank. TANKS: Consists of one (1) 2,000-gallon diesel, aboveground tank. Tank coating appears to be in satisfactory condition. No dripping/leaking issues were observed during the inspection. The tank interstice is manually sticked on a monthly basis and documented. Verified to be dry at time of inspection. SPILL CONTAINMENT: - Single-walled (SW) spill bucket mounted on top of the tank, with a drain valve that goes directly into the tank. The tank is set into concrete secondary containment. OVERFILL PROTECTION: – The vents are present and observed to be in satisfactory condition. Overfill protection consists of visual observation and sticking. PIPING – There is no piping associated with the system, except for the supply and return lines which are flexible hoses connected directly to the generator. No anti-siphon or solenoid valve is required, the generator rests on top of the tank and is not producing a gravity head. RELEASE DETECTION: The facility conducts monthly visual inspections of visible/exposed tank components including: piping, tank coating, sumps, spill containment buckets. The visual and audible alarm panels were checked and found to be functioning properly. The tank interstice is manually stick in a monthly basis and documented. The tank interstitial was verified to be dry at time of inspection PLACARD: The Placard expiration date is: June 30, 2023. Storage tank registration fees are due to the Department each year by July 1. Ensure that your contact information is up-to-date with the Department in order to receive updates concerning your annual registration fees. Once fees are paid, you must print a copy of your placard from the Department's website: http://www.fldepportal.com/go/submit-registration/. RECORDS SHALL BE KEPT FOR THREE YEARS IN ACCORDANCE WITH RULE 62-761.710, F.A.C. Inspection Report sent by e-mail to: kwalker@turnerrealty.com | ||||||||||
03/13/2020 | Editable Letter Activity | Sautter, Mark Allen | |||||||||
Activity Title: | In Compliance Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/13/2020 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 03/13/2020 | User: | SAUTTER_MA_2 | ||||||||
Description: | ICL for inspection conducted on 03/09/2020 | ||||||||||
View Attachment | |||||||||||
03/09/2020 | Site Inspection Activity Closed | Sautter, Mark Allen | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 03/09/2020 | ||||||||||
Activity Closed Date: | 03/13/2020 | Activity Closed By: | SAUTTER_MA_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/13/2020 | ||||||||
Comment: | Finished | ||||||||||
03/04/2020 | Phone Conversation Activity | Sautter, Mark Allen | |||||||||
Call Type: | Outgoing | Activity Status: | Closed | ||||||||
Phone Number: | (863) 244-3879 | Activity Closed Date: | 03/04/2020 | ||||||||
Subject: | Spoke with Brian Harms regarding inspections next week | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/04/2020 | ||||||||
Comment: | Finished | ||||||||||
03/04/2020 | Electronic Communication Activity | Sautter, Mark Allen | |||||||||
Activity Closed Date: | 03/04/2020 | Activity Status: | Closed | ||||||||
Date: | 03/04/2020 | ||||||||||
Recipient: | Trey Turner | ||||||||||
Sender: | Mark Sautter | ||||||||||
Subject: | Inspection Scheduling | ||||||||||
Message: | Hi Trey Hi Mac, I have come across a few more Turner properties and would like to get out to see these next week sometime. Please let me know if there are some especially good (or bad) times to get out there: 9602364 Watkins Eagle – Bobay Road; 9400001 Turner E H Family, Ltd-NE 1 - S. Arcadia Avenue; and 9300330 Long Grove – Hwy 70, 7 miles east of Arcadia. Please let me know whether you’re the contact for any of these properties. Thanks, Mark A. Sautter Environmental Specialist, Senior Lee County Division of Natural Resources Pollutant Storage Tank Program 239-533-8195 – office 239-703-6566 – cell msautter@leegov.com | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 03/04/2020 | ||||||||
Comment: | Finished | ||||||||||
08/16/2017 | Site Inspection Activity Closed | Zimmerman, Chris A. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/16/2017 | ||||||||||
Activity Closed Date: | 08/17/2017 | Activity Closed By: | ZIMMERMAN_CA_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/17/2017 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/16/2017 | User: | ZIMMERMAN_CA_1 | ||||||||
Description: | Checked required documentation (Visuals, insurance, maintenance records, etc..) along with required storage tank components (Tanks, lines, spill buckets, hoses, etc...) Updated registration info as needed. Alarm/Maintenance History: Nothing significant to note. | ||||||||||
08/20/2015 | Attachment | Zimmerman, Chris A. | |||||||||
08/19/2015 | Comment | Zimmerman, Chris A. | |||||||||
Description: | Facility has a SW 2000 gal tank inside of a containment area. line are equipped with manual shut off valves and anti-siphon valves. Containment area dimension: 180" x 133 " x 32" = 3316 gal | ||||||||||
08/19/2015 | Site Inspection Activity Closed | Zimmerman, Chris A. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/19/2015 | ||||||||||
Activity Closed Date: | 08/20/2015 | Activity Closed By: | ZIMMERMAN_CA_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/20/2015 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/19/2015 | User: | ZIMMERMAN_CA_1 | ||||||||
Description: | Checked required documentation (RDRL, Visuals, insurance, maintenance records, etc..) along with required storage tank components (Tanks, lines, spill buckets, hoses, etc...) Updated registration info as needed. Alarm/Maintenance History: Nothing significant to note. Containment area dimension: 180" x 133 " x 32" = 3316 gal | ||||||||||
08/19/2015 | Attachment | Zimmerman, Chris A. | |||||||||
08/11/2011 | Site Inspection Activity Closed | Durrance, William K. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/11/2011 | ||||||||||
Activity Closed Date: | 08/11/2011 | Activity Closed By: | DURRANCE_WK_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/11/2011 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 08/11/2011 | User: | DURRANCE_WK_1 | ||||||||
Description: | 1-2,000 gallon AST located inside secondary containment. Using manual stick for overfill protection Using monthly visual inspection for release detection CFR+FR-satisfactory Placard-satisfactory RDRL-satisfactory Monthly inspections-Satisfactory Tank and containment-satisfactory hoses and valves-satisfactory No evidence of discharge. | ||||||||||
05/24/2011 | Site Inspection Activity Closed | Durrance, William K. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 05/24/2011 | ||||||||||
Activity Closed Date: | 05/24/2011 | Activity Closed By: | DURRANCE_WK_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 05/24/2011 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 05/24/2011 | User: | DURRANCE_WK_1 | ||||||||
Description: | 1-2,000 gallon AST located inside secondary containment. Using manual stick for overfill protection Using monthly visual inspection for release detection CFR+FR-satisfactory Placard-satisfactory RDRL-satisfactory Monthly inspections-Satisfactory Tank and containment-satisfactory hoses and valves-satisfactory No evidence of discharge. | ||||||||||
01/08/2010 | Site Inspection Activity Closed | Durrance, William K. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 01/08/2010 | ||||||||||
Activity Closed Date: | 01/08/2010 | Activity Closed By: | DURRANCE_WK_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/08/2010 | ||||||||
Comment: | Finished | ||||||||||
Comments: | |||||||||||
Comment Date: | 01/08/2010 | User: | DURRANCE_WK_1 | ||||||||
Description: | 1-2,000 gallon AST located inside secondary containment. Using manual stick for overfill protection Using monthly visual inspection for release detection CFR+FR-satisfactory Placard-satisfactory RDRL-satisfactory Monthly inspections-Satisfactory Tank and containment-satisfactory hoses and valves-satisfactory No evidence of discharge. | ||||||||||
11/19/2008 | Site Inspection Activity Closed | Durrance, William K. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 11/19/2008 | ||||||||||
Activity Closed Date: | 11/19/2008 | Activity Closed By: | DURRANCE_WK_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 11/19/2008 | User: | DURRANCE_WK_1 | ||||||||
Description: | 1-2,000 gallon AST located inside secondary containment Using manual stick for overfill protection Using monthly visual inspection for release detection CFR+FR-satisfactory exp. 12/31/08 RDRL-satisfactory Placard-satisfactory exp. 6/30/09 Monthly inspections-satisfactory Tank-satisfactory Containment area-satisfactory piping and valves-satisfactory No evidence of discharge. | ||||||||||
09/21/2007 | Site Inspection Activity Closed | Durrance, William K. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 09/21/2007 | ||||||||||
Activity Closed Date: | 09/21/2007 | Activity Closed By: | DURRANCE_WK_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 09/21/2007 | User: | DURRANCE_WK_1 | ||||||||
Description: | 1-2,000 gal AST located inside secondary containment. Using manual stick for overfill protection. Using monthly visual inspection for release detection. CFR-self insured exp 12/31/07 RDRL-satisfactory Placard-satisfactory-exp. 6/30/07 Monthly inspections reviewed 10/30/05-8/30/07 Tank-satisfactory Containment-satisfactory Valves and piping-satisfactory No evidence of discharge. | ||||||||||
11/08/2006 | Attachment | Durrance, William K. | |||||||||
10/19/2006 | Site Inspection Activity Closed | Durrance, William K. | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 10/19/2006 | ||||||||||
Activity Closed Date: | 10/19/2006 | Activity Closed By: | DURRANCE_WK_1 | ||||||||
Comments: | |||||||||||
Comment Date: | 10/19/2006 | User: | DURRANCE_WK_1 | ||||||||
Description: | 1 2,000 gal AST located inside secondary containment. Using manual stick for overfill protection. Using monthly visual inspection for release detection. CFR+FR,Placard,RDRL,and monthly inspections-OK. Tank,valves, and containment-OK. No evidence of discharge. | ||||||||||
10/17/2005 | Legacy Activity | Durrance, William K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
03/17/2005 | Legacy Activity | Keene, Keith K. | |||||||||
Activity Name: | TANK COMPLIANCE RE-INSPECTION | Activity Status: | Closed | ||||||||
01/27/2005 | Violation Closed | Keene, Keith K. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 762.701(1)(a)1 | ||||||||||
01/27/2005 | Legacy Activity | Keene, Keith K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
10/30/2003 | Violation Closed | Keene, Keith K. | |||||||||
Significance: | Minor | Status: | Closed | ||||||||
Rule: | 510(1)(d) | ||||||||||
10/30/2003 | Legacy Activity | Keene, Keith K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
01/25/2003 | Legacy Activity | Keene, Keith K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
02/27/2002 | Legacy Activity | Keene, Keith K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
01/17/2001 | Legacy Activity | Keene, Keith K. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||
01/21/2000 | Legacy Activity | Joyce, Thomas A. | |||||||||
Activity Name: | TANK ANNUAL COMPLIANCE INSPECTION | Activity Status: | Closed | ||||||||