DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/30/2025        Last Data Refresh: 04/29/2025        Report Generated from DOPPLER
 
Facility ID: 9300330
Facility Name: LONG GROVE
 
11/06/2024 Enforcement Tracking Activity Cerquera, Lina
Activity Status: Open
08/17/2022 Electronic Communication Activity Parks, Jeff S
Activity Closed Date: 08/17/2022 Activity Status: Closed
Date: 08/17/2022
Recipient: Jeff Parks
Sender: Kathy Walker
Subject: 9300330 and 9602364
Message: K. Walker sent the insurance document showing that two sites have been added to the policy.
Events:
Event Type: Activity has been finished Date: 08/17/2022
Comment: Finished
Attachments:
Attachment Date: 08/17/2022 User: PARKS_J_4
Description: Policy addendum
View Attachment
08/15/2022 Violation Open Parks, Jeff S
Significance: SNC-A Status: Open
Criteria ID: 7010
Rule: 62-762.421(2), 62-762.421(3)(c)
08/15/2022 Electronic Communication Activity Parks, Jeff S
Activity Closed Date: 08/15/2022 Activity Status: Closed
Date: 08/15/2022
Recipient: Jeff Parks
Sender: Kathy Walker
Subject: Tank Compliance
Message: See attached email.
Events:
Event Type: Activity has been finished Date: 08/15/2022
Comment: Finished
Attachments:
Attachment Date: 08/15/2022 User: PARKS_J_4
Description: email
View Attachment
08/15/2022 Electronic Communication Activity Parks, Jeff S
Activity Closed Date: 08/15/2022 Activity Status: Closed
Date: 08/15/2022
Recipient: Jeff Parks
Sender: Eugene Turner
Subject: Email Chain regarding inspection scheduling.
Message: Email chain attached.
Events:
Event Type: Activity has been finished Date: 08/15/2022
Comment: Finished
Attachments:
Attachment Date: 08/15/2022 User: PARKS_J_4
Description: Scheduling email chain
View Attachment
08/15/2022 Enforcement Referral Activity Parks, Jeff S
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 11/06/2024
Events:
Event Type: Activity has been submitted for approval Date: 08/15/2022
Comment: Submitted for approval by: Jeff S Parks: This facility is referred for enforcement per division guidance for no CFR greater than 180 days.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 01/24/2023
Comment: Acknowledged and Assigned by Ryan B Snyder
Events:
Event Type: Activity has been assigned Date: 01/24/2023
Comment: Assigned to Lina Cerquera
Events:
Event Type: Activity/Document was accepted on this date Date: 11/06/2024
Comment: Accepted by Lina Cerquera: Colin, please assess referral.
Events:
Event Type: Activity has been finished Date: 11/06/2024
Comment: Finished
Comments:
Comment Date: 08/15/2022 User: PARKS_J_4
Description: This facility is referred for enforcement per division guidance for no CFR greater than 180 days.
Attachments:
Attachment Date: 08/15/2022 User: PARKS_J_4
Description: Compliance G
View Attachment
08/10/2022 Site Inspection Activity Closed Parks, Jeff S
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 08/10/2022
Activity Closed Date: 08/15/2022 Activity Closed By: PARKS_J_4
Events:
Event Type: Activity has been finished Date: 08/15/2022
Comment: Finished
Comments:
Comment Date: 08/15/2022 User: PARKS_J_4
Description: Jeff Parks from Lee County met with your facility representative to conduct the Compliance Inspection of a non-retail fuel tank. TANKS: Consists of one (1) 2,000-gallon diesel, aboveground tank. Tank coating appears to be in satisfactory condition. No dripping/leaking issues were observed during the inspection. The tank interstice is manually sticked on a monthly basis and documented. Verified to be dry at time of inspection. SPILL CONTAINMENT: - Single-walled (SW) spill bucket mounted on top of the tank, with a drain valve that goes directly into the tank. The tank is set into concrete secondary containment. OVERFILL PROTECTION: – The vents are present and observed to be in satisfactory condition. Overfill protection consists of visual observation and sticking. PIPING – There is no piping associated with the system, except for the supply and return lines which are flexible hoses connected directly to the generator. No anti-siphon or solenoid valve is required, the generator rests on top of the tank and is not producing a gravity head. RELEASE DETECTION: The facility conducts monthly visual inspections of visible/exposed tank components including: piping, tank coating, sumps, spill containment buckets. The visual and audible alarm panels were checked and found to be functioning properly. The tank interstice is manually stick in a monthly basis and documented. The tank interstitial was verified to be dry at time of inspection PLACARD: The Placard expiration date is: June 30, 2023. Storage tank registration fees are due to the Department each year by July 1. Ensure that your contact information is up-to-date with the Department in order to receive updates concerning your annual registration fees. Once fees are paid, you must print a copy of your placard from the Department's website: http://www.fldepportal.com/go/submit-registration/. RECORDS SHALL BE KEPT FOR THREE YEARS IN ACCORDANCE WITH RULE 62-761.710, F.A.C. Inspection Report sent by e-mail to: kwalker@turnerrealty.com
03/13/2020 Editable Letter Activity Sautter, Mark Allen
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/13/2020
Comment: Finished
Attachments:
Attachment Date: 03/13/2020 User: SAUTTER_MA_2
Description: ICL for inspection conducted on 03/09/2020
View Attachment
03/09/2020 Site Inspection Activity Closed Sautter, Mark Allen
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/09/2020
Activity Closed Date: 03/13/2020 Activity Closed By: SAUTTER_MA_2
Events:
Event Type: Activity has been finished Date: 03/13/2020
Comment: Finished
03/04/2020 Phone Conversation Activity Sautter, Mark Allen
Call Type: Outgoing Activity Status: Closed
Phone Number: (863) 244-3879 Activity Closed Date: 03/04/2020
Subject: Spoke with Brian Harms regarding inspections next week
Events:
Event Type: Activity has been finished Date: 03/04/2020
Comment: Finished
03/04/2020 Electronic Communication Activity Sautter, Mark Allen
Activity Closed Date: 03/04/2020 Activity Status: Closed
Date: 03/04/2020
Recipient: Trey Turner
Sender: Mark Sautter
Subject: Inspection Scheduling
Message: Hi Trey Hi Mac, I have come across a few more Turner properties and would like to get out to see these next week sometime. Please let me know if there are some especially good (or bad) times to get out there: 9602364 Watkins Eagle – Bobay Road; 9400001 Turner E H Family, Ltd-NE 1 - S. Arcadia Avenue; and 9300330 Long Grove – Hwy 70, 7 miles east of Arcadia. Please let me know whether you’re the contact for any of these properties. Thanks, Mark A. Sautter Environmental Specialist, Senior Lee County Division of Natural Resources Pollutant Storage Tank Program 239-533-8195 – office 239-703-6566 – cell msautter@leegov.com
Events:
Event Type: Activity has been finished Date: 03/04/2020
Comment: Finished
08/16/2017 Site Inspection Activity Closed Zimmerman, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/16/2017
Activity Closed Date: 08/17/2017 Activity Closed By: ZIMMERMAN_CA_1
Events:
Event Type: Activity has been finished Date: 08/17/2017
Comment: Finished
Comments:
Comment Date: 08/16/2017 User: ZIMMERMAN_CA_1
Description: Checked required documentation (Visuals, insurance, maintenance records, etc..) along with required storage tank components (Tanks, lines, spill buckets, hoses, etc...) Updated registration info as needed. Alarm/Maintenance History: Nothing significant to note.
08/20/2015 Attachment Zimmerman, Chris A.
08/19/2015 Comment Zimmerman, Chris A.
Description: Facility has a SW 2000 gal tank inside of a containment area. line are equipped with manual shut off valves and anti-siphon valves. Containment area dimension: 180" x 133 " x 32" = 3316 gal
08/19/2015 Site Inspection Activity Closed Zimmerman, Chris A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/19/2015
Activity Closed Date: 08/20/2015 Activity Closed By: ZIMMERMAN_CA_1
Events:
Event Type: Activity has been finished Date: 08/20/2015
Comment: Finished
Comments:
Comment Date: 08/19/2015 User: ZIMMERMAN_CA_1
Description: Checked required documentation (RDRL, Visuals, insurance, maintenance records, etc..) along with required storage tank components (Tanks, lines, spill buckets, hoses, etc...) Updated registration info as needed. Alarm/Maintenance History: Nothing significant to note. Containment area dimension: 180" x 133 " x 32" = 3316 gal
08/19/2015 Attachment Zimmerman, Chris A.
08/11/2011 Site Inspection Activity Closed Durrance, William K.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/11/2011
Activity Closed Date: 08/11/2011 Activity Closed By: DURRANCE_WK_1
Events:
Event Type: Activity has been finished Date: 08/11/2011
Comment: Finished
Comments:
Comment Date: 08/11/2011 User: DURRANCE_WK_1
Description: 1-2,000 gallon AST located inside secondary containment. Using manual stick for overfill protection Using monthly visual inspection for release detection CFR+FR-satisfactory Placard-satisfactory RDRL-satisfactory Monthly inspections-Satisfactory Tank and containment-satisfactory hoses and valves-satisfactory No evidence of discharge.
05/24/2011 Site Inspection Activity Closed Durrance, William K.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/24/2011
Activity Closed Date: 05/24/2011 Activity Closed By: DURRANCE_WK_1
Events:
Event Type: Activity has been finished Date: 05/24/2011
Comment: Finished
Comments:
Comment Date: 05/24/2011 User: DURRANCE_WK_1
Description: 1-2,000 gallon AST located inside secondary containment. Using manual stick for overfill protection Using monthly visual inspection for release detection CFR+FR-satisfactory Placard-satisfactory RDRL-satisfactory Monthly inspections-Satisfactory Tank and containment-satisfactory hoses and valves-satisfactory No evidence of discharge.
01/08/2010 Site Inspection Activity Closed Durrance, William K.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/08/2010
Activity Closed Date: 01/08/2010 Activity Closed By: DURRANCE_WK_1
Events:
Event Type: Activity has been finished Date: 01/08/2010
Comment: Finished
Comments:
Comment Date: 01/08/2010 User: DURRANCE_WK_1
Description: 1-2,000 gallon AST located inside secondary containment. Using manual stick for overfill protection Using monthly visual inspection for release detection CFR+FR-satisfactory Placard-satisfactory RDRL-satisfactory Monthly inspections-Satisfactory Tank and containment-satisfactory hoses and valves-satisfactory No evidence of discharge.
11/19/2008 Site Inspection Activity Closed Durrance, William K.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/19/2008
Activity Closed Date: 11/19/2008 Activity Closed By: DURRANCE_WK_1
Comments:
Comment Date: 11/19/2008 User: DURRANCE_WK_1
Description: 1-2,000 gallon AST located inside secondary containment Using manual stick for overfill protection Using monthly visual inspection for release detection CFR+FR-satisfactory exp. 12/31/08 RDRL-satisfactory Placard-satisfactory exp. 6/30/09 Monthly inspections-satisfactory Tank-satisfactory Containment area-satisfactory piping and valves-satisfactory No evidence of discharge.
09/21/2007 Site Inspection Activity Closed Durrance, William K.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 09/21/2007
Activity Closed Date: 09/21/2007 Activity Closed By: DURRANCE_WK_1
Comments:
Comment Date: 09/21/2007 User: DURRANCE_WK_1
Description: 1-2,000 gal AST located inside secondary containment. Using manual stick for overfill protection. Using monthly visual inspection for release detection. CFR-self insured exp 12/31/07 RDRL-satisfactory Placard-satisfactory-exp. 6/30/07 Monthly inspections reviewed 10/30/05-8/30/07 Tank-satisfactory Containment-satisfactory Valves and piping-satisfactory No evidence of discharge.
11/08/2006 Attachment Durrance, William K.
10/19/2006 Site Inspection Activity Closed Durrance, William K.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/19/2006
Activity Closed Date: 10/19/2006 Activity Closed By: DURRANCE_WK_1
Comments:
Comment Date: 10/19/2006 User: DURRANCE_WK_1
Description: 1 2,000 gal AST located inside secondary containment. Using manual stick for overfill protection. Using monthly visual inspection for release detection. CFR+FR,Placard,RDRL,and monthly inspections-OK. Tank,valves, and containment-OK. No evidence of discharge.
10/17/2005 Legacy Activity Durrance, William K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
03/17/2005 Legacy Activity Keene, Keith K.
Activity Name: TANK COMPLIANCE RE-INSPECTION Activity Status: Closed
01/27/2005 Violation Closed Keene, Keith K.
Significance: Minor Status: Closed
Rule: 762.701(1)(a)1
01/27/2005 Legacy Activity Keene, Keith K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
10/30/2003 Violation Closed Keene, Keith K.
Significance: Minor Status: Closed
Rule: 510(1)(d)
10/30/2003 Legacy Activity Keene, Keith K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/25/2003 Legacy Activity Keene, Keith K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/27/2002 Legacy Activity Keene, Keith K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/17/2001 Legacy Activity Keene, Keith K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/21/2000 Legacy Activity Joyce, Thomas A.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed