Facility ID: 9700961
Facility Name: LOWER KEYS MEDICAL CTR - DE POO HOSPITAL
 
03/27/2025 Site Inspection Activity Open Forrest, Caleb
Activity Status: Open
On-Site Start Date: 03/26/2025
11/20/2024 Violation Open Forrest, Caleb
Significance: Minor Status: Open
Criteria ID: 6062
Rule: 62-761.600(4)
10/23/2024 Violation Open Forrest, Caleb
Significance: Minor Status: Open
Criteria ID: 6072
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1, 62-761.700(3)(a)1.a, 62-761.700(3)(a)1.b, 62-761.700(3)(a)1.c, 62-761.700(3)(a)1.d, 62-761.700(3)(a)1.e, 62-761.700(3)(a)1.f, 62-761.700(3)(a)1.g, 62-761.700(3)(a)2
10/23/2024 Violation Open Forrest, Caleb
Significance: Minor Status: Open
Criteria ID: 7002
Rule: 62-762.401(1)(b), 62-762.401(2), 62-762.401(3), 62-762.401(3)(a), 62-762.401(3)(b), 62-762.401(3)(c)
10/21/2024 Site Inspection Activity Closed Forrest, Caleb
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 10/21/2024
Activity Closed Date: 11/25/2024 Activity Closed By: FORREST_C
Events:
Event Type: Activity has been finished Date: 11/25/2024
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 10/24/2024
Comment: Submitted for approval by: Caleb Forrest
Events:
Event Type: Activity has not been approved Date: 11/04/2024
Comment: Not approved by M'Liss Bordelon: not approved
09/18/2024 Enforcement Referral Activity Dolan, Judy F.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 09/18/2024
Events:
Event Type: Activity has been assigned Date: 09/18/2024
Comment: Assigned to Judy F. Dolan
Events:
Event Type: Activity has been submitted for approval Date: 09/18/2024
Comment: Submitted for approval by: Judy F. Dolan: Refer to enforcement.
Events:
Event Type: Activity has been finished Date: 09/18/2024
Comment: Finished
Events:
Event Type: Activity/Document was acknowledged on this date Date: 09/18/2024
Comment: Acknowledged and Assigned by Judy F. Dolan
Events:
Event Type: Activity/Document was accepted on this date Date: 09/18/2024
Comment: Accepted by Judy F. Dolan: approved
Comments:
Comment Date: 09/18/2024 User: DOLAN_J
Description: Refer to enforcement.
09/18/2024 Enforcement Tracking Activity Dolan, Judy F.
Activity Status: Open
05/24/2022 Editable Letter Activity Cumbie, Brian
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/01/2022
Comment: Finished
Events:
Event Type: Document has been sent Date: 05/27/2022
Comment: Sent
Attachments:
Attachment Date: 06/01/2022 User: CUMBIE_B
Description: 9700961 Lower Keys Medical Ctr - De Poo Hospital
View Attachment
11/14/2021 Violation Closed Cumbie, Brian
Significance: SNC-B Status: Closed
Criteria ID: 6042
Rule: 62-761.500(4)(a)
11/04/2021 Violation Closed Cumbie, Brian
Significance: Minor Status: Closed
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
11/04/2021 Site Inspection Activity Closed Marconi, Erica L
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 11/04/2021
Activity Closed Date: 05/24/2022 Activity Closed By: CUMBIE_B
Events:
Event Type: Activity/Document has been approved Date: 05/24/2022
Comment: Approved by Brian Cumbie: Approved.
Events:
Event Type: Activity has been submitted for approval Date: 05/24/2022
Comment: Submitted for approval by: Brian Cumbie
Events:
Event Type: Activity has been finished Date: 05/24/2022
Comment: Finished
Comments:
Comment Date: 11/04/2021 User: MARCONI_E
Description: A Routine Compliance Inspection was conducted on November 4, 2021. This facility has one (1) 1,000-gallon DSL underground storage tank (UST) that fuels a day tank servicing an Emergency Generator and one (1) 2,190-gallons sub-base Emergency Generator. Required documentation has been reviewed; Tank components have been inspected; Dispenser shear valves and liners have been inspected. Violations have been cited in this report. Note: 2020 testing was rescheduled due to COVID and change in facility personnel. 2021 is currently being scheduled; no documentation has been received to date. The following is a recommend Best Management Practice: • Use the monthly checklists (attached to the follow-up email sent on 11/5/2021) as they cover all the components of the tank systems to be visually inspected every month. Recommend completing a tank registration form to update the contact name, email, and phone number. A copy of the report will be sent via email to Jimmy Bass (Jimmy.Bass@lkmc.com), Ryan Rumbaugh (ryan.rumbaugh@lkmc.com) and Adriana Carroll (adriana.carroll@lkmc.com).
11/04/2021 Violation Closed Cumbie, Brian
Significance: SNC-A Status: Closed
Criteria ID: 6012
Rule: 62-761.420(2)
Attachments:
Attachment Date: 10/23/2024 User: FORREST_C
Description: 9700961 Financial Responsibility Certificate
View Attachment
11/04/2021 Violation Closed Cumbie, Brian
Significance: Minor Status: Closed
Criteria ID: 6002
Rule: 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2, 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7)
Attachments:
Attachment Date: 10/23/2024 User: FORREST_C
Description: 9700961 Operator Certifications
View Attachment
11/04/2021 Violation Open Cumbie, Brian
Significance: Minor Status: Open
Criteria ID: 6072
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1, 62-761.700(3)(a)1.a, 62-761.700(3)(a)1.b, 62-761.700(3)(a)1.c, 62-761.700(3)(a)1.d, 62-761.700(3)(a)1.e, 62-761.700(3)(a)1.f, 62-761.700(3)(a)1.g, 62-761.700(3)(a)2
11/04/2021 Violation Closed Cumbie, Brian
Significance: Minor Status: Closed
Criteria ID: 7072
Rule: 62-762.601(7), 62-762.602(7)
Attachments:
Attachment Date: 10/23/2024 User: FORREST_C
Description: 9700961 Release Detection AOT 2022
View Attachment
Attachments:
Attachment Date: 10/23/2024 User: FORREST_C
Description: 9700961 Release Detection AOT 2021
View Attachment
Attachments:
Attachment Date: 10/23/2024 User: FORREST_C
Description: 9700961 Release Detection AOT 2023
View Attachment
11/04/2021 Violation Closed Cumbie, Brian
Significance: Minor Status: Closed
Criteria ID: 7041
Rule: 62-762.501(2)(e)3, 62-762.501(2)(e)3.a, 62-762.501(2)(e)3.b, 62-762.501(2)(e)4, 62-762.502(2)(e)4, 62-762.502(2)(e)4.a, 62-762.502(2)(e)4.b, 62-762.502(2)(e)5
11/19/2019 Record Document Activity Winkler, Michael G.
Activity Status: Closed
Contact Name: James Dunscomb Activity Closed Date: 11/19/2019
Events:
Event Type: Activity has been finished Date: 11/19/2019
Comment: Finished
11/19/2019 Editable Letter Activity Winkler, Michael G.
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 11/19/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 11/19/2019
Comment: Finished
Attachments:
Attachment Date: 11/19/2019 User: WINKLER_MG_1
Description: 2019-11-19 RTC sent to James Dunscomb
View Attachment
07/11/2019 Violation Closed Winkler, Michael G.
Significance: SNC-B Status: Closed
Criteria ID: 5042
Rule: 62-762.501(2)(e), 62-762.501(2)(e)1., 62-762.501(2)(e)2., 62-762.501(2)(e)2.a., 62-762.501(2)(e)2.b., 62-762.501(2)(e)2.c., 62-762.501(2)(e)2.d., 62-762.501(2)(e)3.
07/11/2019 Editable Letter Activity Winkler, Michael G.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Compliance Assistance Correspondence Date: 07/11/2019
Comment: Compliance Assistance Correspondence
Events:
Event Type: Document has been sent Date: 07/11/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 07/11/2019
Comment: Finished
Attachments:
Attachment Date: 07/11/2019 User: WINKLER_MG_1
Description: 2019-07-10 CAO sent to Jim Dunscomb
View Attachment
07/11/2019 Violation Closed Winkler, Michael G.
Significance: Minor Status: Closed
Criteria ID: 5102
Rule: 62-762.601(7)
07/11/2019 Violation Closed Winkler, Michael G.
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
07/10/2019 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 07/10/2019
Activity Closed Date: 07/11/2019 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 07/11/2019
Comment: Finished
Comments:
Comment Date: 07/11/2019 User: WINKLER_MG_1
Description: Met Fred Patton and Ryan at the location. This facility has a 1000 gallon UST and a 2190 gal AST servicing emergency generators. See noted violations with respect to periodic integrity testing for the UST, and annual operability testing for the overfill and rupture basin alarms for the AST. Results can be mailed to Michael.WInkler@FLHealth.gov
07/25/2018 Record Document Activity Winkler, Michael G.
Activity Status: Closed
Contact Name: James Dunscomb Activity Closed Date: 07/25/2018
Events:
Event Type: Activity has been finished Date: 07/25/2018
Comment: Finished
07/25/2018 Editable Letter Activity Winkler, Michael G.
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 07/25/2018
Comment: Sent
Events:
Event Type: Activity has been finished Date: 07/25/2018
Comment: Finished
Attachments:
Attachment Date: 07/25/2018 User: WINKLER_MG_1
Description: 2018-07-25 RTC sent to LKMC James Dunscomb
View Attachment
12/04/2017 Electronic Communication Activity Winkler, Michael G.
Activity Closed Date: 12/04/2017 Activity Status: Closed
Date: 12/04/2017
Recipient: James Dunscomb
Sender: Mike Winkler
Subject: Overfill alarm
Message: See attached
Events:
Event Type: Activity has been finished Date: 12/04/2017
Comment: Finished
06/12/2017 Record Document Activity Winkler, Michael G.
Activity Status: Closed
Contact Name: Fred patton Activity Closed Date: 06/12/2017
Events:
Event Type: Activity has been finished Date: 06/12/2017
Comment: Finished
06/05/2017 Violation Closed Winkler, Michael G.
Significance: Minor Status: Closed
Criteria ID: 4057
Rule: 62-761.500(7)(e)
06/05/2017 Editable Letter Activity Winkler, Michael G.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Description: CRDE SHEET
Events:
Event Type: Activity has been finished Date: 06/05/2017
Comment: Finished
Attachments:
Attachment Date: 06/05/2017 User: WINKLER_MG_1
Description: 2017-06-05 NCL
View Attachment
05/30/2017 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 05/30/2017
Activity Closed Date: 06/05/2017 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 06/05/2017
Comment: Finished
Comments:
Comment Date: 06/05/2017 User: WINKLER_MG_1
Description: This is an installation inspection for the new tank labeled tank #3. A 2190 gallon double walled AST. The facility is required to provide proof of testing the overfill alarm and rupture basin sensor at this time.
05/02/2017 Attachment Winkler, Michael G.
04/08/2017 Violation Closed Winkler, Michael G.
Significance: Minor Status: Closed
Criteria ID: 1005
Rule: 62-761.450(1)(a)1.
Comments: The local program should receive notice of upgrade, replacement, and installation tasks prior to the initiation of the work. Local program may accept less notice and still consider this item in compliance. This rule citation is not a requirement to submit construction plans. Notice can be accepted in these formats: Verbal Written Fax Email
04/08/2017 Editable Letter Activity Winkler, Michael G.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 04/08/2017
Comment: Finished
Attachments:
Attachment Date: 04/08/2017 User: WINKLER_MG_1
Description: NCL Emailed
View Attachment
04/08/2017 Violation Closed Winkler, Michael G.
Significance: Minor Status: Closed
Criteria ID: 1001
Rule: 62-761.400(1)(a), 62-761.400(1)(b)
Comments: Does STCM accurately reflect the tanks at the facility? This question concerns the registration process and payment of fees only - it is not about accurate registration. Check the number of tanks listed on the registration placard. Can the facility owner/operator produce a registration form to document submittal to DEP? At the time of tank closure, a registration form should be submitted showing the change in tank codes.
04/08/2017 Violation Closed Winkler, Michael G.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
Comments:
Comment Date: 06/05/2017 User: WINKLER_MG_1
Description: This is an installation inspection for the new tank labeled tank #3. A 2190 gallon double walled AST. The facility is required to provide proof of testing the overfill alarm and rupture basin sensor at this time.
04/08/2017 Violation Closed Winkler, Michael G.
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
03/30/2017 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/30/2017
Activity Closed Date: 04/08/2017 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 04/08/2017
Comment: Finished
Comments:
Comment Date: 04/08/2017 User: WINKLER_MG_1
Description: Met Mr. Fred Patton onsite for a March 30, 2017 Annual compliance inspection. A new AST was discovered installed onsite. The facility was required to provide 30 days, 10 days, and 48 hours notice prior to installation. NOTES: 1.Verify that the new AST is added to the petroleum liability tank schedule for this location. 2. The tank should be tested onsite after installation to verify it has not been damaged during shipment or installation of the generator. 3. The new tank should be added to the FDEP Storage Tank registration as tank "3". A Storage tank registration form is forwarded to the facility at this time. Please contact Michael.Winkler@FLHealth.gov for assistance in completing Section "C" of the STRF.
04/02/2015 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/02/2015
Activity Closed Date: 04/03/2015 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 04/03/2015
Comment: Finished
Comments:
Comment Date: 04/03/2015 User: WINKLER_MG_1
Description: Reviewed a more accurate way to record the monthly release detection activity to specify spill bucket, tank interstice, piping sump and comments. This is a 1000 gallon DW UST for emergency power generation.
03/20/2013 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/20/2013
Activity Closed Date: 03/21/2013 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 03/21/2013
Comment: Finished
Comments:
Comment Date: 03/20/2013 User: WINKLER_MG_1
Description: Camera batteries died during tank piping sump photo. It is a small total containment piping sump with 1" Environ DW piping. One to service the generator and a return. Dry and clean this date.
Comments:
Comment Date: 03/21/2013 User: WINKLER_MG_1
Description: NOTE: Please update storage tank registration Contact information- Gary Clark is no longer the contact person for this facility.
03/20/2013 Site Inspection Activity Closed Winkler, Michael G.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/20/2013
Activity Closed Date: 03/21/2013 Activity Closed By: WINKLER_MG_1
Events:
Event Type: Activity has been finished Date: 03/21/2013
Comment: Finished
Comments:
Comment Date: 03/20/2013 User: WINKLER_MG_1
Description: Camera batteries died during tank piping sump photo. It is a small total containment piping sump with 1" Environ DW piping. One to service the generator and a return. Dry and clean this date.
Comments:
Comment Date: 03/21/2013 User: WINKLER_MG_1
Description: NOTE: Please update storage tank registration Contact information- Gary Clark is no longer the contact person for this facility.
06/09/2011 Site Inspection Activity Closed Bevard, Tara
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/09/2011
Activity Closed Date: 06/17/2011 Activity Closed By: BEVARD_TK_1
Events:
Event Type: Activity has been finished Date: 06/17/2011
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 06/14/2011
Comment: Submitted for approval by
Events:
Event Type: Activity/Document has been approved Date: 06/16/2011
Comment: Approved by Winkler, Michael
Comments:
Comment Date: 06/13/2011 User: BEVARD_TK_1
Description: Always record water level in annular space. Have the water vacuumed out and continue to monitor. (~2" of water in annular space during inspection.) Ensure that water in annular space is due solely to condensation and not to ground water intrustion.
Comments:
Comment Date: 06/13/2011 User: BEVARD_TK_1
Description: Never fill beyond 95% capacity or beyond 950 gallons for this 1000 gallon UST. Overfill protection is via calibrated stick measurements and tank chart. 950 gallons is 41.75" fuel. May 24th of this year documented tank at 48" or 1018 gallons. Always order the correct amount of fuel and monitor fuel system during product delivery. *Make a copy of RDRL (release detection and response level) for DePoo facility.
Comments:
Comment Date: 06/13/2011 User: BEVARD_TK_1
Description: 1000 gallon diesel UST for emergency power generator.
06/09/2011 Site Inspection Activity Closed Bevard, Tara
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/09/2011
Activity Closed Date: 06/17/2011 Activity Closed By: BEVARD_TK_1
Events:
Event Type: Activity has been finished Date: 06/17/2011
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 06/14/2011
Comment: Submitted for approval by
Events:
Event Type: Activity/Document has been approved Date: 06/16/2011
Comment: Approved by Winkler, Michael
Comments:
Comment Date: 06/13/2011 User: BEVARD_TK_1
Description: Always record water level in annular space. Have the water vacuumed out and continue to monitor. (~2" of water in annular space during inspection.) Ensure that water in annular space is due solely to condensation and not to ground water intrustion.
Comments:
Comment Date: 06/13/2011 User: BEVARD_TK_1
Description: Never fill beyond 95% capacity or beyond 950 gallons for this 1000 gallon UST. Overfill protection is via calibrated stick measurements and tank chart. 950 gallons is 41.75" fuel. May 24th of this year documented tank at 48" or 1018 gallons. Always order the correct amount of fuel and monitor fuel system during product delivery. *Make a copy of RDRL (release detection and response level) for DePoo facility.
Comments:
Comment Date: 06/13/2011 User: BEVARD_TK_1
Description: 1000 gallon diesel UST for emergency power generator.
06/09/2011 Site Inspection Activity Closed Bevard, Tara
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/09/2011
Activity Closed Date: 06/17/2011 Activity Closed By: BEVARD_TK_1
Events:
Event Type: Activity has been finished Date: 06/17/2011
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 06/14/2011
Comment: Submitted for approval by
Events:
Event Type: Activity/Document has been approved Date: 06/16/2011
Comment: Approved by Winkler, Michael
Comments:
Comment Date: 06/13/2011 User: BEVARD_TK_1
Description: Always record water level in annular space. Have the water vacuumed out and continue to monitor. (~2" of water in annular space during inspection.) Ensure that water in annular space is due solely to condensation and not to ground water intrustion.
Comments:
Comment Date: 06/13/2011 User: BEVARD_TK_1
Description: Never fill beyond 95% capacity or beyond 950 gallons for this 1000 gallon UST. Overfill protection is via calibrated stick measurements and tank chart. 950 gallons is 41.75" fuel. May 24th of this year documented tank at 48" or 1018 gallons. Always order the correct amount of fuel and monitor fuel system during product delivery. *Make a copy of RDRL (release detection and response level) for DePoo facility.
Comments:
Comment Date: 06/13/2011 User: BEVARD_TK_1
Description: 1000 gallon diesel UST for emergency power generator.
06/15/2010 Editable Letter Activity Lichtler, Gary B.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/15/2010
Comment: Finished
Events:
Event Type: Document has been sent Date: 06/15/2010
Comment: Sent on Tue Jun 15 00:00:00 EDT 2010
Attachments:
Attachment Date: 06/15/2010 User: LICHTLER_GB_1
Description: 2010-06-15 NCL
View Attachment
06/14/2010 Violation Closed Lichtler, Gary B.
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
Comments:
Comment Date: 08/05/2022 User: RAMIREZ_LM
Description: EQ-200
06/14/2010 Site Inspection Activity Closed Lichtler, Gary B.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 06/14/2010
Activity Closed Date: 06/15/2010 Activity Closed By: LICHTLER_GB_1
Events:
Event Type: Activity has been finished Date: 06/15/2010
Comment: Finished
06/14/2010 Violation Closed Lichtler, Gary B.
Significance: SNC-B Status: Closed
Criteria ID: 1076
Rule: 62-761.610(3)(a)1.a., 62-761.610(3)(a)1.b.
Comments: The following exemptions are allowed under .640(3)(a)3: Release detection is not required for piping associated with: a. Suction pumps, provided that a single check valve is installed directly below the suction pump, and the piping is sloped so that the contents of the pipe will drain back to the tank if the suction is broken. Written verification shall be provided by a certified contractor that no other check valves exist between the dispenser and the tank, and that the above criteria are met. Any subsequent modification of the piping which involves disconnection shall be recertified by a Certified Contractor that these conditions are still being met; and b. Manifold piping systems. .640(2) provides for external monitoring methods provided that: well construction requirements are met, site suitability has been determined, and either a groundwater or vapor monitoring method has been implemented. Rule 62-761.610(1)(b) covers release detection for Category-C UST systems. Rule 62-761.610(2) deals with release detection for Category-A and B UST systems. Rules 62-761.610(3)(a)1, 62-761.610(3)(a)2, 62-761.610(3)(b) & 62-761.610(3)(c) deal with all piping release detection.
Comments:
Comment Date: 08/24/2021 User: MURPHY_MA_1
Description: The 1000-gallon Fidelity Manufacturing UL 142 (EQ# 497) was set the day of the closure. It contained a Fidelity Manufacturing Spill bucket housed inside of the cabinet (EQ# 778). The high Fuel Switch and Leak Detection Switch (EQ#817) are FPI sensors both read on panel. The primary overfill is the OPW self-contained audible alarm (EQ#610) located next to the fill inside of the cabinet. There is also a Krueger high fuel gauge (EQ#730) on top of the tank next to fill this is not the primary overfill.
03/12/2009 Site Inspection Activity Closed Smith, Ryan R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/12/2009
Activity Closed Date: 06/03/2009 Activity Closed By: SMITH_RR
Comments:
Comment Date: 06/02/2009 User: SMITH_RR
Description: Pictures unavailable due to camera problems.
08/25/2008 Site Inspection Activity Closed Smith, Ryan R.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/25/2008
Activity Closed Date: 08/29/2008 Activity Closed By: SMITH_RR
07/23/2007 Attachment Hammontree, Timothy D.
07/18/2007 Site Inspection Activity Closed Hammontree, Timothy D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/18/2007
Activity Closed Date: 07/23/2007 Activity Closed By: HAMMONTREE_TD
07/19/2006 Site Inspection Activity Closed Hammontree, Timothy D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/19/2006
Activity Closed Date: 07/19/2006 Activity Closed By: HAMMONTREE_TD
07/20/2005 Legacy Activity Unknown, User
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
11/12/2004 Legacy Activity Lowe, Shana E.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
12/18/2003 Legacy Activity Trebesch, Charles L.
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
Completion Notes: INSTALLATION OF 3/4" ENVIRON DW FLEX PIPE. TESTED O.K.
10/29/2003 Legacy Activity Trebesch, Charles L.
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
10/24/2003 Violation Closed Trebesch, Charles L.
Significance: Minor Status: Closed
Rule: 700(1)(a)1
10/24/2003 Legacy Activity Trebesch, Charles L.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: POST RDRL AT FACILITY
02/28/2003 Legacy Activity Deidrick, John R.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/23/2002 Legacy Activity Shulaw, Benjamin J.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/20/2001 Violation Closed Lawrence, William F.
Significance: Minor Status: Closed
Rule: 700(1)(c)1
02/20/2001 Legacy Activity Lawrence, William F.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/20/2001 Violation Closed Lawrence, William F.
Significance: SNC-B Status: Closed
Rule: 600(1)(d)
02/20/2001 Violation Closed Lawrence, William F.
Significance: SNC-B Status: Closed
Rule: 400(3)
02/20/2001 Violation Closed Lawrence, William F.
Significance: Minor Status: Closed
Rule: 500(2)(d)1
02/20/2001 Violation Closed Deidrick, John R.
Significance: Minor Status: Closed
Rule: 400(2)(a)6
02/25/2000 Legacy Activity Unknown, User
Activity Name: NON-COMPLIANCE LETTER ISSUED Activity Status: Closed
Completion Notes: OPERATOR PROVIDED DOCUMENTS TO CLEAR SNC-B.
02/16/2000 Violation Closed Unknown, User
Significance: SNC-B Status: Closed
Rule: 400(3)
02/16/2000 Legacy Activity Unknown, User
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
Completion Notes: THIS WAS FIRST ROUTINE INSPECTION AFTER REPLACEMENT.
05/07/1999 Legacy Activity Unknown, User
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed
Completion Notes: INSTALLATION OF REPLACEMENT TANK.
05/06/1999 Violation Closed Deidrick, John R.
Significance: Minor Status: Closed
Rule: 800(3)(b)2a
Attachments:
Attachment Date: 02/15/2008 User: JARRETT_SE
Description: 2008-01-31 Sweetbay Distribution Center Updated Facility Site Map 01/31/2008
View Attachment
Attachments:
Attachment Date: 09/21/2021 User: GLENNON_BM_1
Description: 2021-09-08 Tanks 1 & 2
View Attachment
Attachments:
Attachment Date: 09/21/2021 User: GLENNON_BM_1
Description: 2021-09-08 Tank 3
View Attachment
Attachments:
Attachment Date: 09/21/2021 User: GLENNON_BM_1
Description: 2021-09-08 Site Photo
View Attachment
05/06/1999 Legacy Activity Unknown, User
Activity Name: TANK CLOSURE INSPECTION Activity Status: Closed
Completion Notes: CLOSURE OF OLD UST.