Facility ID: 9800911
Facility Name: MIAMI DADE COURTHOUSE
 
03/31/2025 Electronic Communication Activity Williams, Calvin E.
Activity Closed Date: 03/31/2025 Activity Status: Closed
Date: 03/31/2025
Recipient: Calvin Williams
Sender: Mario Reyes
Subject: FW: CEI Annual Certifications - MDC Courthouse
Message: Good morning Calvin, See attachments. Is this the information that was needed? Thanks. Best Regards, Mario Reyes, Building Maintenance Supervisor Miami-Dade People and Internal Operations Department (PIOD) Facilities Management Division Dade County Courthouse 73 W Flagler Street Suite 136 Miami, FL 33130 Cell (786) 774-2421
Events:
Event Type: Activity has been finished Date: 03/31/2025
Comment: Finished
03/31/2025 Editable Letter Activity Williams, Calvin E.
Activity Title: Return to Compliance Letter Activity Status: Open
11/07/2024 Enforcement Referral Activity Williams, Calvin E.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 11/14/2024
Events:
Event Type: Activity has been submitted for approval Date: 11/07/2024
Comment: Submitted for approval by: Calvin E. Williams: Violations stiil open
Events:
Event Type: Activity/Document was acknowledged on this date Date: 11/14/2024
Comment: Acknowledged and Assigned by Ana M. Chirino
Events:
Event Type: Activity/Document was accepted on this date Date: 11/14/2024
Comment: Accepted by Judy F. Dolan: Will Refer to Calvin Williams.
Events:
Event Type: Activity has been finished Date: 11/14/2024
Comment: Finished
Events:
Event Type: Activity has been assigned Date: 11/14/2024
Comment: Assigned to Judy F. Dolan
Comments:
Comment Date: 11/07/2024 User: WILLIAMS_CEW
Description: Violations stiil open
11/06/2024 Enforcement Referral Activity Williams, Calvin E.
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 11/14/2024
Events:
Event Type: Activity has been submitted for approval Date: 11/06/2024
Comment: Submitted for approval by: Calvin E. Williams: Two violations are still outstanding.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 11/14/2024
Comment: Acknowledged and Assigned by Ana M. Chirino
Events:
Event Type: Activity has been finished Date: 11/14/2024
Comment: Finished
Events:
Event Type: Activity has been assigned Date: 11/14/2024
Comment: Assigned to Judy F. Dolan
Events:
Event Type: Activity/Document was accepted on this date Date: 11/14/2024
Comment: Accepted by Judy F. Dolan: Will reassign to Calvin Williams
Comments:
Comment Date: 11/06/2024 User: WILLIAMS_CEW
Description: Two violations are still outstanding.
10/23/2024 Electronic Communication Activity Williams, Calvin E.
Activity Closed Date: 11/12/2024 Activity Status: Closed
Date: 10/23/2024
Recipient: Elizabeth Jarga
Sender: Calvin Williams
Subject: RE: Tank Violations for Justice Bldg.
Message: Good morning Calvin, We apologize for the delay. As requested, I have attached the following, 1. A, B & C Operator’s Certificates from our Maintenance Supervisor Thomas Wolek. 2. Operability Test 2024 3. Spill Bucket – Containment Sump/ Dispenser Test 2024 4. Annual Automatic Tank Gauging Certification 2024 We are working with Cherokee and our management administration to address the issues and equipment failing. We had a site walkthrough and working on allocation for the quoted amount to replace the underground tank with an above tank. If you need additional information or have any questions, please do not hesitate to contact me at 305-469-5799. Thank you for your patience and understanding. Best Regards, Elizabeth L Jara Miami-Dade County, Internal Services Department Facilities Management Division Cell: (786) 890-0471 Email: Elizabeth.Jara@MiamiDade.Gov www.miamidade.gov/internalservices
Events:
Event Type: Activity has been finished Date: 11/12/2024
Comment: Finished
05/20/2024 Editable Letter Activity Williams, Calvin E.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/10/2024
Comment: Sent
Events:
Event Type: Activity has been finished Date: 09/05/2024
Comment: Finished
Attachments:
Attachment Date: 09/05/2024 User: WILLIAMS_CEW
Description: CAOL
View Attachment
04/25/2024 Violation Closed Williams, Calvin E.
Significance: Minor Status: Closed
Criteria ID: 6072
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1, 62-761.700(3)(a)1.a, 62-761.700(3)(a)1.b, 62-761.700(3)(a)1.c, 62-761.700(3)(a)1.d, 62-761.700(3)(a)1.e, 62-761.700(3)(a)1.f, 62-761.700(3)(a)1.g, 62-761.700(3)(a)2
04/25/2024 Site Inspection Activity Closed Williams, Calvin E.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/25/2024
Activity Closed Date: 05/20/2024 Activity Closed By: WILLIAMS_CEW
Events:
Event Type: Activity has been finished Date: 05/20/2024
Comment: Finished
Comments:
Comment Date: 04/25/2024 User: WILLIAMS_CEW
Description: I, Calvin Williams, Southeast District of the Department of Environmental Protection, met with Mario Reyes of Miami Dade County Internal Services Department. I inspected a 500-gallon underground storage tank suction system that’s used for an emergency generator. A VISUAL inspection showed that the tank pad appeared to be in good condition. No cracks or signs of leaks. The spill bucket was intact and free of debris and fluids. Spill bucket integrity test was done 2/5/2024. OVERFILL PROTECTION was provided by a ball float valve as primary and a Pneumercator LC 1002 as secondary. Vent pipe was present. RELEASE DETECTION is provided by the Pneumercator LC 1002. Annual operability test (AOT) for the release detection was done on 2/5/2024. The test from 2022 and 2023 were not present. AOT for the overfill device was done on 2/5/2024. The test for 2022 and 2023 were not present. PIPING appeared to be in good condition. Piping sump triennial integrity test was done on 2/5/2024. RECORD of Certificate of Financial Responsibility was dated from 2/1/2024 to 1/31/2025. Monthly inspections are dated from 12/6/2022 to 3/22/2024. The months of March 2021 until November 2022 were not present. No A, B, or C operator licenses were present. Placard was dated from 7/17/2024 to 6/30/2025. Report was emailed to Alex Munoz. CW
04/25/2024 Violation Closed Williams, Calvin E.
Significance: Minor Status: Closed
Criteria ID: 6002
Rule: 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2, 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7)
04/25/2024 Violation Closed Williams, Calvin E.
Significance: Minor Status: Closed
Criteria ID: 6062
Rule: 62-761.600(4)
01/24/2022 Electronic Communication Activity Williams, Calvin E.
Activity Closed Date: 01/24/2022 Activity Status: Closed
Date: 01/24/2022
Recipient: Calvin Williams
Sender: Luckner Joseph
Subject: FW: Automatic Tank Gauging - Annual Certification Test
Message: See attached inspection report thanks
Events:
Event Type: Activity has been finished Date: 01/24/2022
Comment: Finished
07/30/2021 Electronic Communication Activity Williams, Calvin E.
Activity Closed Date: 10/19/2021 Activity Status: Closed
Date: 07/30/2021
Recipient: Calvin Williams
Sender: Luckner Joseph
Subject: FW: Miami Dade County Courthouse - Sump Repairs
Message: Good morning Mr. Williams, See attached final integrity inspection report. Thanks.
Events:
Event Type: Activity has been finished Date: 10/19/2021
Comment: Finished
06/21/2021 Electronic Communication Activity Williams, Calvin E.
Activity Closed Date: 06/21/2021 Activity Status: Closed
Date: 06/21/2021
Recipient: Calvin Williams
Sender: Luckner Joseph
Subject: FW: Automatic Tank Gauging - Annual Certification Test
Message: See attached inspection report thanks
Events:
Event Type: Activity has been finished Date: 06/21/2021
Comment: Finished
06/21/2021 Electronic Communication Activity Williams, Calvin E.
Activity Closed Date: 06/21/2021 Activity Status: Closed
Date: 06/21/2021
Recipient: Calvin Williams
Sender: Luckner Joseph
Subject: FW: Automatic Tank Gauging - Annual Certification Test
Message: See attached report.
Events:
Event Type: Activity has been finished Date: 06/21/2021
Comment: Finished
06/18/2021 Violation Closed Williams, Calvin E.
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
06/18/2021 Editable Letter Activity Williams, Calvin E.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 10/19/2021
Comment: Finished
Events:
Event Type: Document has been sent Date: 06/18/2021
Comment: Sent
Attachments:
Attachment Date: 10/19/2021 User: WILLIAMS_CEW
Description: 6/18/2021 CAOL
View Attachment
06/03/2021 Violation Closed Williams, Calvin E.
Significance: Minor Status: Closed
Criteria ID: 4067
Rule: 62-761.600(4)
06/03/2021 Site Inspection Activity Closed Williams, Calvin E.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 06/03/2021
Activity Closed Date: 06/18/2021 Activity Closed By: WILLIAMS_CEW
Events:
Event Type: Activity has been finished Date: 06/18/2021
Comment: Finished
Comments:
Comment Date: 06/03/2021 User: WILLIAMS_CEW
Description: I, Calvin Williams, Southeast District of the Department of Environmental Protection, met with Keith Gaskins and Luckner Joseph of Miami-Dade ISD. I inspected a 500-gallon underground tank used for an emergency generator. A VISUAL inspection showed that the tank pad appeared to be in good condition. Spill bucket lid for the fill port was not properly color coded, but a picture of the properly painted lid was sent to the Department before this report was complete. The spill bucket was intact and free of debris and fluids. OVERFILL PROTECTION was provided a Pneumercator LC 1000. Vent pipe was present. RELEASE DETECTION is provided by the Pneumercator LC 1000. Annual operability test for the release detection and overfill device was not present. PIPING appeared to be in good condition. Integrity test for the spill bucket was not present. Integrity test for the piping sump was not present. Operator certification was not present. RECORD of CFR is dated from 2/1/2021 to 1/31/2022. Three years of monthly inspections are dated from 5/15/2021 to 5/25/2021, but the inspections were inconsistent because nine months were missing in 2019. Placard was dated from 6/2/2021 to 6/30/2022. Please update the contact information. Report was emailed. CW
06/03/2021 Violation Closed Williams, Calvin E.
Significance: Minor Status: Closed
Criteria ID: 4076
Rule: 62-761.700(3), 62-761.700(3)(a), 62-761.700(3)(a)1., 62-761.700(3)(a)1.a., 62-761.700(3)(a)1.b., 62-761.700(3)(a)1.c., 62-761.700(3)(a)1.d., 62-761.700(3)(a)1.e., 62-761.700(3)(a)1.f., 62-761.700(3)(a)2.
06/03/2021 Violation Closed Williams, Calvin E.
Significance: Minor Status: Closed
Criteria ID: 4057
Rule: 62-761.500(7)(e)
06/03/2021 Violation Closed Williams, Calvin E.
Significance: SNC-B Status: Closed
Criteria ID: 4059
Rule: 62-761.600(1)(d), 62-761.600(1)(e)
06/03/2021 Violation Closed Williams, Calvin E.
Significance: Minor Status: Closed
Criteria ID: 4001
Rule: 62-761.350(1), 62-761.350(1)(c), 62-761.350(1)(d), 62-761.350(3)(b)2., 62-761.350(5)(a), 62-761.350(5)(b), 62-761.350(5)(c), 62-761.350(7)
08/09/2018 Phone Conversation Activity Williams, Calvin E.
Call Type: Outgoing Activity Status: Closed
Phone Number: (786) 493-2354 Activity Closed Date: 08/09/2018
Subject: Spoke with Roben Harduarsingh the building manager. He reported that the monthly inspections were started. Cherokee came to investigate the small amount fuel in the sump and verified that it was from a delivery. Also an Operabiliy test was done on the Veedor Root release detection system. He will send the information to me as soon as he receives it from Cherokee.
Events:
Event Type: Activity has been finished Date: 08/09/2018
Comment: Finished
07/02/2018 Editable Letter Activity Williams, Calvin E.
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 08/08/2018
Comment: Finished
Events:
Event Type: Compliance Assistance Offer Written Date: 07/09/2018
Comment: Compliance Assistance Offer Written
Events:
Event Type: Document has been sent Date: 07/09/2018
Comment: Sent
Attachments:
Attachment Date: 08/08/2018 User: WILLIAMS_CEW
Description: CAO Letter
View Attachment
06/21/2018 Violation Closed Williams, Calvin E.
Significance: SNC-B Status: Closed
Criteria ID: 4016
Rule: 62-761.430(2)
06/21/2018 Site Inspection Activity Closed Williams, Calvin E.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 06/21/2018
Activity Closed Date: 07/02/2018 Activity Closed By: WILLIAMS_CEW
Events:
Event Type: Activity has been finished Date: 07/02/2018
Comment: Finished
Comments:
Comment Date: 06/21/2018 User: WILLIAMS_CEW
Description: I, Calvin Williams, Southeast District of the Department of Environmental Protection, met with Roben Harduarsingh. I inspected a 500-gallon underground storage tank. It is a tank used for an emergency generator. A VISUAL inspection showed that the tank pad appeared to be in good condition. Spill bucket for the fill port was properly color coded. The spill bucket was intact however a small amount of diesel was in the sump. According to rule 62-761.430(4), F.A.C, - In cases where an Incident Notification Form (INF) is required to be submitted, the investigation shall be completed within 14 days of the date of discovery of the incident to determine if a discharge has occurred. Incident investigations that require additional time can be extended with the written approval of the Department. Please investigate the source and submit an INF. OVERFILL PROTECTION was provided by ball check valve. Vent pipe is present. RELEASE DETECTION is provided by a Pneumercator LC 1000. Annual operability test was not done. PIPING appeared to be in good condition. RECORD of CFR is dated from 2/1/2018 to 1/31/2019. Monthly inspections were not done. Placard was dated from 5/19/2017 to 6/30/2018. Please update the contact information to reflect the new building manager. Report was emailed. Also, I sent a CFR, INF and monthly inspection form to the building manger. CW
06/21/2018 Violation Closed Williams, Calvin E.
Significance: Minor Status: Closed
Criteria ID: 4067
Rule: 62-761.600(4)
06/21/2018 Violation Closed Williams, Calvin E.
Significance: SNC-B Status: Closed
Criteria ID: 4059
Rule: 62-761.600(1)(d), 62-761.600(1)(e)
09/14/2015 Attachment Brown, Stephen E.
09/14/2015 Site Inspection Activity Closed Brown, Stephen E.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 09/14/2015
Activity Closed Date: 09/14/2015 Activity Closed By: BROWN_SE
Events:
Event Type: Activity has been finished Date: 09/14/2015
Comment: Finished
Comments:
Comment Date: 09/14/2015 User: BROWN_SE
Description: The on-site physical inspection was conducted on September 10, 2015. I met with the Building Manager, Mr. JC Izquierdo The facility has 1-500 gallon, double walled fiberglass gallon emergency generator underground storage tank system with double walled fiberglass piping. The tank is located on the west side of the building along SW 1st Avenue. I inspected the fill port and the piping sump and all appeared to be in excellent condition. The storage tank system is equipped with a Pneumercator LC 1000 for monitoring of the tank interstice and piping sump. Under the current state regulations, release detection is not required for underground emergency generator tanks. The facility is listed in the Miami-Dade County Bond Rating Test. The contacts for the owner and operator were not current and needed to be updated. A registration form was filled out and signed by Mr. Izquierdo to make the needed corrections. The registration form was sent to Tallahassee Registration on September 14, 2015. Inspector’s notes: The site drawing and photo appears to be in order.
12/12/2013 Site Inspection Activity Closed Williams, Calvin E.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 12/12/2013
Activity Closed Date: 12/17/2013 Activity Closed By: WILLIAMS_CEW
Events:
Event Type: Activity has been finished Date: 12/17/2013
Comment: Finished
Comments:
Comment Date: 12/12/2013 User: WILLIAMS_CEW
Description: I, Calvin Williams, Southeast District of the Department of Environmental Protection, met with Bryan Johnson of Miami Dade County. I inspected a 500 gallon underground storage tank. It is a tank used for an emergency generator. A VISUAL inspection showed that the tank pad appeared to be in good condition. Despite the construction that was happening there were no stains or cracks. Spill bucket for the fill port was properly color coded. The spill bucket was intact and free of debris and fluids. OVERFILL PROTECTION was provided by a Pneumercator LC 1000. Vent pipe was present. RELEASE DETECTION is not required but it was provided by the Pneumercator LC 1000. PIPING in the sump appeared to be in good condition. BOOT was pulled back. RECORD of CFR is from 10/1/2013 to 9/30/2014. Two years of monthly inspections are dated from 12/14/2011 to 12/3/2013. RDRL is current. Placard was dated from 7/1/2013 to 6/30/2014. Registration information was verified. Contact information needs to be changed. A registration form was sent to Carol Dickson prior to the inspection. The report was emailed. CW
04/24/2012 Attachment Brown, Stephen E.
04/24/2012 Site Inspection Activity Closed Brown, Stephen E.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/24/2012
Activity Closed Date: 04/24/2012 Activity Closed By: BROWN_SE
Events:
Event Type: Activity has been finished Date: 04/24/2012
Comment: Finished
Comments:
Comment Date: 04/24/2012 User: BROWN_SE
Description: n site inspection date: April 20, 2012 Met on site with Mr. David Racine. The piping sump and spill bucket appeared to be in excellent condition with no evidence of corrosion or water intrusion. Although not required, the tank and piping are monitored with a Pnuemercator LC 1000. The Pnuemercator is checked on a weekly basis and a log is kept inside the building. I recommended to Mr. Racine that an addition column be added to the log to specify that the release detection alarm is checked. Registration was corrected on site with the correct contact information. Facility Placard and Financial Insurance is up to date.
04/05/2012 Phone Conversation Activity Brown, Stephen E.
Call Type: Incoming Activity Status: Closed
Activity Closed Date: 04/05/2012
Subject: Spoke to Dazina to set up inspection for April 19, 2012. Will meet with John Carmichael. Will call 305-349-7600 the day if inspection.
Events:
Event Type: Activity has been finished Date: 04/05/2012
Comment: Finished
02/17/2010 Site Inspection Activity Closed Jackson, Michael E.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/17/2010
Activity Closed Date: 02/22/2010 Activity Closed By: JACKSON_ME
Events:
Event Type: Activity has been finished Date: 02/22/2010
Comment: Finished
Comments:
Comment Date: 02/18/2010 User: JACKSON_ME
Description: The registration for this tank does not indicate that it is Double Walled. I took photos of the electronic interstice monitoring port on the tank and was given several documents dated 1998 and 1999 regarding the installation and testing of this Double Walled Plasteel Brand tank. Documents are attached. Approval for registration change has been made. MJ
02/08/2010 Document Management Activity Correa, Liliana
Activity Title: Inspection Report - Non-Compliance Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/08/2010
Comment: Finished
Attachments:
Attachment Date: 02/08/2010 User: CORREA_LI_1
Description: Last Chance Letter
View Attachment
01/07/2010 Meeting Activity Cajuste, Patrick J.
Activity Closed Date: 01/07/2010 Activity Status: Closed
Location: Miami Dade Court House
Subject: On site with BLDG manager Victor Rodriguez. The tank on site has not been upgraded. No contract on site. I spoke to County contact Juan Silva. Mr. Silva informed me that the tank will be upgraded by the end of the month. The Last Chance Letter was e-mailed to silvaj@miamidade.gov.
Events:
Event Type: Activity has been finished Date: 01/07/2010
Comment: Finished
Comments:
Comment Date: 01/07/2010 User: CAJUSTE_PJ_1
Description: On site with BLDG manager Victor Rodriguez. The tank on site has not been upgraded. No contract on site. I spoke to County contact Juan Silva. Mr. Silva informed me that the tank will be upgraded by the end of the month. The Last Chance Letter was e-mailed to silvaj@miamidade.gov.
07/07/2008 Site Inspection Activity Closed Dolan, Judy F.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/07/2008
Activity Closed Date: 07/08/2008 Activity Closed By: DOLAN_J
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: This is a Underground Emergency GeneratorTank. TheState of Florida does not require release detection. However, all monitoring should be continued due to County Requirements. This tank is in an unusual location under the court house steps. Part of the tank is buried and part of the tank is in the craw space. According to Florida Administrative Code Defination # 65: "Tank" means an enclosed stationary container or structure that is designed or used to store regulated substances, and the volumne of which, including the volume of underground piping, is ten (10) percent or more buried beneath the surface of the ground."
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: Tanks levels were being monitored.
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: Placard,monitoring records and Release Detection Response Level were all viewed and appropriate.
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: We discussed the required upgrade deadline of 12/31/2009 for all single walled tanks. They were not sure how they were going to remove the tank since it was under the steps of the court house. They can close it in place as long as they follow closure procedures. They are planning on meeting the upgrade deadline.
Comments:
Comment Date: 07/08/2008 User: DOLAN_J
Description: Inspection took place on March 19, 2008. Information was entered into the FIRST Database System on 7/7/08.
07/07/2008 Site Inspection Activity Closed Dolan, Judy F.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/07/2008
Activity Closed Date: 07/08/2008 Activity Closed By: DOLAN_J
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: This is a Underground Emergency GeneratorTank. TheState of Florida does not require release detection. However, all monitoring should be continued due to County Requirements. This tank is in an unusual location under the court house steps. Part of the tank is buried and part of the tank is in the craw space. According to Florida Administrative Code Defination # 65: "Tank" means an enclosed stationary container or structure that is designed or used to store regulated substances, and the volumne of which, including the volume of underground piping, is ten (10) percent or more buried beneath the surface of the ground."
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: Tanks levels were being monitored.
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: Placard,monitoring records and Release Detection Response Level were all viewed and appropriate.
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: We discussed the required upgrade deadline of 12/31/2009 for all single walled tanks. They were not sure how they were going to remove the tank since it was under the steps of the court house. They can close it in place as long as they follow closure procedures. They are planning on meeting the upgrade deadline.
Comments:
Comment Date: 07/08/2008 User: DOLAN_J
Description: Inspection took place on March 19, 2008. Information was entered into the FIRST Database System on 7/7/08.
07/07/2008 Site Inspection Activity Closed Dolan, Judy F.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/07/2008
Activity Closed Date: 07/08/2008 Activity Closed By: DOLAN_J
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: This is a Underground Emergency GeneratorTank. TheState of Florida does not require release detection. However, all monitoring should be continued due to County Requirements. This tank is in an unusual location under the court house steps. Part of the tank is buried and part of the tank is in the craw space. According to Florida Administrative Code Defination # 65: "Tank" means an enclosed stationary container or structure that is designed or used to store regulated substances, and the volumne of which, including the volume of underground piping, is ten (10) percent or more buried beneath the surface of the ground."
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: Tanks levels were being monitored.
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: Placard,monitoring records and Release Detection Response Level were all viewed and appropriate.
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: We discussed the required upgrade deadline of 12/31/2009 for all single walled tanks. They were not sure how they were going to remove the tank since it was under the steps of the court house. They can close it in place as long as they follow closure procedures. They are planning on meeting the upgrade deadline.
Comments:
Comment Date: 07/08/2008 User: DOLAN_J
Description: Inspection took place on March 19, 2008. Information was entered into the FIRST Database System on 7/7/08.
07/07/2008 Site Inspection Activity Closed Dolan, Judy F.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/07/2008
Activity Closed Date: 07/08/2008 Activity Closed By: DOLAN_J
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: This is a Underground Emergency GeneratorTank. TheState of Florida does not require release detection. However, all monitoring should be continued due to County Requirements. This tank is in an unusual location under the court house steps. Part of the tank is buried and part of the tank is in the craw space. According to Florida Administrative Code Defination # 65: "Tank" means an enclosed stationary container or structure that is designed or used to store regulated substances, and the volumne of which, including the volume of underground piping, is ten (10) percent or more buried beneath the surface of the ground."
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: Tanks levels were being monitored.
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: Placard,monitoring records and Release Detection Response Level were all viewed and appropriate.
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: We discussed the required upgrade deadline of 12/31/2009 for all single walled tanks. They were not sure how they were going to remove the tank since it was under the steps of the court house. They can close it in place as long as they follow closure procedures. They are planning on meeting the upgrade deadline.
Comments:
Comment Date: 07/08/2008 User: DOLAN_J
Description: Inspection took place on March 19, 2008. Information was entered into the FIRST Database System on 7/7/08.
07/07/2008 Site Inspection Activity Closed Dolan, Judy F.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/07/2008
Activity Closed Date: 07/08/2008 Activity Closed By: DOLAN_J
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: This is a Underground Emergency GeneratorTank. TheState of Florida does not require release detection. However, all monitoring should be continued due to County Requirements. This tank is in an unusual location under the court house steps. Part of the tank is buried and part of the tank is in the craw space. According to Florida Administrative Code Defination # 65: "Tank" means an enclosed stationary container or structure that is designed or used to store regulated substances, and the volumne of which, including the volume of underground piping, is ten (10) percent or more buried beneath the surface of the ground."
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: Tanks levels were being monitored.
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: Placard,monitoring records and Release Detection Response Level were all viewed and appropriate.
Comments:
Comment Date: 07/07/2008 User: DOLAN_J
Description: We discussed the required upgrade deadline of 12/31/2009 for all single walled tanks. They were not sure how they were going to remove the tank since it was under the steps of the court house. They can close it in place as long as they follow closure procedures. They are planning on meeting the upgrade deadline.
Comments:
Comment Date: 07/08/2008 User: DOLAN_J
Description: Inspection took place on March 19, 2008. Information was entered into the FIRST Database System on 7/7/08.
04/17/2007 Attachment White, Cliff M.
04/17/2007 Site Inspection Activity Closed White, Cliff M.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/17/2007
Activity Closed Date: 04/17/2007 Activity Closed By: WHITE_CM
Comments:
Comment Date: 04/17/2007 User: WHITE_CM
Description: Fill Sump and piping Sump clean and dry. No record for monthly visuals and annual operability testing.
04/17/2007 Violation Closed White, Cliff M.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
04/17/2007 Violation Closed White, Cliff M.
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
04/16/2007 Issue Document Activity White, Cliff M.
Activity Status: Closed
Contact Name: David Racine Activity Closed Date: 04/16/2007
06/15/2006 Site Inspection Activity Closed Barath, Jeff A.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 06/15/2006
Activity Closed Date: 07/12/2006 Activity Closed By: BARATH_J
Comments:
Comment Date: 07/12/2006 User: BARATH_J
Description: Actual inspection conducted 05/30/06 on a paper TCI form.
11/15/2004 Legacy Activity Maroney, Emily K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/30/2004 Legacy Activity Rainey, Allen T
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
Completion Notes: PHOTOS OF REPAIRED FILLBOX COVER SUBMITTED 4/30/04. RRBD ENTERED AS PART OF STCM CLEANUP EFFORTS FOR ESTIR.
06/05/2003 Legacy Activity Smith, Jennifer K.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
04/29/2003 Violation Closed Rainey, Allen T
Significance: Minor Status: Closed
Rule: 700(1)(c)1
04/29/2003 Violation Closed Smith, Jennifer K.
Significance: SNC-B Status: Closed
Rule: 400(3)
04/29/2003 Legacy Activity Smith, Jennifer K.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed