DEP Logo Florida Department of
Environmental Protection


Bob Martinez Center
2600 Blair Stone Road
Tallahassee, Florida 32399-2400
Storage Tanks &
Contamination
Monitoring Information
 
Journal Report
Report Run Date: 04/20/2025        Last Data Refresh: 04/19/2025        Report Generated from DOPPLER
 
Facility ID: 9801796
Facility Name: MURPHY USA #7708
 
09/03/2024 Electronic Communication Activity Goodman, Ted A
Activity Closed Date: 09/03/2024 Activity Status: Closed
Date: 09/03/2024
Recipient: Ted Goodman, Robert Zimmerman
Sender: Valerie Laroche, PPM Consultants
Subject: Hydrostatic Test Results
Message: Please see the attached testing results for the Dispenser 3/4 UDC along with the waste manifest for the PCW removed. UDC 3/4 passed 1-hour hydrostatic test on 6/10/24; no discharge was detected. PCW was removed and properly disposed.
Events:
Event Type: Activity has been finished Date: 09/03/2024
Comment: Finished
Attachments:
Attachment Date: 09/03/2024 User: GOODMAN_TA_1
Description: UDC 3/4 Hydrostatic Test Results
View Attachment
Attachments:
Attachment Date: 09/03/2024 User: GOODMAN_TA_1
Description: UDC 3/4 Hydro Test PCW Waste Manifest
View Attachment
09/03/2024 Incident Activity Goodman, Ted A
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 09/03/2024
Events:
Event Type: Activity has been finished Date: 09/03/2024
Comment: Finished
06/25/2024 Record Document Activity Zimmerman, Robert A
Activity Status: Closed
Contact Name: Valerie Laroche Activity Closed Date: 06/25/2024
Events:
Event Type: Activity has been finished Date: 06/25/2024
Comment: Finished
Comments:
Comment Date: 06/25/2024 User: ZIMMERMAN_RA_2
Description: Received UDC 3/4 post repair CIE test certification and waste manifest; entered documents into FIRST.
06/10/2024 Document Management Activity Zimmerman, Robert A
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/10/2024
Comment: Finished
Comments:
Comment Date: 06/10/2024 User: ZIMMERMAN_RA_2
Description: Spatco dispatched to the site on 6/7/24 to respond to alarm for Dispenser 3/4 UDC fuel leak. Will complete hydro testing in addition to repairs.
Attachments:
Attachment Date: 06/10/2024 User: ZIMMERMAN_RA_2
Description: 62-761.900(6) Incident Notification Form_Murphy 7708
View Attachment
Attachments:
Attachment Date: 06/10/2024 User: ZIMMERMAN_RA_2
Description: Activity 62-761.900(6) Incident Notification Form_Murph
View Attachment
04/29/2024 Enforcement Tracking Activity Paul, Jennifer
Activity Status: Open
04/29/2024 Enforcement Referral Activity Zimmerman, Robert A
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 04/29/2024
Events:
Event Type: Activity has been submitted for approval Date: 04/29/2024
Comment: Submitted for approval by: Robert A Zimmerman: I was directed to refer this facility immediately.
Events:
Event Type: Activity has been finished Date: 04/29/2024
Comment: Finished
Events:
Event Type: Activity/Document was acknowledged on this date Date: 04/29/2024
Comment: Acknowledged and Assigned by Jennifer Paul
Events:
Event Type: Activity has been assigned Date: 04/29/2024
Comment: Assigned to Jennifer Paul
Events:
Event Type: Activity/Document was accepted on this date Date: 04/29/2024
Comment: Accepted by Jennifer Paul: Accepted
Comments:
Comment Date: 04/29/2024 User: ZIMMERMAN_RA_2
Description: I was directed to refer this facility immediately.
Comments:
Comment Date: 04/29/2024 User: ZIMMERMAN_RA_2
Description: I was directed to refer this facility immediately.
04/29/2024 Enforcement Referral Activity Zimmerman, Robert A
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 04/29/2024
Events:
Event Type: Activity has been submitted for approval Date: 04/29/2024
Comment: Submitted for approval by: Robert A Zimmerman: I was directed to refer this facility immediately.
Events:
Event Type: Activity has been finished Date: 04/29/2024
Comment: Finished
Events:
Event Type: Activity/Document was acknowledged on this date Date: 04/29/2024
Comment: Acknowledged and Assigned by Jennifer Paul
Events:
Event Type: Activity has been assigned Date: 04/29/2024
Comment: Assigned to Jennifer Paul
Events:
Event Type: Activity/Document was accepted on this date Date: 04/29/2024
Comment: Accepted by Jennifer Paul: Accepted
Comments:
Comment Date: 04/29/2024 User: ZIMMERMAN_RA_2
Description: I was directed to refer this facility immediately.
Comments:
Comment Date: 04/29/2024 User: ZIMMERMAN_RA_2
Description: I was directed to refer this facility immediately.
01/30/2024 Violation Open Zimmerman, Robert A
Significance: Minor Status: Open
Criteria ID: 7064
Rule: 62-762.601(1)(d), 62-762.602(1)(d), 62-762.601(1)(g), 62-762.602(1)(g)
01/30/2024 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 01/30/2024 Activity Status: Closed
Date: 01/30/2024
Recipient: Brad Weinischke
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and associated compliance letter email attachments to facility representative; "Brad Weinischke" brad.weinischke@murphyusa.com
Events:
Event Type: Activity has been finished Date: 01/30/2024
Comment: Finished
01/30/2024 Editable Letter Activity Zimmerman, Robert A
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 01/30/2024
Comment: Sent
Events:
Event Type: Activity has been finished Date: 01/30/2024
Comment: Finished
Attachments:
Attachment Date: 01/30/2024 User: ZIMMERMAN_RA_2
Description: CAO 9801796 , MURPHY USA #7708 2024.
View Attachment
01/30/2024 Violation Open Zimmerman, Robert A
Significance: Minor Status: Open
Criteria ID: 6062
Rule: 62-761.600(4)
01/30/2024 Violation Open Zimmerman, Robert A
Significance: Minor Status: Open
Criteria ID: 6053
Rule: 62-761.500(7)(c), 62-761.500(7)(c)1, 62-761.500(7)(c)2, 62-761.500(7)(d)
01/30/2024 Violation Open Zimmerman, Robert A
Significance: Minor Status: Open
Criteria ID: 6062
Rule: 62-761.600(4)
01/30/2024 Violation Open Zimmerman, Robert A
Significance: Minor Status: Open
Criteria ID: 7064
Rule: 62-762.601(1)(d), 62-762.602(1)(d), 62-762.601(1)(g), 62-762.602(1)(g)
01/24/2024 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 01/24/2024
Activity Closed Date: 01/30/2024 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 01/30/2024
Comment: Finished
Comments:
Comment Date: 01/30/2024 User: ZIMMERMAN_RA_2
Description: Sent TCI report and associated compliance letter email attachments to facility representative; "Brad Weinischke" brad.weinischke@murphyusa.com
01/18/2024 Phone Conversation Activity Zimmerman, Robert A
Call Type: Outgoing Activity Status: Closed
Phone Number: 870-918-4331 Activity Closed Date: 01/18/2024
Subject: Contacted facility representative Brad Weinischke for compliance outreach notification scheduling of upcoming TCI and to give a reminder that the three-year record review requirement is: Registration placard, proof of financial responsibility and storage tanks mechanism forms, monthly visual inspections, monthly electronic release detection monitoring records, A/B/C level UST operator certifications, containment integrity evaluation testing, annual overfill protection device, line leak detector and electronic release detection system operability test certifications.
Events:
Event Type: Activity has been finished Date: 01/18/2024
Comment: Finished
02/24/2023 Editable Letter Activity Zimmerman, Robert A
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 02/24/2023
Comment: Sent
Events:
Event Type: Activity has been finished Date: 02/24/2023
Comment: Finished
Attachments:
Attachment Date: 02/24/2023 User: ZIMMERMAN_RA_2
Description: RTC 9801796, MURPHY USA #7708 2023.
View Attachment
02/24/2023 Record Document Activity Zimmerman, Robert A
Activity Status: Closed
Contact Name: Amanda Boshears Activity Closed Date: 02/24/2023
Events:
Event Type: Activity has been finished Date: 02/24/2023
Comment: Finished
Comments:
Comment Date: 02/24/2023 User: ZIMMERMAN_RA_2
Description: Received proof of violation resolution documents - STP containment access work order and spill bucket vacuum-test; entered documents into FIRST.
02/24/2023 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 02/24/2023 Activity Status: Closed
Date: 02/24/2023
Recipient: Amanda Boshears
Sender: Robert Zimmerman
Subject: Issued RTC
Message: Sent RTC email attachment to facility representative: amanda.boshears@murphyusa.com
Events:
Event Type: Activity has been finished Date: 02/24/2023
Comment: Finished
01/27/2023 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 01/27/2023 Activity Status: Closed
Date: 01/27/2023
Recipient: Amanda Boshears
Sender: Robert Zimmerman
Subject: Violation resolution status compliance assistance outreach inquiry.
Message: Compliance assistance outreach contact with facility representative "Amanda Boshears" , regarding violation resolution status.
Events:
Event Type: Activity has been finished Date: 01/27/2023
Comment: Finished
07/17/2022 Electronic Communication Activity Goodman, Ted A
Activity Closed Date: 07/17/2022 Activity Status: Closed
Date: 07/17/2022
Recipient: Brad Weinischke (brad.weinischke@murphyusa.com
Sender: Ted Goodman
Subject: FDEP FACID #12/9801796 - Murphy USA #7708 - Open Incident Investigation
Message: On July 19, 2021, Murphy USA submitted an Incident Notification Form (INF) for the referenced facility, and included a copy of a laboratory analytical report documenting exceedances of FDEP groundwater cleanup target levels for benzene, toluene, and total xylenes in groundwater samples collected from two monitoring wells. The INF also communicated Murphy USA’s intent to conduct integrity testing of tanks, lines, spill buckets, piping sumps, and dispenser sumps for the purpose of determining whether the groundwater analytical results were the result of the July 19, 2018 petroleum products discharge or provided evidence of a new discharge. Chapter 62-761.430(4) Florida Administrative Code stipulates that an incident investigation must be completed within 14 days of the date of discovery of the incident, and provides that this time period may be extended with prior written approval from the FDEP or the county. To date, the results of the incident investigation/evaluation have not been received by this office. Please submit the results of your incident investigation within 10 days of receipt of this email communication. If an incident investigation is not received within that timeframe then, based on the analytical data provided, we will be forced to conclude that a new discharge has occurred and Murphy USA will be required to initiate site assessment activities. The FDEP facility identification number for this facility is 12/9801796. Please include this facility ID number on all future correspondence. If you should have any questions, please let me know.
Events:
Event Type: Activity has been finished Date: 07/17/2022
Comment: Finished
03/01/2022 Violation Closed Zimmerman, Robert A
Significance: SNC-B Status: Closed
Criteria ID: 6063
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2
03/01/2022 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 03/01/2022 Activity Status: Closed
Date: 03/01/2022
Recipient: Brad Weinischke
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and associated compliance letter email attachments to facility representative; brad.weinischke@murphyusa.com
Events:
Event Type: Activity has been finished Date: 03/01/2022
Comment: Finished
03/01/2022 Editable Letter Activity Zimmerman, Robert A
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/01/2022
Comment: Finished
Events:
Event Type: Document has been sent Date: 03/01/2022
Comment: Sent
Attachments:
Attachment Date: 03/01/2022 User: ZIMMERMAN_RA_2
Description: CAO 9801796, MURPHY USA #7708.
View Attachment
03/01/2022 Violation Closed Zimmerman, Robert A
Significance: SNC-B Status: Closed
Criteria ID: 6063
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2
02/15/2022 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/15/2022
Activity Closed Date: 03/01/2022 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 03/01/2022
Comment: Finished
Comments:
Comment Date: 03/01/2022 User: ZIMMERMAN_RA_2
Description: Sent TCI report and associated compliance letter email attachments to facility representative; brad.weinischke@murphyusa.com
01/31/2022 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 01/31/2022 Activity Status: Closed
Date: 01/31/2022
Recipient: Brad Weinischke
Sender: Robert Zimmerman
Subject: Compliance outreach TCI notification-scheduling
Message: Contacted facility representative "Brad Weinischke" for compliance outreach notification scheduling of upcoming TCI and to give a reminder that the three-year record review requirement is: Registration placard, proof of financial responsibility and storage tanks mechanism forms, monthly visual inspections, monthly electronic release detection monitoring records, A/B/C level UST operator certifications, containment integrity evaluation testing, annual overfill protection device, line leak detector and electronic release detection system operability test certifications.
Events:
Event Type: Activity has been finished Date: 01/31/2022
Comment: Finished
10/11/2021 Electronic Communication Activity Goodman, Ted A
Activity Closed Date: 10/11/2021 Activity Status: Closed
Date: 10/11/2021
Recipient: Brad Weinischke
Sender: Ted Goodman
Subject: FDEP FACID #12/9801796 - Murphy USA #7708
Message: Mr. Weinischke, On July 19, 2021, Murphy USA submitted an Incident Notification Form (INF) for the referenced facility, and included a copy of a laboratory analytical report documenting exceedances of FDEP groundwater cleanup target levels for benzene, toluene, and total xylenes in groundwater samples collected from two monitoring wells. The INF also communicated Murphy USA’s intent to conduct integrity testing of tanks, lines, spill buckets, piping sumps, and dispenser sumps for the purpose of determining whether the groundwater analytical results were the result of the July 19, 2018 petroleum products discharge or provided evidence of a new discharge. Chapter 62-761.430(4) Florida Administrative Code stipulates that an incident investigation must be completed within 14 days of the date of discovery of the incident, and provides that this time period may be extended with prior written approval from the FDEP or the county. To date, the results of the incident investigation/evaluation have not been received by this office. Please submit the results of your incident investigation within 10 days of receipt of this email communication. If an incident investigation is not received within that timeframe then, based on the analytical data provided, we will be forced to conclude that a new discharge has occurred and Murphy USA will be required to initiate site assessment activities. The FDEP facility identification number for this facility is 12/9801796. Please include this facility ID number on all future correspondence. If you should have any questions, please let me know. Regards,
Events:
Event Type: Activity has been finished Date: 10/11/2021
Comment: Finished
07/19/2021 Incident Activity Zimmerman, Robert A
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 09/23/2022
Events:
Event Type: Activity has been finished Date: 09/23/2022
Comment: Finished
07/19/2021 Document Management Activity Zimmerman, Robert A
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 09/23/2022
Comment: Finished
Comments:
Comment Date: 09/23/2022 User: GOODMAN_TA_1
Description: This incident was rolled into the contamination assessment of the 7/19/2018 petroleum products discharge. A Supplemental Site Assessment Report submitted on 9/1/22 recommended No Further Action. The SSAR/No Further Action Proposal was approved by the NE District Office on 9/19/22. Issuance of an SRCO is imminent. The assessment and NFAP closes this incident.
Attachments:
Attachment Date: 07/19/2021 User: ZIMMERMAN_RA_2
Description: 62-761.900(6) Incident Notification Form
View Attachment
Attachments:
Attachment Date: 07/19/2021 User: ZIMMERMAN_RA_2
Description: 7708 Pace Lab Report 7-13-21
View Attachment
Attachments:
Attachment Date: 09/23/2022 User: GOODMAN_TA_1
Description: Inicident Notification Form 07-13-2021
View Attachment
09/13/2019 Editable Letter Activity Zimmerman, Robert A
Activity Title: In Compliance Letter Activity Status: Closed
Description: 10/30/2019 TIN Compliance Letter
Events:
Event Type: Document has been sent Date: 09/13/2019
Comment: Sent
Events:
Event Type: Activity has been finished Date: 09/13/2019
Comment: Finished
Attachments:
Attachment Date: 09/13/2019 User: ZIMMERMAN_RA_2
Description: ICL 9801796, MURPHY USA 7708
View Attachment
09/13/2019 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 09/13/2019 Activity Status: Closed
Date: 09/13/2019
Recipient: Brad Weinischke
Sender: Robert Zimmerman
Subject: TCI report
Message: Sent TCI report and ICL email attachments to facility representative; Brad Weinischke
Events:
Event Type: Activity has been finished Date: 09/13/2019
Comment: Finished
09/10/2019 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 09/10/2019
Activity Closed Date: 09/13/2019 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 09/13/2019
Comment: Finished
Comments:
Comment Date: 09/10/2019 User: ZIMMERMAN_RA_2
Description: Sent TCI report and ICL email attachments to facility representative;
09/04/2019 Comment Zimmerman, Robert A
Description: "Brad Weinischke" 870-918-4331
09/04/2019 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 09/04/2019 Activity Status: Closed
Date: 09/04/2019
Recipient: Brad Weinischke
Sender: Robert Zimmerman
Subject: Compliance outreach TCI notification-scheduling
Message: Contacted facility representative Brad Weinischke for notification and schedule upcoming TCI and to give a reminder that the three-year record review requirement is: Registration Placard, Proof of Financial Responsibility, STFM, monthly visual inspections and electronic release detection records, annual containment integrity testing, containment integrity testing, annual overfill protection, line leak detector, operability test and A/B/C UST operator certifications.
Events:
Event Type: Activity has been finished Date: 09/04/2019
Comment: Finished
09/04/2019 Comment Zimmerman, Robert A
Description: Facility Manager Richard Swanson (386) 719-9277
04/19/2019 Attachment Zimmerman, Robert A
04/19/2019 Record Document Activity Zimmerman, Robert A
Activity Status: Closed
Contact Name: Alison Michalek Activity Closed Date: 04/19/2019
Events:
Event Type: Activity has been finished Date: 04/19/2019
Comment: Finished
Comments:
Comment Date: 04/19/2019 User: ZIMMERMAN_RA_2
Description: Received CIE, LLD, impact valve, ATG, electronic release detection system,m tank tight and line tight testing certifications; entered documents into FIRST.
04/19/2019 Attachment Zimmerman, Robert A
12/19/2018 Editable Letter Activity Oliva, Linda
Activity Title: Return to Compliance Letter Activity Status: Closed
Description: Marathon Coconut 577 Compliance Assistance Offer Letter
Events:
Event Type: Activity has been finished Date: 12/19/2018
Comment: Finished
Attachments:
Attachment Date: 12/19/2018 User: OLIVA_L
Description: RTC
View Attachment
10/24/2018 TCAR Activity Ramsey, Timothy H
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 10/24/2018
Events:
Event Type: Activity has been finished Date: 10/24/2018
Comment: Finished
10/24/2018 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 10/24/2018 Activity Status: Closed
Date: 10/24/2018
Recipient: BRAD WEINISCHKE
Sender: Robert Zimmerman
Subject: TXI report
Message: Sent TXI report email attachment to facility representative.
Events:
Event Type: Activity has been finished Date: 10/24/2018
Comment: Finished
10/24/2018 Electronic Communication Activity Ramsey, Timothy H
Activity Closed Date: 10/24/2018 Activity Status: Closed
Date: 10/24/2018
Recipient: Elizabeth Titus
Sender: Tim Ramsey
Subject: Copy of Closure Assessment Review letter
Message: Emailed Copy of Closure Assessment Review letter To Murphy USA contact
Events:
Event Type: Activity has been finished Date: 10/24/2018
Comment: Finished
10/24/2018 Editable Letter Activity Ramsey, Timothy H
Activity Title: Closure Assessment Report (Complete) Activity Status: Closed
Description: Valley installation testing_12_jun_2019_results
Events:
Event Type: Activity has been finished Date: 10/24/2018
Comment: Finished
Attachments:
Attachment Date: 10/24/2018 User: RAMSEY_TH_1
Description: Closure Review Letter
View Attachment
07/23/2018 Document Management Activity Zimmerman, Robert A
Activity Title: Discharge Report Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 07/23/2018
Comment: Finished
Comments:
Comment Date: 07/23/2018 User: ZIMMERMAN_RA_2
Description: Discharge discovery was determined from water samples taken from temporary well installed at the center of the UST removal excavation pit.
Attachments:
Attachment Date: 07/23/2018 User: ZIMMERMAN_RA_2
Description: DRF MUSA 7708-5797, 9801796 signed
View Attachment
07/23/2018 Discharge Reporting Activity Zimmerman, Robert A
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 10/24/2018
Events:
Event Type: Activity has been finished Date: 10/24/2018
Comment: Finished
07/09/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/09/2018
Activity Closed Date: 10/24/2018 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 10/24/2018
Comment: Finished
Comments:
Comment Date: 10/24/2018 User: ZIMMERMAN_RA_2
Description: TXI report email attachment was sent to facility representative.
07/09/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/09/2018
Activity Closed Date: 04/23/2019 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 04/23/2019
Comment: Finished
Comments:
Comment Date: 04/19/2019 User: ZIMMERMAN_RA_2
Description: Sent TIN email attachment to facility representative; KRYSTAL.TERRELL@MURPHYUSA.COM
03/16/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/16/2018
Activity Closed Date: 06/28/2018 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 06/28/2018
Comment: Finished
Comments:
Comment Date: 03/16/2018 User: ZIMMERMAN_RA_2
Description: Requested by facility representative Brad Weinischke to re-inspect facility for violation resolution verification. The premium STP sump appears to have new electrical conduit installed. Electrical conduit entry boots have not been installed.
03/16/2018 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/16/2018
Activity Closed Date: 06/28/2018 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 06/28/2018
Comment: Finished
01/31/2018 Electronic Communication Activity Dohaney, Tim
Activity Closed Date: 01/31/2018 Activity Status: Closed
Date: 01/31/2018
Recipient: DOHANEY
Sender: MURPHY
Subject: PROVIDED PART P
Message: COMPLETES FR DOCUMENTATION
Events:
Event Type: Activity has been finished Date: 01/31/2018
Comment: Finished
01/30/2018 Violation Closed Dohaney, Tim
Significance: Minor Status: Closed
Criteria ID: 4015
Rule: 62-761.420(3), 62-761.420(4)
01/30/2018 Electronic Communication Activity Dohaney, Tim
Activity Closed Date: 01/30/2018 Activity Status: Closed
Date: 01/30/2018
Recipient: dohaney
Sender: murphy oil
Subject: 2 emails received with photo of painted fills as well as MLLD results for last 3 years.
Message: Resolves several issues, but not all. Murphy responded that they are working on them.
Events:
Event Type: Activity has been finished Date: 01/30/2018
Comment: Finished
01/22/2018 Electronic Communication Activity Dohaney, Tim
Activity Closed Date: 01/22/2018 Activity Status: Closed
Date: 01/22/2018
Recipient: Dohaney
Sender: Murphy
Subject: received response from Murphy with supporting information to resolve certain violations
Message: see attachments
Events:
Event Type: Activity has been finished Date: 01/22/2018
Comment: Finished
01/03/2018 Editable Letter Activity Dohaney, Tim
Activity Title: Warning Letter Activity Status: Closed
Description: Property owner 2019
Events:
Event Type: Activity has been finished Date: 01/03/2018
Comment: Finished
Attachments:
Attachment Date: 01/03/2018 User: DOHANEY_T
Description: District WL
View Attachment
12/12/2017 Electronic Communication Activity Dohaney, Tim
Activity Closed Date: 12/12/2017 Activity Status: Closed
Date: 12/12/2017
Recipient: Brad Weinischke and Krystal Terrell - Murphy Oil
Sender: Dohaney
Subject: enforcement referral
Message: see attachment
Events:
Event Type: Activity has been finished Date: 12/12/2017
Comment: Finished
Attachments:
Attachment Date: 12/12/2017 User: DOHANEY_T
Description: Email to Murphy Oil
View Attachment
12/12/2017 Enforcement Tracking Activity Dohaney, Tim
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 12/19/2018
Events:
Event Type: Activity has been finished Date: 12/19/2018
Comment: Finished
12/10/2017 Enforcement Referral Activity Zimmerman, Robert A
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 12/12/2017
Events:
Event Type: Activity/Document was acknowledged on this date Date: 12/11/2017
Comment: Acknowledged and Assigned by Tim Dohaney
Events:
Event Type: Activity has been assigned Date: 12/11/2017
Comment: Assigned to Tim Dohaney
Events:
Event Type: Activity has been submitted for approval Date: 12/10/2017
Comment: Submitted for approval by: Robert A Zimmerman: Two phone calls were made and email was sent to facility representative with out violation resolution.
Events:
Event Type: Activity has been finished Date: 12/12/2017
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 12/12/2017
Comment: Accepted by Tim Dohaney: Reviewed and accepted
Comments:
Comment Date: 12/10/2017 User: ZIMMERMAN_RA_2
Description: Two phone calls were made and email was sent to facility representative with out violation resolution.
Comments:
Comment Date: 12/10/2017 User: ZIMMERMAN_RA_2
Description: Two phone calls were made and email was sent to facility representative with out violation resolution.
12/10/2017 Enforcement Referral Activity Zimmerman, Robert A
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 12/12/2017
Events:
Event Type: Activity/Document was acknowledged on this date Date: 12/11/2017
Comment: Acknowledged and Assigned by Tim Dohaney
Events:
Event Type: Activity has been assigned Date: 12/11/2017
Comment: Assigned to Tim Dohaney
Events:
Event Type: Activity has been submitted for approval Date: 12/10/2017
Comment: Submitted for approval by: Robert A Zimmerman: Two phone calls were made and email was sent to facility representative with out violation resolution.
Events:
Event Type: Activity has been finished Date: 12/12/2017
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 12/12/2017
Comment: Accepted by Tim Dohaney: Reviewed and accepted
Comments:
Comment Date: 12/10/2017 User: ZIMMERMAN_RA_2
Description: Two phone calls were made and email was sent to facility representative with out violation resolution.
Comments:
Comment Date: 12/10/2017 User: ZIMMERMAN_RA_2
Description: Two phone calls were made and email was sent to facility representative with out violation resolution.
09/22/2017 Phone Conversation Activity Zimmerman, Robert A
Call Type: Outgoing Activity Status: Closed
Phone Number: (870) 875-7610 Activity Closed Date: 09/22/2017
Subject: Contact with facility representative BRAD WEINISCHKE regarding action needed to resolve open violations.
Events:
Event Type: Activity has been finished Date: 09/22/2017
Comment: Finished
09/22/2017 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 09/22/2017 Activity Status: Closed
Date: 09/22/2017
Recipient: BRAD WEINISCHKE
Sender: Robert Zimmerman
Subject: Violation resolution
Message: Re-sent TCI report to facility representative BRAD WEINISCHKE after having a phone call with facility representative regarding action needed to resolve open violations.
Events:
Event Type: Activity has been finished Date: 09/22/2017
Comment: Finished
06/14/2017 Editable Letter Activity Zimmerman, Robert A
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/14/2017
Comment: Finished
Events:
Event Type: Document has been sent Date: 04/04/2017
Comment: Sent
Attachments:
Attachment Date: 06/14/2017 User: ZIMMERMAN_RA_2
Description: NCL 9801796, MURPHY USA #5671
View Attachment
06/14/2017 Electronic Communication Activity Zimmerman, Robert A
Activity Closed Date: 06/14/2017 Activity Status: Closed
Date: 06/14/2017
Recipient: Brad Weinischke
Sender: Robert Zimmerman
Subject: TCI Report.
Message: Sent TCI report and NCL email attachment to facility registration account owner information contact.
Events:
Event Type: Activity has been finished Date: 06/14/2017
Comment: Finished
04/04/2017 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 1124
Rule: 62-761.710(3)(a), 62-761.710(3)(b), 62-761.710(3)(c), 62-761.710(3)(d), 62-761.710(3)(e), 62-761.710(3)(f), 62-761.710(3)(g), 62-761.710(3)(h)
Comments: The Rule cites does not list routine operation and maintenance records. If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. Periodic inspections and tank system measurements - rules 62-761.610(3)(a)1, 62-761.700(4)-(5) & 62-761.700(6) b. Supporting claims for equipment in use at facility. - rule 62-761.600(1)(a)3 c. History of what has been done at facility - see 62-761.500 rules. d. Cathodic protection system history - rules 62-761.500(1)(e)1 & 62-761500(1)(e)3 e. Site suitability determination - this document must be updated when site conditions change- rule 62-761.600(1)(f) f. Vapor monitoring plan - this document must be updated annually - rule 62-761.600(1)(g) g. Closure reports - rule 62-761.800(3)(d) h. Single check valve - PSSC documentation that no other buried valves exist - rule 62-761.610(3)(a)1
04/04/2017 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/04/2017
Activity Closed Date: 06/14/2017 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 06/14/2017
Comment: Finished
Comments:
Comment Date: 04/04/2017 User: ZIMMERMAN_RA_2
Description: Discussed modification to the UST rule and presented UST outreach tool to the facility representative.
Comments:
Comment Date: 04/04/2017 User: ZIMMERMAN_RA_2
Description: Sent TCI report and NCL email attachment to facility representative.
04/04/2017 Site Inspection Activity Closed Zimmerman, Robert A
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 04/04/2017
Activity Closed Date: 06/14/2017 Activity Closed By: ZIMMERMAN_RA_2
Events:
Event Type: Activity has been finished Date: 06/14/2017
Comment: Finished
Comments:
Comment Date: 04/04/2017 User: ZIMMERMAN_RA_2
Description: Discussed modification to the UST rule and presented UST outreach tool to the facility representative.
Comments:
Comment Date: 04/04/2017 User: ZIMMERMAN_RA_2
Description: Sent TCI report and NCL email attachment to facility representative.
04/04/2017 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
04/04/2017 Violation Closed Zimmerman, Robert A
Significance: Minor Status: Closed
Criteria ID: 1049
Rule: 62-761.510(1)(b)3.
Comments: Refer to the color coded chart included in the API 1637 Reference Standard. Note that airport fuel identification is described in API Bulletin 1542. Other identification methods are: tag or decal on the surface adjacent to the fill, tag on the fillpipe adapter, or colored plastic identification card inside the spill containment unit. Major oil retailers often have their own specific color scheme. See rule 62-761.500(5)(a).
03/23/2017 Phone Conversation Activity Zimmerman, Robert A
Call Type: Outgoing Activity Status: Closed
Phone Number: (386) 719-9277 Activity Closed Date: 03/23/2017
Subject: Contact facility representative for notification and schedule upcoming TCI.
Events:
Event Type: Activity has been finished Date: 03/23/2017
Comment: Finished
01/05/2015 Record Document Activity Defalco, Lynal
Activity Status: Closed
Contact Name: richard dunn PG - PRP Activity Closed Date: 01/05/2015
Events:
Event Type: Activity has been finished Date: 01/05/2015
Comment: Finished
01/05/2015 Issue Document Activity Defalco, Lynal
Activity Status: Closed
Contact Name: defalco Activity Closed Date: 02/06/2015
Events:
Event Type: Activity has been finished Date: 02/06/2015
Comment: Finished
09/25/2014 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 09/24/2014
Activity Closed Date: 09/30/2014 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 09/30/2014
Comment: Finished
Comments:
Comment Date: 09/30/2014 User: SHULAW_BJ_1
Description: No violations cited during this inspection. Comments: Two USTs, both 1 compartmented with 4 dispensers. A Gilbarco EMC monitors product levels, the 2 sumps, 4 dispenser pans and 2 interstices. Spill buckets are monitored visually. The sumps were wet. Spill buckets were wet, sensors properly placed. Sumps, spill buckets and liners look tight. Dispenser liners were dry, shear valves secure, hoses good. The area is clean. The electronic and visual records matched. The monitor was on time, showed all normal and gave a printout. Most inspections were on time. The registration placard and RDRL are in the log. A Certificate of Financial Responsibility and insurance self test were provided. The class C certificates for USTs were obtained by the operator. Discharge Information: No discharges This report will be sent via USPS. If you have any questions please contact me at 386-758-2185, 386-697-7329 cell, fax 386-758-2187, or email Benjamin.Shulaw@flhealth.gov
09/25/2014 Record Document Activity Defalco, Lynal
Activity Status: Closed
Contact Name: roy therrien - PPM Activity Closed Date: 09/25/2014
Events:
Event Type: Activity has been finished Date: 09/25/2014
Comment: Finished
09/25/2014 Issue Document Activity Defalco, Lynal
Activity Status: Closed
Contact Name: defalco Activity Closed Date: 09/25/2014
Events:
Event Type: Activity has been finished Date: 09/25/2014
Comment: Finished
06/19/2014 Record Document Activity Kirts, Brian D
Activity Status: Closed
Contact Name: Richard A. Dunn, P.G. Activity Closed Date: 06/19/2014
Events:
Event Type: Activity has been finished Date: 06/19/2014
Comment: Finished
06/19/2014 Issue Document Activity Kirts, Brian D
Activity Status: Closed
Contact Name: Brian Kirts, P.E. Activity Closed Date: 06/19/2014
Events:
Event Type: Activity has been finished Date: 06/19/2014
Comment: Finished
05/05/2014 Discharge Reporting Activity Kirts, Brian D
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/06/2015
Events:
Event Type: Activity has been finished Date: 02/06/2015
Comment: Finished
05/05/2014 Record Document Activity Kirts, Brian D
Activity Status: Closed
Contact Name: Roy Therrian, P.E. Activity Closed Date: 05/05/2014
Events:
Event Type: Activity has been finished Date: 05/05/2014
Comment: Finished
05/05/2014 Record Document Activity Kirts, Brian D
Activity Status: Closed
Contact Name: Alan B. Chandler Activity Closed Date: 05/05/2014
Events:
Event Type: Activity has been finished Date: 05/05/2014
Comment: Finished
05/05/2014 Issue Document Activity Kirts, Brian D
Activity Status: Closed
Contact Name: Brian Kirts, P.E. Activity Closed Date: 05/05/2014
Events:
Event Type: Activity has been finished Date: 05/05/2014
Comment: Finished
05/01/2014 Electronic Communication Activity Dohaney, Tim
Activity Closed Date: 05/01/2014 Activity Status: Closed
Date: 05/01/2014
Recipient: CCHD
Sender: Dohaney_t
Subject: Closure Report Referral to District
Message: See attached email
Events:
Event Type: Activity has been finished Date: 05/01/2014
Comment: Finished
03/19/2014 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/19/2014
Activity Closed Date: 04/30/2014 Activity Closed By: KASSEES_RP_1
Events:
Event Type: Activity has been finished Date: 04/30/2014
Comment: Finished
Comments:
Comment Date: 03/19/2014 User: KASSEES_RP_1
Description: This is a spill bucket installation inspection report initiated because of an incident that occured, causing a fuel spill at this site and severely damaging the regular fill port spill bucket. The UST system regular fillport had a new replacement spill bucket installed instead of the older one damaged in the incident. The contractor installing the new spill bucket was Guardien Fueling Technologies out of Jacksonville, FL. (PSSSC # PCC 056681). The contractor removed the damaged spill bucket then installed and tested the new one. The environmental consultant who performed the closure assessment upon the removal of the old damaged spill bucket was PPM Consultants. A copy of the Spill Bucket Closure Assessment Report has been received by our office. No signature was obtained as the inspection report was entered at the office and not onsite in the field. A copy of the inspection report mailed via USPS to the owner/operator upon its completion. If you have any questions or concerns please feel free to contact me at: phone number- (386) 758-2140 and / or E - mail address - Ramsey_Kassees@doh.state.fl.us.
03/19/2014 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/19/2014
Activity Closed Date: 04/30/2014 Activity Closed By: KASSEES_RP_1
Events:
Event Type: Activity has been finished Date: 04/30/2014
Comment: Finished
Comments:
Comment Date: 03/19/2014 User: KASSEES_RP_1
Description: This is a spill bucket closure inspection report initiated because of an incident that occured, causing a fuel spill at this site and severely damaging a the regular fill port spill bucket. The incident reportedly caused a spill of about 60 gallons on the concrete overburden, the surrounding asphalt pavement and some soil on the highway right of way adjacent to the UST system lot. The 60 gallon figure comes from the driver inventory accounting, according to the consultants on site (AAG, PPM, DGS). AAG was onsite to cperform the recovery and cleanup after the fire Department secured the area and neutralized the product volatility. Approximately 300 gallons of product, foam and water were recovered from the site. Additionally, a small amount of soil that was impacted on the highway right of way was removed by the AAG Technicians. The Wal-Mart Environmental Consultants, DGS, inspected the roadside side ditch and nearest storm sewer drain and reported that there were no impacts. PPM Consultants were contracted to perform the closure assessment for the damaged spill bucket removal. The damaged, regular unleaded gasoline, spill bucket was removed by Guardian Fueling Technologies out of Jacksonville (PSSSC # PCC 056681). It was replaced with a new spill bucket. The consultant performing the spill bucket closure assessment was PPM Consultants, some fuel contamination was encountered during the OVA screening of the pea gravel around the spill bucket. However, the samples sent to the laboratory for analysis returned mixed results. One sample (SB Closure @ 2 feet) is reported showing soils impacted by Benzene, Toluene and Xylenes; however, the actual numbers do not seem to be adding up. No signature was obtained as the inspection report was entered at the office and not onsite in the field. No spill bucket closure photos were obtained as the removed components were immediately discarded prior to my arrival. A copy of the inspection report mailed via USPS to the owner/operator upon its completion. If you have any questions or concerns please feel free to contact me at: phone number- (386) 758-2140 and / or E - mail address - Ramsey_Kassees@doh.state.fl.us.
01/28/2013 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/28/2013
Activity Closed Date: 02/05/2013 Activity Closed By: KASSEES_RP_1
Events:
Event Type: Activity has been finished Date: 02/05/2013
Comment: Finished
Comments:
Comment Date: 02/05/2013 User: KASSEES_RP_1
Description: Violations: There were no violations cited at the time of the inspection. Additional comments and notes: Please see the attached handwritten inspection field notes, site schematic and system description for raw details The facility owner/operator appears to have decided to opt out of performing monthly visual inspections (MVIs) as part of the release detection (RD). There were no current MVIs at the site, to speak of, at the time of the inspection, but the weekly electronic RD printouts were pretty consistantly printed out, organized and saved. The breakaway for the dispensing hose at dispenser pump # 4 is showing signs of wear, tear and weathering. Please replace it ASAP. Discharge Statement: There is no new information or obvious evidence of recent release or discharge. A copy of the inspection report mailed, via USPS to the owner/operator, by USPS upon its completion. If you have any questions or concerns please feel free to contact me at: phone number- (386) 758-2140 and / or E - mail address - Ramsey_Kassees@doh.state.fl.us .
01/28/2013 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 01/28/2013
Events:
Event Type: Activity has been finished Date: 01/28/2013
Comment: Finished
05/23/2012 Record Document Activity Shulaw, Benjamin J.
Activity Status: Closed
Contact Name: Cindy House Activity Closed Date: 05/23/2012
Events:
Event Type: Activity has been finished Date: 05/23/2012
Comment: Finished
04/01/2012 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 04/01/2012
Comment: Finished
Attachments:
Attachment Date: 04/01/2012 User: SHULAW_BJ_1
Description: 1Apr12 NCL
View Attachment
03/30/2012 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 1123
Rule: 62-761.710(2)(a), 62-761.710(2)(b), 62-761.710(2)(c), 62-761.710(2)(d), 62-761.710(2)(e), 62-761.710(2)(f), 62-761.710(2)(g), 62-761.710(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-761.640(3)(b)1-2, 62-761.640(3)(c) & 62-761.700(1)(c)5 b. Repair, operation, and maintenance - rules 62-761.700(1)(a)1, 62-761.700(1)(a)5, 62-761.700(1)(a)6 & 62-761.700(1)(c)3 c. Release detection - rules 62-761.600(1)(e), 62-761.610(3)(b), 62-761.640(2)(c)4, 62-761.640(2)(e), 62-761.640(3)(d), 62-761.640(3)(e)1-5 & 62-761.640(3)(e)9 d. Release detection response level descriptions - rules 62-761.600(1)(b) & 62-761.640(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-761.610(3)(a)1, 62-761.640(1)(a) & 62-761.640(4)(a) f. Financial responsibility - rule 62-761.400(3) g. Repairs and replacements - rule 62-761.700(1)(a)6 The following are not this rule's issues: Rules 62-761.450(1)(a)1, 62-761.450(1)(a)2, 62-761.450(1)(a)3 & 62-761.450(1)(a)4 are verbal notices of activities that may also be written Rule 62-761.450(1)(b) is a registration issue Rules 62-761.450(2), 62-761.450(3)(a) & 62-761.450(3)(b) are INF/DRF reporting issues Rules 62-761.600(1)(a)3 & 62-761.600(1)(f) are covered by rule 62-761.710(3) Anything with cathodic protection is covered by rule 62-761.710(3)
03/30/2012 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 03/30/2012
Activity Closed Date: 04/01/2012 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 04/01/2012
Comment: Finished
03/30/2012 Violation Closed Shulaw, Benjamin J.
Significance: SNC-B Status: Closed
Criteria ID: 1062
Rule: 62-761.600(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells; ATG in alarm; ATG panel hidden from view; ATG tape spool empty; buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. Facilities with continuous electronic leak detection ATG systems (e.g., Veeder-Root CSLD) are required to provide one passing test per product per month, although the system must be in daily operation with monthly summary logs. This method has no minimum fuel requirement. If there is a record keeping problem, see rule 62-761.710(2).
03/30/2012 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
03/30/2012 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
03/30/2012 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
05/12/2011 Record Document Activity Shulaw, Benjamin J.
Activity Status: Closed
Contact Name: Cindy House Activity Closed Date: 05/12/2011
Events:
Event Type: Activity has been finished Date: 05/12/2011
Comment: Finished
05/11/2011 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 05/11/2011
Comment: Finished
Attachments:
Attachment Date: 05/11/2011 User: SHULAW_BJ_1
Description: 11May11 NCL.
View Attachment
03/11/2011 Violation Closed Shulaw, Benjamin J.
Significance: SNC-B Status: Closed
Criteria ID: 1004
Rule: 62-761.400(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-761.710(2).
03/11/2011 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/11/2011
Comment: Finished
Attachments:
Attachment Date: 03/11/2011 User: SHULAW_BJ_1
Description: 11Mar11 NCL
View Attachment
03/11/2011 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 03/08/2011
Activity Closed Date: 03/11/2011 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 03/11/2011
Comment: Finished
03/11/2011 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
03/11/2011 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
08/18/2010 Record Document Activity Shulaw, Benjamin J.
Activity Status: Closed
Contact Name: Cindy House Activity Closed Date: 08/18/2010
Events:
Event Type: Activity has been finished Date: 08/18/2010
Comment: Finished
Comments:
Comment Date: 08/18/2010 User: SHULAW_BJ_1
Description: I have received documentation of the annual tests done 10Mar10.
03/28/2010 Editable Letter Activity Shulaw, Benjamin J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/28/2010
Comment: Finished
Attachments:
Attachment Date: 03/28/2010 User: SHULAW_BJ_1
Description: 28Mar10 NCL
View Attachment
03/19/2010 Violation Closed Shulaw, Benjamin J.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
Comments:
Comment Date: 01/02/2020 User: COLSON_NJ_1
Description: Phoenix Products Firesteel (MH15322), double walled, sub-base generator AST (EQ-625). System shares a remote fill - Morrison Bros. 715 (EQ-787). High level sensors - FPI Sensors International (EQ-817). Krueger level gauge (EQ-730). Reportedly equipped with a Morrison Bros. 9095A flow shutoff valve (EQ-356). Pneumercator LS600 tank interstice sensor (EQ-240).
03/18/2010 Attachment Shulaw, Benjamin J.
03/18/2010 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 03/19/2010
Activity Closed Date: 03/28/2010 Activity Closed By: SHULAW_BJ_1
Events:
Event Type: Activity has been finished Date: 03/28/2010
Comment: Finished
Comments:
Comment Date: 03/28/2010 User: SHULAW_BJ_1
Description: The Automatic Tank Gauging and Line Leak Detectors haven't been tested. Discharge Information: A non compliance letter citing the violations accompanies this inspection report; please find it attached. Please provide our office with documentation confirming the resolution of the cited violations within thirty days of receipt of this inspection report and attached non compliance letter. If you have any questions please contact me at 386-623-0831 cell, fax 386-758-2187, or office 386-758-2140 or email Benjamin_Shulaw@doh.state.fl.us
11/14/2008 Attachment Shulaw, Benjamin J.
11/14/2008 Emergency Preparedness Information Activity Shulaw, Benjamin J.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 11/14/2008
11/14/2008 Site Inspection Activity Closed Shulaw, Benjamin J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/14/2008
Activity Closed Date: 11/14/2008 Activity Closed By: SHULAW_BJ_1
Comments:
Comment Date: 11/14/2008 User: SHULAW_BJ_1
Description: Should make better notes on problems and their resolution as well as system condition on inspection logs. Discharge Information: There is no new information or obvious evidence of recent release or discharge, within the last year. For more detailed discharge information, please consult the Petroleum Clean Up Section at the F D E P H.Q. in Tallahassee; or the F D E P Northeast District Office in Jacksonville; or the official compliance facility file at the Columbia C H D, Environmental Health Section, in Lake City. Other Comments: For more inspection details and information; please see the copy of the inspection field notes, site schematic and system description that is electronically, as well as physically, attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058.
11/14/2008 Attachment Shulaw, Benjamin J.
04/28/2008 Site Inspection Activity Closed Oymayan, Avo J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/28/2008
Activity Closed Date: 07/16/2009 Activity Closed By: OYMAYAN_AJ_1
Comments:
Comment Date: 04/28/2008 User: OYMAYAN_AJ_1
Description: Copies of the annual function tests for the release detection equipment have been provided to our office on 4-25-2008. They were as follows: 1). The annual MLLD function test was performed by Tanknology Inc. on 9-17-2007, with passing results. 2).The anuual ATG Monitor function test was performed by Murphy Oil personell on with passing results. 3).The annual sensors function test was performed by Murphy Oil personell on with passing results. This facility has no more open violations and it is therefore in compliance without enforcement (CWOE).
04/14/2008 Editable Letter Activity Oymayan, Avo J.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Comments:
Comment Date: 04/14/2008 User: OYMAYAN_AJ_1
Description: This second noncompliance letter has been addressed mistakenly to Mr. Larry Freeman with Jiffy Food Store # 316. It was meant to be addressed to the facility shown on the lettter, that being Murphy USA # 5671, in Lake City, Florida. A copy of this letter was mailed properly to Murphy USA #5671.
04/14/2008 Editable Letter Activity Oymayan, Avo J.
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
11/28/2007 Violation Closed Oymayan, Avo J.
Significance: Minor Status: Closed
Criteria ID: 1117
Rule: 62-761.700(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, ATGs, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non-discriminating, or tied into electrical circuits. ATG probes inside of tanks require calibration testing, if used for release detection as well as inventory measurements.
11/28/2007 Editable Letter Activity Oymayan, Avo J.
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
11/19/2007 Site Inspection Activity Closed Oymayan, Avo J.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 11/19/2007
Activity Closed Date: 11/28/2007 Activity Closed By: OYMAYAN_AJ_1
Comments:
Comment Date: 11/19/2007 User: OYMAYAN_AJ_1
Description: Violations Summary: There were three violations, grouped into one, cited at the time of the inspection, as follows: 1). Copies of the annual A T G Monitor function test, the annual U S T I. M. , sump and dispenser sensors function test, and the annual line leak detector function test were not provided for review at the time of the inspection. Please retrieve this information and provide it to our office for review. A non compliance letter citing the violation accompanies this inspection report. Please find it attached. Please provide our office with documentation conforming the resolution of the cited violation within thirty days of receipt of this non compliance letter. Additional Notes: Please find out and provide our office with information whether or not the facility's Overfill Protection includes a BCV (ball check valve), in addition to the existing fillport flappers. A facility of this type is required to have either one of these overfill protection devices, and not both. The vapor recovery ports could have built in BCV's and if so, they would render the flapper valves not efficient in providing overfill protection. So, please clarify this issue. Discharge Information: There is no new information or obvious evidence of recent release or discharge. Furthermore, it appears as if the facility has no history of previous release or discharge, as there does not appear to be any record of past contamination. Other Comments: For more inspection details and information, please see the copy of the inspection fieldnotes, site schematic and system description that is electronically as well as physically attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058.
11/19/2007 Emergency Preparedness Information Activity Oymayan, Avo J.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 11/19/2007
10/29/2007 Site Inspection Activity Closed Oymayan, Avo J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/29/2007
Activity Closed Date: 11/19/2007 Activity Closed By: OYMAYAN_AJ_1
Comments:
Comment Date: 11/09/2007 User: OYMAYAN_AJ_1
Description: Could not do this inspection on 10/29/2007 due to scheduling conflict between my office and Murphy Oil. Will reschedule. Please disregard this inspection and see the inspection initiated on 11-19-2007.
08/10/2007 Site Inspection Activity Closed Oymayan, Avo J.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/10/2007
Activity Closed Date: 08/10/2007 Activity Closed By: OYMAYAN_AJ_1
Comments:
Comment Date: 08/10/2007 User: OYMAYAN_AJ_1
Description: Adequate response has been received by the department that confirms that the following violations have been resolved: 1). All of the alarm sensors in the fuel dispenser liners have been re- positioned properly. 2). The fuel dispensing hose on pump 7 has been replaced. There are no more open violations at this facility. It is in compliance without enforcement (C W O E).
05/24/2007 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 05/24/2007
05/23/2007 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 05/23/2007
05/23/2007 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 05/23/2007
03/22/2007 Editable Letter Activity Oymayan, Avo J.
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 03/22/2007
Comment: Sent on Thu Mar 22 00:00:00 EST 2007
Attachments:
Attachment Date: 03/22/2007 User: OYMAYAN_AJ_1
Description: NCL Report
View Attachment
03/21/2007 Violation Closed Oymayan, Avo J.
Significance: Minor Status: Closed
Criteria ID: 1105
Rule: 62-761.700(1)(a)1.a., 62-761.700(1)(a)1.b., 62-761.700(1)(a)1.c., 62-761.700(1)(a)1.d.
Comments: Mark this as out of compliance if you observe a needed repair that hasn't been completed, and the potential for a release exists. Examples of components that would need repair include (but are not limited to) leaking dispensers, cracked spill containment, improperly anchored shear valves, or any compromised containment component. Upon the detection of one of the above conditions, has the facility initiated and completed repairs?
03/21/2007 Violation Closed Oymayan, Avo J.
Significance: Minor Status: Closed
Criteria ID: 1059
Rule: 62-761.600(1)(a)2.
Comments: Mark this as out of compliance if release detection systems are not functioning or not maintained properly. The inspector will have to know what release detection components have been installed at the facility. Furthermore, develop a library of installation and system operation specifications. These documents will assist you in determining calibration/maintenance as required by the manufacturer. Additional guidance can be found in the Appendix sections of the USEPA "List of Leak Detection Evaluations for Underground Storage Tank Systems" and the DEP Master Equipment List. Installations - have the release detection components been function tested? Just because a piece of equipment is new out of the box does not mean it is fully functional. Have it demonstrated! Calibration/Maintenance - the facility must provide documentation attesting to these operability tests. Operation - The RDRL must be developed, and the facility personnel must be knowledgeable of all the components of the release detection system. Theoretically, they should be able to demonstrate to you how they monitor the release detection system. See rule 62-761.700(1)(c)3
02/19/2007 Site Inspection Activity Closed Oymayan, Avo J.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 02/19/2007
Activity Closed Date: 03/22/2007 Activity Closed By: OYMAYAN_AJ_1
Comments:
Comment Date: 03/21/2007 User: OYMAYAN_AJ_1
Description: Violations Summary: There were two violations at the time of the inspection, as follows: 1). Dispenser hose on pump 7 showing signs of excessive wear and tear. Please replace / repair this fuel hose. 2). All sump sensors in the fuel dispenser liners are positioned improperly (set too high). Please position these sensors properly to ensure adequate release detection. A non compliance letter citing the violations accompanies this inspection report. Please find it attached. Please provide our office with documentation confirming the resolution of the cited violations within thirty days of receipt of this inspection report and attached non compliance report. Additional Notes: There were several issues noted during the inspection that were not cited as violations, nevertheless, should be addressed. They are as follows: 1). The premium gasoline sump containment unit contained about three inches of water, below all piping. Please remove all liquid and keep sump clean and dry. 2). The regular gasoline sump containment unit contained about six inches of water, below all piping. Please remove all liquid and keep sump clean and dry. 3). Both premium and regular gasoline fillport covers are in need of repainting. 4). Both Instertitial Monitoring sump sensors are woking, but are "sticky" at times. Please look into this matter to ensure that these sensors are working continuously and effectively to ensure proper release detection . Discharge Information: There is no new information or obvious evidence of recent release or discharge. Furthermore, it appears as if the facility has no history of previous release or discharge, as there does not appear to be any record of past contamination. Other Comments: For more inspection details and information, please see the copy of the inspection field notes, site schematics and system description, that is electronically as well as physically attached to this inspection report. If you have any questions or concerns, please feel free to contact me at (386) 758-2140 or (386) 758-1058.
02/14/2007 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 02/14/2007
11/25/2006 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/25/2006
Activity Closed Date: 11/25/2006 Activity Closed By: KASSEES_RP_1
Comments:
Comment Date: 11/25/2006 User: KASSEES_RP_1
Description: A T C R (reinspection) performed on 11/22/2006 confirms that the following violation has been resolved: 1). The inaccessible sump containment unit, was made accessible. It appears to be in good condition; also clean and dry. This facility is in compliance without enforcement.
09/22/2006 Emergency Preparedness Information Activity Kassees, Ramsey D.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/22/2006
06/14/2006 Violation Closed Kassees, Ramsey D.
Significance: Minor Status: Closed
Criteria ID: 1115
Rule: 62-761.700(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
06/14/2006 Editable Letter Activity Kassees, Ramsey D.
Activity Title: District Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/14/2006
Comment: Sent on Wed Jun 14 01:43:34 EST 2006
Attachments:
Attachment Date: 06/14/2006 User: KASSEES_RP_1
Description: NCL Report
View Attachment
05/30/2006 Site Inspection Activity Closed Kassees, Ramsey D.
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 05/30/2006
Activity Closed Date: 06/14/2006 Activity Closed By: KASSEES_RP_1
Comments:
Comment Date: 06/14/2006 User: KASSEES_RP_1
Description: Only one violation is cited at this time (sump containment units holding excessive liquid accumulation and not being adequately accessible), even though a second violation (failure to provide RDRL) was noted, on the inspection report field notes, at the time of the inspection. This second violation was corrected the next day when a written RDRL was found on file. Therefore this corrected violation was not cited.
04/21/2005 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/29/2004 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
05/27/2003 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
02/07/2002 Legacy Activity Defalco, Lynal
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
12/14/2000 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
01/25/2000 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
08/03/1999 Legacy Activity Kassees, Ramsey D.
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed