11/12/2024 Enforcement Tracking Activity Chang, Louise
Activity Status: Open
05/20/2024 Enforcement Referral Activity Tykoski, Bradley R
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 11/12/2024
Events:
Event Type: Activity has been submitted for approval Date: 05/20/2024
Comment: Submitted for approval by: Bradley R Tykoski: Site is being referred as they will have unresolved violations after 90 days of Compliance Assistance. They have a new tank on order and awaiting delivery.
Events:
Event Type: Activity has been finished Date: 11/12/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 11/12/2024
Comment: Accepted by Louise Chang: Case to be assigned to Colin Campbell
Events:
Event Type: Activity/Document was acknowledged on this date Date: 11/12/2024
Comment: Acknowledged and Assigned by Louise Chang
Events:
Event Type: Activity has been assigned Date: 11/12/2024
Comment: Assigned to Louise Chang
Comments:
Comment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Request site be granted additional Compliance Assistance with Sarasota County as they await delivery on a new AST. Lead time for new tank purchase was 32-34 weeks putting estimated delivery in beginning of October 2024.
Comments:
Comment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Site is being referred as they will have unresolved violations after 90 days of Compliance Assistance. They have a new tank on order and awaiting delivery.
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #5
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #3
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #4
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Referral Letter Email
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Referral Letter
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Ritz Carlton Hotel Violation Response
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #2
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #6
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: FDEP Referral Memorandum
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #1
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #7
View Attachment
05/20/2024 Enforcement Referral Activity Tykoski, Bradley R
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 11/12/2024
Events:
Event Type: Activity has been submitted for approval Date: 05/20/2024
Comment: Submitted for approval by: Bradley R Tykoski: Site is being referred as they will have unresolved violations after 90 days of Compliance Assistance. They have a new tank on order and awaiting delivery.
Events:
Event Type: Activity has been finished Date: 11/12/2024
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 11/12/2024
Comment: Accepted by Louise Chang: Case to be assigned to Colin Campbell
Events:
Event Type: Activity/Document was acknowledged on this date Date: 11/12/2024
Comment: Acknowledged and Assigned by Louise Chang
Events:
Event Type: Activity has been assigned Date: 11/12/2024
Comment: Assigned to Louise Chang
Comments:
Comment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Request site be granted additional Compliance Assistance with Sarasota County as they await delivery on a new AST. Lead time for new tank purchase was 32-34 weeks putting estimated delivery in beginning of October 2024.
Comments:
Comment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Site is being referred as they will have unresolved violations after 90 days of Compliance Assistance. They have a new tank on order and awaiting delivery.
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #5
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #3
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #4
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Referral Letter Email
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Referral Letter
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Ritz Carlton Hotel Violation Response
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #2
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #6
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: FDEP Referral Memorandum
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #1
View Attachment
Attachments:
Attachment Date: 05/20/2024 User: TYKOSKI_B_1
Description: Tank Additional Photo #7
View Attachment
02/29/2024 Electronic Communication Activity Tykoski, Bradley R
Activity Closed Date: 02/29/2024 Activity Status: Closed
Date: 02/29/2024
Recipient: Brad Tykoski
Sender: Gale Scott from Ritz-Carlton Engineering
Subject: Written Response for FDEP ID 9803858 Compliance
Message: See attachment.
Events:
Event Type: Activity has been finished Date: 02/29/2024
Comment: Finished
Attachments:
Attachment Date: 02/29/2024 User: TYKOSKI_B_1
Description: Inspection Response Email
View Attachment
Attachments:
Attachment Date: 02/29/2024 User: TYKOSKI_B_1
Description: Inspection Response
View Attachment
02/27/2024 Record Document Activity Tykoski, Bradley R
Activity Status: Closed
Contact Name: Gale Scott Activity Closed Date: 02/28/2024
Events:
Event Type: Activity has been finished Date: 02/28/2024
Comment: Finished
02/14/2024 Violation Open Tykoski, Bradley R
Significance: SNC-B Status: Open
Criteria ID: 7019
Rule: 62-762.501(1)(b), 62-762.501(1)(b)1, 62-762.501(1)(b)1.a, 62-762.501(1)(b)1.b, 62-762.501(1)(b)1.c, 62-762.502(1)(b)1, 62-762.502(1)(b)1.a, 62-762.502(1)(b)1.b, 62-762.502(1)(b)1.c, 62-762.502(1)(b)
02/14/2024 Electronic Communication Activity Tykoski, Bradley R
Activity Closed Date: 02/14/2024 Activity Status: Closed
Date: 02/14/2024
Recipient: Gale Scott
Sender: Brad Tykoski
Subject: Upcoming Mandatory Compliance Inspection for RITZ CARLTON HOTEL FAC ID: 9803858
Message: See attachment.
Events:
Event Type: Activity has been finished Date: 02/14/2024
Comment: Finished
02/14/2024 Editable Letter Activity Tykoski, Bradley R
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been submitted for approval Date: 02/14/2024
Comment: Submitted for approval by: Bradley R Tykoski
Events:
Event Type: Activity has been finished Date: 02/14/2024
Comment: Finished
Events:
Event Type: Document has been sent Date: 02/14/2024
Comment: Sent
Events:
Event Type: Compliance Assistance Offer Verbal Date: 02/14/2024
Comment: Compliance Assistance Offer Verbal
Events:
Event Type: Activity/Document has been approved Date: 02/14/2024
Comment: Approved by John Hickey: approved
Attachments:
Attachment Date: 02/14/2024 User: TYKOSKI_B_1
Description: CAO Email
View Attachment
Attachments:
Attachment Date: 02/14/2024 User: TYKOSKI_B_1
Description: CAO
View Attachment
02/14/2024 Site Inspection Activity Closed Tykoski, Bradley R
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/14/2024
Activity Closed Date: 02/14/2024 Activity Closed By: TYKOSKI_B_1
Events:
Event Type: Activity has been submitted for approval Date: 02/14/2024
Comment: Submitted for approval by: Bradley R Tykoski
Events:
Event Type: Activity has been finished Date: 02/14/2024
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 02/14/2024
Comment: Approved by John Hickey: Approved
Comments:
Comment Date: 02/14/2024 User: TYKOSKI_B_1
Description: Effective June 25, 2024, regardless of the date of installation of the storage tank system, fillbox covers shall be marked or the fill connection tagged and facility signage shall be prominently displayed in accordance with the following document, hereby adopted and incorporated by reference: Using the API Color-Symbol System to Identify Equipment, Vehicles, and Transfer Points for Petroleum Fuels and Related Products at Dispensing and Storage Facilities and Distribution Terminals, API Recommended Practice 1637, 4th Edition, April 2020. API 1637 is a copyright protected document and is available for inspection at the Department of Environmental Protection or the Department of State address provided in subsection 62-762.211(1), F.A.C., or the American Petroleum Institute information provided in paragraph 62-762.211(2)(b), F.A.C.. Mark spill bucket/fillbox in accordance with the API Color-Symbol System by/before June 25, 2024.
02/14/2024 Violation Open Tykoski, Bradley R
Significance: Minor Status: Open
Criteria ID: 7091
Rule: 62-762.701(4)(c), 62-762.702(4)(c)
02/14/2024 Violation Open Tykoski, Bradley R
Significance: SNC-B Status: Open
Criteria ID: 7069
Rule: 62-762.601(2), 62-762.601(2)(a), 62-762.601(2)(a)1, 62-762.601(2)(a)2, 62-762.601(2)(a)3, 62-762.601(2)(a)4, 62-762.601(2)(a)5, 62-762.601(2)(a)6, 62-762.601(2)(a)7, 62-762.601(2)(a)8, 62-762.602(2), 62-762.602(2)(a), 62-762.602(2)(a)1, 62-762.602(2)(a)2, 62-762.602(2)(a)3, 62-762.602(2)(a)4, 62-762.602(2)(a)5, 62-762.602(2)(a)6, 62-762.602(2)(a)7, 62-762.602(2)(a)8
02/14/2024 Violation Closed Tykoski, Bradley R
Significance: Minor Status: Closed
Criteria ID: 7043
Rule: 62-762.501(2)(f)2
02/14/2024 Violation Open Tykoski, Bradley R
Significance: Minor Status: Open
Criteria ID: 7030
Rule: 62-762.501(1)(f), 62-762.502(1)(f)
04/02/2021 Editable Letter Activity Neuhaus, Andrew
Activity Title: In Compliance Letter Activity Status: Closed
Description: Site
Events:
Event Type: Activity has been submitted for approval Date: 04/02/2021
Comment: Submitted for approval by: Andrew Neuhaus
Events:
Event Type: Document has been sent Date: 04/02/2021
Comment: Sent
Events:
Event Type: Activity/Document has been approved Date: 04/20/2021
Comment: Approved by Maggie A Murphy: approved
Events:
Event Type: Activity has been finished Date: 04/20/2021
Comment: Finished
Attachments:
Attachment Date: 04/02/2021 User: NEUHAUS_AE_1
Description: ICL
View Attachment
03/29/2021 Electronic Communication Activity Neuhaus, Andrew
Activity Closed Date: 03/29/2021 Activity Status: Closed
Date: 03/29/2021
Recipient: Gale Scott
Sender: Andrew Neuhaus
Subject: Schedule Inspection
Message: Attached.
Events:
Event Type: Activity has been finished Date: 03/29/2021
Comment: Finished
03/23/2021 Site Inspection Activity Closed Neuhaus, Andrew
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/23/2021
Activity Closed Date: 04/02/2021 Activity Closed By: NEUHAUS_AE_1
Events:
Event Type: Activity/Document has been approved Date: 03/30/2021
Comment: Approved by Maggie A Murphy: approved
Events:
Event Type: Activity has been finished Date: 04/02/2021
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 03/29/2021
Comment: Submitted for approval by: Andrew Neuhaus
02/08/2019 Editable Letter Activity Neuhaus, Andrew
Activity Title: In Compliance Letter Activity Status: Closed
Description: Compliance Assistance Offer Letter - CORRECTED
Events:
Event Type: Activity/Document has been approved Date: 02/11/2019
Comment: Approved by John Hickey: Approved
Events:
Event Type: Activity has been finished Date: 02/12/2019
Comment: Finished
Events:
Event Type: Activity has been submitted for approval Date: 02/08/2019
Comment: Submitted for approval by: Andrew Neuhaus
Events:
Event Type: Document has been sent Date: 02/08/2019
Comment: Sent
Attachments:
Attachment Date: 02/08/2019 User: NEUHAUS_AE_1
Description: ICL
View Attachment
01/31/2019 Electronic Communication Activity Neuhaus, Andrew
Activity Closed Date: 01/31/2019 Activity Status: Closed
Date: 01/31/2019
Recipient: Gale Scott
Sender: Andrew Neuhaus
Subject: Schedule Inspection
Message: Attached
Events:
Event Type: Activity has been finished Date: 01/31/2019
Comment: Finished
01/29/2019 Site Inspection Activity Closed Neuhaus, Andrew
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 01/29/2019
Activity Closed Date: 01/31/2019 Activity Closed By: NEUHAUS_AE_1
Events:
Event Type: Activity has been submitted for approval Date: 01/31/2019
Comment: Submitted for approval by: Andrew Neuhaus
Events:
Event Type: Activity/Document has been approved Date: 01/31/2019
Comment: Approved by John Hickey: Approved
Events:
Event Type: Activity has been finished Date: 01/31/2019
Comment: Finished
10/24/2016 Site Inspection Activity Closed Ramsey, Timothy H
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/24/2016
Activity Closed Date: 10/24/2016 Activity Closed By: RAMSEY_TH_2
Events:
Event Type: Activity has been finished Date: 10/24/2016
Comment: Finished
Comments:
Comment Date: 10/24/2016 User: RAMSEY_TH_2
Description: > John Bond and Gale Scott assisted with the inspection at the facility. > Release detection methods for the facility's AST system are: electronic monitoring for the interstice of the AST; visual monitoring for all components installed on the AST system. > The facility's RDRL is satisfactory, and the RDRL is attached to the Facility Information in FIRST. > The facility's 2016-2017 storage tank registration placard is posted in the generator enclosure. > Financial responsibility records and CFR for the facility's AST system are satisfactory. > Monthly electronic and visual AST release detection records from November 2014, to date, are satisfactory. > Testing records indicate Tampa Armature Works conducted annual operability tests for the AST electronic release detection equipment on 11/25/2015. > The 1,500-gallon double-wall steel UL-142 sub-base generator AST is in good condition > Krueger level gauge installed on the AST is satisfactory. > Spill bucket installed at the AST fill pipe is satisfactory, and the spill bucket is marked in accordance with API RP-1637 to identify the product stored in the tank. > AST fill pipe is equipped with a 2" threaded cap. > No fuel leaks were observed on the AST system. > All indicator lights and the audible alarms on the annunciator located at the gen-set and at the remote annunciator located in the security office are operational. The annunciators indicate no active alarms. > Leak / rupture circuits on both annunciators are clearly labeled. > A copy of the inspection report was provided to Gale Scott by email.
10/24/2016 Phone Conversation Activity Ramsey, Timothy H
Call Type: Incoming Activity Status: Closed
Phone Number: 941-309-2235 Activity Closed Date: 10/24/2016
Subject: Called Gale Scott with facility to schedule Routine inspection and discuss required records for inspection
Events:
Event Type: Activity has been finished Date: 10/24/2016
Comment: Finished
10/24/2016 Electronic Communication Activity Ramsey, Timothy H
Activity Closed Date: 10/24/2016 Activity Status: Closed
Date: 10/24/2016
Recipient: Gale Scott
Sender: Tim Ramsey
Subject: Copy of Routine storage tank inspection
Message: Emailed copy of inspection to Gale Scott
Events:
Event Type: Activity has been finished Date: 10/24/2016
Comment: Finished
11/17/2014 Site Inspection Activity Closed Wall, Kenneth
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 11/17/2014
Activity Closed Date: 11/17/2014 Activity Closed By: WALL_KD_1
Events:
Event Type: Activity has been finished Date: 11/17/2014
Comment: Finished
02/13/2013 Site Inspection Activity Closed Wall, Kenneth
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/13/2013
Activity Closed Date: 02/15/2013 Activity Closed By: WALL_KD_1
Events:
Event Type: Activity has been finished Date: 02/15/2013
Comment: Finished
05/17/2011 Attachment Wall, Kenneth
05/16/2011 Site Inspection Activity Closed Wall, Kenneth
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/16/2011
Activity Closed Date: 05/16/2011 Activity Closed By: WALL_KD_1
Events:
Event Type: Activity has been finished Date: 05/16/2011
Comment: Finished
07/14/2009 Attachment Wall, Kenneth
07/14/2009 Site Inspection Activity Closed Wall, Kenneth
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 07/14/2009
Activity Closed Date: 07/27/2009 Activity Closed By: WALL_KD_1
Comments:
Comment Date: 07/14/2009 User: WALL_KD_1
Description: Release detection methods for the facility's AST system are outlined on the RDRL, and the RDRL is attached to the General Facility Information. Tank registration placard is current and onsite. Please complete the Certification of Financial Responsibility form provided during the inspection. Monthly visual release detection records for the AST system for March 2008 through June 2009 are well organized and complete. The 1,500-gallon double-wall steel UL-142 sub-base generator AST is satisfactory. Recommend refinishing the steel AST to prevent corrosion. The steel spill bucket at the AST fill pipe is satisfactory, and the spill bucket is marked to identify the product stored in the tank. A threaded pipe cap is installed on the AST fill pipe. No fuel leaks were observed at the fuel hoses within the generator enclosure. The annunciator panels / tank monitors located in the generator enclosure and at the security/loss prevention office are operational, and no alarms are active on the annunciator panels. The tank rupture sensor circuits on both annunciators have been clearly labeled. Annual operability test record for the AST electronic release detection equipment was performed on 7/16/2009 by Tampa Armature Works.
02/27/2008 Site Inspection Activity Closed Telemeco-Anders, Debbie Y.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 02/27/2008
Activity Closed Date: 03/10/2008 Activity Closed By: ANDERS_DT_1
Comments:
Comment Date: 02/27/2008 User: ANDERS_DT_1
Description: Annual Compliance Inspection 3/10/08 Release Detection * RDRL is on file. * Monthly visual release detection records for the past 12 months are satisfactory. Observations * Current registration placard is posted * The subbase generator AST (manufactured by ComFab Inc. EQ#-386), fuel hoses, spill container, vents and Krugar level gauge are in good condition. * No alarms are activated on the Kohler annunciator. * The leak sneso circuit on the security office annunciator was not accessed. * CFR was current. Tests * Annual Operability test was performed 4/18/07 on the interstitial monitoring equipment byTampa Armature Works. NOTE: Monthly visuals shall not exceed 35 day intervals. (See April 2-May 11, 2007, May 11-June 17, 2007, and August 4-September 21, 2007 inspection records)
04/20/2007 Record Document Activity Telemeco-Anders, Debbie Y.
Activity Status: Closed
Contact Name: Gale Scott Activity Closed Date: 04/20/2007
04/17/2007 Attachment Telemeco-Anders, Debbie Y.
04/17/2007 Site Inspection Activity Closed Telemeco-Anders, Debbie Y.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/17/2007
Activity Closed Date: 04/20/2007 Activity Closed By: ANDERS_DT_1
Comments:
Comment Date: 04/17/2007 User: ANDERS_DT_1
Description: Annual Compliance Inspection 4/18/07 Release Detection * RDRL is on file. * Monthly visual release detection records for the past 16 months are satisfactory. Observations * Current registration placard is posted * The subbase generator AST, fuel hoses, spill container, vents and Krugar level gauge are in good condition. * No alarms are activated on the Kohler annunciator. * CFR was updated. Tests * Annual Operability test was performed 4/18/07 on the interstitial monitoring equipment byTampa Armature Works. RECOMMEND: Labeling or marking the leak sensor cirsuit on the security office annunciator. NOTE: Monthly visuals shall not exceed 35 day intervals (See January 3 to February 10 20007)
04/12/2006 Legacy Activity Benanti, Linda G.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/13/2005 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/12/2004 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
04/01/2003 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
08/23/2002 Legacy Activity Starkey, Dorene M.
Activity Name: RESPONSE RECEIVED BY DEPARTMENT Activity Status: Closed
05/30/2002 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 400(1)-(2)
05/30/2002 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 400(2)(a)6
05/30/2002 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 640(2)(e)
05/30/2002 Violation Closed Starkey, Dorene M.
Significance: Minor Status: Closed
Rule: 710(1)
05/30/2002 Legacy Activity Starkey, Dorene M.
Activity Name: TANK ANNUAL COMPLIANCE INSPECTION Activity Status: Closed
09/07/2001 Legacy Activity Starkey, Dorene M.
Activity Name: TANK INSTALLATION - FINAL INSPECTION Activity Status: Closed