Facility ID: 9809544
Facility Name: HAMILTONS GENERAL STORE
 
06/03/2024 Editable Letter Activity Merritt, Sara
Activity Title: Warning Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/03/2024
Comment: Finished
Attachments:
Attachment Date: 06/03/2024 User: MERRITT_S
Description: Warning Letter
View Attachment
05/20/2024 Violation Open Merritt, Sara
Significance: SNC-B Status: Open
Criteria ID: 7012
Rule: 62-762.431(2)
05/20/2024 Document Management Activity Merritt, Sara
Activity Title: Incident Notification Form Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 05/20/2024
Comment: Finished
Attachments:
Attachment Date: 05/20/2024 User: MERRITT_S
Description: INF - transition sump
View Attachment
01/31/2024 Incident Activity Merritt, Sara
Activity Status: Open
08/30/2023 Enforcement Tracking Activity Gillman, Mark
Activity Status: Open
08/24/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 7007
Rule: 62-762.411(4)
08/24/2023 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 08/30/2023
Events:
Event Type: Activity has been submitted for approval Date: 08/24/2023
Comment: Submitted for approval by: Muhammad Rafique Khan: 2023/9/24 few violations were closed today by virtue of testing they submitted on 8-9-2023,two new violations were added for inf and repair or replacement of cracked transition sump #1. rest of the violations are still waiting response.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 08/30/2023
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been finished Date: 08/30/2023
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 08/30/2023
Comment: Accepted by Mark Gillman: Accepted
Events:
Event Type: Activity has been assigned Date: 08/30/2023
Comment: Assigned to Mark Gillman
Comments:
Comment Date: 08/24/2023 User: KHAN_MR_1
Description: 2023/9/24 few violations were closed today by virtue of testing they submitted on 8-9-2023,two new violations were added for inf and repair or replacement of cracked transition sump #1. rest of the violations are still waiting response.
Comments:
Comment Date: 08/24/2023 User: KHAN_MR_1
Description: 2023/9/24 few violations were closed today by virtue of testing they submitted on 8-9-2023,two new violations were added for inf and repair or replacement of cracked transition sump #1. rest of the violations are still waiting response.
08/24/2023 Enforcement Referral Activity Khan, Muhammad Rafique
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 08/30/2023
Events:
Event Type: Activity has been submitted for approval Date: 08/24/2023
Comment: Submitted for approval by: Muhammad Rafique Khan: 2023/9/24 few violations were closed today by virtue of testing they submitted on 8-9-2023,two new violations were added for inf and repair or replacement of cracked transition sump #1. rest of the violations are still waiting response.
Events:
Event Type: Activity/Document was acknowledged on this date Date: 08/30/2023
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been finished Date: 08/30/2023
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 08/30/2023
Comment: Accepted by Mark Gillman: Accepted
Events:
Event Type: Activity has been assigned Date: 08/30/2023
Comment: Assigned to Mark Gillman
Comments:
Comment Date: 08/24/2023 User: KHAN_MR_1
Description: 2023/9/24 few violations were closed today by virtue of testing they submitted on 8-9-2023,two new violations were added for inf and repair or replacement of cracked transition sump #1. rest of the violations are still waiting response.
Comments:
Comment Date: 08/24/2023 User: KHAN_MR_1
Description: 2023/9/24 few violations were closed today by virtue of testing they submitted on 8-9-2023,two new violations were added for inf and repair or replacement of cracked transition sump #1. rest of the violations are still waiting response.
08/24/2023 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 7075
Rule: 62-762.701(1), 62-762.701(1)(a), 62-762.701(1)(a)1, 62-762.701(1)(a)2, 62-762.701(1)(a)3, 62-762.702(1), 62-762.702(1)(a), 62-762.702(1)(a)1, 62-762.702(1)(a)2, 62-762.702(1)(a)3
08/09/2023 Record Document Activity Khan, Muhammad Rafique
Activity Status: Closed
Contact Name: Magnificent Petroleum Activity Closed Date: 08/24/2023
Events:
Event Type: Activity has been finished Date: 08/24/2023
Comment: Finished
Comments:
Comment Date: 08/24/2023 User: KHAN_MR_1
Description: Magnificent Petroleum Sent: Wednesday, August 9, 2023 1:12 PM sent atg testing,for dispenser liner,transition sump integrity testing(TRANSITION SUMP # 1 IS CRACKED PER TESTING RESULTS OF 7-13-2023)
06/06/2023 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 7065
Rule: 62-762.601(1)(e), 62-762.602(1)(e)
06/06/2023 Editable Letter Activity Khan, Muhammad Rafique
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/06/2023
Comment: Finished
Events:
Event Type: Document has been sent Date: 06/06/2023
Comment: Sent
Attachments:
Attachment Date: 06/06/2023 User: WILSON_ML_1
Description: Compliance Assistance Offer Letter
View Attachment
06/06/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 7090
Rule: 62-762.701(4)(b), 62-762.701(4)(b)1, 62-762.701(4)(b)2, 62-762.702(4)(b), 62-762.702(4)(b)1, 62-762.702(4)(b)2
06/06/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 7041
Rule: 62-762.501(2)(e)3, 62-762.501(2)(e)3.a, 62-762.501(2)(e)3.b, 62-762.501(2)(e)4, 62-762.502(2)(e)4, 62-762.502(2)(e)4.a, 62-762.502(2)(e)4.b, 62-762.502(2)(e)5
06/06/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 7072
Rule: 62-762.601(7), 62-762.602(7)
06/06/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 7072
Rule: 62-762.601(7), 62-762.602(7)
06/06/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 7089
Rule: 62-762.701(4), 62-762.701(4)(a), 62-762.701(4)(a)1, 62-762.701(4)(a)1.a, 62-762.701(4)(a)1.b, 62-762.701(4)(a)1.c, 62-762.701(4)(a)1.d, 62-762.701(4)(a)1.e, 62-762.701(4)(a)1.f, 62-762.701(4)(a)2, 62-762.702(4), 62-762.702(4)(a), 62-762.702(4)(a)1, 62-762.702(4)(a)1.a, 62-762.702(4)(a)1.b, 62-762.702(4)(a)1.c, 62-762.702(4)(a)1.d, 62-762.702(4)(a)2
06/06/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 7001
Rule: 62-762.101(5)
06/06/2023 Violation Closed Khan, Muhammad Rafique
Significance: SNC-B Status: Closed
Criteria ID: 7009
Rule: 62-762.421(2), 62-762.421(3)(c)
06/06/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 7089
Rule: 62-762.701(4), 62-762.701(4)(a), 62-762.701(4)(a)1, 62-762.701(4)(a)1.a, 62-762.701(4)(a)1.b, 62-762.701(4)(a)1.c, 62-762.701(4)(a)1.d, 62-762.701(4)(a)1.e, 62-762.701(4)(a)1.f, 62-762.701(4)(a)2, 62-762.702(4), 62-762.702(4)(a), 62-762.702(4)(a)1, 62-762.702(4)(a)1.a, 62-762.702(4)(a)1.b, 62-762.702(4)(a)1.c, 62-762.702(4)(a)1.d, 62-762.702(4)(a)2
06/06/2023 Violation Closed Khan, Muhammad Rafique
Significance: Minor Status: Closed
Criteria ID: 7030
Rule: 62-762.501(1)(f), 62-762.502(1)(f)
05/23/2023 Site Inspection Activity Closed Khan, Muhammad Rafique
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 05/23/2023
Activity Closed Date: 06/06/2023 Activity Closed By: KHAN_MR_1
Events:
Event Type: Activity has been finished Date: 06/06/2023
Comment: Finished
Comments:
Comment Date: 05/23/2023 User: KHAN_MR_1
Description: A copy of this report will be sent to Nur Hossain @ TEACH_2_CHILDREN@YAHOO.COM Tank #1 - 15,000 gallon, Newberry double-walled, steel, compartmented aboveground storage tank (EQ #338). Tank #2 - 15,000 gallon, Newberry double-walled, steel, compartmented aboveground storage tank (EQ #338). Both tanks were installed in July 2007. both tanks were discolored. Piping: Aboveground, single-walled, steel coated piping. Underground, APT XP flexible piping (EQ #618) with mechanical FE Petro line leak detectors (EQ #335). Aboveground piping looked ok. Transition Sump couldn't be open, it has flaps on it. Overfill protection: Morison gauges. Spill containment boxes were full of product (both) Dispensers sumps were dry, hoses and nozzles looked ok. Release detection: Interstitial monitoring with Krueger "at-a-glance" gauge (EQ #675) and monthly visual inspections of tanks and tank related equipment (tank exteriors, aboveground piping, dispenser hoses and nozzles, dispenser sumps and transition sump). The ATG Veeder-Root TLS-300 (EQ #196)is for inventory only.
05/23/2023 Phone Conversation Activity Khan, Muhammad Rafique
Call Type: Outgoing Activity Status: Closed
Phone Number: (000) 000-0000 Activity Closed Date: 06/06/2023
Subject: no anwer,sent email
Events:
Event Type: Activity has been finished Date: 06/06/2023
Comment: Finished
05/14/2020 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: teach_2_children@yahoo.com Activity Closed Date: 05/14/2020
Events:
Event Type: Activity has been finished Date: 05/14/2020
Comment: Finished
Comments:
Comment Date: 05/14/2020 User: WILSON_ML_1
Description: Greetings, I have attached the above referenced facility’s In Compliance Letter and Inspection Report. Please feel free to contact this office should you have any questions or concerns. Kind Regards, Monica L. Wilson Planning Consultant I Florida Department of Health in Escambia County Environment Health Division 1300 W Gregory Street, Pensacola, Florida 32502 Phone: 850-595-6700 ext 2004 Cell: 850-554-4315 Fax: 850-595-6774 www.EscambiaHealth.com Follow us on Twitter: @HealthyEscambia The Department’s mission is to protect, and improve the health of all people in Florida through integrated state, county, and community efforts NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
05/14/2020 Editable Letter Activity Wilson, Monica L
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 05/14/2020
Comment: Sent
Events:
Event Type: Activity has been finished Date: 05/14/2020
Comment: Finished
Attachments:
Attachment Date: 05/14/2020 User: WILSON_ML_1
Description: In Compliance Letter
View Attachment
05/13/2020 Site Inspection Activity Closed Pangahas, Regiene L
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/13/2020
Activity Closed Date: 05/13/2020 Activity Closed By: PANGAHAS_RL_1
Events:
Event Type: Activity has been finished Date: 05/13/2020
Comment: Finished
Comments:
Comment Date: 05/13/2020 User: PANGAHAS_RL_1
Description: A copy of this report will be sent to the email address(es) provided under contact information. Tank Information: Tank #1 - 15,000 gallon, Newberry double-walled, compartmented aboveground storage tank (EQ #338). Piping: APT XP (EQ #618) with mechanical FE Petro line leak detectors (EQ #335). Overfill protection: Spill containment boxes. Release detection: Interstitial monitoring with Krueger "at-a-glance" gauge (EQ #675); visual monitoring of transition sump (aboveground piping to underground piping) and dispenser sumps; ATG Veeder-Root TLS-300 (EQ #196) for inventory only. Tank #2 - 15,000 gallon, Newberry double-walled, compartmented aboveground storage tank (EQ #338). Piping: APT XP (EQ #618) with mechanical FE Petro line leak detectors (EQ #335). Overfill protection: Spill containment boxes. Release detection: Interstitial monitoring with Krueger "at-a-glance" gauge (EQ #675); visual monitoring of transition sump (aboveground piping to underground piping) and dispenser sumps. ATG Veeder-Root TLS-300 (EQ #196) for inventory only. All facility records were up-to-date. Tanks and aboveground piping appeared to be in good condition. Dispenser sumps were dry and appeared to be in good condition. Hoses and nozzles appeared to be in good condition. Contact Information: Jessica Hamilton Phone:850-263-2294/ 850-326-8596 Email: teach_2_children@yahoo.com
05/13/2020 Phone Conversation Activity Pangahas, Regiene L
Call Type: Outgoing Activity Status: Closed
Phone Number: (850) 263-2294 Activity Closed Date: 05/13/2020
Subject: Regiene Pangahas called to schedule an inspection. Email was also sent (See Electronic Communication Activities).
Events:
Event Type: Activity has been finished Date: 05/13/2020
Comment: Finished
05/13/2020 Electronic Communication Activity Pangahas, Regiene L
Activity Closed Date: 05/13/2020 Activity Status: Closed
Date: 05/13/2020
Recipient: teach_2_children@yahoo.com
Sender: Regiene.Pangahas@flhealth.gov
Subject: FAC 9809544- Storage Tanks Compliance Inspection Notification
Message: Good morning, As per our conversation earlier, our inspection is scheduled on May 13th, Thursday at 10:30 am for the following facility: 9809544 Hamilton LLC 3725 Highway 2, Graceville, FL 32440 The tank owner/operator or a facility representative will need to accompany the inspector and provide access to all tank related equipment. Tank equipment may include: tank exterior, piping, piping sumps, spill boxes, overfill equipment, leak detector gages, automatic tank gauges, dispenser hoses and dispenser sumps. Please be sure the tank equipment is ready for inspection. In addition, the following records need to be available for review: • Proof of Financial Responsibility (for example: Tank Insurance Policy). • Current Tank Registration Placard (should be displayed on site). • Maintenance and Repair Records for the last three years. • Monthly Visual Inspection Checklists for the last three years. • Testing Records: Annual Operability Testing for overfill devices and release detection devices, as applicable. • Annual Line Leak Detector Test for underground pressurized piping, Integrity testing for piping sumps, spill buckets, and dispenser sumps, as applicable. I looked at your records and you will need an Annual Operability Test for your Release Detection, which is a Krueger Gauge, and integrity test for transition sump (and every three years thereafter). I attached a template for Annual Operability Test to give you an idea of what it looks like. Please note that you don’t have to use that template and the template is for Overfill Protection Device, not Release Detection. For more information, please see this link: https://floridadep.gov/waste/storage-tank-compliance Kind regards, Regiene Pangahas Environmental Specialist II FDOH-Environmental Health Division 1300 West Gregory Street Pensacola, FL 32502 850-595-6700 ext. 2007 The Department’s mission is to protect, promote and improve the health of all people in Florida through integrated state, county and community efforts. PLEASE NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
Events:
Event Type: Activity has been finished Date: 05/13/2020
Comment: Finished
09/13/2017 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: teach_2_children@yahoo.com Activity Closed Date: 09/14/2017
Events:
Event Type: Activity has been finished Date: 09/14/2017
Comment: Finished
Attachments:
Attachment Date: 09/14/2017 User: WILSON_ML_1
Description: In Compliance Letter
View Attachment
08/30/2017 Electronic Communication Activity Pangahas, Regiene L
Activity Closed Date: 08/30/2017 Activity Status: Closed
Date: 08/30/2017
Recipient: 'teach_2_children@yahoo.com'
Sender: Regiene.Pangahas@flhealth.gov
Subject: Storage Tank Inspection Notification
Message: Good afternoon Ms. Hamilton, An annual compliance inspection for regulated storage tank(s) will be conducted for your facility for the current year. Please see the attached file for what you will need to prepare before the day of the inspection. Please note that there should be a facility representative available during the inspection. This representative will provide access to facility records and to the tank system. Let me know if you have any questions. Have a great day! Kind regards, Regiene Pangahas Environmental Specialist II Florida Department of Health in Escambia County 1300 West Gregory Street Pensacola, FL 32502 850-595-6700 ext. 2007 www.EscambiaHealth.com MISSION: To protect, promote and improve the health of all people in Florida through integrated state, county and community efforts. VISION: To be the Healthiest State in the Nation. VALUES: ICARE (Innovation, Collaboration, Accountability, Responsiveness, Excellence) PLEASE NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
Events:
Event Type: Activity has been finished Date: 08/30/2017
Comment: Finished
08/30/2017 Phone Conversation Activity Pangahas, Regiene L
Call Type: Outgoing Activity Status: Closed
Phone Number: (850) 263-3394 Activity Closed Date: 08/30/2017
Subject: Regiene Pangahas called the number prior to this day but the manager wasn't there and she was told to call back the next day to schedule a compliance inspection. She talked with Jessica Hamilton and the inspection was scheduled on August 18 but was later rescheduled to August 31st by the manager.
Events:
Event Type: Activity has been finished Date: 08/30/2017
Comment: Finished
08/14/2017 Site Inspection Activity Closed Pangahas, Regiene L
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/14/2017
Activity Closed Date: 09/05/2017 Activity Closed By: PANGAHAS_RL_1
Events:
Event Type: Activity has been finished Date: 09/05/2017
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 09/05/2017
Comment: Approved by Charles L. Payne: Inspection approved by Charles Payne.
Events:
Event Type: Activity has been submitted for approval Date: 09/05/2017
Comment: Submitted for approval by: Regiene L Pangahas
Comments:
Comment Date: 08/31/2017 User: PANGAHAS_RL_1
Description: A copy of this report will be sent to the email address(es) provided under contact information. Tank Information: Tank #1 - 15,000 gallon, Newberry double-wall, compartmented aboveground storage tank (EQ #338). Piping: APT XP (EQ #618) with mechanical FE Petro line leak detectors (EQ #335). Overfill protection: Spill containment boxes. Release detection: Interstital monitoring with Krueger "at-a-glance" gauge (EQ #675). Visual monitoring of transition sump (aboveground piping to underground piping) and dispenser sumps. ATG Veeder-Root TLS-300 (EQ #196) for inventory only. Tank #2 - 15,000 gallon, Newberry double-wall, compartmented aboveground storage tank (EQ #338). Piping: APT XP (EQ #618) with mechanical FE Petro line leak detectors (EQ #335). Overfill protection: Spill containment boxes. Release detection: Interstital monitoring with Krueger "at-a-glance" gauge (EQ #675). Visual monitoring of transition sump (aboveground piping to underground piping) and dispenser sumps. ATG Veeder-Root TLS-300 (EQ #196) for inventory only. All facility records were up-to-date. Tanks and aboveground piping appeared to be in good condition. Elbow part of the piping shows signs of corrosion. Rust must be removed and piping must be repainted (See Area of Concern). Krueger gauges must be checked annually for proper operation (See Area of Concern). Boots for piping transition sump show signs of wear and must be replaced (See Area of Concern). Spill containment contains PCW and must be cleaned (See Area of Concern). Dispenser liners were dry and appeared to be in good condition. Hoses and nozzles appeared to be in good condition. Contact Information: Jessica Hamilton Phone:850-263-2294/ 850-326-8596 Email: teach_2_children@yahoo.com
08/14/2017 Electronic Communication Activity Pangahas, Regiene L
Activity Closed Date: 08/14/2017 Activity Status: Closed
Date: 08/14/2017
Recipient: teach_2_children@yahoo.com
Sender: Regiene.Pangahas@flhealth.gov
Subject: Storage Tank Inspection Notification
Message: Good afternoon Ms. Hamilton, An annual compliance inspection for regulated storage tank(s) will be conducted for your facility for the current year. Please see the attached file for what you will need to prepare before the day of the inspection. Please note that there should be a facility representative available during the inspection. This representative will provide access to facility records and to the tank system. Let me know if you have any questions. Have a great day! Kind regards, Regiene Pangahas Environmental Specialist II Florida Department of Health in Escambia County 1300 West Gregory Street Pensacola, FL 32502 850-595-6700 ext. 2007 www.EscambiaHealth.com MISSION: To protect, promote and improve the health of all people in Florida through integrated state, county and community efforts. VISION: To be the Healthiest State in the Nation. VALUES: ICARE (Innovation, Collaboration, Accountability, Responsiveness, Excellence) PLEASE NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
Events:
Event Type: Activity has been finished Date: 08/14/2017
Comment: Finished
08/14/2017 Phone Conversation Activity Pangahas, Regiene L
Call Type: Outgoing Activity Status: Closed
Phone Number: (850) 263-2294 Activity Closed Date: 08/14/2017
Subject: Regiene Pangahas talked with Jessica Hamilton to schedule storage tank compliance inspection. It was scheduled on August 18, 2017.
Events:
Event Type: Activity has been finished Date: 08/14/2017
Comment: Finished
08/25/2015 Site Inspection Activity Closed Merritt, Sara
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 08/21/2015
Activity Closed Date: 08/25/2015 Activity Closed By: MERRITT_S
Events:
Event Type: Activity has been finished Date: 08/25/2015
Comment: Finished
07/07/2015 Site Inspection Activity Closed Merritt, Sara
Activity Result: Minor Out of Compliance Activity Status: Closed
On-Site Start Date: 07/02/2015
Activity Closed Date: 07/07/2015 Activity Closed By: MERRITT_S
Events:
Event Type: Activity has been finished Date: 07/07/2015
Comment: Finished
07/02/2015 Violation Closed Merritt, Sara
Significance: Minor Status: Closed
Criteria ID: 2120
Rule: 62-762.701(1)(c)1.
Comments: Facility equipment shall be maintained to a degree to allow you access. Water in spill containment units, especially above the fill cap shall be removed. Water in any sumps and dispenser liners above the piping opening/penetration (invert) shall be removed. All regulated substance shall be removed from any of the specified system components. Regulated substances: sheen, free product, mixed product water. Petroleum contact water shall be disposed of in accordance with the Department Hazardous Waste Section's Ch. 62-740 F.A.C., "Petroleum Contact Water".
07/02/2015 Violation Closed Merritt, Sara
Significance: Minor Status: Closed
Criteria ID: 2110
Rule: 62-762.701(1)(a)1.a., 62-762.701(1)(a)1.b., 62-762.701(1)(a)1.c., 62-762.701(1)(a)1.d.
06/10/2015 Enforcement Tracking Activity Merritt, Sara
Activity Status: Closed
Activity Result: Closed Without Enforcement Activity Closed Date: 10/14/2015
Events:
Event Type: Activity has been finished Date: 10/14/2015
Comment: Finished
05/26/2015 Enforcement Referral Activity Brazile, David
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 06/10/2015
Events:
Event Type: Activity has been finished Date: 06/10/2015
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 06/10/2015
Comment: Accepted by: Sara Merritt: No Comments Provided.
Events:
Event Type: Activity has been submitted for approval Date: 05/27/2015
Comment: Submitted for approval by David Brazile
Events:
Event Type: Activity has been assigned Date: 06/09/2015
Comment: Assigned to Sara Merritt
Events:
Event Type: Activity/Document was acknowledged on this date Date: 06/09/2015
Comment: Acknowledged and Assigned by: Mark Gillman
Comments:
Comment Date: 05/26/2015 User: BRAZILE_DO_1
Description: As of 5/26/2015, 7:40 PM. this office did not receive any response from the current owner(s)/operator(s) of this facility. The open violations remain. This facility is being referred to the Department of Environmental Protection for compliance assistance.
Comments:
Comment Date: 05/27/2015 User: BRAZILE_DO_1
Description: As of 5/26/2015, 7:40 PM. this office did not receive any response from the current owner(s)/operator(s) of this facility. The open violations remain. This facility is being referred to the Department of Environmental Protection for compliance assistance.
05/26/2015 Enforcement Referral Activity Brazile, David
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 06/10/2015
Events:
Event Type: Activity has been finished Date: 06/10/2015
Comment: Finished
Events:
Event Type: Activity/Document was accepted on this date Date: 06/10/2015
Comment: Accepted by: Sara Merritt: No Comments Provided.
Events:
Event Type: Activity has been submitted for approval Date: 05/27/2015
Comment: Submitted for approval by David Brazile
Events:
Event Type: Activity has been assigned Date: 06/09/2015
Comment: Assigned to Sara Merritt
Events:
Event Type: Activity/Document was acknowledged on this date Date: 06/09/2015
Comment: Acknowledged and Assigned by: Mark Gillman
Comments:
Comment Date: 05/26/2015 User: BRAZILE_DO_1
Description: As of 5/26/2015, 7:40 PM. this office did not receive any response from the current owner(s)/operator(s) of this facility. The open violations remain. This facility is being referred to the Department of Environmental Protection for compliance assistance.
Comments:
Comment Date: 05/27/2015 User: BRAZILE_DO_1
Description: As of 5/26/2015, 7:40 PM. this office did not receive any response from the current owner(s)/operator(s) of this facility. The open violations remain. This facility is being referred to the Department of Environmental Protection for compliance assistance.
04/17/2015 Editable Letter Activity Wilson, Monica L
Activity Title: County Subsequent Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 04/17/2015
Comment: Sent on Fri Apr 17 00:00:00 EDT 2015
Events:
Event Type: Activity has been finished Date: 04/17/2015
Comment: Finished
Attachments:
Attachment Date: 04/17/2015 User: WILSON_ML_1
Description: 2nd Non-Compliance Letter
View Attachment
02/26/2015 Editable Letter Activity Brazile, David
Activity Title: 1st Non-Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 02/27/2015
Comment: Sent on Fri Feb 27 00:00:00 EST 2015
Events:
Event Type: Activity has been finished Date: 02/27/2015
Comment: Finished
Attachments:
Attachment Date: 02/27/2015 User: WILSON_ML_1
Description: 1st Non-Compliance Letter
View Attachment
02/20/2015 Violation Closed Brazile, David
Significance: Minor Status: Closed
Criteria ID: 2133
Rule: 62-762.711(2)(a), 62-762.711(2)(b), 62-762.711(2)(c), 62-762.711(2)(d), 62-762.711(2)(e), 62-762.711(2)(f), 62-762.711(2)(g), 62-762.711(2)(h)
Comments: If the problem involves failure to perform according to the standards in each of the following areas, then note these items in addition to the paperwork for this rule: a. and g. Inventory - rules 62-762.641(3)(b)1-2, 62-762.641(3)(b)3 and 62-762.701(1)(c)6 b. Repair, operation, and maintenance - rules 62-762.701(1)(a)1, 62-762.701(1)(a)4, 62-762.701(1)(a)6 and 62-762.701(1)(c)3 c. Release detection - rules 62-762.601(1)(e), 62-762.601(2)(g), 62-762.611(2)(b), 62-762.611(3)(b), 62-762.611(3)(d)2, 62-762.641(2)(c) and 62-762.641(2)(e) d. Release detection response level descriptions - rules 62-762.601(1)(b) and 62-762.641(1)(c) e. Tightness, pressure, and breach of integrity tests - rules 62-762.611(3)(a)1 and 62-762.641(1)(a) f. Financial responsibility - rule 62-762.401(3) g. Repairs and replacements - rule 62-762.701(1)(a)6 The following are not issues for this rule: Rules 62-762.451(1)(a)2, 62-762.451(1)(a)3 and 62-762.451(1)(a)4 are verbal notices of activities that may also be written Rule 62-762.451(1)(b) is a registration issue Rules 62-762.451(2)(a), 62-762.451(3)(a) and 62-762.451(3)(b) are INF/DRF reporting issues Rules 62-762.601(1)(a)3 and 62-762.601(1)(f) are covered by 62-762.711(3) Anything with cathodic protection is covered by 62-762.711(3)
02/20/2015 Site Inspection Activity Closed Brazile, David
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/20/2015
Activity Closed Date: 02/26/2015 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 02/26/2015
Comment: Finished
Comments:
Comment Date: 02/26/2015 User: BRAZILE_DO_1
Description: NOTE: As of 2/26/2015, no monthly visual records have been received for July 2012 thru February 2015. The facility changed ownership in January/February 2015. The previous owner stated that Petrol Flow Inc. performed the monthly visual inspection through December 2014. However, no monthly visual records were received from Petrol Flow after a request for them was made during the compliance inspection on 2/20/2015. Also, the new facility owners did not provide any monthly visual records for January/February 2015.
Comments:
Comment Date: 02/20/2015 User: BRAZILE_DO_1
Description: 2015/02/20 - TCI - Tank #1 and Tank #2 - 15,000 GL, Aboveground Storage Tank, Newberry double-wall, compartmented tank (EQ-338). Piping: APT XP (EQ-618) with mechanical FE Petro line leak detectors (EQ-335). Transition sump (aboveground piping to underground piping) and dispenser sumps present. Overfill protection: Spill containment boxes and ATG Veeder-Root TLS-300 (EQ-196). Release detection: Tank - Interstital monitoring with Krueger "at-a-glance" gauge (EQ-675). Piping - Mechanical line leak detectors. Sumps- Visual monitoring.
02/20/2015 Site Inspection Activity Closed Brazile, David
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/20/2015
Activity Closed Date: 02/26/2015 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 02/26/2015
Comment: Finished
Comments:
Comment Date: 02/26/2015 User: BRAZILE_DO_1
Description: NOTE: As of 2/26/2015, no monthly visual records have been received for July 2012 thru February 2015. The facility changed ownership in January/February 2015. The previous owner stated that Petrol Flow Inc. performed the monthly visual inspection through December 2014. However, no monthly visual records were received from Petrol Flow after a request for them was made during the compliance inspection on 2/20/2015. Also, the new facility owners did not provide any monthly visual records for January/February 2015.
Comments:
Comment Date: 02/20/2015 User: BRAZILE_DO_1
Description: 2015/02/20 - TCI - Tank #1 and Tank #2 - 15,000 GL, Aboveground Storage Tank, Newberry double-wall, compartmented tank (EQ-338). Piping: APT XP (EQ-618) with mechanical FE Petro line leak detectors (EQ-335). Transition sump (aboveground piping to underground piping) and dispenser sumps present. Overfill protection: Spill containment boxes and ATG Veeder-Root TLS-300 (EQ-196). Release detection: Tank - Interstital monitoring with Krueger "at-a-glance" gauge (EQ-675). Piping - Mechanical line leak detectors. Sumps- Visual monitoring.
02/20/2015 Violation Closed Brazile, David
Significance: SNC-B Status: Closed
Criteria ID: 2069
Rule: 62-762.601(1)(d)
Comments: Mark this as out of compliance if any release detection method has not been monitored as required. Look for evidence that the release detection system is not being properly monitored. Examples include: blocked access to monitoring wells, buried or submerged sampling ports; corroded locks; or no dispenser keys. Be aware that manual tank gauging requires weekly sampling. Electronic line leak detectors may be wired into an ATG with a memory of test cycles. Facilities with static/periodic ATG systems are required to provide one passing test per product per month. This method has a minimum fuel capacity requirement. If there is a record keeping problem, see rule 62-762.711(2).
02/20/2015 Violation Closed Brazile, David
Significance: Minor Status: Closed
Criteria ID: 2122
Rule: 62-762.701(1)(c)3.
Comments: Facility must prove that all release detection devices, such as in line leak detectors, sump and liner sensors, etc. function properly. Sensing devices may be optical, vapor, float activated, discriminating, non discriminating, or tied into electrical circuits.
10/31/2012 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/31/2012
Activity Closed Date: 10/31/2012 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 10/31/2012
Comment: Finished
Comments:
Comment Date: 10/31/2012 User: BRAZILE_DO_1
Description: Tank #1 and Tank #2 - 15,000 GL, Aboveground Storage Tank, Newberry double-wall, compartmented tank (EQ-338). Piping: APT XP (EQ-618) with mechanical FE Petro line leak detectors (EQ-335). Transition sump (aboveground piping to underground piping) and dispenser sumps present. Overfill protection: Spill containment boxes and ATG Veeder-Root TLS-300 (EQ-196). Release detection: Tank - Interstital monitoring with Krueger "at-a-glance" gauge (EQ-675). Piping - Mechanical line leak detectors. Sumps- Visual monitoirng.
Comments:
Comment Date: 10/31/2012 User: BRAZILE_DO_1
Description: NOTE: Leak Detectors are currently Scheduled to be tested November 2, 2012
10/31/2012 Emergency Preparedness Information Activity Brazile, David
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 10/31/2012
Events:
Event Type: Activity has been finished Date: 10/31/2012
Comment: Finished
10/31/2012 Site Inspection Activity Closed Brazile, David
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 10/31/2012
Activity Closed Date: 10/31/2012 Activity Closed By: BRAZILE_DO_1
Events:
Event Type: Activity has been finished Date: 10/31/2012
Comment: Finished
Comments:
Comment Date: 10/31/2012 User: BRAZILE_DO_1
Description: Tank #1 and Tank #2 - 15,000 GL, Aboveground Storage Tank, Newberry double-wall, compartmented tank (EQ-338). Piping: APT XP (EQ-618) with mechanical FE Petro line leak detectors (EQ-335). Transition sump (aboveground piping to underground piping) and dispenser sumps present. Overfill protection: Spill containment boxes and ATG Veeder-Root TLS-300 (EQ-196). Release detection: Tank - Interstital monitoring with Krueger "at-a-glance" gauge (EQ-675). Piping - Mechanical line leak detectors. Sumps- Visual monitoirng.
Comments:
Comment Date: 10/31/2012 User: BRAZILE_DO_1
Description: NOTE: Leak Detectors are currently Scheduled to be tested November 2, 2012
05/10/2011 Comment Albury, Jace E.
Description: 1-15000 gallon (compartmented 9000/6000) double wall Newberry Tank (eq# 338) AST for diesel and 1-15000 gallon (compartmented 11000/4000) double wall Newberry Tank (eq# 338) AST for unleaded and premium. Piping is double wall APT XP (eq# 618). Morrison Brothers (eq# 535) remote fill/spill buckets. APT (eq# 423) dispenser liners and transition sumps. Flow shut-off overfill prevention. F.E. Petro mechanical line leak detectors. Veeder Root TLS 350 for fuel monitoring only. Release detection is by monthly visual inspection of tank interstice, with Krueger interstice gauge, transition sumps and dispenser liners with mechanical line leak detectors.
05/10/2011 Emergency Preparedness Information Activity Albury, Jace E.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 05/10/2011
Events:
Event Type: Activity has been finished Date: 05/10/2011
Comment: Finished
05/10/2011 Site Inspection Activity Closed Albury, Jace E.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/10/2011
Activity Closed Date: 05/12/2011 Activity Closed By: ALBURY_JE_1
Events:
Event Type: Activity has been finished Date: 05/12/2011
Comment: Finished
Comments:
Comment Date: 05/10/2011 User: ALBURY_JE_1
Description: Inspected 1-15000 gallon (compartmented 9000/6000) double wall Newberry Tank AST for diesel and 1-15000 gallon (compartmented 11000/4000) double wall Newberry Tank AST for unleaded and premium. Piping is double wall APT XP. Morrison Brothers remote fill/spill buckets dry and product lines marked. APT dispenser liners and transition sumps dry. Transition sump located adjacent to off-road diesel dispenser has undergone some settling, but appears to be sound. Flow shut-off overfill prevention. Petro-Flow Inc., onsite during inspection. Technician loosened pressure test boot in satellite dispenser to allow for piping release detection between satellite pump and main pump. Release detection is by monthly visual inspection of tank interstice, with Krueger interstice gauge, transition sumps and dispenser liners with mechanical line leak detectors. No visual signs of release. Inspection completed with Mark Gillman, FDEP Pensacola, for QA/QC.
05/10/2011 Attachment Albury, Jace E.
07/28/2010 Attachment Albury, Jace E.
07/28/2010 Attachment Albury, Jace E.
06/09/2010 Attachment Bristol, Susan M.
06/09/2010 Editable Letter Activity Bristol, Susan M.
Activity Title: District Non-Compliance Letter Activity Status: Open
Description: 8506959_INF for failed hydro test on sump & spill bucke
04/23/2010 Site Inspection Activity Closed Albury, Jace E.
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/23/2010
Activity Closed Date: 04/23/2010 Activity Closed By: ALBURY_JE_1
Events:
Event Type: Activity has been finished Date: 04/23/2010
Comment: Finished
Comments:
Comment Date: 04/23/2010 User: ALBURY_JE_1
Description: Inspected 1-15000g (compartmented 9000/6000) DW AST for diesel and 1-15000g (compartmented 11000/4000) DW AST for unleaded and premium. Piping is DW APT XP. Release detection is monthly visuals of tank interstice with Krueger gauge, transition sumps and dispenser liners, and mechanical line leak detectors. Tank interstice, transition sumps, and dispenser liners dry. No visual signs of release. Tanks and aboveground piping will need to be repainted soon to prevent corrosion. Recommend protecting transition sump and piping boots from deterioration from sunlight and installing barricades to protect from vehicle traffic.
04/23/2010 Emergency Preparedness Information Activity Albury, Jace E.
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 04/23/2010
Events:
Event Type: Activity has been finished Date: 04/23/2010
Comment: Finished
01/17/2008 Violation Closed Bristol, Susan M.
Significance: SNC-B Status: Closed
Criteria ID: 2004
Rule: 62-762.401(3)(a)1.
Comments: There are various financial responsibility mechanisms available: Risk Retention Group (RRG) Endorsements Certificate of Insurance Guarantee Letter of Credit Fully Funded Trust Fund Self-Insurance with letter from CFO Stand-by Trust Fund Bond Rating Test (Local Governments) Local Government Financial Test Local Government Guarantee Local Government Fund For detailed information, refer to the DEP's Financial Responsibility Handbook pages 2-1, 2-2. Verify which mechanism(s) are used by the facility. State and federal facilities are exempt from financial responsibility, being considered a type of self insurance. They are always in compliance for this category. Document state or federal as appropriate. Financial responsibility must be maintained on out-of-service tanks. Note: Mark the absence of/or the lack of complete info in the certification of financial responsibility under Rule 62-762.401(3).
01/16/2008 Site Inspection Activity Closed Bristol, Susan M.
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 06/08/2007
Activity Closed Date: 06/09/2010 Activity Closed By: BRISTOL_S
Events:
Event Type: Activity has been finished Date: 06/09/2010
Comment: Finished