Florida Department of Environmental Protection Bob Martinez Center 2600 Blair Stone Road Tallahassee, Florida 32399-2400 |
Storage Tanks & Contamination Monitoring Information |
|||||||||
Journal Report | |||||||||||
Report Run Date: 04/27/2025 Last Data Refresh: 04/26/2025 Report Generated from DOPPLER | |||||||||||
Facility ID: | 9815055 | ||||||||||
Facility Name: | STETSON UNIV-LYNN BUSINESS CTR | ||||||||||
07/30/2024 | Enforcement Tracking Activity | Stamm, Trey | |||||||||
Activity Status: | Open | ||||||||||
02/26/2024 | Electronic Communication Activity | Finney, Brittany N | |||||||||
Activity Closed Date: | 02/26/2024 | Activity Status: | Closed | ||||||||
Date: | 02/26/2024 | ||||||||||
Recipient: | brittany.finney@ocfl.net | ||||||||||
Sender: | sproctor1@stetson.edu | ||||||||||
Subject: | Re: Stetson University - MVIs received for 2 facilities | ||||||||||
Message: | see attached | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/26/2024 | ||||||||
Comment: | Finished | ||||||||||
02/23/2024 | Phone Conversation Activity | Finney, Brittany N | |||||||||
Call Type: | Incoming | Activity Status: | Closed | ||||||||
Phone Number: | (407) 280-3046 | Activity Closed Date: | 02/23/2024 | ||||||||
Subject: | Received a call from Sean Proctor with facilities management regarding the open violations; he said he will provide proof of the MVIs that are being performed; he also stated he has reached out to his contractor regarding testing needed & that he will supply pictures of the labeled tanks | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/23/2024 | ||||||||
Comment: | Finished | ||||||||||
02/23/2024 | Electronic Communication Activity | Gregory, Jane W | |||||||||
Activity Closed Date: | 02/23/2024 | Activity Status: | Closed | ||||||||
Date: | 02/23/2024 | ||||||||||
Recipient: | jevans1@stetson.edu; glen.becker@ocfl.net; brittany.finney@ocfl.net | ||||||||||
Sender: | jane.gregory@ocfl.net | ||||||||||
Subject: | Stetson Storage Tanks | ||||||||||
Message: | Hi Jason, As we discussed, the letter that was sent to Stetson regarding storage tanks violations at the Lynn Business Center, Sage Hall and Carlton Union is attached. Also attached are the inspection reports and compliance assistance offers. Our inspector tried several different ways to assist with resolving the violations but without any luck. I read through the file and the outstanding violations can be summarized as follows: Lynn Business Center: • 10/12/2023 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Please arrange for current testing of the overfill protection equipment to be performed. Please supply testing for review. • 10/12/2023 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Please immediately begin completing the monthly visual inspections of the tank. A visual inspection form will be emailed to the facility contact. Please submit the next two months of inspections as completed. Visual inspections must be conducted & documented every 30-35 days. Please maintain records for up to three years for future inspection purposes. • 10/12/2023 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Please arrange for current testing of the release detection sensor to be performed. Please supply testing for review. Carlton Union Building: • 10/12/2023 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Please arrange for current testing of the overfill protection equipment to be performed. Please supply testing for review. • 10/12/2023 7043 Minor 1.11 Fillbox covers not marked according to requirements. Please label the spill bucket with a "DIESEL" sign. Please supply a picture for review once complete. • 10/12/2023 7065 SNC-B 1.6 Storage tank system not visually inspected once a month. Please immediately begin completing the monthly visual inspections of the tank. A visual inspection form will be emailed to the facility contact. Please submit the next two months of inspections as completed. Visual inspections must be conducted & documented every 30-35 days. Please maintain records for up to three years for future inspection purposes. • 10/12/2023 7072 Minor 1.8 Annual operability testing of release detection systems not completed. Please arrange for current testing of the release detection sensor to be performed. Please supply testing for review. Sage Hall: • 10/18/2023 7020 Minor 1.2 Integrity Testing of secondary containment systems and interstitial spaces not performed before being placed into service. Please have the testing completed on the spill bucket or supply testing records from the time of installation. • 10/18/2023 7031 SNC-B 3.1 Any component(s) of storage tank system not installed according to manufacturer's instructions. An onsite breach of integrity test is required after the tank is set in place. Please have the breach of integrity testing completed, or supply testing records from the time of installation. All integrity tests should be conducted in accordance with manufacturer's specifications. This can be provided by: 1) The tank holding vacuum for at least one hour following being set in place 2) An onsite pressure testing showing the tank secondary holds for at least one hour • 10/18/2023 7041 Minor 1.10 Failure to designate, register, or annually test primary overfill protection device, Please supply post installation testing, or arrange for testing to be performed. Please supply records for review. • 10/18/2023 7058 Minor 3.2 Valves do not meet standards of Section 7 of PEI/RP200-13 for piping systems with gravity head. Please arrange for a manual valve to be installed on the piping supply line. The correct order shall be: tank> manual or isolation valve> solenoid valve. Please supply a work order and pictures once installation is complete. • 10/18/2023 7072 Minor 1.8 Annual operability testing of release detection systems not complet | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/23/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/23/2024 | User: | GREGORY_JW_1 | ||||||||
Description: | Email to property owner about violations | ||||||||||
View Attachment | |||||||||||
02/16/2024 | Enforcement Referral Activity | Becker, Glen | |||||||||
Activity Result: | Accepted | Activity Status: | Closed | ||||||||
Activity Closed Date: | 07/30/2024 | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was acknowledged on this date | Date: | 02/28/2024 | ||||||||
Comment: | Acknowledged and Assigned by DANIEL K HALL | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been assigned | Date: | 02/28/2024 | ||||||||
Comment: | Assigned to DANIEL K HALL | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been submitted for approval | Date: | 02/16/2024 | ||||||||
Comment: | Submitted for approval by: Glen Becker: Violations have not been addressed. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/30/2024 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Activity/Document was accepted on this date | Date: | 07/30/2024 | ||||||||
Comment: | Accepted by Trey Stamm: Assigned to and Accepted by Trey Stamm | ||||||||||
Comments: | |||||||||||
Comment Date: | 02/16/2024 | User: | BECKER_GT_1 | ||||||||
Description: | Violations have not been addressed. | ||||||||||
02/08/2024 | Electronic Communication Activity | Perez, Erick | |||||||||
Activity Status: | Open | ||||||||||
Date: | 02/08/2024 | ||||||||||
02/08/2024 | Electronic Communication Activity | Perez, Erick | |||||||||
Activity Closed Date: | 02/08/2024 | Activity Status: | Closed | ||||||||
Date: | 02/08/2024 | ||||||||||
Recipient: | STETSON UNIVERSITY C/O Bonita Dukes | ||||||||||
Sender: | erick.perez@ocfl.net, jane.gregory@ocfl.net, brittany.finney@ocfl.net | ||||||||||
Subject: | Potential Storage Tanks Management Violations at Multiple Stetson University Locations: Lynn Business Center FAC ID 9815055, Carlton Union Building FAC ID 9815827, and Sage Hall FAC ID 9818595 | ||||||||||
Message: | The inspection reports and Compliance Assistance Offers for these facilities, including violations cited and guidance for achieving compliance is attached to this letter. We encourage you to resolve the open violations immediately. Compliance assistance is available from your inspector, Brittany Finney at brittany.finney@ocfl.net or 321-689-8611. Thank you for your prompt attention to this matter. | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/08/2024 | ||||||||
Comment: | Finished | ||||||||||
02/02/2024 | Issue Document Activity | Becker, Glen | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Brittany Finney to Stetson University | Activity Closed Date: | 02/15/2024 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 02/15/2024 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 02/15/2024 | User: | BECKER_GT_1 | ||||||||
Description: | 2/2/2024 letter | ||||||||||
View Attachment | |||||||||||
01/16/2024 | Electronic Communication Activity | Finney, Brittany N | |||||||||
Activity Closed Date: | 01/16/2024 | Activity Status: | Closed | ||||||||
Date: | 01/16/2024 | ||||||||||
Recipient: | sproctor1@stetson.edu; mcouturier@stetson.edu | ||||||||||
Sender: | brittany.finney@ocfl.net | ||||||||||
Subject: | Fw: Carlton Union & Lynn Business Center - Tank Inspection Reports & Compliance Assistance Offer | ||||||||||
Message: |
From: Finney, Brittany |
||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 01/16/2024 | ||||||||
Comment: | Finished | ||||||||||
10/12/2023 | Violation Closed | Finney, Brittany N | |||||||||
Significance: | SNC-B | Status: | Closed | ||||||||
Criteria ID: | 7065 | ||||||||||
Rule: | 62-762.601(1)(e), 62-762.602(1)(e) | ||||||||||
10/12/2023 | Editable Letter Activity | Finney, Brittany N | |||||||||
Activity Title: | Compliance Assistance Offer Letter | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Compliance Assistance Offer Verbal | Date: | 10/13/2023 | ||||||||
Comment: | Compliance Assistance Offer Verbal | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/18/2023 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 10/13/2023 | ||||||||
Comment: | Sent | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 10/18/2023 | User: | PIERCE_BN_1 | ||||||||
Description: | Compliance Assistance Offer Letter | ||||||||||
View Attachment | |||||||||||
10/12/2023 | Violation Open | Finney, Brittany N | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7072 | ||||||||||
Rule: | 62-762.601(7), 62-762.602(7) | ||||||||||
10/12/2023 | Violation Open | Finney, Brittany N | |||||||||
Significance: | Minor | Status: | Open | ||||||||
Criteria ID: | 7041 | ||||||||||
Rule: | 62-762.501(2)(e)3, 62-762.501(2)(e)3.a, 62-762.501(2)(e)3.b, 62-762.501(2)(e)4, 62-762.502(2)(e)4, 62-762.502(2)(e)4.a, 62-762.502(2)(e)4.b, 62-762.502(2)(e)5 | ||||||||||
09/29/2023 | Site Inspection Activity Closed | Finney, Brittany N | |||||||||
Activity Result: | Major Out of Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 09/29/2023 | ||||||||||
Activity Closed Date: | 10/12/2023 | Activity Closed By: | PIERCE_BN_1 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 10/12/2023 | ||||||||
Comment: | Finished | ||||||||||
07/18/2023 | Electronic Communication Activity | Finney, Brittany N | |||||||||
Activity Closed Date: | 07/20/2023 | Activity Status: | Closed | ||||||||
Date: | 07/18/2023 | ||||||||||
Recipient: | mcouturier@stetson.edu; sproctor1@stetson.edu | ||||||||||
Sender: | brittany.finney@ocfl.net | ||||||||||
Subject: | Tank Compliance Inspections due at 2 Stetson locations *Please reply to confirm date/time. | ||||||||||
Message: | see attached | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 07/20/2023 | ||||||||
Comment: | Finished | ||||||||||
08/25/2019 | Editable Letter Activity | Perry, Jacqueline | |||||||||
Activity Title: | In Compliance Letter | Activity Status: | Closed | ||||||||
Description: | RTC letter 10-25-2019 | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/25/2019 | ||||||||
Comment: | Finished | ||||||||||
Events: | |||||||||||
Event Type: | Document has been sent | Date: | 08/22/2019 | ||||||||
Comment: | Sent | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 08/25/2019 | User: | PERRY_JF_2 | ||||||||
Description: | In compliance | ||||||||||
View Attachment | |||||||||||
08/22/2019 | Site Inspection Activity Closed | Perry, Jacqueline | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 08/22/2019 | ||||||||||
Activity Closed Date: | 08/25/2019 | Activity Closed By: | PERRY_JF_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/25/2019 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 08/22/2019 | User: | PERRY_JF_2 | ||||||||
Description: | Gen/set system | ||||||||||
View Attachment | |||||||||||
Attachments: | |||||||||||
Attachment Date: | 08/22/2019 | User: | PERRY_JF_2 | ||||||||
Description: | Fill end of tank | ||||||||||
View Attachment | |||||||||||
08/05/2019 | Electronic Communication Activity | Perry, Jacqueline | |||||||||
Activity Closed Date: | 08/05/2019 | Activity Status: | Closed | ||||||||
Date: | 08/05/2019 | ||||||||||
Recipient: | mclifton@stetson.edu | ||||||||||
Sender: | jacqueline.perry@ocfl.net | ||||||||||
Subject: | Provided notification of up coming routine compliance inspection | ||||||||||
Message: | Provided notification of up coming routine compliance inspection | ||||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 08/05/2019 | ||||||||
Comment: | Finished | ||||||||||
11/30/2017 | Site Inspection Activity Closed | Perry, Jacqueline | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 11/30/2017 | ||||||||||
Activity Closed Date: | 12/08/2017 | Activity Closed By: | PERRY_JF_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/08/2017 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 12/05/2017 | User: | PERRY_JF_2 | ||||||||
Description: | Gen/set system | ||||||||||
View Attachment | |||||||||||
11/30/2017 | Issue Document Activity | Perry, Jacqueline | |||||||||
Activity Status: | Closed | ||||||||||
Contact Name: | Michele Clifton | Activity Closed Date: | 12/08/2017 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 12/08/2017 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 12/08/2017 | User: | PERRY_JF_2 | ||||||||
Description: | In compliance | ||||||||||
View Attachment | |||||||||||
06/27/2016 | Attachment | Perry, Jacqueline | |||||||||
06/27/2016 | Document Management Activity | Perry, Jacqueline | |||||||||
Activity Title: | Map, Sketches And Drawings | Activity Status: | Closed | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/27/2016 | ||||||||
Comment: | Finished | ||||||||||
Attachments: | |||||||||||
Attachment Date: | 06/27/2016 | User: | PERRY_JF_2 | ||||||||
Description: | Stetson map | ||||||||||
View Attachment | |||||||||||
06/21/2016 | Attachment | Rauenzahn, Ruth | |||||||||
05/03/2016 | Site Inspection Activity Closed | Perry, Jacqueline | |||||||||
Activity Result: | In Compliance | Activity Status: | Closed | ||||||||
On-Site Start Date: | 05/03/2016 | ||||||||||
Activity Closed Date: | 06/20/2016 | Activity Closed By: | PERRY_JF_2 | ||||||||
Events: | |||||||||||
Event Type: | Activity has been finished | Date: | 06/20/2016 | ||||||||
Comment: | Finished |