02/20/2025 Enforcement Tracking Activity Gillman, Mark
Activity Status: Open
02/14/2025 Editable Letter Activity Elliott, Emily
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Description: RTC
Events:
Event Type: Document has been sent Date: 02/14/2025
Comment: Sent
Events:
Event Type: Activity has been finished Date: 02/14/2025
Comment: Finished
Attachments:
Attachment Date: 02/14/2025 User: MCLEOD_SL_1
Description: Enforcement Referral Notice
View Attachment
02/14/2025 Enforcement Referral Activity Elliott, Emily
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 02/20/2025
Events:
Event Type: Activity has been submitted for approval Date: 02/14/2025
Comment: Submitted for approval by: Emily Elliott: See attachments.
Events:
Event Type: Activity/Document was accepted on this date Date: 02/20/2025
Comment: Accepted by Mark Gillman: Accepted
Events:
Event Type: Activity/Document was acknowledged on this date Date: 02/20/2025
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been assigned Date: 02/20/2025
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity has been finished Date: 02/20/2025
Comment: Finished
Comments:
Comment Date: 02/14/2025 User: ELLIOTT_EV_1
Description: See attachments.
Comments:
Comment Date: 02/14/2025 User: ELLIOTT_EV_1
Description: See attachments for details.
02/14/2025 Enforcement Referral Activity Elliott, Emily
Activity Result: Accepted Activity Status: Closed
Activity Closed Date: 02/20/2025
Events:
Event Type: Activity has been submitted for approval Date: 02/14/2025
Comment: Submitted for approval by: Emily Elliott: See attachments.
Events:
Event Type: Activity/Document was accepted on this date Date: 02/20/2025
Comment: Accepted by Mark Gillman: Accepted
Events:
Event Type: Activity/Document was acknowledged on this date Date: 02/20/2025
Comment: Acknowledged and Assigned by Mark Gillman
Events:
Event Type: Activity has been assigned Date: 02/20/2025
Comment: Assigned to Mark Gillman
Events:
Event Type: Activity has been finished Date: 02/20/2025
Comment: Finished
Comments:
Comment Date: 02/14/2025 User: ELLIOTT_EV_1
Description: See attachments.
Comments:
Comment Date: 02/14/2025 User: ELLIOTT_EV_1
Description: See attachments for details.
02/11/2025 Violation Open Elliott, Emily
Significance: Minor Status: Open
Criteria ID: 7005
Rule: 62-762.411(1)(b), 62-762.411(1)(c), 62-762.411(2)(a), 62-762.411(2)(b), 62-762.411(2)(c)
02/11/2025 Site Inspection Activity Closed Elliott, Emily
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 02/11/2025
Activity Closed Date: 02/14/2025 Activity Closed By: ELLIOTT_EV_1
Events:
Event Type: Activity has been finished Date: 02/14/2025
Comment: Finished
Comments:
Comment Date: 02/11/2025 User: ELLIOTT_EV_1
Description: Met onsite with David Mooney (Spatco Technician) for this routine tank compliance inspection. A copy of this inspection report and enforcement referral notice letter will be emailed to Diane Rae at drae@bjs.com, Bill Peters at bpeters@bjs.com, and Sara Merritt at Sara.Merritt@FloridaDEP.gov. Underground Storage Tanks: Tank #1 and Tank #2 are 20,000 gallons Fiber Glass Systems, Double-Wall Fiberglass Tanks (EQ-191) containing Unleaded Gas. Tank #3 is a 24,000 gallons Fiber Glass Systems, Double-Wall Fiberglass Tanks (EQ-191) that is compartmented containing 12,000 gallons Premium and 12,000 gallons Diesel. All three tanks were installed October 2019. Facility has two unknown Aboveground Storage Tanks that appeared to be sub-base tanks that supply diesel fuel to an emergency generator. Our department was not notified about the installation of the Aboveground Storage Tanks. – Violation Issued. It was noted that the unregistered Aboveground Storage Tank System contains diesel fuel despite not having a current placard. The facility will be immediately referred to enforcement according to the Florida Administrative Code 62.762.401(5) -Violation Issued. Piping: 3" Franklin Fueling, UPP Double-Wall piping (EQ-816). (Vent piping) Ameron, Dualoy 3000/LCX, 2' Double-Wall fiberglass piping (EQ-291). Dispensers: Franklin Fueling Systems, PT Dispenser Liners (EQ-423). The dispenser sumps were mostly clean and dry at the time of inspection. The boots appeared to be in good condition. The hoses and nozzles appeared to be in good condition. STP Sumps: Franklin Fueling Systems, APT Sump Liner (EQ-423). The STP sumps were mostly clean and dry at the time of inspection. The boots appeared to be in good condition. The sensors were in the correct position. Spill Containments: Emco Wheaton Double Walled Secondary Spill Containment (EQ-741). The double wall spill containments were mostly clean and dry at the time of inspection. The gauges were normal at the time of inspection. Overfill Prevention: Emco Wheaton, Guardian Overfill Prevention Valves (EQ-414). Release Detection: The tanks interstitial sensors and STP sump sensors are monitored by a Veeder-Root TLS-450, with dual point, and non-discriminating sensors (EQ-724). DPLLD sensor (EQ-722), Universal Sensor/Probe Interface Module (USM), with water detection sensor. (EQ-723). Sensor status reports are printed monthly. All function normal on ATG at the time of inspection. Monthly Visual Inspection are being conducted by the facility. Records: All facility records were received for the underground storage tank system, including associated tank component testing, monthly visual inspection with electronic release detection ATG printouts, and financial responsibility forms and the current placard was posted at the facility. See Violation Section for Corrective Actions.
02/11/2025 Violation Open Elliott, Emily
Significance: SNC-A Status: Open
Criteria ID: 7125
Rule: 62-762.401(5)
09/30/2024 Editable Letter Activity Mcleod, Shelly L
Activity Title: Closure Assessment Report (Complete) Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 09/30/2024
Comment: Finished
Events:
Event Type: Document has been sent Date: 09/30/2024
Comment: Sent
Attachments:
Attachment Date: 09/30/2024 User: MCLEOD_SL_1
Description: Closure Assessment Report (Complete)
View Attachment
09/30/2024 Document Management Activity Mcleod, Shelly L
Activity Title: Closure Document Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 09/30/2024
Comment: Finished
Attachments:
Attachment Date: 09/30/2024 User: MCLEOD_SL_1
Description: Closure Assessment Report Addendum
View Attachment
09/30/2024 TCAR Activity Mcleod, Shelly L
Activity Result: Satisfied Activity Status: Closed
Activity Closed Date: 09/30/2024
Events:
Event Type: Activity has been finished Date: 09/30/2024
Comment: Finished
Comments:
Comment Date: 09/30/2024 User: MCLEOD_SL_1
Description: 09/24/2024 - Received the Closure Assessment Report for UST (Double Wall Regular Spill Containment) submitted by Ashley Rowe with Applied Science and Engineering LLC. 09/24/2024 - Upon review of the Closure Assessment Report (Double Wall Regular Spill Containment) Emily Elliott has determined that this office shall issue an IAW Letter.
06/10/2024 Document Management Activity Payne, Charles L.
Activity Title: Closure Document Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 06/10/2024
Comment: Finished
Attachments:
Attachment Date: 06/10/2024 User: PAYNE_CL_1
Description: Closure Assessment Report (Reg. 1 SB)
View Attachment
06/10/2024 Editable Letter Activity Payne, Charles L.
Activity Title: Closure Assessment Report (Incomplete) Activity Status: Closed
Description: In Compliance Letter
Events:
Event Type: Document has been sent Date: 06/10/2024
Comment: Sent
Events:
Event Type: Activity has been finished Date: 06/10/2024
Comment: Finished
Attachments:
Attachment Date: 06/10/2024 User: PAYNE_CL_1
Description: Closure Assessment Report Review Letter
View Attachment
04/04/2024 Editable Letter Activity Elliott, Emily
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 04/04/2024
Comment: Sent
Events:
Event Type: Activity has been finished Date: 04/04/2024
Comment: Finished
Attachments:
Attachment Date: 04/04/2024 User: ELLIOTT_EV_1
Description: In Compliance Letter
View Attachment
04/03/2024 Comment Elliott, Emily
Description: Replaced Regular Spill Containment: (EQ-695) Emco Wheaton Retail Corporation, Emco Wheaton Secondary Spill Containment Models A1004 UL File no. MH21149.
04/02/2024 Site Inspection Activity Closed Elliott, Emily
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 04/02/2024
Activity Closed Date: 04/04/2024 Activity Closed By: ELLIOTT_EV_1
Events:
Event Type: Activity has been finished Date: 04/04/2024
Comment: Finished
Comments:
Comment Date: 04/03/2024 User: ELLIOTT_EV_1
Description: Type of Inspection: UST Component Installation Inspection (Double Wall Regular Spill Containment). Location: 7060 Plantation Road, Pensacola, FL 32504 Facility Owner: BJ’s Wholesale Club, Inc Facility Contact: Diane Rae (774-512-6468 / drae@bjs.com) Contractor: Petro Flow, Inc (850-798-2228 / petroflowinc@gmail.com) PSSC License #: 1256798 Closure Requirements: A Closure Assessment Report for the Regular Double Wall Spill Containment will be due to this office 60 days after closure activities. The report will be due May 31, 2024. Equipment Installed: Spill Containment: (EQ-695) Emco Wheaton Retail Corporation, Emco Wheaton Secondary Spill Containment Models A1004 UL File no. MH21149. The Double Wall Regular Spill Containment was installed, and vacuum tested by Petro Flow, Inc and passed (see attachments for a copy of the test results). The testing was completed, and the results were reviewed by our office prior to the facility bringing the system back into service. The new double wall regular spill containment appears to have been installed per manufacturer's instructions. No violations at the time of inspection.
02/12/2024 Incident Activity Elliott, Emily
Activity Result: Has not led to Discharge Activity Status: Closed
Activity Closed Date: 10/03/2024
Events:
Event Type: Activity has been finished Date: 10/03/2024
Comment: Finished
Comments:
Comment Date: 10/03/2024 User: ELLIOTT_EV_1
Description: 02/12/2024: Diane Rae submitted an INF because the Regular Spill Bucket failed integrity testing (vacuum testing). 04/02/2024 – Regular Spill Containment was replaced, and sampling was conducted by Applied Science and Engineering LLC. 09/30/2024 – The Closure Assessment Report was received and review. No discharged appeared to occur from this incident.
02/12/2024 Document Management Activity Elliott, Emily
Activity Title: Incident Notification Form Activity Status: Closed
Description: DRF
Events:
Event Type: Activity has been finished Date: 02/12/2024
Comment: Finished
Attachments:
Attachment Date: 02/12/2024 User: ELLIOTT_EV_1
Description: INF BJs Wholesale Club Retail Gas St Club #382
View Attachment
03/17/2023 Editable Letter Activity Elliott, Emily
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 03/17/2023
Comment: Finished
Events:
Event Type: Document has been sent Date: 03/17/2023
Comment: Sent
Attachments:
Attachment Date: 03/17/2023 User: WILSON_ML_1
Description: In Compliance Letter
View Attachment
03/15/2023 Electronic Communication Activity Elliott, Emily
Activity Closed Date: 03/15/2023 Activity Status: Closed
Date: 03/15/2023
Recipient: Rae, Diane
Sender: Elliott, Emily V
Subject: Routine Tank Compliance Inspection: BJS WHOLESALE CLUB RETAIL GAS ST CLUB #382 (FAC ID: 9817495)
Message: Good Afternoon, The Florida Department of Health in Escambia County - Environmental Health Division is contracted with the Florida Department of Environmental Protection to conduct Storage Tank System Compliance Inspections at facilities located in Escambia County. I have the above referenced facility due for their routine petroleum storage tank inspection. I will be in the area Tuesday, March 14, 2023 at 09:00 AM. I will need to meet with someone to accompany me and provide access to all the tank related equipment. In addition to the visual inspection, the following records will need to be available for review: • Proof of Financial Responsibility (for example: Tank Insurance Policy) • Current Tank Registration Placard • Operator Training Certificates for facilities with USTs. • Maintenance and Repair Records for the last two years. • Monthly Visual Inspection Checklists for the last two years. • Monthly Electronic Release Detection for the last two years. (for example: Liquid Sensor Status Tapes) • Testing Records: Annual Line Leak Detector Test, Annual Operability Test for electronic release detection equipment, Annual Operability Test for overfill devices, Annual Operability Test for double wall spill bucket interstice gauges, Integrity Testing for Dispenser Sumps, Piping/STP Sumps and Spill Buckets. I look forward to hearing back from you.
Events:
Event Type: Activity has been finished Date: 03/15/2023
Comment: Finished
03/14/2023 Site Inspection Activity Closed Elliott, Emily
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 03/14/2023
Activity Closed Date: 03/17/2023 Activity Closed By: ELLIOTT_EV_1
Events:
Event Type: Activity has been submitted for approval Date: 03/17/2023
Comment: Submitted for approval by: Emily Elliott
Events:
Event Type: Activity has been finished Date: 03/17/2023
Comment: Finished
Events:
Event Type: Activity/Document has been approved Date: 03/17/2023
Comment: Approved by Charles L. Payne: TCI approved by Charles Payne on 3/17/2023.
Comments:
Comment Date: 03/14/2023 User: ELLIOTT_EV_1
Description: Met onsite with Christopher O’Brien (Service Technican) for this routine tank compliance inspection. A copy of this inspection report and in compliance letter will be emailed to Diane Rae at drae@bjs.com. TANKS: Tank #1 and Tank #2 are 20,000 gallons Fiber Glass Systems, Double-Wall Fiberglass Tanks (EQ-191) containing Unleaded Gas. Tank #3 is a 24,000 gallons Fiber Glass Systems, Double-Wall Fiberglass Tanks (EQ-191) that is compartmented containing 12,000 gallons Premium and 12,000 gallons Diesel. All three tanks were installed October 2019. PIPING: 3" Franklin Fueling, UPP Double-Wall piping (EQ-816). (Vent piping) Ameron, Dualoy 3000/LCX, 2' Double-Wall fiberglass piping (EQ-291). DISPENSERS: Franklin Fueling Systems, PT Dispenser Liners (EQ-423). Mostly clean and dry at the time of inspection. Hoses and nozzles appeared to be in good condition. STP SUMPS: Franklin Fueling Systems, APT Sump Liner (EQ-423). Mostly clean and dry at the time of inspection. SPILL CONTAINMENT: Emco Wheaton Double Walled Secondary Spill Containment (EQ-741). Mostly clean and dry at the time of inspection. OVERFILL PREVENETION: Emco Wheaton, Guardian Overfill Prevention Valves (EQ-414). RELEASE DETECTION: Tank IM Sensors and STP Sump Sensors are monitored by a Veeder-Root TLS-450, with dual point, and non-discriminating sensors (EQ-724). DPLLD sensor (EQ-722), Universal Sensor/Probe Interface Module (USM), with water detection sensor. (EQ-723). Sensor status reports are printed monthly. All function normal on ATG at the time of inspection. Monthly Visual Inspection are being conducted by the facility. No Violations at the time of inspection.
07/07/2022 Editable Letter Activity Wilson, Monica L
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 07/07/2022
Comment: Sent
Events:
Event Type: Activity has been finished Date: 07/07/2022
Comment: Finished
Attachments:
Attachment Date: 07/07/2022 User: WILSON_ML_1
Description: Return to Compliance Letter
View Attachment
06/22/2022 Record Document Activity Gartin, Daniel Q
Activity Status: Closed
Contact Name: Rae, Diane Activity Closed Date: 06/23/2022
Events:
Event Type: Activity has been finished Date: 06/23/2022
Comment: Finished
Comments:
Comment Date: 06/23/2022 User: GARTIN_D
Description: The facility sensor originally was showing alarm state however all functions were listed normal. Dispatched team from McKinney Equipment, Inc noted a potential electrical surge from recent thunderstorm activities in the area may have caused this tripped alarm state. All functions normal was associated with sensors with all alarm cleared and reset status.
06/22/2022 Record Document Activity Gartin, Daniel Q
Activity Status: Closed
Contact Name: Rae, Diane Activity Closed Date: 06/23/2022
Events:
Event Type: Activity has been finished Date: 06/23/2022
Comment: Finished
Comments:
Comment Date: 06/23/2022 User: GARTIN_D
Description: Including attachment from previous recorded document.
Attachments:
Attachment Date: 06/23/2022 User: GARTIN_D
Description: Work Order BJs Gas St Club 382
View Attachment
06/20/2022 Editable Letter Activity Gartin, Daniel Q
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 06/22/2022
Comment: Sent
Events:
Event Type: Activity has been finished Date: 06/22/2022
Comment: Finished
Attachments:
Attachment Date: 06/22/2022 User: WILSON_ML_1
Description: Compliance Assistance Offer Letter
View Attachment
06/20/2022 Electronic Communication Activity Gartin, Daniel Q
Activity Closed Date: 06/20/2022 Activity Status: Closed
Date: 06/20/2022
Recipient: Gartin, Daniel Q
Sender: Wilson, Monica L
Subject: FW: BJs Wholesale Club Retail Gas St Club #382 (Fac No 9817495), 7060 Plantation Rd, Pensacola
Message: Please see Mark’s Email below for complaint. Monica L. Wilson Planning Consultant I Florida Department of Health in Escambia County Environment Health Division 1300 W Gregory Street, Pensacola, Florida 32502 Phone: 850-595-6700 ext 2004 Cell: 850-554-4315 Fax: 850-595-6774 www.EscambiaHealth.com Follow us on Twitter: @HealthyEscambia The Department’s mission is to protect, and improve the health of all people in Florida through integrated state, county, and community efforts NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure. From: Gillman, Mark Sent: Tuesday, June 14, 2022 3:04 PM To: Wilson, Monica L ; Payne, Charles L Cc: Long, Kevin W Subject: FW: BJs Wholesale Club Retail Gas St Club #382 (Fac No 9817495), 7060 Plantation Rd, Pensacola EXTERNAL EMAIL: DO NOT CLICK links or open attachments unless you recognize the sender and know the content is safe. My apologies. The contact person for the facility is Chris Mason, and he can be reached at 850-619-8472. Please reach out to him to set up your visit. Thanks, Mark From: Gillman, Mark Sent: Tuesday, June 14, 2022 3:00 PM To: Wilson, Monica L ; Payne, Charles L Cc: Long, Kevin W ; Richardson, Cliff J Subject: BJs Wholesale Club Retail Gas St Club #382 (Fac No 9817495), 7060 Plantation Rd, Pensacola Hi Monica/Charles: Today, our District OER Manager, Kevin Long, received a notice that reported petroleum odor in the sewer manways near the subject facility. Kevin responded and couldn’t detect any significant odors using his equipment. I would, though, like for someone in your office to conduct an inspection to follow up and determine if there has been any unexplained loss of product from one of their tanks, and to review their ATG inventory/RD information. Given the large volume of petroleum stored at the facility and the lengthy underground piping, I believe it would be a good idea to check it out on the tank inspector side. The last routine inspection was in May 2021, and everything appeared in compliance. There are no other known contaminated areas around that site, nor are there any other fueling facilities nearby. Please follow up with an inspection tomorrow if possible. Conduct the inspection as fact finding to get a fix on if there has been any unexplained loss, but invoice it as a “complaint” inspection. Kevin would like to meet the inspector at the site during the inspection, so please give him a call at 850-258-4354 once you plan your time to be there. I will be in the field tomorrow and unable to go along. Thanks for looking into this on short notice. Mark Mark Gillman Environmental Consultant Florida Department of Environmental Protection Compliance Assurance Program Mark.gillman@dep.state.fl.us Office: 850.595.0586
Events:
Event Type: Activity has been finished Date: 06/20/2022
Comment: Finished
06/15/2022 Violation Closed Gartin, Daniel Q
Significance: SNC-B Status: Closed
Criteria ID: 6063
Rule: 62-761.700(1), 62-761.700(1)(a), 62-761.700(1)(a)1, 62-761.700(1)(a)2
06/15/2022 Site Inspection Activity Closed Gartin, Daniel Q
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 06/15/2022
Activity Closed Date: 06/20/2022 Activity Closed By: GARTIN_D
Events:
Event Type: Activity has been finished Date: 06/20/2022
Comment: Finished
Comments:
Comment Date: 06/15/2022 User: GARTIN_D
Description: The complaint inspection was conducted at BJs Wholesale Club Retail Gas ST, Club #382 by request of FDEP due a received report of petroleum odor in the sewer manways at a nearby location to the subject facility. Dispatched Operation Emergency Response FDEP Kevin Long noted no detectable significant odors with equipment on 06/14/2022. On 06/15/2022, Daniel Gartin conducted a review of the ATG inventory/RD and associated liquid status at the facility. The review of the facility's inventory and deliveries noted multiple deliveries can occur at the facility per day. These deliveries are most likely due to high consumer traffic that was observed at the facility than any unexplained product lost from associated facility's underground storage tanks. The review of the ATG liquid status and alarm history noted all functions were normal at the time of inspection. However, the Veeder Root TLS-450 noted an Sensor Out Alarm for the Regulat East Interstitial sensor and alarm history noted the same alarm, Sensor Out Alarm, for perm/dsl int on the previous day. It is noted that Liquid Status from the Sensor Status Report and Sensor Diagnostic - Liquid Sensor Information Report both resulted in Normal status with no indication of a sensor out alarm. Violation issued to facility to investigate why associated alarm history regarding Sensor Out Alarm is occurring at this facility.
Attachments:
Attachment Date: 06/16/2022 User: GARTIN_D
Description: FDEP Approval
View Attachment
05/18/2021 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: drae@bjs.com; gm382@bjs.com; sornell@bjs.com; michelle.adkins@washingtonprime.com Activity Closed Date: 05/18/2021
Events:
Event Type: Activity has been finished Date: 05/18/2021
Comment: Finished
Comments:
Comment Date: 05/18/2021 User: WILSON_ML_1
Description: Greetings, I have attached the above referenced facility’s In Compliance Letter and Inspection Report. Please feel free to contact this office should you have any questions or concerns. Kind Regards, Monica L. Wilson Planning Consultant I Florida Department of Health in Escambia County Environment Health Division 1300 W Gregory Street, Pensacola, Florida 32502 Phone: 850-595-6700 ext 2004 Cell: 850-554-4315 Fax: 850-595-6774 www.EscambiaHealth.com Follow us on Twitter: @HealthyEscambia The Department’s mission is to protect, and improve the health of all people in Florida through integrated state, county, and community efforts NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
05/18/2021 Editable Letter Activity Wilson, Monica L
Activity Title: In Compliance Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 05/18/2021
Comment: Finished
Events:
Event Type: Document has been sent Date: 05/18/2021
Comment: Sent
Attachments:
Attachment Date: 05/18/2021 User: WILSON_ML_1
Description: In Compliance Letter
View Attachment
05/18/2021 Electronic Communication Activity Pangahas, Regiene L
Activity Closed Date: 05/18/2021 Activity Status: Closed
Date: 05/18/2021
Recipient: drae@bjs.com; robert.demchak@washingtonprime.com; michelle.adkins@washingtonprime.com
Sender: Regiene.Pangahas@flhealth.gov
Subject: RE: FAC ID# 9817495 BJs Wholesale Club Retail Gas Storage Tank(s) System - Inspection Notification
Message: Good morning, This is a reminder for the upcoming routine compliance inspection at your facilities on May 7th, Friday. Please note that the following are also needed for underground storage tanks: Operator Training Certificates (A, B, and C) for facilities with USTs. Operator C Training certificates must at least be available at the site. Kind regards, Regiene L. Pangahas Environmental Specialist III Florida Department of Health Environmental Health Division 1300 West Gregory Street Pensacola, FL 32502 850-595-6700 ext. 2007 www.EscambiaHealth.com Follow us on Twitter: @HealthyEscambia The Department’s mission is to protect, promote and improve the health of all people in Florida through integrated state, county and community efforts. PLEASE NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
Events:
Event Type: Activity has been finished Date: 05/18/2021
Comment: Finished
05/18/2021 Electronic Communication Activity Pangahas, Regiene L
Activity Closed Date: 05/18/2021 Activity Status: Closed
Date: 05/18/2021
Recipient: drae@bjs.com; robert.demchak@washingtonprime.com
Sender: Regiene.Pangahas@flhealth.gov
Subject: FAC ID# 9817495 BJs Wholesale Club Retail Gas Storage Tank(s) System - Inspection Notification
Message: Good morning, The Florida Department of Health in Escambia County - Environmental Health Division is contracted with the Florida Department of Environmental Protection to conduct Storage Tank System Compliance Inspections at facilities located in Escambia County. The facility listed below are scheduled for a Tank Compliance Inspection on Friday, May 7th around 9:45am-10:15nn timeframe. Please contact the inspector if you have a conflict with the said schedule. Otherwise, please be ready for the inspection. FAC ID# 9817495 BJs Wholesale Club Retail Gas 7060 Plantation Rd, Pensacola, FL 32504 The tank owner/operator or a facility representative will need to accompany the inspector and provide access to all tank related equipment. Tank equipment may include: tank exterior, piping, piping sumps, spill boxes, overfill equipment, leak detector gauges, automatic tank gauges, dispenser hoses and dispenser sumps. Please be sure the tank equipment is ready for inspection. In addition, the following records need to be available for review: • Proof of Financial Responsibility or Proof of Insurance. Make sure it is in the State of Florida DEP Form 62-761.900(3) https://www.flrules.org/Gateway/reference.asp?No=Ref-11170 • Current Tank Registration Placard displayed in plain view at the site. • Maintenance and Repair Records for the last three years. • Monthly Visual Inspection Checklists for the last three years. • Monthly Electronic Release Detection for the last three years (as applicable). Check of Tank IM Sensor may be noted on Monthly Visual Inspection Checklist. • Testing Records (as applicable): Annual Operability Test Report for Tank Interstitial Monitoring Sensor/Release Detection Devices (e.g. Basin Alarm, Veeder Root, Krueger Leak Gauge, etc.); Annual Operability Testing for Overfill Protection Devices (e.g. Clock Gauge, Krueger Fuel Gauge, etc.). • For underground components (as applicable): Annual Line Leak Detector Test for underground pressurized piping and/or piping over surface water. Integrity Testing for Dispenser Sumps, Piping/STP Sumps and Spill Buckets (single-walled spill buckets: hydrostatic test; double-walled spill buckets: vacuum test). Failure to comply with the state rules and regulations will result in violations and possible penalties. For more information, please view “Preparing for a Storage Tank Facility Inspection Information Video” on the DEP website: https://floridadep.gov/waste/permitting-compliance-assistance/content/storage-tank-systems-guidance-and-information Storage Tanks Compliance: https://floridadep.gov/waste/storage-tank-compliance If you have any questions or need additional information, please let me know. Thank you. Kind regards, Regiene L. Pangahas Environmental Specialist III Florida Department of Health Environmental Health Division 1300 West Gregory Street Pensacola, FL 32502 850-595-6700 ext. 2007 www.EscambiaHealth.com Follow us on Twitter: @HealthyEscambia The Department’s mission is to protect, promote and improve the health of all people in Florida through integrated state, county and community efforts. PLEASE NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
Events:
Event Type: Activity has been finished Date: 05/18/2021
Comment: Finished
05/07/2021 Site Inspection Activity Closed Pangahas, Regiene L
Activity Result: In Compliance Activity Status: Closed
On-Site Start Date: 05/07/2021
Activity Closed Date: 05/18/2021 Activity Closed By: PANGAHAS_RL_1
Events:
Event Type: Activity has been finished Date: 05/18/2021
Comment: Finished
Comments:
Comment Date: 05/07/2021 User: PANGAHAS_RL_1
Description: A copy of this report will be sent to the email address(es) provided under contact information. Tank(s) Information: Tank #1: 20,000 gallon, CSI, FRP, double-walled, fiberglass tanks (EQ #191). Piping: 3" Franklin Fueling, UPP, double-walled piping (EQ #816); vent piping-Ameron, Dualoy 3000/LCX, 2' double-walled fiberglass piping (EQ #291). Release Detection: Veeder-Root TLS-450 with dual point and non-discriminating sensors.(EQ #724); DPLLD sensor (EQ #722); Universal Sensor/Probe Interface Module(USM) with water detection sensor (EQ #723); Franklin Fueling dispenser sumps (EQ #423); Bravo, fiberglass, conduit pass-through fittings (EQ #820). Overfill Protection: Emco Wheaton, Guardian Overfill Prevention Valves(EQ #414); Emco Wheaton, double-walled, SS, spill buckets with gauges (EQ #741) and vapor recoveries. Tank #2: 20,000 gallon, CSI, FRP, double-walled, fiberglass tanks (EQ #191). Piping: 3" Franklin Fueling, UPP, double-walled piping (EQ #816); vent piping-Ameron, Dualoy 3000/LCX, 2' double-walled fiberglass piping (EQ #291). Release Detection: Veeder-Root TLS-450 with dual point and non-discriminating sensors.(EQ #724); DPLLD sensor (EQ #722); Universal Sensor/Probe Interface Module(USM) with water detection sensor (EQ #723); Franklin Fueling dispenser sumps (EQ #423); Bravo, fiberglass, conduit pass-through fittings (EQ #820). Overfill Protection: Emco Wheaton, Guardian Overfill Prevention Valves(EQ #414); Emco Wheaton, double-walled, SS, spill buckets with gauges (EQ #741) and vapor recoveries. Tank #3: 24,000 gallon CSI FRP, double-walled fiberglass, compartmented tank (EQ #191). Piping: 3" Franklin Fueling, UPP, double-walled piping (EQ #816); vent piping-Ameron, Dualoy 3000/LCX, 2' double-walled fiberglass piping (EQ #291). Release Detection: Veeder-Root TLS-450 with dual point and non-discriminating sensors.(EQ #724); DPLLD sensor (EQ #722); Universal Sensor/Probe Interface Module(USM) with water detection sensor (EQ #723); Franklin Fueling dispenser sumps (EQ #423); Bravo, fiberglass, conduit pass-through fittings (EQ #820). Overfill Protection: Emco Wheaton, Guardian Overfill Prevention Valves(EQ #414); Emco Wheaton, double-walled, SS, spill buckets with gauges (EQ #741) and vapor recoveries. Registration information was up-to-date. Registration placard was posted on site. Financial responsibility/insurance was up-to-date. Operator A, B, and C training certificates were available. All facility records were up-to-date All spill buckets and vapor recovery buckets appeared to be in good condition. STP sumps were dry at the time of inspection. All dispenser sumps were dry and appeared to be in good condition. Product line entry boots appeared to be in good condition. Hoses and nozzles appeared to be in good condition. Contact Information: Diane Rae Phone: 774-512-6468 Email: drae@bjs.com Tom Condon Emaill: GM382@bjs.com Sharon Ornell Email: sornell@bjs.com Michelle Adkins Email: michelle.adkins@washingtonprime.com
05/21/2020 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: drae@bjs.com Activity Closed Date: 05/21/2020
Events:
Event Type: Activity has been finished Date: 05/21/2020
Comment: Finished
Comments:
Comment Date: 05/21/2020 User: WILSON_ML_1
Description: Greetings, I have attached the above referenced facility’s Return to Compliance Letter. Please feel free to contact this office should you have any questions or concerns. Kind Regards, Monica L. Wilson Planning Consultant I Florida Department of Health in Escambia County Environment Health Division 1300 W Gregory Street, Pensacola, Florida 32502 Phone: 850-595-6700 ext 2004 Cell: 850-554-4315 Fax: 850-595-6774 www.EscambiaHealth.com Follow us on Twitter: @HealthyEscambia The Department’s mission is to protect, and improve the health of all people in Florida through integrated state, county, and community efforts NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
05/21/2020 Editable Letter Activity Wilson, Monica L
Activity Title: Return to Compliance Letter Activity Status: Closed
Events:
Event Type: Document has been sent Date: 05/21/2020
Comment: Sent
Events:
Event Type: Activity has been finished Date: 05/21/2020
Comment: Finished
Attachments:
Attachment Date: 05/21/2020 User: WILSON_ML_1
Description: Return to Compliance Letter
View Attachment
05/20/2020 Record Document Activity Bragg, Shane D
Activity Status: Closed
Contact Name: Diane Rae Activity Closed Date: 05/20/2020
Events:
Event Type: Activity has been finished Date: 05/20/2020
Comment: Finished
Comments:
Comment Date: 05/20/2020 User: BRAGG_SD_2
Description: A copy of the financial responsibility for the tanks was sent in by the contacts. Violation for no financial responsibility has been resolved. Facility has returned to compliance. Signed copy of the letter sent to Diane Rae at DRae@BJS.com.
05/19/2020 Record Document Activity Bragg, Shane D
Activity Status: Closed
Contact Name: Tony Frick(Great Dane Petroluem) Activity Closed Date: 05/19/2020
Events:
Event Type: Activity has been finished Date: 05/19/2020
Comment: Finished
Comments:
Comment Date: 05/19/2020 User: BRAGG_SD_2
Description: Copy of shear valve and overfill testing were sent in by the contact. Violation for the UST not being installed according to standard has been resolved.
03/02/2020 Electronic Communication Activity Bragg, Shane D
Activity Closed Date: 03/02/2020 Activity Status: Closed
Date: 03/02/2020
Recipient: Shane Bragg
Sender: Tony Frick(Great Dane Petroleum)
Subject: RE: BJ's Wholesale Club Retail Gas Station, Club #382
Message: Shane, my apologies for the delay. Attached are the Final testing results for the BJ’s. Thanks for your patience. NOTE NEW EMAIL ADDRESS Tfrick@greatdanepetro.com Tony Frick North Branch Manager Great Dane Petroleum Contractors, Inc. 2173 Platinum Rd. Apopka Fl. 32703 T. 407-880-0850 C. 407-448-4706 E. tfrick@greatdanepetro.com Update New Email Address
Events:
Event Type: Activity has been finished Date: 03/02/2020
Comment: Finished
Comments:
Comment Date: 03/02/2020 User: BRAGG_SD_2
Description: Copy of testing results were sent in by the contractor. Results included the line and tank tightness test, tank breech of integrity testing, line leak detector testing, ATG/sensor test, and PV valve testing. Violation not resolved as the shear valve, and overfill valve testing are still need to satisfy the violation.
02/24/2020 Violation Closed Bragg, Shane D
Significance: SNC-B Status: Closed
Criteria ID: 4032
Rule: 62-761.500(1)(f), 62-761.500(1)(f)1., 62-761.500(1)(f)2., 62-761.500(1)(f)3., 62-761.500(1)(f)4., 62-761.500(1)(f)5.
Comments:
Comment Date: 03/02/2020 User: BRAGG_SD_2
Description: Copy of testing results were sent in by the contractor. Results included the line and tank tightness test, tank breech of integrity testing, line leak detector testing, ATG/sensor test, and PV valve testing. Violation not resolved as the shear valve, and overfill valve testing are still need to satisfy the violation.
02/24/2020 Editable Letter Activity Bragg, Shane D
Activity Title: Compliance Assistance Offer Letter Activity Status: Closed
Events:
Event Type: Activity has been finished Date: 02/24/2020
Comment: Finished
Events:
Event Type: Document has been sent Date: 02/24/2020
Comment: Sent
Attachments:
Attachment Date: 02/24/2020 User: WILSON_ML_1
Description: Compliance Assistance Offer Letter
View Attachment
02/24/2020 Issue Document Activity Wilson, Monica L
Activity Status: Closed
Contact Name: drae@bjs.com Activity Closed Date: 02/24/2020
Events:
Event Type: Activity has been finished Date: 02/24/2020
Comment: Finished
Comments:
Comment Date: 02/24/2020 User: WILSON_ML_1
Description: Greetings, I have attached the above referenced facility’s Compliance Assistance Offer Letter and Inspection Report. I have also attached the Financial Mechanism Form Part P mentioned in the violation section of the inspection report along with Part D. If you will be using a different financial mechanism other than insurance, please let us know so that we can get the correct Financial Mechanism Form to you to resolve the violation. Please feel free to contact this office should you have any questions or concerns. Kind Regards, Monica L. Wilson Planning Consultant I Florida Department of Health in Escambia County Environment Health Division 1300 W Gregory Street, Pensacola, Florida 32502 Phone: 850-595-6700 ext 2004 Cell: 850-554-4315 Fax: 850-595-6774 www.EscambiaHealth.com Follow us on Twitter: @HealthyEscambia The Department’s mission is to protect, and improve the health of all people in Florida through integrated state, county, and community efforts NOTE: Florida has a very broad public records law. Most written communications to or from state officials regarding state business are public records available to the public and media upon request. Your email communication may therefore be subject to public disclosure.
02/24/2020 Violation Closed Bragg, Shane D
Significance: SNC-B Status: Closed
Criteria ID: 4014
Rule: 62-761.420(2)
02/04/2020 Attachment Bragg, Shane D
10/30/2019 Attachment Bragg, Shane D
10/25/2019 Site Inspection Activity Closed Bragg, Shane D
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 10/25/2019
Activity Closed Date: 02/24/2020 Activity Closed By: BRAGG_SD_2
Events:
Event Type: Activity has been finished Date: 02/24/2020
Comment: Finished
Comments:
Comment Date: 02/04/2020 User: BRAGG_SD_2
Description: Backfilling was completed. Concrete was poured over the tank pad, and around the dispenser sumps. ATG sensors were being installed into the STP and dispenser sumps.
Comments:
Comment Date: 12/20/2019 User: BRAGG_SD_2
Description: Tanks were back filled using gravel. The STP sumps, fill pipes, and spill buckets were installed on the tanks. The dispenser sumps were installed in place. Piping was ran between the STP sumps and dispenser sumps. Piping was welded to connections at the dispenser sumps in accordance with the manufactures installation guidelines. Piping was pressurized with air, none of the fittings were seen leaking, or bubbling. All primary and secondary pipe air gauges were holding steady pressure. All dispenser sumps and STP sumps were seen passing hydrostatic test.
Comments:
Comment Date: 11/27/2019 User: BRAGG_SD_2
Description: 11/19/2019. Regeine Pangahas was on site to witness the tanks being set into the excavation and see them secured to dead men.
Comments:
Comment Date: 02/24/2020 User: BRAGG_SD_2
Description: Testing was and financial responsibility was not submitted as part of the installation paperwork. Refer to violations section of this report for violations and corrective actions. Signed copy of this inspection report emailed to Diane Rae at DRae@BJS.com. Signature lost due to FIRST connectivity problems.
Comments:
Comment Date: 10/30/2019 User: BRAGG_SD_2
Description: UST System installation. Scope of work: Install 3 fiberglass USTs, and all associated piping, STP sumps, and dispenser sumps. Owner: BJ's Wholesale Club, Diane Rae, 774-512-6468, drae@bjs.com. Contractor: Great Dane Petroleum Contractors, Mike Pavelko, 407-466-3046, MPavelko@GreatDanePetro.com. PSSC License: PCC056839. Consultant: Stantec, Zach Rich, 207-887-3508, Zach.Ricj@Stantec.com. Equipment installed: Tanks: Two(2) CSI 20,000 gallon FRP, Double-Wall Fiberglass tanks(EQ-191), one(1) CSI 24,000 gallon FRP, Double-Wall Fiberglass, compartmented tank(EQ-191). STP sumps are part of tank EQ. Dispenser sumps: Franklin Fueling(EQ-423). Piping: 3" Franklin Fueling, UPP Double-Wall piping(EQ-816). Ameron, Dualoy 3000/LCX, 2' Double-Wall fiberglass piping(EQ-291). Spill Buckets: Seven(7) Emco Wheaton, Double-Wall, SS, Spill buckets with gauges(EQ-741), four used as fills, and three as vapor recoveries. ATG/Release Detection: Veeder-Root TLS-450, with dual point, and non-discriminating sensors.(EQ-724). DPLLD sensor(EQ-722), Universal Sensor/Probe Interface Module(USM), with water detection sensor. (EQ-723) Piping/Sump Fittings: Bravo, fiberglass, conduit pass-through fittings(EQ-820). Overfill Prevention: Four(4) Emco Wheaton, Guardian Overfill Prevention Valves(EQ-414) 10/25/2019 Tanks were delivered to the facility removed from trucks and set on beds of pea-gravel until ready for installation. Tanks appeared to be in good condition and did not have any signs of damage. Brine filled interstices were full and no leaks were seen on the tanks. 10/29/2019 Air pressure test were conducted on the tanks. Each primary was pressurized to 5 PSI, and was holding.
10/25/2019 Site Inspection Activity Closed Bragg, Shane D
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 10/25/2019
Activity Closed Date: 02/24/2020 Activity Closed By: BRAGG_SD_2
Events:
Event Type: Activity has been finished Date: 02/24/2020
Comment: Finished
Comments:
Comment Date: 02/04/2020 User: BRAGG_SD_2
Description: Backfilling was completed. Concrete was poured over the tank pad, and around the dispenser sumps. ATG sensors were being installed into the STP and dispenser sumps.
Comments:
Comment Date: 12/20/2019 User: BRAGG_SD_2
Description: Tanks were back filled using gravel. The STP sumps, fill pipes, and spill buckets were installed on the tanks. The dispenser sumps were installed in place. Piping was ran between the STP sumps and dispenser sumps. Piping was welded to connections at the dispenser sumps in accordance with the manufactures installation guidelines. Piping was pressurized with air, none of the fittings were seen leaking, or bubbling. All primary and secondary pipe air gauges were holding steady pressure. All dispenser sumps and STP sumps were seen passing hydrostatic test.
Comments:
Comment Date: 11/27/2019 User: BRAGG_SD_2
Description: 11/19/2019. Regeine Pangahas was on site to witness the tanks being set into the excavation and see them secured to dead men.
Comments:
Comment Date: 02/24/2020 User: BRAGG_SD_2
Description: Testing was and financial responsibility was not submitted as part of the installation paperwork. Refer to violations section of this report for violations and corrective actions. Signed copy of this inspection report emailed to Diane Rae at DRae@BJS.com. Signature lost due to FIRST connectivity problems.
Comments:
Comment Date: 10/30/2019 User: BRAGG_SD_2
Description: UST System installation. Scope of work: Install 3 fiberglass USTs, and all associated piping, STP sumps, and dispenser sumps. Owner: BJ's Wholesale Club, Diane Rae, 774-512-6468, drae@bjs.com. Contractor: Great Dane Petroleum Contractors, Mike Pavelko, 407-466-3046, MPavelko@GreatDanePetro.com. PSSC License: PCC056839. Consultant: Stantec, Zach Rich, 207-887-3508, Zach.Ricj@Stantec.com. Equipment installed: Tanks: Two(2) CSI 20,000 gallon FRP, Double-Wall Fiberglass tanks(EQ-191), one(1) CSI 24,000 gallon FRP, Double-Wall Fiberglass, compartmented tank(EQ-191). STP sumps are part of tank EQ. Dispenser sumps: Franklin Fueling(EQ-423). Piping: 3" Franklin Fueling, UPP Double-Wall piping(EQ-816). Ameron, Dualoy 3000/LCX, 2' Double-Wall fiberglass piping(EQ-291). Spill Buckets: Seven(7) Emco Wheaton, Double-Wall, SS, Spill buckets with gauges(EQ-741), four used as fills, and three as vapor recoveries. ATG/Release Detection: Veeder-Root TLS-450, with dual point, and non-discriminating sensors.(EQ-724). DPLLD sensor(EQ-722), Universal Sensor/Probe Interface Module(USM), with water detection sensor. (EQ-723) Piping/Sump Fittings: Bravo, fiberglass, conduit pass-through fittings(EQ-820). Overfill Prevention: Four(4) Emco Wheaton, Guardian Overfill Prevention Valves(EQ-414) 10/25/2019 Tanks were delivered to the facility removed from trucks and set on beds of pea-gravel until ready for installation. Tanks appeared to be in good condition and did not have any signs of damage. Brine filled interstices were full and no leaks were seen on the tanks. 10/29/2019 Air pressure test were conducted on the tanks. Each primary was pressurized to 5 PSI, and was holding.
10/25/2019 Site Inspection Activity Closed Bragg, Shane D
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 10/25/2019
Activity Closed Date: 02/24/2020 Activity Closed By: BRAGG_SD_2
Events:
Event Type: Activity has been finished Date: 02/24/2020
Comment: Finished
Comments:
Comment Date: 02/04/2020 User: BRAGG_SD_2
Description: Backfilling was completed. Concrete was poured over the tank pad, and around the dispenser sumps. ATG sensors were being installed into the STP and dispenser sumps.
Comments:
Comment Date: 12/20/2019 User: BRAGG_SD_2
Description: Tanks were back filled using gravel. The STP sumps, fill pipes, and spill buckets were installed on the tanks. The dispenser sumps were installed in place. Piping was ran between the STP sumps and dispenser sumps. Piping was welded to connections at the dispenser sumps in accordance with the manufactures installation guidelines. Piping was pressurized with air, none of the fittings were seen leaking, or bubbling. All primary and secondary pipe air gauges were holding steady pressure. All dispenser sumps and STP sumps were seen passing hydrostatic test.
Comments:
Comment Date: 11/27/2019 User: BRAGG_SD_2
Description: 11/19/2019. Regeine Pangahas was on site to witness the tanks being set into the excavation and see them secured to dead men.
Comments:
Comment Date: 02/24/2020 User: BRAGG_SD_2
Description: Testing was and financial responsibility was not submitted as part of the installation paperwork. Refer to violations section of this report for violations and corrective actions. Signed copy of this inspection report emailed to Diane Rae at DRae@BJS.com. Signature lost due to FIRST connectivity problems.
Comments:
Comment Date: 10/30/2019 User: BRAGG_SD_2
Description: UST System installation. Scope of work: Install 3 fiberglass USTs, and all associated piping, STP sumps, and dispenser sumps. Owner: BJ's Wholesale Club, Diane Rae, 774-512-6468, drae@bjs.com. Contractor: Great Dane Petroleum Contractors, Mike Pavelko, 407-466-3046, MPavelko@GreatDanePetro.com. PSSC License: PCC056839. Consultant: Stantec, Zach Rich, 207-887-3508, Zach.Ricj@Stantec.com. Equipment installed: Tanks: Two(2) CSI 20,000 gallon FRP, Double-Wall Fiberglass tanks(EQ-191), one(1) CSI 24,000 gallon FRP, Double-Wall Fiberglass, compartmented tank(EQ-191). STP sumps are part of tank EQ. Dispenser sumps: Franklin Fueling(EQ-423). Piping: 3" Franklin Fueling, UPP Double-Wall piping(EQ-816). Ameron, Dualoy 3000/LCX, 2' Double-Wall fiberglass piping(EQ-291). Spill Buckets: Seven(7) Emco Wheaton, Double-Wall, SS, Spill buckets with gauges(EQ-741), four used as fills, and three as vapor recoveries. ATG/Release Detection: Veeder-Root TLS-450, with dual point, and non-discriminating sensors.(EQ-724). DPLLD sensor(EQ-722), Universal Sensor/Probe Interface Module(USM), with water detection sensor. (EQ-723) Piping/Sump Fittings: Bravo, fiberglass, conduit pass-through fittings(EQ-820). Overfill Prevention: Four(4) Emco Wheaton, Guardian Overfill Prevention Valves(EQ-414) 10/25/2019 Tanks were delivered to the facility removed from trucks and set on beds of pea-gravel until ready for installation. Tanks appeared to be in good condition and did not have any signs of damage. Brine filled interstices were full and no leaks were seen on the tanks. 10/29/2019 Air pressure test were conducted on the tanks. Each primary was pressurized to 5 PSI, and was holding.
10/25/2019 Site Inspection Activity Closed Bragg, Shane D
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 10/25/2019
Activity Closed Date: 02/24/2020 Activity Closed By: BRAGG_SD_2
Events:
Event Type: Activity has been finished Date: 02/24/2020
Comment: Finished
Comments:
Comment Date: 02/04/2020 User: BRAGG_SD_2
Description: Backfilling was completed. Concrete was poured over the tank pad, and around the dispenser sumps. ATG sensors were being installed into the STP and dispenser sumps.
Comments:
Comment Date: 12/20/2019 User: BRAGG_SD_2
Description: Tanks were back filled using gravel. The STP sumps, fill pipes, and spill buckets were installed on the tanks. The dispenser sumps were installed in place. Piping was ran between the STP sumps and dispenser sumps. Piping was welded to connections at the dispenser sumps in accordance with the manufactures installation guidelines. Piping was pressurized with air, none of the fittings were seen leaking, or bubbling. All primary and secondary pipe air gauges were holding steady pressure. All dispenser sumps and STP sumps were seen passing hydrostatic test.
Comments:
Comment Date: 11/27/2019 User: BRAGG_SD_2
Description: 11/19/2019. Regeine Pangahas was on site to witness the tanks being set into the excavation and see them secured to dead men.
Comments:
Comment Date: 02/24/2020 User: BRAGG_SD_2
Description: Testing was and financial responsibility was not submitted as part of the installation paperwork. Refer to violations section of this report for violations and corrective actions. Signed copy of this inspection report emailed to Diane Rae at DRae@BJS.com. Signature lost due to FIRST connectivity problems.
Comments:
Comment Date: 10/30/2019 User: BRAGG_SD_2
Description: UST System installation. Scope of work: Install 3 fiberglass USTs, and all associated piping, STP sumps, and dispenser sumps. Owner: BJ's Wholesale Club, Diane Rae, 774-512-6468, drae@bjs.com. Contractor: Great Dane Petroleum Contractors, Mike Pavelko, 407-466-3046, MPavelko@GreatDanePetro.com. PSSC License: PCC056839. Consultant: Stantec, Zach Rich, 207-887-3508, Zach.Ricj@Stantec.com. Equipment installed: Tanks: Two(2) CSI 20,000 gallon FRP, Double-Wall Fiberglass tanks(EQ-191), one(1) CSI 24,000 gallon FRP, Double-Wall Fiberglass, compartmented tank(EQ-191). STP sumps are part of tank EQ. Dispenser sumps: Franklin Fueling(EQ-423). Piping: 3" Franklin Fueling, UPP Double-Wall piping(EQ-816). Ameron, Dualoy 3000/LCX, 2' Double-Wall fiberglass piping(EQ-291). Spill Buckets: Seven(7) Emco Wheaton, Double-Wall, SS, Spill buckets with gauges(EQ-741), four used as fills, and three as vapor recoveries. ATG/Release Detection: Veeder-Root TLS-450, with dual point, and non-discriminating sensors.(EQ-724). DPLLD sensor(EQ-722), Universal Sensor/Probe Interface Module(USM), with water detection sensor. (EQ-723) Piping/Sump Fittings: Bravo, fiberglass, conduit pass-through fittings(EQ-820). Overfill Prevention: Four(4) Emco Wheaton, Guardian Overfill Prevention Valves(EQ-414) 10/25/2019 Tanks were delivered to the facility removed from trucks and set on beds of pea-gravel until ready for installation. Tanks appeared to be in good condition and did not have any signs of damage. Brine filled interstices were full and no leaks were seen on the tanks. 10/29/2019 Air pressure test were conducted on the tanks. Each primary was pressurized to 5 PSI, and was holding.
10/25/2019 Site Inspection Activity Closed Bragg, Shane D
Activity Result: Major Out of Compliance Activity Status: Closed
On-Site Start Date: 10/25/2019
Activity Closed Date: 02/24/2020 Activity Closed By: BRAGG_SD_2
Events:
Event Type: Activity has been finished Date: 02/24/2020
Comment: Finished
Comments:
Comment Date: 02/04/2020 User: BRAGG_SD_2
Description: Backfilling was completed. Concrete was poured over the tank pad, and around the dispenser sumps. ATG sensors were being installed into the STP and dispenser sumps.
Comments:
Comment Date: 12/20/2019 User: BRAGG_SD_2
Description: Tanks were back filled using gravel. The STP sumps, fill pipes, and spill buckets were installed on the tanks. The dispenser sumps were installed in place. Piping was ran between the STP sumps and dispenser sumps. Piping was welded to connections at the dispenser sumps in accordance with the manufactures installation guidelines. Piping was pressurized with air, none of the fittings were seen leaking, or bubbling. All primary and secondary pipe air gauges were holding steady pressure. All dispenser sumps and STP sumps were seen passing hydrostatic test.
Comments:
Comment Date: 11/27/2019 User: BRAGG_SD_2
Description: 11/19/2019. Regeine Pangahas was on site to witness the tanks being set into the excavation and see them secured to dead men.
Comments:
Comment Date: 02/24/2020 User: BRAGG_SD_2
Description: Testing was and financial responsibility was not submitted as part of the installation paperwork. Refer to violations section of this report for violations and corrective actions. Signed copy of this inspection report emailed to Diane Rae at DRae@BJS.com. Signature lost due to FIRST connectivity problems.
Comments:
Comment Date: 10/30/2019 User: BRAGG_SD_2
Description: UST System installation. Scope of work: Install 3 fiberglass USTs, and all associated piping, STP sumps, and dispenser sumps. Owner: BJ's Wholesale Club, Diane Rae, 774-512-6468, drae@bjs.com. Contractor: Great Dane Petroleum Contractors, Mike Pavelko, 407-466-3046, MPavelko@GreatDanePetro.com. PSSC License: PCC056839. Consultant: Stantec, Zach Rich, 207-887-3508, Zach.Ricj@Stantec.com. Equipment installed: Tanks: Two(2) CSI 20,000 gallon FRP, Double-Wall Fiberglass tanks(EQ-191), one(1) CSI 24,000 gallon FRP, Double-Wall Fiberglass, compartmented tank(EQ-191). STP sumps are part of tank EQ. Dispenser sumps: Franklin Fueling(EQ-423). Piping: 3" Franklin Fueling, UPP Double-Wall piping(EQ-816). Ameron, Dualoy 3000/LCX, 2' Double-Wall fiberglass piping(EQ-291). Spill Buckets: Seven(7) Emco Wheaton, Double-Wall, SS, Spill buckets with gauges(EQ-741), four used as fills, and three as vapor recoveries. ATG/Release Detection: Veeder-Root TLS-450, with dual point, and non-discriminating sensors.(EQ-724). DPLLD sensor(EQ-722), Universal Sensor/Probe Interface Module(USM), with water detection sensor. (EQ-723) Piping/Sump Fittings: Bravo, fiberglass, conduit pass-through fittings(EQ-820). Overfill Prevention: Four(4) Emco Wheaton, Guardian Overfill Prevention Valves(EQ-414) 10/25/2019 Tanks were delivered to the facility removed from trucks and set on beds of pea-gravel until ready for installation. Tanks appeared to be in good condition and did not have any signs of damage. Brine filled interstices were full and no leaks were seen on the tanks. 10/29/2019 Air pressure test were conducted on the tanks. Each primary was pressurized to 5 PSI, and was holding.